Saudi Aramco Test Report: UPS/DC Vented Ni-Cad Wet Cell, Jobsite Acceptance Test SATR-P-3102 Elect
Saudi Aramco Test Report: UPS/DC Vented Ni-Cad Wet Cell, Jobsite Acceptance Test SATR-P-3102 Elect
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
TEST PROCEDURE ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
Check that whether any cell electrolyte reached the low-level line, water
should be added to bring all cells to the high-level line. SAES-P-103
A3 Water quality should be in accordance with manufacturer’s instructions. Sec. 3.2
ANSI/IEEE Std 1106-2005 Annex C.2
Page 1 of 7
At the conclusion of the test, determine the battery capacity according SAES-P-103
A8
the procedure outlined in Section 9.4 (IEEE 1106-2005) Sec. 3.2
Page 2 of 7
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) REV 3 30-Jun-08
UPS/DC Vented Ni-Cad Wet Cell, Jobsite Acceptance Test SATR-P-3102 ELECT-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
Weak cells that can not pass the test shall be replaced. SAES-P-103
A9
SA Pre-Commissioning Form P- 002 Sec. 3.2
1. Use digital low resistance ohmmeters or measurement of millivolt drop during capacity testing.
2. When working on the electrical connections to the batteries, insulated tools should be used. (PE 1-2003 Sec. 2.5.10)
3. The instruments used for voltage measurement shall be voltmeters of an accuracy class equal to 0,5 or better. The resistance of the voltmeters used
shall be at least 1 kΩ/V (see IEC 60051 or IEC 60485).
4. The instruments used for current measurement shall be ammeters of an accuracy class equal to 0,5 or better. The entire assembly of ammeter, shunt
and leads shall be of an accuracy class of 0,5 or better (see IEC 60051 or refer to IEC 60359).
5. For measuring temperature, thermometers shall be used having a suitable measuring range in which the value of each graduated division is not in excess
of 1 °C. The absolute accuracy of the instruments shall be at least 1 °C.
6. For measuring electrolyte densities, hydrometers or other instruments shall be used with scales so graduated that the value of each division is not in
excess of 5 kg/m3. The absolute accuracy of the instruments shall be at least 5 kg/m3.
8. The test equipment calibration cycle shall not exceed twelve months.
Schedule Q, Att. IV, Sec. 7
C. TEST RESULTS
D. CONCLUSIONS
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
Bolt-torque levels should be in accordance with Table 100.12 unless NETA ATS 2007
D2
otherwise specified by manufacturer. 7.18.3.1.3
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If NETA ATS 2007
D3
manufacturer's data is not available, investigate any values which deviate 7.18.3.1.2
from similar connections by more than 50% of the lowest value.
Page 3 of 7
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) REV 3 30-Jun-08
UPS/DC Vented Ni-Cad Wet Cell, Jobsite Acceptance Test SATR-P-3102 ELECT-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
Battery terminal float and equalize voltage shall be within the NETA ATS 2007
D7
manufacturer's recommended operating range for the cell type. 7.18.1.1.2.2
Page 4 of 7
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) REV 3 30-Jun-08
UPS/DC Vented Ni-Cad Wet Cell, Jobsite Acceptance Test SATR-P-3102 ELECT-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
Consult the battery manufacturer for cell internal ohmic values in excess NETA ATS 2007
D9
of 25% between identical cell that are in fully charge state. 7.18.1.1.3.2.6
Test results are acceptable and in accordance with Saudi Aramco Schedule Q
D10
Engineering Standards and contractual requirements. Att. II
REMARKS:
REFERENCE DOCUMENTS:
1. Schedule Q Quality Requirements (Pro Forma Contract), February 2008
2. NEMA PE 1 Uninterruptible Power Systems (UPS) - Specification and Performance Verification (1-2003)
3. Acceptance Testing Specifications - NETA (2007)
4. Saudi Aramco Pre-Commissioning Form P # 002, March 2006
5. SAES-P-103 UPS and DC Systems, 02 June 2008
6. ANSI / IEEE Std 1106-2005 Nickel-Cadmium Storage Batteries, 2005 Edition
ATTACHMENT(S):
1. Attachment - 1 SAE Table 10.2 U.S Standard Bolt Torques for Bus Connections
NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products
or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states
that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a specified purpose.
4. Labeled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization concerned
with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the manufacturer
indicates compliance with appropriate standards or performance in a specified manner.
*Person Responsible for Implementation of Test and Analysis of Results Y = YES N = NO F = FAILED