Hady Habib's Hydraulic Calculation: Hazard Classification: Area Coverage by Sprinkler (As)
Hady Habib's Hydraulic Calculation: Hazard Classification: Area Coverage by Sprinkler (As)
Address ADDRESS
City CITY
Date 05-Jan-15
Area coverage by sprinkler(As) : 100 ft² selected from tables As hazard type
P friction and residual = 273.348 bar P static = 1.650485437 bar P total = 274.9985 bar
Hydraulic Calculations
for
ABC COMPANY
ADDRESS - CITY
Contract No. CONTRACT NUMBER Date 05-Jan-15
Design data:
Occupancy classification Special Occupancy (High-Piled) Hazards Density 0.15 gpm/ft²
Area of application 1500 ft² Coverage per sprinkler 100 ft² No. of sprinklers calculated 15
Hose streams 15 gpm Total water required including hose streams 216 gpm
Hady Habib's Hydraulic calculation sheet
using
NFPA® 13 : Standard for the Installation of Sprinkler Systems - 2013 Edition
For more information: nicearb@yahoo.com
Name of contractor CONTRACTOR
Name of designer HADY HABIB
Address DESIGNER ADDRESS
Authority having jurisdiction
Hady Habib's Hydraulic calculation sheet
using NFPA® 13 : Standard for the Installation of Sprinkler Systems - 2013 Edition
Nicearb@yahoo.com
Item Description Unit Qyt. Rate Total
1/2 in. 45° elbow Pcs 0 50.00 0
3/4 in. 45° elbow Pcs 0 30.00 0
1 in. 45° elbow Pcs 0 17.00 0
1 1/4 in. 45° elbow Pcs 0 25.00 0
1 1/2 in. 45° elbow Pcs 0 30.00 0
2 in. 45° elbow Pcs 3 37.00 111.00
2 1/2 in. 45° elbow Pcs 0 43.50 0
3 in. 45° elbow Pcs 4 50.00 200.00
3 1/2 in. 45° elbow Pcs 0 56.50 0
4 in. 45° elbow Pcs 0 63.00 0
5 in. 45° elbow Pcs 0 69.50 0
6 in. 45° elbow Pcs 0 76.00 0
8 in. 45° elbow Pcs 0 82.50 0
10 in. 45° elbow Pcs 0 89.00 0
12 in. 45° elbow Pcs 0 95.50 0
1/2 in. 90° standard elbow Pcs 0 10.00 0
3/4 in. 90° standard elbow Pcs 0 20.00 0
1 in. 90° standard elbow Pcs 9 17.00 153.00
1 1/4 in. 90° standard elbow Pcs 0 25.00 0
1 1/2 in. 90° standard elbow Pcs 0 30.00 0
2 in. 90° standard elbow Pcs 1 15.00 15.00
2 1/2 in. 90° standard elbow Pcs 1 21.50 21.50
3 in. 90° standard elbow Pcs 0 21.40 0
3 1/2 in. 90° standard elbow Pcs 0 21.30 0
4 in. 90° standard elbow Pcs 2 21.20 42.40
5 in. 90° standard elbow Pcs 0 21.10 0
6 in. 90° standard elbow Pcs 0 21.00 0
8 in. 90° standard elbow Pcs 5 20.90 104.5
10 in. 90° standard elbow Pcs 0 20.80 0
12 in. 90° standard elbow Pcs 1 20.70 20.70
1/2 in. 90° long-turn elbow Pcs 0 30.00 0
3/4 in. 90° long-turn elbow Pcs 0 14.00 0
1 in. 90° long-turn elbow Pcs 1 45.00 45.00
1 1/4 in. 90° long-turn elbow Pcs 0 44.67 0
1 1/2 in. 90° long-turn elbow Pcs 0 52.17 0
2 in. 90° long-turn elbow Pcs 1 59.67 59.666666667
2 1/2 in. 90° long-turn elbow Pcs 0 67.17 0
3 in. 90° long-turn elbow Pcs 0 39.00 0
3 1/2 in. 90° long-turn elbow Pcs 0 60.00 0
4 in. 90° long-turn elbow Pcs 0 59.67 0
5 in. 90° long-turn elbow Pcs 0 64.67 0
Hady Habib's Hydraulic calculation sheet
using NFPA® 13 : Standard for the Installation of Sprinkler Systems - 2013 Edition
Nicearb@yahoo.com
Item Description Unit Qyt. Rate Total
6 in. 90° long-turn elbow Pcs 0 69.67 0
8 in. 90° long-turn elbow Pcs 0 74.67 0
10 in. 90° long-turn elbow Pcs 0 33.00 0
12 in. 90° long-turn elbow Pcs 0 40.00 0
1/2 in. Tee or cross (flow turned 90°) Pcs 0 10.00 0
3/4 in. Tee or cross (flow turned 90°) Pcs 0 55.56 0
1 in. Tee or cross (flow turned 90°) Pcs 0 44.83 0.00
1 1/4 in. Tee or cross (flow turned 90°) Pcs 0 44.83 0
1 1/2 in. Tee or cross (flow turned 90°) Pcs 0 44.83 0
2 in. Tee or cross (flow turned 90°) Pcs 0 44.83 0
2 1/2 in. Tee or cross (flow turned 90°) Pcs 0 44.83 0
3 in. Tee or cross (flow turned 90°) Pcs 100 54.80 5480.37
3 1/2 in. Tee or cross (flow turned 90°) Pcs 0 53.69 0
4 in. Tee or cross (flow turned 90°) Pcs 0 52.58 0
5 in. Tee or cross (flow turned 90°) Pcs 0 51.47 0
6 in. Tee or cross (flow turned 90°) Pcs 0 49.22 0
8 in. Tee or cross (flow turned 90°) Pcs 0 51.52 0
10 in. Tee or cross (flow turned 90°) Pcs 0 47.00 0
12 in. Tee or cross (flow turned 90°) Pcs 3 60.00 180.00
1/2 in. Butterfly valve Pcs 0 40.00 0
3/4 in. Butterfly valve Pcs 0 80.00 0
1 in. Butterfly valve Pcs 3 48.08 144.25
1 1/4 in. Butterfly valve Pcs 0 48.08 0
1 1/2 in. Butterfly valve Pcs 0 48.08 0
2 in. Butterfly valve Pcs 0 48.08 0
2 1/2 in. Butterfly valve Pcs 0 48.08 0
3 in. Butterfly valve Pcs 0 105.19 0
3 1/2 in. Butterfly valve Pcs 0 91.66 0
4 in. Butterfly valve Pcs 70 78.14 5469.5925926
5 in. Butterfly valve Pcs 0 64.61 0
6 in. Butterfly valve Pcs 0 46.06 0
8 in. Butterfly valve Pcs 3 47.61 142.81666667
10 in. Butterfly valve Pcs 0 19.00 0
12 in. Butterfly valve Pcs 0 32.25 0
1/2 in. Gate valve Pcs 0 5.00 0
3/4 in. Gate valve Pcs 0 40.00 0
1 in. Gate valve Pcs 4 51.33 205.33
1 1/4 in. Gate valve Pcs 0 51.33 0
1 1/2 in. Gate valve Pcs 0 51.33 0
2 in. Gate valve Pcs 0 51.33 0
2 1/2 in. Gate valve Pcs 0 51.33 0
Hady Habib's Hydraulic calculation sheet
using NFPA® 13 : Standard for the Installation of Sprinkler Systems - 2013 Edition
Nicearb@yahoo.com
Item Description Unit Qyt. Rate Total
3 in. Gate valve Pcs 0 119.57 0
3 1/2 in. Gate valve Pcs 0 101.94 0
4 in. Gate valve Pcs 0 84.30 0
5 in. Gate valve Pcs 0 66.67 0
6 in. Gate valve Pcs 0 42.89 0
8 in. Gate valve Pcs 1 43.69 43.688888889
10 in. Gate valve Pcs 0 7.62 0
12 in. Gate valve Pcs 0 23.53 0
1/2 in. Swing check* Pcs 0 58.00 0
3/4 in. Swing check* Pcs 0 96.67 0
1 in. Swing check* Pcs 5 88.25 441.25
1 1/4 in. Swing check* Pcs 0 79.83 0
1 1/2 in. Swing check* Pcs 0 71.42 0
2 in. Swing check* Pcs 0 63.00 0
2 1/2 in. Swing check* Pcs 0 54.58 0
3 in. Swing check* Pcs 0 46.17 0
3 1/2 in. Swing check* Pcs 0 37.75 0
4 in. Swing check* Pcs 10 29.33 293.33333333
5 in. Swing check* Pcs 0 99.57 0
6 in. Swing check* Pcs 0 78.38 0
8 in. Swing check* Pcs 7 57.19 400.33
10 in. Swing check* Pcs 0 36.00 0
12 in. Swing check* Pcs 0 14.81 0
NFPA® 13 Libraries,
Museums
Standard for the Nursing or accomodation
Offices,
Installation of Sprinkler Residential
Systems Restaurant seating areas
Theaters and auditoriums,
2013 Edition Unused attics
Ordinary Hazard Occupancies
Group 1 Group 2
Automobile parking Cereal mills
Bakeries Chemical plants — ordinary
Beverage manufacturing Confectionery products
Canneries Distilleries
Dairy products Dry cleaners
Electronic plants Feed mills
glass products manufacturing Horse stables
Laundries Leather goods manufacturing
Restaurant service areas Libraries — large stack room areas
showrooms Machine shops
Metal working
Mercantile
Paper and pulp mills
Paper process plants
Piers and wharves
Post offices
Printing and publishing
Repair garages
Resin application area
Stages
Textile manufacturing
Tire manufacturing
Tobacco products manufacturing
Wood machining
Wood product assembly
Extra Hazard Occupancies
Group 1 Group 2
Aircraft hangars Asphalt saturating
Combustible hydraulic fluid use areas Flammable liquids spraying
Die casting Flow coating
Metal extruding Manufactured home
Plywood and particles Open oil quenching
Printing Plastics processing
Rubber Solvent cleaning
Saw mills Varnish and paint dipping
Textile All kind
Upholstering with plastic foams
Table 6.2.3.1 Sprinkler Discharge Characteristi
Nominal
K-Factor
[gpm/(psi)1/2]
Table 23.4.4.7.1 Hazen–Williams C Values
Unlined cast or ductile iron 100 1.4
Black steel (dry systems including preaction) 100 1.9
Black steel (wet systems including deluge) 120 2.8
Galvanized steel (dry systems including preaction) 100 4.2
Galvanized steel (wet systems including deluge) 120 5.6
Plastic (listed) all 150 8.0
Cement-lined cast- or ductile iron 140
Copper tube or stainless steel 150
Asbestos cement 140 11.2
Concrete 140
14.0
16.8
19.6
22.4
25.2
28.0
2.3.1 Sprinkler Discharge Characteristics Identification
Nominal Percent of
K-Factor Range K-Factor Range Nominal Thread
K-Factor
[gpm/(psi)1/2] [L/min/(bar)1/2] K-5.6 Type
[L/min/(bar)1/2]
Discharge
Construction Type
Noncombustible unobstructed
Noncombustible unobstructed
Noncombustible obstructed
Noncombustible obstructed
Combustible unobstructed with no exposed members
Combustible unobstructed with no exposed members
Combustible unobstructed with exposed members 3 ft (0.91 m) or more on center
Combustible unobstructed with exposed members 3 ft (0.91 m) or more on center
Combustible unobstructed with members less than 3 ft (0.91 m) on center
Combustible obstructed with exposed members 3 ft (0.91 m) or more on center
Combustible obstructed with members less than 3 ft (0.91 m) on cente
Combustible concealed spaces in accordance with 8.6.4.1.4
*See 8.6.4.1.4.4.
pright Spray Sprinklers for Light Hazard
Maximum
Maximum Spacing
System Type Protection Area
ft2 m2 ft2 m2
Hydraulically calculated 225 20.9 15 4.6
Pipe schedule 220 18.6 15 4.6
Hydraulically calculated 225 20.9 15 4.6
Pipe schedule 200 18.6 15 4.6
Hydraulically calculated 225 20.9 15 4.6
Pipe schedule 200 18.6 15 4.6
Hydraulically calculated 225 20.9 15 4.6
Pipe schedule 200 18.6 15 4.6
All 130 12.1 15 4.6
All 168 15.6 15 4.6
All 130 12.1 15 4.6
All 120 11.1 15 4.6
Parallel to Parallel to
the slope 10 the slope
perpendicul 3.05
ar to the perpendicul
slop * ar to the
slop *
Table 8.6.2.2.1(b) Protection Areas and Maximum Spacing of Standard Pendent
and Upright Spray Sprinklers for Ordinary Hazard
Maximum
Maximum Spacing
Construction Type System Type Protection Area
ft2 m2 ft2 m2
All All 130 12.1 15 4.6
Table 8.6.2.2.1(c) Protection Areas and Maximum Spacing of Standard Pendent and Upright Spray Sprinklers for
Extra Hazard
Maximum
Maximum Spacing
Construction Type System Type Protection Area
ft2 m2 ft2
All Pipe schedule 90 8.4 12*
All Hydraulically calculated with density ≥0.25 100 9.3 12*
All Hydraulically calculated with density <0.25 130 12.1 15
*In buildings where solid structural members create bays up to 25 ft (7.6 m) wide, maximum spacing between
sprinklers is permitted up to 12 ft 6 in. (3.8 m).
ray Sprinklers for Table 8.6.2.2.1(d) Protection Areas and Maximum Spacing of Standard Pendent and Upright Spray
High-Piled Storage
Maximum
Maximum Spacing Construction
System Type Protection Area
Type
m2 ft2
3.7* All Hydraulically calculated with density ≥0.25 100
3.7* All Hydraulically calculated with density <0.25 130
4.6 *In buildings where solid structural members create bays up to 25 ft (7.6 m) wide, maximum spacin
sprinklers is permitted up to 12 ft 6 in. (3.8 m).
cing between
rd Pendent and Upright Spray Sprinklers for
Table 23.4.3.1.1 Equivalent Schedule 40 Steel Pipe Length Chart
Maximum
Maximum Spacing Fittin
Protection Area
Gate valve - -
Swing check* - -
none
For SI units, 1 in. = 25.4 mm; 1 ft = 0.3048 m.
Note: Information on 1⁄2 in. pipe is included in this table only because it is allo
*Due to the variation in design of swing check valves, the pipe equivalents in
pe Length Chart
1 in. 1 1/4 in. 1 1/2 in. 2 in. 2 1/2 in. 3 in. 3 1/2 in. 4 in. 5 in.
(25mm) (32mm) (40mm) (50mm) (65mm) (80mm) (90mm) (100mm) (125mm)
1 1 2 2 3 3 3 4 5
0.3 0.3 0.6 0.6 0.9 0.9 0.9 1.2 1.5
2 3 4 5 6 7 8 10 12
0.6 0.9 1.2 1.5 1.8 2.1 2.4 3 3.7
2 2 2 3 4 5 5 6 8
0.6 0.6 0.6 0.9 1.2 1.5 1.5 1.8 2.4
5 6 8 10 12 15 17 20 25
1.5 1.8 2.4 3 3.7 4.6 5.2 6.1 7.6
- - - 6 7 10 - 12 9
1.8 2.1 3 3.7 2.7
- - - 1 1 1 1 2 2
0.3 0.3 0.3 0.3 0.6 0.6
5 7 9 11 14 16 19 22 27
1.5 2.1 2.7 3.4 4.3 4.9 5.8 6.7 8.2
d Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
to as ASME SA53 pipe - is intended for mechanical and pressure applications. Can be used in steam,
le for welding and forming like coiling, bending and flanging.
0