Design Calculation Sheet: Mechanical & Industrial Department
Design Calculation Sheet: Mechanical & Industrial Department
:D0052
Data
mv = Pvi-Pvo = (1322-2928.3)/1.92E+10
Gt
= -8.37E-08 Kg/m2s
1 of 12
Proj. No. :D0052
q = tai-tao = 22-46/0.56
Rt
= -42.85 W/m2
where q is the rate of flow of heat per unit area
tai is the inside air temp.
tao is the outside air temp.
Rt is the total thermal resistence of the structure
* No condensation occurs when saturation vapour pressure is greater than the calculated vapour pressure.
2 of 12
Proj. No. :D0052
1-Apr-21
Computed by
MG
Approved by
3 of 12
Proj. No. :D0052
1-Apr-21
Computed by
MG
Approved by
Result*
No Cond.
No Cond.
No Cond.
No Cond.
No Cond.
No Cond.
No Cond.
4 of 12
Proj. No. :D0052
Data
mv = Pvi-Pvo = (1492.6-1473)/1.92E+10
Gt
= 1.02E-09 Kg/m2s
where mv is the rate of vapour mass transfer per unit area
Pvi is the inside vapour pressure @ 24 C & 50% rh
5 of 12
Proj. No. :D0052
q = tai-tao = (24-16)/0.56
Rt
= 14.28 W/m2
where q is the rate of flow of heat per unit area
tai is the inside air temp.
tao is the outside air temp.
Rt is the total thermal resistence of the structure
* No condensation occurs when saturation vapour pressure is greater than the calculated vapour pressure.
** Although the result is positivepressure difference,the difference is very low which indicates a risk
of condensation .
6 of 12
Proj. No. :D0052
1-Apr-21
Computed by
MG
Approved by
7 of 12
Proj. No. :D0052
1-Apr-21
Computed by
MG
Approved by
Result*
No Cond.
No Cond.
No Cond.
No Cond.
No Cond.
No Cond.
No Cond.
8 of 12
Proj. No. :D0052
Data
= 1.13E+10 (N s/kg)
= 0.44 (N s/kg)
mv = Pvi-Pvo = (1492.9-4975)/1.13E+10
Gt
= -3.10E-07 Kg/m2s
where mv is the rate of vapour mass transfer per unit area
9 of 12
Proj. No. :D0052
q = tai-tao = (24-38)/0.44
Rt
= -32.11 W/m2
where q is the rate of flow of heat per unit area
tai is the inside air temp.
tao is the outside air temp.
Rt is the total thermal resistence of the structure
* No condensation occurs when saturation vapour pressure is greater than the calculated vapour pressure.
10 of 12
Proj. No. :D0052
1-Apr-21
Computed by
Approved by
11 of 12
Proj. No. :D0052
1-Apr-21
Computed by
Approved by
Result*
No Cond.
condensation occurs
condensation very
likely to occur