Machine Model GENCLS_PLAYBACK

Machine Model GENCLS_PLAYBACK


Synchronous machine represented by “classical” modeling or
Thevenin Voltage Source to play Back known
voltage/frequency signal
Zab  0.03
on 100 MVA base

Responding
Recorded System
Voltage
A B

States:
1 – Angel
Mechanical Swing Equations
Responding
2 – Speed w System
I ppd
𝛿̇ = 𝜔 ∗ 𝜔0
gencls 1 𝑃𝑚𝑒𝑐ℎ − 𝐷𝜔
B 𝜔̇ = ( − 𝑇𝑒𝑙𝑒𝑐 )
2𝐻 1+𝜔
Zab  0.03 𝜔 = per unit speed deviation, so 𝜔 = 0 means we
on 100 MVA base are at synchronous speed and 𝜔 = 1 would
mean it’s spinning at double synchronous speed
𝜔0 = synchronous speed 2𝜋𝑓0 where 𝑓0 is the
Responding nominal system frequency in Hz
System
I ppd
Note: If option Ignore Speed Effects in Generator
gencls
Swing Equation is true, then instead use
A B 1
𝜔̇ = (𝑃 − 𝐷𝜔 − 𝑇𝑒𝑙𝑒𝑐 )
2𝐻 𝑚𝑒𝑐ℎ
Model supported by PSLF