Professional Documents
Culture Documents
ATA 21-Air Conditioning and Cabin Pressurisation
ATA 21-Air Conditioning and Cabin Pressurisation
eJAMF
Issue: 21.05.2010
Author: KlJ
ATA 21, 36
EASA Part-66
B1
EJAMF_M11.04_B1_E
Training Manual
www.Lufthansa-Technical-Training.com
Revision Identification:
The date given in the column ”Issue” on the face of this cover is binding for the complete Training Manual.
Dates and author’s ID, which may be given at the base of the individual pages, are for information about the latest revision of that page(s) only.
The LTT production process ensures that the Training Manual contains a complete set of all necessary pages in the latest finalized revision.
Lufthansa Technical Training
AIR CONDITIONING & CABIN FUNDAMENTALS
PRESSURISATION
AIR SOURCES
On all jet aircraft there is a very good air source available.
The engine compressor provides enough air for combustion purposes and also
for the pneumatic system.
You can see that the compressed air is bled from the engines, so therefore it is
called Engine Bleed Air or EBA. The engines are not the only source of air
supply for the pneumatic system. The auxiliary power unit APU is used to
supply the pneumatic system.
The only built−in air pressure sources are the engines and the APU. If both the
APU and engines are not running we can assume that the aircraft is on the
ground; if it isn’t we have a very serious problem.
If the aircraft is on ground, the pneumatic system can be supplied with external
air. This third air source can be delivered via connectors, the High Pressure
Ground Connectors.
FOR TRAINING PURPOSES ONLY!
TEMPERATURE REGULATION
The temperature in the pneumatic system must not exceed acceptable values.
You can see that if engine thrust increases then temperature increases and
vice versa. A built−in precooler is used to cool the engine bleed air
temperature. Cooling air is taken from the engine fan duct. The cooling air is
simply fan air. The cooling effect depends on the mass and temperature of fan
air.
You can probably guess that in order to vary the cooling effect, the mass of fan
air must also be varied. A fan air valve is used to allow more or less fan air to
pass the precooler.
FOR TRAINING PURPOSES ONLY!
DISTRIBUTION
The pneumatic air is distributed via ducts.
Depending on the location of the air ducts they are known as the pylon duct,
the left and right wing ducts, the APU duct and the crossover duct or
cross−bleed manifold. The cross−bleed manifold is usually located in the
fuselage and connects the left and right wing pneumatic ducts. A cross−bleed
valve is found to isolate the left from the right wing pneumatic duct.
The pneumatic ducts are monitored by a leak detection system.
FOR TRAINING PURPOSES ONLY!
AIR CONDITIONING
INTRODUCTION
INTRODUCTION
Nowadays, aircraft fly at very high altitudes mainly for economic reasons.
This presents some problems, because humans are not able to live in this
environment without help.
At an altitude of 40,000 feet the temperature is about −56 Celcius
corresponding to 133 Fahrenheit.
The air pressure is so low that there is not sufficient oxygen for human survival.
Therefore, the crew and passengers must be protected against freezing and
death.
The air conditioning system makes sure there is correct pressure in the cabin
to support life and it also ventilates the cabin to keep the temperature in a
comfortable range.
Now imagine an aircraft standing on the ground on a hot and sunny day with no
air conditioning. This would be uncomfortable and potentially life−threatening
for passengers on board. Also the equipment on the aircraft would be in danger
of overheating.
In summary, we can say the air conditioning system cools and heats the air. It
also ventilates the cabin and pressurizes the aircraft at high flight altitudes.
FOR TRAINING PURPOSES ONLY!
Pressurized Areas
FOR TRAINING PURPOSES ONLY!
Unpressurized Areas
Figure 16 Pressurization
HAM US/F KlJ 01.04.2008 09|Air Conditioning Functions/A/B1 Page 33
Lufthansa Technical Training
AIR CONDITIONING FUNDAMENTALS
INTRODUCTION
ATA 21
SYTEM LAYOUT
Here you see the principle layout of the air conditioning system.
The air supply comes from the pneumatic system.
The air conditioning system starts after the pack valve.
The air is cooled by 2 or more identical packs. Basic temperature and humidity
regulation are carried out in this area of the system.
The air conditioning system then mixes cooled air with hot air to give the
desired temperature in the conditioned compartments.
The air conditioning system also supplies the necessary cooling of panels,
batteries and electronic racks by ventilating them with air.
Finally, the conditioned air is distributed to the compartments.
The cabin and flight compartment are pressurized to supply a pressure
corresponding to all flight altitudes.
This is regulated by the outflow valve.
FOR TRAINING PURPOSES ONLY!
Introduction Cont.
The air conditioning packs, the valves and the mixing unit are located in the
center wing box area.
The air conditioning controls are located on the overhead panel in the cockpit.
You will also find the indication displays in the cockpit.
The pack and zone controllers are located in the avionics compartment.
The low pressure ground connectors are located on the lower fuselage,
accessible by a door.
FOR TRAINING PURPOSES ONLY!
Introduction cont.
The basic idea of cooling is that because heat is a form of energy it cannot be
made or destroyed, it can only be transformed.
Heat can only flow from an object to a cooler object.
FOR TRAINING PURPOSES ONLY!
Introduction cont.
There are 3 types of cooling device used on aircraft.
They are the
heat exchanger,
the vapor−cycle machine and the
air−cycle machine.
FOR TRAINING PURPOSES ONLY!
PRINCIPLES OF COOLING
Heat exchangers are very effective, but they do not have sufficient power to
cool all of the cabin air, especially on the ground.
Vapor−cycle machines are used in aircraft when engine bleed air is not
available.
The cooling principle is basically the same as in a refrigerator. An expansion
valve expands a special pressurized cooling fluid by a specific amount.
The special cooling fluid expands which results in the fluid becoming colder.
This cold fluid flows through an evaporator, which is a special heat exchanger
and is heated by the cabin air which flows across the evaporator. So the result
is that the cabin air temperature decreases.
The cooling fluid, which is now heated by the cabin air, changes its state from a
fluid to a gas.
The special cooling fluid, which is now a gas, is compressed in the compressor.
This compression gives the gas a higher temperature. This hot gas flows
through a condensor, which is a special heat exchanger.
In the condenser the special cooling gas is cooled down by ambient air. It
becomes liquid and the cycle starts again.
You can find vapor cycle machines on small aircraft with propellers, on aircraft
without an APU and on older aircraft.
FOR TRAINING PURPOSES ONLY!
COOLING DESCRIPTION
COOLING PACK DESCRIPTION
The function of the cooling pack is to cool hot bleed air to a value given by the
pack controller.
The cooling pack has:
a pack valve, which is the tap of the pack,
an ozone converter which is located upstream of the pack valve and
a heat exchanger which usually has 2 units, the primary and secondary or
main heat exchanger.
There is also an air−cycle machine and a bypass valve also called temperature
control valve.
The cooling pack also has a ram air system which has ram air ducts with ram
air inlet and exit doors and a fan.
Cooling pack sensors sense the temperature in the pack and these permit the
pack to be controlled and monitored.
There is an anti−ice valve or sometimes an anti−ice function which eliminates
icing conditions in the water separator and so, of course, there is a water
separator.
The cooling pack has a pack check valve which is located downstream of the
water separator.
The pack check valve prevents backflow into the pack. Each pack has a pack
controller which controls pack operation.
FOR TRAINING PURPOSES ONLY!
OZONE CONVERTER
The ozone converter is built in upstream of the cooling pack.
Ozone converters are found particularly in aircraft which fly at high altitudes,
because there is a lot of ozone in the atmosphere. Because ozone harms a
person’s health, the function of the ozone converter is to minimize the amount
of ozone in the cabin.
The ozone converter minimizes the amount of ozone in the cabin by using a
catalyst which converts the ozone to harmless oxygen.
FOR TRAINING PURPOSES ONLY!
PACK VALVE
The pack valve is a flow control valve, so it is sometimes named the pack flow
control valve or FCV.
It determines the amount of air going to the cabin.
For this reason it is located upstream of the air conditioning packs.
The pack valve is a venturi−type butterfly valve, which is controlled by a
solenoid.
It is pneumatically operated and spring−loaded to closed.
FOR TRAINING PURPOSES ONLY!
HEAT EXCHANGER
Cooling in the cooling packs is a system of heat exchangers and a cooling
machine, the air−cycle machine.
Modern packs have 2 heat exchangers to improve the cooling effect. So you
can see what the 2 heat exchangers look like we have separated them for you.
They are named the primary heat exchanger and the secondary or main
heat exchanger.
Normally, as we have mentioned, the 2 heat exchangers are mounted together
so they appear to be 1 component.
The advantage of the 2 heat exchangers being mounted together is that only 1
cooling duct is necessary.
FOR TRAINING PURPOSES ONLY!
Figure 35 Operation
HAM US/F KlJ 01.04.2008 12|Air Cycle Machine/B1 Page 71
Lufthansa Technical Training
AIR CONDITIONING FUNDAMENTALS
COOLING DESCRIPTION
ATA 21
BYPASS VALVE
To adjust the temperature in the pack there is a turbine bypass valve built in.
This valve is also called temperature control valve in some aircraft types. This
valve determines the air mass to the turbine.
The more air that flows to the turbine, the higher the turbine speed and the
more the cooling effect.
The location of the bypass valve can change with aircraft type. Sometimes,
only the turbine is bypassed. If this is the case, a bypass check valve is built in
to bypass the compressor, so only part of the air is compressed.
Sometimes, you can find a bypass valve which bypasses the whole air−cycle
machine.
FOR TRAINING PURPOSES ONLY!
RAM AIR
The temperature in the cooling pack can be adjusted by the bypass valve, but
as we mentioned before, adjusting the ram air flow through the heat exchanger
influences the efficiency of the heat exchanger and therefore the temperature
in the cooling pack.
The heat exchanger has a cooling air inlet and it has a cooling air outlet.
As ram air is used as cooling air, the air inlet is named the ram air inlet or RAI
and the air outlet is named the ram air outlet or exit or RAE.
Here you can see a different type of heat exchanger. On this type of heat
exchanger the principle is the same, but the airflow is different from the other
type.
FOR TRAINING PURPOSES ONLY!
A fan is found in the ram air system because on the ground there is no ram
effect. The fan is usually mounted on the same shaft as the compressor and
the turbine, so the fan runs when the pack is operative.
FOR TRAINING PURPOSES ONLY!
WATER SEPARATION
INTRODUCTION
In this lesson we examine why and how the cooling packs separate water from
bleed air in the cooling cycle.
Water has to be eliminated because temperatures can reach −50 Celsius,
corresponding to 122° Fahrenheit, in the cooling packs and any water droplets
in lines and valves could freeze. Also, any water in the cabin could end up as
fog or water droplets causing passenger discomfort and corrosion in the cabin
and the distribution lines.
As you can see from the diagram, the amount of water in the air depends
mainly on temperature.
The warmer the air, the more water it can carry. So, as you have probably
realized, air near the ground has a large amount of water dissolved in it. This
water condenses in the cooling cycle.
At high flight altitudes the air is very cold and, therefore, very dry so there is no
water which can condense in the cabin. This very dry air is good for the aircraft,
but not so good for the passengers who would prefer more humidity.
FOR TRAINING PURPOSES ONLY!
Introduction Cont.
Water separation happens in the cooling pack.
There are 2 ways to separate water. Which system is used depends on the
manufacturer of the cooling pack.
Water can be separated in the high pressure loop, after the air is compressed
by the compressor and before it goes into the turbine.
Or water can be separated in the low pressure loop, which means the water
droplets are separated after leaving the air−cycle machine and before leaving
the pack.
In any system the separated water is then collected and sent to the ram air
inlet duct to increase the cooling efficiency of the heat exchanger.
FOR TRAINING PURPOSES ONLY!
ICE PROTECTION
Here is a pack with a low pressure water separator.
A pressure transmitter sends differential pressure information between the
water separator inlet and outlet to the pack controller.
When the differential pressure increases, the pack controller assumes there is
ice and opens the turbine bypass valve more.
FOR TRAINING PURPOSES ONLY!
PACK SENSOR
There are several sensors built−in to each pack.
The minimum number of sensors you could have in a pack is 3.
These sensors are:
the compressor discharge temperature sensor,
the pack discharge temperature sensor and
the compressor overheat switch.
This switch is installed for safety reasons and informs the pack controller of
abnormal conditions. In some aircraft types you can find an overheat sensor
instead of a switch.
The pack controller also receives other signals.
The pack controller monitors the pack flow control valve position and sends it
to the ECAM or EICAS for indication.
The pack controller controls the position of the bypass valve and signals the
valve to open more or less depending on the temperature necessary. The valve
position is measured by limit switches and a position potentiometer.
The pack controller controls the position of the ram air inlet door depending on
the temperature required and the flight mode.
The ram air inlet door position is measured by limit switches and a position
potentiometer.
The pack controller controls the position of the ram air exit door, depending on
the temperature required and the flight mode. The ram air exit door position is
measured by limit switches and a position potentiometer.
So, in summary, the pack controller receives signals from the pack flow control
valve, the bypass valve, the ram air inlet door and the ram air exit door.
FOR TRAINING PURPOSES ONLY!
The cockpit also sends a flow demand signal to the pack controller. So,
together with signals from these sensors, the pack controller receives all this
data about the pack.
Pack regulation starts when the flow control valve opens. When the pack
switch in the cockpit is set to ON, the signal goes directly to the pack valve.
The pack valve opens if bleed air is available.
PACK INDICATION
All these signals about components and temperatures are used for pack
control, and you have probably worked out that they are also used for
indication.
FOR TRAINING PURPOSES ONLY!
Figure 59 Indication
HAM US/F KlJ 01.04.2008 09|Pack Indication/B1 Page 119
Lufthansa Technical Training
AIR CONDITIONING FUNDAMENTALS
PACK CONTROL
ATA 21
DISTRIBUTION
MIXING UNIT
The cold air from the packs goes into the mixing chamber unit also called the
plenum chamber and is then distributed to the different zones in the aircraft.
The mixing unit is a large chamber, like a big duct which has ports for incoming
air and outgoing air.
The mixing unit lets the cold air from the packs mix with discharged cabin air. It
directs the mixed air through the primary supply ducts to the different aircraft
zones.
FOR TRAINING PURPOSES ONLY!
RECIRCULATION SYSTEM
As you have already seen the mixing unit also gets discharged cabin air to
increase the airflow rate to the cabin.
This system is called recirculation system.
The system supports the airflow from the packs, so that the packs do not have
to run on high airflow each time. This reduces the operational costs of the
aircraft.
When the recirculation system is on there is an airflow through the mixing unit
and through the cabin.
The recirculation fans suck discharged cabin air from the underfloor area, clean
it with filters and feed it back into the mixing unit.
FOR TRAINING PURPOSES ONLY!
HAM US/F KlJ 01.04.2008 11|Ram Air and Ground Supply/B1/A Page 146
Lufthansa Technical Training
AIR CONDITIONING FUNDAMENTALS
DISTRIBUTION
ATA 21
FOR TRAINING PURPOSES ONLY!
PROTECTION CIRCUTS
The protection circuits of the zone temperature control system protect the
system from duct overheat in the event of component malfunctions or
miscontrol in manual mode.
The protection circuits are independent of the temperature control circuits. The
circuits can be either external or internal to the zone temperature controller.
The protection circuits use sensors or overheat switches in the air supply ducts
located downstream of the trim air valves.
When the duct temperature exceeds a critical level, which in this example is
about 90°C, corresponding to 194F, then the protection circuit becomes
active. It triggers a crew alert in the cockpit, for example a FAULT light in the
control pushbutton.
At the same time the protection circuit automatically closes the trim air
pressure regulating valve. This also closes the trim air valves.
The hot trim air therefore stops independently of the failure source.
In some aircraft types you must indicate to the protection circuit that you have
recognized this failure condition by pressing the pushbutton which displays the
fault light.
When the trim air system is off, then the ducts are only supplied from the
packs and the recirculation system. This cools down all ducts.
When the duct temperature decreases below for example 70°C, corresponding
to 158F, the FAULT light extinguishes. This indicates that you can reactivate
the zone temperature control system.
When the trim air system is on again, the trim air pressure regulating valve and
the trim air valves move to the position that is defined by the zone temperature
control circuit.
FOR TRAINING PURPOSES ONLY!
COMPONENTS
The zone controller which is the main component is usually a digital computer.
It is located in the electric and electronic equipment compartment.
The other components are usually located behind the forward cargo
compartment.
All trim air valves in an aircraft are generally of the same valve type. They are
usually operated by an electrical stepper motor.
The valves have potentiometers and limit switches for position feedback and
for control and indication.
Usually, there is also a manual override and visual position indicator on the
valve.
The trim air system switches off completely when a trim air valve is blocked in
the open position or when the zone controller doesn’t get a feedback signal
from a valve.
FOR TRAINING PURPOSES ONLY!
Components Cont.
The trim air pressure regulating valve is a solenoid controlled and pressure
actuated valve.
When the solenoid is de−energized, the valve is closed by a spring.
When you energize the solenoid then the valve is openes by air pressure from
the pneumatic system.
The valve regulates the downstream pressure to, for example, 4 psi above
cabin pressure.
The exact value depends on the aircraft type.
The valve position is always monitored by the zone controller by means of a
limit switch.
There is also often an pressure switch or sensor downstream of the valve
which monitors the trim air pressure.
Our example shows the trim air pressure regulating valve located inside the
pressurized area of the aircraft. In this case the valve receives cabin pressure
directly.
In this example which shows another aircraft type, there are 2 valves in the
unpressurized area near the packs.
In this case cabin pressure is supplied via pressure reference tubes.
Some valves have a second solenoid. It is energized when the duct
temperature increases to an overheat condition. This reduces the trim air
pressure and also the hot airflow.
FOR TRAINING PURPOSES ONLY!
Components Cont.
Finally, we will have a look at the temperature sensors in the zone temperature
control system.
We can differentiate between 2 types of temperature sensor installation. The
duct temperature sensors and the zone temperature sensors. All sensors are
of the thermistor type.
The duct sensors measure the temperature of the airflow directly and send the
signal to the zone controller. If a sensor fails the zone controller usually closes
the corresponding trim air valve.
To prevent this some aircraft types have 2 sensors in 1 housing.
FOR TRAINING PURPOSES ONLY!
Components Cont.
The zone temperature sensors are installed in the cabin ceiling area.
There is 1 or more in each zone, depending on the size of the zone.
The sensors must be ventilated to measure the real temperature. In some
aircraft types this is done by an electrical fan.
Another way is for the sensors to be connected to the lavatory ventilation or the
equipment cooling system which draws air through the sensors.
FOR TRAINING PURPOSES ONLY!
VENTILATION
INTRODUCTION
You can find several different types of ventilation systems on an aircraft.
There is a ventilation system for the galleys and lavatories which removes hot,
humid and stale air.
Another type of ventilation system in the cargo compartments can change the
air when necessary, for example, when carrying live cargo.
There is also a separate system for equipment cooling.
The first system we are going to study is the cargo ventilation.
The various cargo compartments can be sub−divided into 4 different ventilation
types:
the non−ventilated cargo compartment,
the ventilated cargo compartment heated,
the ventilated cargo compartment unheated and
the air−conditioned cargo compartment.
FOR TRAINING PURPOSES ONLY!
SYSTEM COMPONENTS
The equipment cooling system uses electrically operated valves to control the
air flow for the different modes of operation. These valves work as shut−off
valves, but in some aircraft they can also be moved to a partially open position.
There are 2 similar fans in this cooling system which transports the air. They
guarantee system operation even if 1 fan is not operating.
Sometimes there is a skin heat exchanger installed which increases the cooling
efficiency. The skin heat exchanger is a duct or duct system directly under the
aircraft skin. It works as an air − to − air heat exchanger. Warm air flows
through this duct and is cooled by the cold skin when the aircraft is flying at
high altitudes.
FOR TRAINING PURPOSES ONLY!
AUTOMATIC OPERATION
Usually the equipment cooling system works automatically in 2 different modes.
These modes depend mainly on the ambient temperature and whether the
aircraft is on the ground or in flight.
In automatic operation there are 2 normal modes.
One is called inboard, which means that the exhaust air goes to the underfloor
area or to the forward cargo compartment.
The second mode is called outboard, which means that the air goes out of the
aircraft.
The outboard mode is normally used on ground.
The electric equipment is cooled by air from outside the aircraft which enters
through the skin air inlet valve.
The 2 fans transport the air, which exits the aircraft via the extractor valve. All
other valves are closed.
When the outside temperature is so cold that the equipment could be damaged
by ice or humidity, cabin air is used instead of ambient air.
FOR TRAINING PURPOSES ONLY!
OVERRIDE OPERATION
The override operation occurs for example when the equipment cooling system
has a component failure or if smoke is detected.
In these abnormal situations the cockpit crew gets an indication from the
controller. When this happens they must manually operate the cooling system.
FOR TRAINING PURPOSES ONLY!
Override Operation
If there is a component failure, for example if 1 fan is damaged then a low flow
situation is detected by a low flow detector. This low flow detector sends a
signal to the equipment cooling system computer. In this case, the cockpit crew
gets a caution message on the ECAM or EICAS display.
On some aircraft types a fault light is also displayed.
In our example the blower push button switch has to be pushed to close the
valves.
The equipment continues to be cooled by the 1 operational fan which moves
the air in a closed circuit around the equipment and by the surrounding air from
the cockpit.
On some aircraft this configuration is selected automatically.
The cooling efficiency can be increased by supplying conditioned pack air or by
using a skin heat exchanger.
FOR TRAINING PURPOSES ONLY!
pressure of 8.2 psi a force of about 56500 Newtons that act on 1m2.
This corresponds to a weight of 5,700 liters of water that act on the earth
surface that is 5.7 tons.
Definitions Cont.
When the aircraft is on ground with open doors the ambient pressure and the
cabin pressure are the same.
Now the aircraft climbs to 40,000 ft in 20 minutes. This means that the aircraft
has a positive rate of climb of 2,000 ft /min, this is also called vertical speed.
In the same time the cabin has to climb only to 8000 ft. This is called the cabin
rate or cabin vertical speed. In our example the cabin climbs, with a positive
climb rate of 400 ft/min. This means that the pressure in the cabin decreases
at the same time
When there is a negative cabin rate, like during a descent, then the pressure
increases. This means that an increase of cabin altitude is always a decrease
of the cabin pressure and a decrease of cabin altitude is an increase of cabin
pressure.
FOR TRAINING PURPOSES ONLY!
Definitions Cont.
The pressure changes and therefore the cabin rates must not exceed a certain
value for a longer period of time.
This is because the human ear needs some time to compensate for the
pressure inside the inner ear.
Therefore the positive cabin rate should not exceed 500 ft/min and the negative
cabin rate should not exceed 300 ft/min.
FOR TRAINING PURPOSES ONLY!
SYSTEM LAYOUT
As you have learned already the pressurized cabin gets a constant airflow from
the air conditioning system.
The pressure in the cabin is regulated by 1 or more outflow valves, which limit
the amount of air leaving the cabin. You can find the valves on the aft fuselage
or on some aircraft there is 1 aft valve and 1 forward valve.
Air also leaves the cabin via leakages and overboard vents for example from
the lavatories. This is taken into account by the control circuits.
The cabin pressure and therefore the cabin altitude is stable when the amount
of air which enters the cabin and the amount of air which leaves the cabin are
the same.
When pack number 2 is switched off the cabin air supply is decreased.
Without any reaction the cabin altitude increases.
To stabilize the cabin altitude you must also decrease the amount of air that
leaves the cabin.
When the outflow valves are driven to a more closed position the airflow that
leaves the cabin is decreased. This stabilizes the cabin altitude again at for
example 6,000 ft.
Another parameter that influences the cabin pressure is the flight altitude,
because it determines the differential pressure at the outflow valves.
When the aircraft flies higher, for example at 40000 ft, the differential pressure
increases. This also increases the airflow through the outflow valves if they
stay in the same position. Therefore to hold the cabin altitude at the same level
you must drive the outflow valves toward closed.
Note that some aircraft types have a reduced maximum flight altitude when
only 1 pack is operating. This is for when you cannot hold the cabin altitude
FOR TRAINING PURPOSES ONLY!
PROTECTION FUNCTIONS
The aviation regulations require that pressurization systems have protection
functions.
They must prevent damage to the aircraft and injury to the people on board,
when the system has a failure or when extreme environmental conditions
appear.
The protection functions must become active when there is an excessive cabin
altitude, or excessive differential pressure, or negative differential pressure.
When the cabin altitude increases above normal values − 3 things must
happen at different altitudes.
Before reaching 10000 ft the flight crew gets a warning to put on the oxygen
masks.
At 14000 ft the oxygen masks are automatically released from the
passenger cabin ceiling.
At 15000 ft the outflow valves must close automatically and independently
of the normal control signal.
FOR TRAINING PURPOSES ONLY!
DITCHING MODE
In some aircraft types you can find a ditching pushbutton on the control panel.
You can use this button to isolate the cabin from entering water during an
emergency landing on sea
When you press the ditching pushbutton you close all valves below the flotation
line of the aircraft, and also the pack valves, so water can’t enter the aircraft via
these valves.
When the negative pressure relief valve is located below the flotation line, as in
our example, a standpipe prevents water entering the cabin.
FOR TRAINING PURPOSES ONLY!
AUTOMATIC MODE
As you already know a cabin pressure controller automatically controls the
normal pressurization.
To do this the controller uses the atmospheric ambient pressure. It receives the
pressure from the air data system or from a static port. It also uses the cabin
pressure from a direct pressure port on the controller.
The controller converts pressure signals into altitudes.
For an average value it uses the references of the international standard
atmosphere which you know from other units such as aerodynamics and
oxygen.
To get exact values you must take into account the actual weather conditions
which influence the pressure. This is acheived by a reference pressure signal
called the barometric correction.
In modern aircraft either the flight management or the air data system delivers
this signal automatically.
On other aircraft you must select this barometric correction value on the
pressurization panel.
FOR TRAINING PURPOSES ONLY!
HAM US/F KlJ 01.04.2008 24|Outflow and Safety Valves/B1 Page 266
Lufthansa Technical Training
AIR CONDITIONING FUNDAMENTALS
PRESSURE CONTROL SYSTEM
ATA 21
FOR TRAINING PURPOSES ONLY!
HAM US/F KlJ 01.04.2008 25|Outflow and Safety Valves/B1 Page 268
Lufthansa Technical Training
AIR CONDITIONING FUNDAMENTALS
PRESSURE CONTROL SYSTEM
ATA 21
FOR TRAINING PURPOSES ONLY!
HAM US/F KlJ 01.04.2008 26|Outflow and Safety Valves/B1 Page 270
Lufthansa Technical Training
AIR CONDITIONING FUNDAMENTALS
PRESSURE CONTROL SYSTEM
ATA 21
FOR TRAINING PURPOSES ONLY!
HAM US/F KlJ 01.04.2008 27|Outflow and Safety Valves/B1 Page 272
Lufthansa Technical Training
AIR CONDITIONING FUNDAMENTALS
PRESSURE CONTROL SYSTEM
ATA 21
FOR TRAINING PURPOSES ONLY!
HAM US/F KlJ 01.04.2008 28|Cabin Pressure Leakage Test/B1 Page 274
Lufthansa Technical Training
AIR CONDITIONING FUNDAMENTALS
PRESSURE CONTROL SYSTEM
ATA 21
FOR TRAINING PURPOSES ONLY!
HAM US/F KlJ 01.04.2008 29|Cabin Pressure Leakage Test/B1 Page 276
Lufthansa Technical Training
AIR CONDITIONING FUNDAMENTALS
PRESSURE CONTROL SYSTEM
ATA 21
FOR TRAINING PURPOSES ONLY!
TABLE OF CONTENTS
M11.04 AIR CONDITIONING & ICE PROTECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
CABIN PRESSURISATION . . . . . . . . . . 1 PACK CONTROL AND INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
PACK SENSORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
SOURCES OF AIR SUPPLY INCLUDING ENGINE BLEED . . . . . . . 2 PACK SENSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
GENERAL SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 PACK TEMPERATURE CONTROL . . . . . . . . . . . . . . . . . . 106
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 PACK INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
AIR SOURCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
BLEED AIR PRESSURE REGULATION . . . . . . . . . . . . . 6 MIXING UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
TEMPERATURE REGULATION . . . . . . . . . . . . . . . . . . . . 10 CABIN AIR DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . 130
DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 RECIRCULATION SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . 136
CONTROL AND MONITORING . . . . . . . . . . . . . . . . . . . . . 14 COCKPIT AIR SUPPLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
AIR CONDITIONING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 RAM AIR AND GROUND SUPPLY . . . . . . . . . . . . . . . . . . 146
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 ZONE TEMPERATURE CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
PRESSURIZATION AND ZONES . . . . . . . . . . . . . . . . . . . 18 TRIM AIR SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
AIR CONDITIONING FUNCTIONS . . . . . . . . . . . . . . . . . . 24 MANUAL TEMPERATURE CONTROL . . . . . . . . . . . . . . . 152
SYTEM LAYOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 AUTOMATIC TEMPERATURE CONTROL . . . . . . . . . . . 154
TEMPERATURE CONTROL OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . 36 PROTECTION CIRCUTS . . . . . . . . . . . . . . . . . . . . . . . . . . 158
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
PRINCIPLES OF COOLING . . . . . . . . . . . . . . . . . . . . . . . . 44 CONTROLS AND INDICATIONS . . . . . . . . . . . . . . . . . . . . 168
COOLING DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 VENTILATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
COOLING PACK DESCRIPTION . . . . . . . . . . . . . . . . . . . 48 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
OZONE CONVERTER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 NON VENTILATED CARGO COMPARTMENT . . . . . . . . 174
PACK VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 VENTILATED CARGO COMPARTMENT . . . . . . . . . . . . . 176
PACK VALVE FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . 56 CARGO COMPARTMENT - VENTILATED AND
HEATED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
HEAT EXCHANGER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
CARGO COMPARTMENT - AIR CONDITIONED . . . . . . 194
AIR CYCLE MACHINE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
LAVATORY AND GALLEY VENTILATION . . . . . . . . . . . . 202
BYPASS VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
RAM AIR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 EQUIPMENT COOLING SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
WATER SEPARATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
SYSTEM COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . 206
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
AUTOMATIC OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . 210
LOW PRESSURE WATER SEPARATION . . . . . . . . . . . . 84
OVERRIDE OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . 214
HIGH PRESSURE WATER SEPARATION . . . . . . . . . . . 90
PRESSURE CONTROL SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Page i
EJAMF M11.04 B1 E
TABLE OF CONTENTS
DEFINITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
SYSTEM LAYOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
PROTECTION FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . 230
CONTROL AND INDICATION . . . . . . . . . . . . . . . . . . . . . . 238
DITCHING MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
AUTOMATIC MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
OUTFLOW AND SAFETY VALVES . . . . . . . . . . . . . . . . . . 266
CABIN PRESSURE LEAKAGE TEST . . . . . . . . . . . . . . . . 274
Page ii
EJAMF M11.04 B1 E
TABLE OF FIGURES
Figure 1 Pneumatic System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Figure 36 Bypass Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Figure 2 Pressure Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Figure 37 Bypass Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Figure 3 Pneumatic System Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Figure 38 Ram Air System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Figure 4 Engine Bleed Pick-ups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Figure 39 Ram Air Inlet / Exit Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Figure 5 Temperature Regulation Components . . . . . . . . . . . . . . . . . . . . 11 Figure 40 Water Content in Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Figure 6 Distribution Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Figure 41 Water Separation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Figure 7 Control and Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Figure 42 Low Pressure Water Seperator . . . . . . . . . . . . . . . . . . . . . . . . . 85
Figure 8 Air Conditioning Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Figure 43 Water Separator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Figure 9 Pressurization and Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Figure 44 Water Aspirator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Figure 10 Aircraft Decks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Figure 45 High Pressure Water Separation . . . . . . . . . . . . . . . . . . . . . . . . 91
Figure 11 Aircraft Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Figure 46 Water Extractor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Figure 12 Requirements of Air Conditioning Systems . . . . . . . . . . . . . . . 25 Figure 47 Bypass Valve Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Figure 13 Regulations for Airfreshness . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Figure 48 Ice Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Figure 14 Cleanliness and Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Figure 49 Anti-Ice Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Figure 15 Humidity of Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Figure 50 Air Conditioning Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Figure 16 Pressurization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Figure 51 Pack Control Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Figure 17 System Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Figure 52 Pack Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Figure 18 Air Conditioning System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Figure 53 Pack Temperature Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Figure 19 Air Conditioning Compartment Location . . . . . . . . . . . . . . . . . . 39 Figure 54 Pack Temperature Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Figure 20 Heat Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Figure 55 Failure Conditions - Pack Control Faillure . . . . . . . . . . . . . . . . 111
Figure 21 Cooling Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Figure 56 Compressor Overheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Figure 22 Heat Exchanger and Vapour Cycle Machine . . . . . . . . . . . . . . 45 Figure 57 Bypass Valve Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Figure 23 Air Cycle Machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Figure 58 Pack Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Figure 24 Cooling Pack Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Figure 59 Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Figure 25 Catalytic Ozone Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Figure 60 ECS Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Figure 26 Pack Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Figure 61 Airbus ECS Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Figure 27 Pack Valve and Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Figure 62 Boeing ECS Maintenance Page . . . . . . . . . . . . . . . . . . . . . . . . 125
Figure 28 Regulating Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Figure 63 Mixing Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Figure 29 Airflow Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Figure 64 Mixing Unit Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Figure 30 High Flow Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Figure 65 Passenger Cabin Air Distribution . . . . . . . . . . . . . . . . . . . . . . . . 131
Figure 31 Pack Flow Selector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Figure 66 Air Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Figure 32 Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Figure 67 Passengers Individual Air Outlets . . . . . . . . . . . . . . . . . . . . . . . 135
Figure 33 Air Cycle Machine Description . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Figure 68 Recirculation System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Figure 34 ACM Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Figure 69 Recirculation System Components . . . . . . . . . . . . . . . . . . . . . . 139
Figure 35 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Figure 70 Cockpit Air Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Page i
EJAMF M11.04 B1 E
TABLE OF FIGURES
Figure 71 Cockpit Air Supply Outlets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143 Figure 106 Equipment Cooling - Inboard Mode . . . . . . . . . . . . . . . . . . . . 213
Figure 72 Cockpit Air Supply Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145 Figure 107 Override Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Figure 73 Emergency Ram Air Inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147 Figure 108 Override Mode - Fault Condition . . . . . . . . . . . . . . . . . . . . . . . 217
Figure 74 Zone Temperature Control - System Layout . . . . . . . . . . . . . . 149 Figure 109 Override Mode - Smoke Condition . . . . . . . . . . . . . . . . . . . . . 219
Figure 75 Trim Air System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151 Figure 110 Cabin Altitude Differential Pressure . . . . . . . . . . . . . . . . . . . . 221
Figure 76 Manual Temperature Control . . . . . . . . . . . . . . . . . . . . . . . . . . . 153 Figure 111 Cabin Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Figure 77 Automatic Temperature Control . . . . . . . . . . . . . . . . . . . . . . . . . 155 Figure 112 Cabin Rate Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
Figure 78 Trim Air Valve Control Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . 157 Figure 113 Cabin Pressurization System . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Figure 79 Protection Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159 Figure 114 Overboard Shut-off Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Figure 80 Trim Air Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161 Figure 115 Excessive Cabin Altitude or Pressure . . . . . . . . . . . . . . . . . . . 231
Figure 81 Trim Air Pressure Regulating Valve . . . . . . . . . . . . . . . . . . . . . 163 Figure 116 Excessive Differential Pressure . . . . . . . . . . . . . . . . . . . . . . . . 233
Figure 82 Duct Temperature Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165 Figure 117 Negative Differential Pressure . . . . . . . . . . . . . . . . . . . . . . . . . 235
Figure 83 Zone Temperature Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167 Figure 118 Equalization Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
Figure 84 Controls and Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169 Figure 119 Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
Figure 85 B747 Controls and Indications . . . . . . . . . . . . . . . . . . . . . . . . . . 171 Figure 120 Cabin Pressure Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
Figure 86 Ventilation Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173 Figure 121 Ditching Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
Figure 87 Non-ventilated Cargo Compartments . . . . . . . . . . . . . . . . . . . . 175 Figure 122 Ditching Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Figure 88 Ventilated Cargo Compartments . . . . . . . . . . . . . . . . . . . . . . . . 177 Figure 123 Automatic Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
Figure 89 Ventilated Cargo Compartment . . . . . . . . . . . . . . . . . . . . . . . . . 179 Figure 124 Ground Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
Figure 90 Ventilated Cargo Compartment on Airbus . . . . . . . . . . . . . . . . 181 Figure 125 Pre-Pessurization Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
Figure 91 Cargo Ventilation Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183 Figure 126 Internal Climb Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
Figure 92 Cargo Heating System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185 Figure 127 External Climb Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Figure 93 Electrical Heating System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187 Figure 128 Abort Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
Figure 94 Cargo Compartment Hot Air Flow . . . . . . . . . . . . . . . . . . . . . . . 189 Figure 129 Cruise Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
Figure 95 Cargo Heating System Control . . . . . . . . . . . . . . . . . . . . . . . . . 191 Figure 130 Cruise Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
Figure 96 Cargo Overheat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193 Figure 131 Cruise Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
Figure 97 Air Conditioned Cargo Compartments . . . . . . . . . . . . . . . . . . . 195 Figure 132 Descent Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
Figure 98 Cargo Compartment Air Supply . . . . . . . . . . . . . . . . . . . . . . . . . 197 Figure 133 Outflow Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
Figure 99 Air Conditioned Cargo Compartment Contol . . . . . . . . . . . . . . 199 Figure 134 Safety Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269
Figure 100 Fault Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201 Figure 135 Differential Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
Figure 101 Lavatory and Galley Air Extraction . . . . . . . . . . . . . . . . . . . . . 203 Figure 136 Differential Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273
Figure 102 Equipment Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . 205 Figure 137 Leakage Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275
Figure 103 Equipment Cooling via Skin Heat Exchanger . . . . . . . . . . . . 207 Figure 138 Safety Barriers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
Figure 104 Abnormal Situations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Figure 105 Equipment Cooling - Outboard Mode . . . . . . . . . . . . . . . . . . . 211
Page ii
EJAMF M11.04 B1 E
TABLE OF FIGURES
Page iii
EJAMF M11.04 B1 E
TABLE OF FIGURES
Page iv