Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 1

Design calculation sheet

Project no: PEARL QATAR Facility Mgt(Q07048) Date:27/12/2007 Sheet no.: 1 of 1 Computed by: A.B

Subject: AIR HANDLING UNIT - PRESSURE DROP Checked by: N.E

Approved by:

Column number 1 2

Tag number WH-AHU-02 WH-AHU-01

System served Ware House Ware House

Location Ware House Ware House

Floor Served First Ground

Accessories Static 50.000 1.432


INTERNAL STATIC
PRESSURE. AIR Cooling Coil 50.000 1.036
SIDE (in Pa)
Sub total ( Internal) 100.000 2.468

Supply Duct work

Duct Run (m) 44.000 80

Friction Pa\m 20.000 0.065

Return Duct work

Duct Run (m) 25.000 65

Friction Pa\m 20.000 0.099

Duct Work 1380.000 0.171

EXTERNAL STATIC Fittings 15% 207.000 0.026


PRESSURE. AIR Volume Damper 25.000 0.100
SIDE (in Pa)
Duct Heater (if any) 0.000 0.000

Fire Damper 25.000 0.100

Terminal Box (if any) 75.000 0.000

Air Outlet 25.000 0.100

Fresh Air Louver (if any) 0.000 0.000

30% Safety 483.600 0.089

Sub total ( External) 2220.600 0.585


TOTAL AIR SIDE TOTAL + 10% safety 2552.660 3.358
EXTERNAL (pa) 2220.600 146
Summary
TOTAL (pa) 2553 836
Accessories Static consists of:1-Flat filter
2-Bag filter 3-Mixing Box Section 4-Fan
NOTE: Section
3.5KW-94% 11.6KW-77.4%

You might also like