Streszczenie. Niniejszy artykuł przedstawia projektowanie energetycznego filtru typu C wyższych harmonicznych, którego zadaniem jest
zmniejszenie współczynnika zawartości harmonicznych w przemysłowym systemie zasilania. Zaproponowano nową metodę projektowania C-filtru
oraz przedstawiono przykład zastosowania tej metody projektowania w praktyce dla zakładu przemysłowego. (Nowa metoda projektowania filtru
typu C).
(7) ZF
jRT U 2 2 12 j
1U 2
5.
6.
2.88
1.12
1.87
0.78
RT 1 QF nr2 1 jU 2 2 12 QF 7 1.75 1.24
8. 1.00 0.72
Distribution of the load-generated harmonic current 9. 1.12 0.81
between the filter tuned to that harmonic and the system is: THD 5.87 4.07
*Total harmonic voltage distortion factor THDu determined from
I S n r Z F n r components up to 15th order.
k
(8) I F n r Z S n r For the arc furnace power supply system (Fig. 2) and the
design requirements:
U2 Network 3rd harmonic filters C-type filter
U 4 n r4 Q F k 2 12 L2S
2
RT QF = 20 Mvar
n Q F k1 L S
3 2
U = 30 kV QF = 20 Mvar
r L3 = 18.48 mH
Sz = 1500 MVA nr = 1.9
C3 = 63 F
Summarizing, the C-type filter parameters can be LS = 3.129 mH qF2 = 10
R3 = 30.0 m
determined from formulas (6), (4), (2) and (8). RS = 30.0 m k=1
nr = 2.95
the C-type filter parameters determined from (2), (4), (6)
An Example of the C-Type Filter Design and (8) are: C1 = 70.736F, C2 = 198.24F, L2 = 51.11mH,
In result of the arc furnace modernization (fig. 2.) its RT = 276.86 .
power and, consequently, the level of load-generated
harmonics have increased. It was, therefore, decided to Figure 3a shows frequency-impedance characteristics
expand the existing reactive power compensation and of: the power network, the resultant impedance of two
harmonic mitigation system. Considering the system single-tuned 3rd harmonic filters, and the C-type filter
expansion the designed C-type filter should be tuned to the impedance. Figure 3b shows frequency-impedance
2nd harmonic due to the fact that this harmonic, though characteristics of: the network, the resultant impedance of
present in the system, it is not reduced whereas the 3rd the network and two 3rd harmonic filters, and the resultant
harmonic filters are already installed. Although currently the impedance of the network, two 3rd harmonic filters and the
2nd harmonic level in the existing system does not exceed C-type filter.
the limit, connection of new loads may increase the 2nd Data listed in table 2 demonstrate that connecting the C-
harmonic to an unacceptable level. type filter results in the expected reduction of the 2nd
Sz = 1500 MVA 110 kV voltage harmonic in the supply system, whereas other
harmonics are reduced to a small extent. Further reduction
P5 of the second harmonic can be achieved by improving the
S = 75 MVA C-type filter quality factor and, consequently, reduction of
S = 75 MVA
110/30kV 110/30kV
the filter impedance for the filter resonant frequency and
increasing the impedance for higher harmonics.
30 kV
Table 2. Voltage harmonics without filters, with two 3rd harmonic
P1 P3 P4 P2
Q1 Q2 filters, and with two 3rd harmonic filters and the C-type filter
Q3 Q3 Order Busbars Busbars voltage Busbars voltage
XL3 XL3 XL2 voltage voltage harmonics with harmonics with two
RT harmonic harmonics two 3rd 3rd harmonic filters
without harmonic filters and the C-type filter
XC3 XC3 XC2 filters
30/1.2kV
115MVA 2. 1.76 2.47 1.32
F3 F3 XC1
3. 3.01 0,27 0.27
FC
F2 4. 1.66 0.95 0.91
5. 2.88 1.87 1.78
Fig. 2. Diagram of the modernized arc furnace power supply 6. 1.12 0.78 0.74
system 7 1.75 1.24 1.18
8. 1.00 0.72 0.69
Prior to the modernization the system comprised two 9. 1.12 0.81 0.78
parallel, single-tuned 3rd harmonic filters that were the THDU* 5.87 4.07 3.37
cause of a slight increase in the voltage 2nd harmonic. *Total harmonic voltage distortion factor THDu determined from
The increase in the arc furnace power entails an increase in components up to 15th order.
the passive filters' powers. The planned extension of the
system should also be taken into account. The increased
power of the compensation circuit, as well as installation of
15
ZF 4
qF2=10
10
Zs 2
5
R
0 00
1 1.5 2 2.5 3 3.5 4 1 2 3 4 5 6
n
n
nr
10 b) 3000
b)
9
RT 2500
8
Zs||Z2x3h
|Zs||Z2x3h|
|Zs||Z2x3h||ZCfiltr|
7
2000
6
5
Zs||Z2x3h||ZCfilter 1500
Zs
|Zs|
4 k =0.33
1000 R = 840
3
k=1
2 R = 276.86
500
1
0 0
1 1.5 2 2.5 3 3.5 4 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
n k
Fig. 3. Frequency-impedance characteristics of: a) the power Fig. 4. a) The C-type filter frequency characteristics for various
network equivalent impedance (ZS), the resultant impedance of two quality factors, b) the resistance RT vs. the coefficient k
3rd harmonic filters (Z2x3h), the C-type filter impedance (ZCfilter), the
resultant impedance of two 3rd harmonic filters and the C-type filter Implementation and Measurements
(ZF); b) the impedance seen from the load terminals: without filters In order to verify the effectiveness of the proposed method
(ZS), the network equivalent impedance and two 3rd harmonic has been designed a C-type filter for an electric arc furnace
filters impedance connected in parallel (Zs||Z2x3h), and parallel power supply system (Fig, 2).
connection of the network equivalent impedance, two 3rd harmonic
The designed C-type filter was installed in the arc furnace
filters and the C-type filter impedances (Zs||Z2x3h||ZCfilter).
supply system. The capacitance C1 is composed of 60
Figure 4a shows the C-type filter frequency capacitors (20 per phase) with capacitance 14.15F each,
characteristics for different quality factors, figure 4b which gives total capacitance C1 = 70.75F. The
illustrates the relation between the resistance RT and the capacitance C2 is composed of 24 capacitors (8 per phase)
coefficient k that indicates the distribution of the current with capacitances 24.6F each, which gives total
harmonic to which the filter is tuned. capacitance C2 = 196.8F. The reactor L2 parameters
should be recalculated because of alteration of the
Table 3. The percentage distribution of the harmonic current capacitance C2 due to the installation modifications
between the filter tuned to that harmonic and the supply network; (L2 = 51.48mH). The resistor resistance is RT
the corresponding RT values and the designed filter quality factor = 300 10%. The diagram of the actual single-phase
IF [%] IS RT filter circuit is depicted in Fig. 5.
k
[%] []
38.5 61.5 1.60 172
44.4 55.6 1.25 221
50.0 50.0 1.00 276.86 51.48mH
300
51.9 48.1 0.93 300
…
57.1 42.9 0.75 350
8 x 24.6F
66.6 33.3 0.50 555
75.0 25.0 0.33 840
83.3 16.7 0.25 1111
91.0 9.0 0.10 2778
…
20 x 14.15F
Data in table 3 shows the percentage distribution of the
harmonic current between the filter tuned to that harmonic
and the supply network. The values of the factor k
corresponding to the RT values are also provided in the
table. Fig. 5. Diagram of the actual C-type filter circuit
Fig. 10. Total harmonic current distortion factor THDI at the 110kV
side
Fig. 6. The voltage and current at the 110kV side
Fig. 7. The voltage at the 30kV side Fig. 11. Total harmonic distortion factor THDI of the furnace and C-
type filter currents