Delta Company Ltd.

Description: Contract no.: Sheet:


CT failure relay 13092 1 of 1
Site: Location no.:
MODON-2 110/33/13.8 KV SS 13.8 KV SWG Panel no.: AH 19

MVTP31V1CB0751E - CT SUPERVISION RELAY SI NO: 33072625/10/14

PICKUP TEST;
R ph Y ph B ph
Voltage Setting
(V) Pick up (V) Pick up (V) Pick up (V)
2 2.01 2.01 2.01

3 3.01 3.01 3.01

5 5.01 5.01 5.01

9 9.01 9.01 9.01

TIMING TEST:

Phase Contacts No. Actual Operating time at 2xVs Expected operating time (s)

R 1,3 2.99 3 +/-5%

Y 1,3 2.99 3 +/-5%

B 1,3 2.99 3 +/-5%

FUNCTIONAL TEST:

Item Description Checked

1 All contacts checked. ok

2 All output contacts resistance measured. ok

3 Flag operation checked. ok

Tested by: NECE Witnessed by: N.G


Name Engr: Keerthirajan Ramadoss Name Engr :
SEC – ID
NEC-24
Signature & Date : Signature & Date :
- -2015 - -2015