Criticality Categories based on DEP 31.22.00.

30
Operational Risk: Category
∙ Explosive/fire potential : Release >10 tonne (11 tons) of flammable fluid
1
∙ Stored energy : >1000 MJ(737 MM ft-lb)

∙ Explosive/fire potential : Release >2 tonnes (2.2 tons) of flammable fluid


∙ Toxicity : Very toxic
2
∙ Stored energy : <1000 MJ(737 MM ft-lb)
3
∙ Potential for rapid corrosion or cracking : Potential

∙ Explosive/fire potential : Release < 2 tonnes (2.2 tons) of flammable fluid or release of non-flammable fluid
∙ Toxicity : Not very toxic
3
∙ Stored energy : <300 MJ(221 MM ft-lb)
∙ Potential for rapid corrosion or cracking : None

Design complexity: Category


∙ Design Pressure based on flange class : Class 1500 and higher
∙ Design Temperature : >510 °C (950 F)
∙ Cyclic service : Severe cyclic service 1
∙ Specialty design : Prototype design
∙ Heat Exchanger Specifics : Proprietary closures and TEMA Type ‘D’ front channel

∙ Design Pressure based on flange class : Class 600 and 900


∙ Design Temperature : >440 °C (824 F) or when creep analysis is required
∙ Lower Design Temperature : <-50 °C (-58 F)
∙ Cyclic service : Yes 2
∙ Design methodology : Stress analysis 3
∙ Specialty design : Proprietary design component
∙ Heat Exchanger Specifics : Supplemental or alternate design analysis

∙ Design Pressure based on flange class : Class 150 and 300


∙ Design Temperature : <440 °C (824 F)
∙ Lower Design Temperature : >-50 °C(-58 F)
∙ Cyclic service : No 3
∙ Design methodology : Vessel design software/design by rule
∙ Specialty design : No specialty design elements
∙ Heat Exchanger Specifics : Exchangers of standard TEMA types

Fabrication complexity: Category


∙ Wall Thickness : >100 mm (4 in)
∙ Vessel Outside Diameter : >7 m (23 feet)
∙ Base Material : Difficult materials requiring specialized fabrication procedures
1
∙ Overlay/ Cladding/ internal coating : Other overlay materials than austenitic stainless steel
∙ PWHT : Stainless steel or Nickel alloys with PWHT
∙ Heat exchanger Specifics : Refractory, external jacketed or internal bundle shrouds

∙ Wall Thickness : >50 mm (2 in)


∙ Vessel Outside Diameter : >5 m (16.4 feet)
∙ Base Material : The balance of fabrication materials
∙ Overlay/ Cladding/ internal coating : Austenitic stainless steel, internal coatings 2
3
∙ PWHT : Local PWHT
∙ Internals: Complex internals
∙ Heat exchanger Specifics : Non-standard fabrication processes

∙ Wall Thickness : <50 mm (2 in)


∙ Vessel Outside Diameter : <5 m (16.4 feet)
∙ Base Material : CS <510mPa (74ksi) 304/304L or 316/316L SS
∙ Overlay/ Cladding/ internal coating : No overlay No coating or non-critical coating 3
∙ PWHT : No PWHT or complete PWHT
∙ Internals: Simple trays, packing, distributors
∙ Heat exchanger Specifics : Standard fabrication processes

Final Criticality Category: 3


Category 1 Highest category, associated with potentially high operational risk.
Warrants the most stringent design and fabrication requirements.
Category 2 Medium category, associated with potentially moderate operational risk. Warrants some special design and fabrication requirements.

Category 3 Lowest category, associated with reduced operational risk.


Standard design and fabrication requirements are sufficient.

Originating Discipline Engineer Discipline/Process Engineer Process Owner

Signature: Signature: Signature:


Name: TP Raghavendra Name: Name:

Date: 2/2/2021 Date: Date: