Release Note H-Designer v6.9 b196 - EN Release

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Release Notes for H-Designer

What’s Open case in the software/ program H-designer version 6.9.0 build 196
Open Case Description and Comments
New features are not supported by H- Due to the memory size in H-T60b-S(P)(N), H-T60c-S(P)(N)
T60b-S(P)(N), H-T60c-S(P)(N) and H- and H-T60t-S are not big enough for code size with all new
T60t-S. features in build 176 (and after).
Communication of dual ports would Under some conditions, dual port communication would
lead HMI crashed. lead HMI crashed after a period of time.
Multilink communication would not In multilink connection, Sometimes more than two slaves
work normally. would make the multilink communication not work.
Downloading application into an old ADP v6.7.0 build 193software does not support to
version of PWS6400 is not supported download application file into old version of PWS6400
by ADP build 193. HMI with manufacture date before (and) 0936. (Please
refer to DATE on tag at rear of HMI panel)
For this old PWS6400, please use ADP v6.3.1(or before)
instead.
SIEMENS PLC S7-200 and S7-200 According limited by SIEMENS protocol, when Baud rate is
SMART when Baud rate 9600 and configured by 9600 and 19200 which will cause Timer and
19200 will get discontinuous value. Counter get the PLC discontinuous value. The solution of
the situation, please adjust Timer and Counter frequency
to balance the update speed. Double confirm by third
party HMI which has the same limitation of SIEMENS PLC.

What’s new/ corrected/ improved in the software/ program H-designer.


Version Build Bug fix/ Error Description/ New Functionality
number Function
V6.9 196 Bug fix ELMO PLC initial Marco crash
ADP6.8 when used ‘extension status block’ of Recipe function; it
is display error guide light.
Communication error and incomplete information.
ADP is not supported FX3U-485 M8255-M8511.
When it is off-line simulation, if checked ‘Save current Language’
when used Numeric Entry Keypad which will cause crash.
PWS6700 connected to Delta PLC communication error when
change page.
Trend Graph Error
Read Bit location error of S7-300 DBX
PWS6800 and PWS6A00 communicated with S71200, the
DB99.DBX0.0 isn’t feedback without any error message.
Customer implemented project in PWS1711 as Master to
communicate with Wago PLC. When transfer the project to
PWS6600S-S which become slowly.
PWS6A00 communicates with Facon PLC which configured baud
rate 38400 and SW5 = ON, the communication caused system
Author Date Approved by Revision Revision date Document Page

Jamie 2014/12 - - v1 1 (3)


Release Notes for H-Designer

crash. If change SW5 to Off or Baud rate change to 9600 which


communication smoothly.
ADP 6.8 alarm triggers voice fail.
ADP 6.8 keyboard cannot show Chinese.
ADP 6.8 Mitsubishi QJ71E71 cannot trigger alarm by using L
device type.
PWS6710T download project to USB Fail, the error message
shows ‘unknown device’.
Windows font library cannot use well.
Momentary button fail.
ADP 6.8 It gets problem to download recipe through COM port.
When on-line simulation select Hitachi H/EH1 series which will
cause ADP crash.
CF card cannot detect when HMI reboot system.
CPU is occupied 99%-100% when communications around 1
week.
There are IP connections fail via Modbus TCP/IP.
Modify Koyo K sequence PLC default address from 0 to 1.
Hitachi EH2 has communication fail when on line simulation.
Modify ADP6.7macro mov slow issue.
PWS6800 gets wrong symbol when data print out.
Seven segment font display as boldface.
Mitsubishi FX3U 485 uses double word getting wrong Input and
output on R600 address.
ADP6.6 and ADP 6.8 print screen to file crash.
PWS6600S Trigger and Reset alarm will be marked when
selected the alarm.
RCPNO and RCPNM of receipt cannot update synchronization.
FX3U R value error when off-line simulation.
FX3U-485BD gets Fail error message when off-line simulation.
The recipe name cannot show on drop-down list correctly when
first time download program.
PWS5610S-S displays alarm Error.
Use RecipeEditor to edit recipe and upload through USB,
Ethernet and serial caused recipe name error.
PWS6400 start and close Alarm function which will get wrong
time and date by randomly.
PWS6A00 connected to 13 units TOHO thermal controller, it will
get invalid value randomly.
Use Softpanel under Win XP which connect to MicroLogix
1000/15000 Eth fail.
PWS mono type gets wrong display color when select alarm
message.
ADP& H-Designer select HP PCL LaserJet P1606dn(USB) when
configure Parameters shows “it cannot open P6AP30.tsk” error
message.
Micro printer SPRT SP-A series com 1 cannot print on
Author Date Approved by Revision Revision date Document Page

Jamie 2014/12 - - v1 2 (3)


Release Notes for H-Designer

PWS6700/PWS6710.
Micro printer SPRT SP-A series cannot print alarm in control
area.
Use USB store alarm data cause HMI crash.

What’s new/ corrected/ improved in the H-designer drivers.


Version Build Bug fix/ Error Description/ New Functionality
number Function
V6.9 196 Customized Create ‘hour’ condition of Trend Graph
Function Add Enlarge the alarm act dialog
The min hold time function for action and screen/previous
screen buttons
New Create Historic Data Table
features
New TECO AP-114BR-A PLC
Drivers SIMATIC S7-200 SMART Serial communication PLC
SIMATIC S7-200 SMART Ethernet communication PLC

Author Date Approved by Revision Revision date Document Page

Jamie 2014/12 - - v1 3 (3)