INCOMING VECO SUPPLY

Z(UTILITY) + Z(TRANSFORMER) + Z(LINE)


= 9.486 + j28.45

Z(UTILITY) = 3.18x10 - 4 + j3.81x10 - 3


Note:

Impedance Diagram Development @ 100 MVA base


Zpu (new) = Zpu (old) x MVA(base)/ MVA(old)
1 / ( (1/ Z(DP-B) ) + ( 1/ Z9DP-1) ) + ( 1/ Z(DP-2) ) + ( 1/ Z(DP-G) )
Z(TRANSFORMER) = 9.48 + j28.459 I(fault - current) = MVA(base)/ V(@fault) x Zth (pu)
= 27.39 + j6.75

Z(LINE) = 0.00647 + j0.00426 Figure 2: Equivalent Impedance Diagram


B1 @ MDP - ATS BUS

I(fault) = 100x10 6 / ( 230 x 16.67 )


= 26.081 kA
Use 26kAIC for Main CB
1 / ( ( 1/ 9.486 + j28.45 ) + ( 27.39 + j6.75))
= 12.475 + j11.067 B1
Z(DP-B) Z(DP-1) Z(DP-2) Z(DP-G)

88.88 + j17.25 147.42 + j42.03 463.19 + j60.122 60.96 + j17.36

Figure 3: Total Equivalent Impedance Diagram Figure 4: Solving for ½ cycle singe phase fault @ B1
Figure 1: Impedance Diagram

PROFESSIONAL ELECTRICAL ENGINEER: PROFESSIONAL SEAL : PROJECT TITLE: APPROVED BY: DRAFTED BY: SHEET NO.

Engr . Alcasid, Ivy Hirro REE, RME


EDWIN C. CHAVEZ
REG NO. DATE:
PROPOSED 4 STOREY RESIDENCE JAN YBAÑEZ
OWNER
DATE :

-
01 March 2021

-
E-16
PTR NO. DATE: - -

TIN NO. LOCATION : LOT 3, PRISTINA NORTH SUBDIVISION ADDRESS: CEBU CITY - - SHEET : 2-2