Power

The Fuel System Generation

General Without Intermediate Fuel Tank (Fig. C1)


Dependent upon the specific site layout, the fuel can be The simplest arrangement would be to supply the engine
supplied to the engine either from:- directly from the bulk storage tank and return the injector
1. The sub-base fuel tank located under the spill directly to this tank. A typical arrangement for this is
generating set. shown in Fig. C1.
2. An intermediate daily service tank located within
the plant room or generator enclosure, which is The principle limitations of this method are:
automatically refilled from a bulk storage tank; or In order to gravity feed the engine, the outlet from the
3. A bulk storage tank, provided that the outlet bulk storage tank must be a minimum of 600mm
connection from this tank is at least 500mm higher above the generator plinth level;
than the base on which the generator is mounted. The spill return pipe to the fuel tank must be routed to
Reputable fuel suppliers deliver clean, moisture free oil. avoid excessive static head on the spill return for the
Most of the dirt and water in the fuel is introduced engine.
through careless handling, dirty storage tanks or lines This is generally 165mm Hg or approximately 0.22
and poorly fitted tank covers. bar.
The final selection of the fuel system is very much The supply pipework from the bulk storage tank to the
dependent upon the site layout and the relative heights engine must be sized to allow the total volume of fuel
of the generator and the bulk storage facility. The engine required by the engine (consumed fuel plus spill return
is designed to run on light domestic fuel oil to the fuel) to flow under gravity.
following specification:-
There are many fuel composition requirements that must With Intermediate Fuel Tank (Fig. C2)
be met when purchasing diesel fuel. The following table Where, due to site constraints, it is not possible to supply
lists fuel properties and their limits: the more critical the engine direct from the bulk tank an intermediate tank
definitions follow. can be located within the plant room/generator enclosure
It is very important that the fuel oil purchased for use in which supplies fuel directly to the engine.
any engine be as clean and water-free as possible. Dirt This type of system can be further enhanced by the
in the fuel can clog injector outlets and ruin the finely addition of the following optional items of equipment:
machined precision parts in the fuel injection system.
Water in the fuel will accelerate corrosion of these parts. 1. An automatic duplex fuel transfer pump and
primary filter system arranged to start the standby
pump should the duty pump fail. The transfer
Fuel Oil Recommendations pump(s) must be sized to cater for the total fuel
Diesel fuel used for Cummins engines should be class required by the engine, i.e. fuel consumed and the
A1 or class A2. spill return volumes (Fig. C5);
2. A fusible link operated dead weight drop valve
Sub-Base Fuel Tank designed to cut off the supply of fuel to the
All Cummins Power Generation sets can be supplied intermediate tank and to transmit a signal in the
with or without base fuel tanks. Capacities vary but are event of fire;
designed to provide approximately 8 hours of operation 3. A fusible link operated dump valve, arranged to
at full load. In practice with a variable load this will be dump the contents of the local tank back into the
extended. Recommended room layout drawings (Section bulk tank in the event of a fire within the generator
B) incorporate base fuel tanks on the generators and the enclosure.
room height allows for this feature.
The connection details for these additional items of
This provides a self contained installation without the equipment are indicated. See Fig. C2.
addition of external fuel lines, trenches and fuel transfer
pumps. Generators with base tanks are delivered fully
connected and ready to run.
All base tanks have provision to accept fuel lines from
externally mounted bulk fuel tanks or auxiliary free
standing fuel tanks installed in the generator room.
Fuel transfer can be manually, electrically or
automatically transferred via electric motor driven units.
For critical standby installations, it is recommended that
a positive head of fuel is present at the engine fuel lift
pump at all times.
C1
Section C
Power
The Fuel System Generation

Fig. C1 Fuel System Without Intermediate Tank

Fig. C2 Fuel System With Intermediate Tank

C2
Section C