GENERAL NOTE

Generator Details:
- Location of Generator is Ground Floor of Utility Building
Stair Details B. Fire Hydrant System
- Capacity of Generator is 330 KVA
- shall have a minimum width of 1.5 m (60 in.) for all COMMERCIAL occupancies and 2.0 - As per Fire Act - 2003 & 2014 Fire Hydrant System is Provided.
- Area of Generator room as per BNBC- Table 8.2.9
m (79 in.) for all assembly occupancies. For assembly use areas provided for prayer halls, - Proposed Fire Pump Set is - 1) Electrical Pupm- 750 GPM @ 9 Bar
- Separation from production floor with 05 hour (10'' Brick Wall) Fire Rated wall and 2 hour Fire Door as per Fire Act - 2003 &
dining halls and like areas that are for integral use by the factory workers, the minimum Head 2) Diesel Pump - 750 GMP @9 bar Head 3) Jockey Pump - 25
2014
width for the primary occupancy use of the building shall be permitted to be used GPM @ 10 Bar Head. as per BNBC chapter 4 and NFPA 20
- Proper Ventilation should provide
- Total 05 (Five) Number of Stair - Provided Class-ll Connection (Ø40 mm) inside the floor
- The room have sufficient access and working space to permit safe operation and maintenance of the equipment within
- interior stair with 1.5m Width. Exterior Stair with 1.5m Width - Provided Class-l Connection (Ø65 mm)in the Landing of Stair
generator room. Access shall be no less than 1.07 m (3ft 6in) on all sides of the generator.
- Discharge of all stair is OUT SIDE of the Building - Design Drawing should be Reviewed by BFSCD
- Exhaust shall be in accordance with NFPA 37. All exhaust systems shall discharge to the exterior of the building in a safe
- All Stair enclosure is separate from the production floor with 10'' (5 hr. Rated) and 5'' (1.5
location.
Hr. Rated) Brick wall
- All Exit of Stair is Separated with 1.5 Hr. & 2 Hr. Fire Rated Door. Boiler Room Details: N/A C. Automatic Water Sprinkler System
- Exterior exit stairs is separated from the building with the rating requirements of 6.3.1.2. - Location of Boiler Room is Ground Floor of Utility Building - As per Fire Act - 2003 & 2014 Automatic Water Sprinkler System is Provided.
The rating wall isl extend 3.05 m (10 ft) beyond the ends of the stair structure -Capacity 500 LTR - 02 (Two) number of Riser is consider for Automatic Water Sprinkler system
- Walking surfaces of stairway treads shall be uniformly slip resistant. - Area of Boiler Room AS Per BNBC - Installation should be as per NFPA-13
- Separation from production floor with 05 hour (10'' Brick Wall) Fire Rated wall and 2 hour Fire Door - Design Drawing should be reviewed by BFSCD
as per Fire Act - 2003 & 2014
Fire Door Details - Proper Ventilation should provide D. Water Reservoir
- Fire Door is Consider in all Fire rated Exit with following properties - The room have sufficient access and working space to permit safe operation and maintenance of the equipment within - As per Fire Act - 2003 & 2014 Underground Water Reservoir is Provided.
a) Single Motion Panic Bar generator room. Access shall be no less than 1.07 m (3ft 6in) on all sides of the generator. - Capacity of Reservoir is 67500 US Gallon
b) With self- or automatic closing and upon closing shall include positive latching - Exhaust shall be in accordance with NFPA 37. All exhaust systems shall discharge to the exterior of the building in a safe - Back up is for 90 Minutes
hardware location. - Installation should be as per NFPA-22 & NFPA- 24
c) Door Coordinator for Double Leaf - Design Drawing should be reviewed by BFSCD
Fire Pump Room Details
d) Fire Rated Smoke Seal
- Location of Fire Pump Room is in Ground Floor
e) With Vision Panel LPS Details
- Positive Suction Type
f) Interface with Detection System Lighting Protection shall be provided for in accordance with the following:
- Proper Ventilation should provide
g) All Items should be Listed - shall have protection against lightning depending on the probability of a stroke and
- The room have sufficient access and working space to permit safe operation and maintenance of the equipment within
h) Fire doors assemblies shall conform to NFPA 252 acceptable risk levels. Steps shall be taken for an objective assessment of the risk and of
generator room. Access shall be no less than 1.07 m (3ft 6in) on all sides of the generator.
12955-2008, or IS 3614 Part II. The ASTM standard referenced in the BNBC Part 4 Section the magnitude of the consequences of lightning strikes following BNBC Part 8, section 2.9.
- Exhaust shall be in accordance with NFPA 37. All exhaust systems shall discharge to the exterior of the building in a safe The marginal Risk Index shall be 40. Structures higher than 53 m (174 ft) require protection in
1.5.4 has been withdrawn.
, BS 476 Part 22, EN 1364-1, GB location. all cases
i) Etc.
- A complete lightning protection system shall consist of air termination network, down
conductors and earth termination
Fire Command / Control Room Details - lighting protection system shall be required for existing construction if the marginal Risk
Means of Egress Details - Location of Fire Command / Control Room is in security room Index is 40 or greater and the structure is higher than 53 m (174 ft)
- Discharge area of All Means of Egress is outside of Building - With Fire Detection Control Panel - Air Termination Network. The air termination network is that part which is intended to
- Minimum Width of Aisle mark should be 36'' - Central Public Addressing System intercept lightning discharges. It consists of vertical and horizontal conductors arranged to
- Minimum aisles shall be maintained free of storage - Local Fire Fighting equipments protect the required area. No part of the roof should be more than 9 m (30 ft) from the
- 24x7 hour attendant nearest horizontal conductor except that an additional 0.3 m (1 ft) may be added for
-
each 0.3 m (1 ft) or part thereof by which the part to be protected is below the nearest
- The means of egress paths shall be illuminated at all times the building is occupied. - Proper Ventilation should provide
conductor.
Illumination shall be a minimum of 10 lux for all corridors, exit doors, and stairways. Aisles - The room have sufficient access and working space to permit safe operation and maintenance of the equipment within - Down Conductor.
shall be provided with a minimum 2.5 lux. generator room. Access shall be no less than 1.07 m (3ft 6in) on all sides of the generator. The down conductor is the conductor which runs from the air termination to the earth
- Exit signs may be illuminated either by lamps external to the sign or by lamps contained - Exhaust shall be in accordance with NFPA 37. All exhaust systems shall discharge to the exterior of the building in a safe termination. A building with a base area not exceeding 100 m2 (1,076 ft2) shall be provided
within the sign. The source of illumination shall provide not less than 50 lux at the location. with one down conductor. For a large building there shall be one down conductor for the
illuminated surface with a contrast of not less than 0.5. Approved self-luminous signs first 100 m2 (1,076 ft2) plus a further one for every 300 m2 or part thereof in excess of the first
100 m2 (1,076 ft2). Alternatively, for a larger building one down conductor may be provided
which provide evenly illuminated letters having a minimum luminance of 0.2cd/m2 may
for every 30 m (100 ft) of perimeter. The number chosen can be the smaller of the numbers
also be used. Fire Detection System given by these alternative methods of calculation.
- Lighting for exit signs shall either be provided with emergency power or battery - Automatic or manual fire alarm and detection systems shall be installed throughout all new and existing buildings and -Earth Termination.
backup. The earth termination is that part which discharges the current into the general mass of the
structures where required
earth. The total resistance of an electrode for a lightning protection system must not
- Automatic detection initiating devices shall include either smoke or fire detection devices spaced in accordance with exceed 10 ohms.
NFPA 72. When complete sprinkler protection is provided throughout a floor with waterflow devices designed to initiate
Sub-Station Details the alarm notification, smoke and fire detection devices can be eliminated throughout that floor Electrical Single Line Diagram Details
- Location of Sub-Station is Ground Floor of water base Building - A Control Panel will be in Fire Control Room.
- All Exhaust Fan, Fire Door, Lift, Fire Pump, Zone control valve will be interfaced with Detection system. - For whole Buildings, a Single Line Diagram (SLD) shall be maintained and continuously
- Capacity of Transformer is 1000 KVA
updated to reflect as built conditions. The SLD shall show a correct power distribution path
- Area of Sub-station as per BNBC- Table 8.2.8 - Provide Audio-Visual Notifier system
from the incoming power source to switchgear, switchboards, panelboards, MCCs, fuses, circuit
- Separation from production floor with 05 hour (10'' Brick Wall) Fire Rated wall and 2 - Provide Listed Products and Cables breakers, automatic transfer switches, and continuous current ratings.
hour Fire Door as per Fire Act - 2003 & 2014 - Design and Drawing of Fire Detection system should be Reviewed by BFSCD - Conductors shall be so enclosed in earthed metal or incombustible insulating materials so that
- Proper Ventilation should provide it is not possible to have ready accesses to them unless the points between which a voltage
exceeding 240 volts may be present are 2m or more apart. In case such points are kept apart
- working space to permit safe operation and maintenance of the equipment within the Fire Fighting System Details the means of access shall be marked to indicate the voltage present
sub-station shall be no less than 1.07 m (3ft 6in) Where terminals or other fixed live parts between which a voltage exceeding 240V exists are
- The layout of the substation shall be in accordance of the power flow, i.e. from utility A. Portable Fire Extinguisher housed in separate enclosures or items of apparatus which although separated are within reach
network to HT room, then to transformer and finally to the low voltage switchgear room. - Provide Portable Fire Extinguisher as per Fire Act-2003 & 2014 of each other a notice shall be placed in such a position that anyone gaining access to live parts
In general, the substation HT to LT Transformer shall be placed in one corner of the room is warned of the magnitude of the voltage that exists between them.
- Portable fire extinguishers shall be installed throughout the Building in accordance with BNBC Part 4 Section 4.10 and
- Flexible cable or cords shall not be used as fixed wiring unless contained in an enclosure
so that the HT side remains away from the passage of the persons NFPA 10. affording mechanical protection. Flexible cords may be used for connections to portable
- The HT Panel shall be located near the exterior, just after or adjacent to the HT panel. - Extinguishers shall be placed so that maximum travel distance to the nearest unit shall not exceed 30 m (100 ft).
- Fire extinguishers having a gross weight not exceeding 18.14 kg (40 lb) shall be installed so that the top of the fire - Every circuit shall be legibly identified as to its clear, evident, and specific purpose or use.
extinguisher is not more than 1.53 m (5 ft) above the floor (NFPA 10 6.1.3.8). Spare positions that contain unused overcurrent devices or switches shall be described
accordingly. The identification shall include a circuit directory that is located on the face or
- Fire extinguishers having a gross weight greater than 18.14 kg (40 lb) (except wheeled types) shall be installed so that
inside of the panel door. Circuits used for the same purpose must be identified by their
the top of the fire extinguisher is not more than 1.07 m (3½ ft) above the floor (NFPA 10 6.1.3.8).
- Design and Drawing of SLD should be Reviewed by BFSCD

CONSULTANT PROJECT NAME & ADDRESS: DESIGN BY CHECKED BY BUILDING OWNER ARCHITECT ENGINEER FIRE SAFETY PROFESSIONAL AUTHORIZED BY DRAWING TITLE

MARICO BD LIMITED GENERAL NOTE

DRAWING TYPE SUB. DATE


Mouchak, Kaliakoir, Gazipur,
House-27, Road-01, Sector-06 Dhaka, Bangladesh. FIRE SAFETY PLAN SSL/NOV-22/2020
Uttara, Dhaka-1230, Bangladesh. BUILDING TYPE CAD BY SCALE SHEET NO
Cell: 01730791994, 01711195266 FACTORY MD. RASHEDUZZAMAN MD. ASAD AR. ZAED HOSSEN ENGR.MD.SHAH ALAM BADSHA MAJOR AKM SHAKIL NEWAZ (RETD.) MAHMUDA AKTER
Email: info@safetysource.com.bd B. Sc IN EEE B. Sc IN EEE B. ARCH (SUB). MIAB B. Sc IN CIVIL ENGINEER MSDM, MBA, EX DIRECTOR CHAIRMAN MD. RASHEDUZZAMAN 1:100 FSP-004
IAB MEMBERSHIP NO- H-221 MEMBERSHIP NO.M-37480 FIRE SERVICE & CIVIL DEFENCE SAFETY SOURCE LTD.

You might also like