Kay Electric CA PML ION 7500 PQ METERS ®

PML ION 7500 Power Quality Analyzers


Data Logging

Module 1 (Metering Data Logging)


RMS Real Time measurements @ 1 sg. Standard speed up to 2 samples per cycle

The PML ION 7500 PQ METERS ® units offer a comprehensive array of instantaneous
(real-time) measurements, including a choice of high accuracy, 1 second or -speed, ½ cycle
measurements, including true RMS, per phase and total : Real Time, average, minimum, and
maximum values for:

_ Voltage & current


_ Active power (kW)
_ Reactive power (kVAR)
_ Apparent power (kVA)
_ Power factor
_ Frequency
_ Voltage and current unbalance
_ Phase reversal

Energy and Demand


Module 2 (Energy and Demand)

Energy
The units are fully bi-directional and meter energy in four quadrants. They provide active, reactive
and apparent energy parameters and can integrate any instantaneous power parameter to
measurements like Volt-Hours, Amp- Hours, etc. Energy registers can be logged automatically on a
programmed schedule.:

_ kWh delivered & received


_ kWh net (delivered - received)
_ kWh total (delivered + received)
_ kVARh, kVAh delivered & received
_ kVARh, kVAh net (delivered - received)
_ kVARh, kVAh total (delivered + received)
_ Volt-hours & Amp-hours
_ Integration of any instantaneous measurement
Demand
The units support all standard demand calculation methods, including block, sliding
window (rolling interval), thermal (exponential), predicted demand. They can be configured
to measure demand on any instantaneous value and can record peak (maximum) and minimum
demand with accurate date and time stamps to the second. Peak demand registers can be reset
manually (password protected) or logged and reset automatically on a programmed schedule.

_ kW demand, min/max
_ kVAR demand, min/max

Página 1 de 5
Kay Electric CA PML ION 7500 PQ METERS ®

_ kVA demand, min/max


_ Amps demand, min/max
_ Volts demand, min/max
_ Demand on any instantaneous measurement

Power Quality Metering


Module 3 (Waveform capture and Recording)
Compliance Monitoring*
_ EN 50160 compliance monitoring
_ IEC 61000-4-7 harmonics & inter-harmonics
_ IEC 61000-4-15 flicker
_ CBEMA/ITIC
_ IEEE 519 and IEEE 1159

Waveform Recording
The meters can simultaneously capture all voltage and current channels.

_ Sub-cycle disturbance capture


_ Record back-to-back waveforms for up to several seconds
_ Display and compare multiple waveforms in PEGASYS software
_ Record 14 cycles at 128 samples/cycle to 96 cycles at 16 samples/cycle with the 7500
ION

Measure Up-time Using Nines


The current electricity supply infrastructure can typically provide electricity with 99.9%
reliability,
3 nines or 8.8 hours downtime a year). However, any disruption is unacceptable for
businesses in the digital economy that can require up to 99.9999999%, (9 nines or 2 cycles
downtime) to effectively run their business model. Measure the number of nines of
reliability with the 7500 ION and 7600 ION.

Out-of-Limit Detection
The meters offer accurate and reliable setpoint capabilities for the detection, recording, and
realtime
reporting of frequency variations, voltage or current phase imbalances, loss of voltage or
current phase, power factor variations, etc.

Performance Indicators
The units can be configured to meter a wide range of utility performance indicators,
including:

_ Total outage time (in seconds)


_ Out-of-tolerance duration for total harmonic distortion, voltage, frequency, power
Factor and hundreds of other definable indices

Página 2 de 5
Kay Electric CA PML ION 7500 PQ METERS ®

Harmonic Distortion Metering


Complete harmonic distortion metering, recording and real-time reporting, up to the 63rd
harmonic, (127th for 7600 ION via PEGASYS software), for all voltage and current inputs.
_ Individual harmonics
_ Total even harmonics
_ Total odd harmonics
_ Total harmonics (even + odd)
_ K-factor, Crest factor

Symmetrical Components*
Zero, negative and positive sequences including phase & magnitude for voltage & current
inputs.
Identify harmful voltage & current unbalances in equipment before they cause damage.

Disturbance Detection
High-speed setpoints allow the reliable detection and recording of events, sequence-of-
events, and alarm conditions, including magnitude, duration and equipment status.
Waveform recorders are configurable and can record all voltage and current inputs
simultaneously.
Control the number of pre-event and post-event cycles recorded. Trigger waveform
recording

Sag/Swell Detection
The 7500 ION incorporates a dedicated sag/swell capture capability that can be used to
analyze the severity and potential impact of sags and swells.
_ Magnitude and duration data suitable for plotting on voltage tolerance curves
_ Per-phase triggers for waveform recording or control operations

Transient Capture*
_ The 7500 ION can detect and record subcycle transients as short as 65 _s @ 60 Hz, (78 _s
@ 50 Hz)
_ Analyze transients by plotting them on a voltage tolerance (e.g. CBEMA) curve

Data & Event Recording


The 7500 ION is equipped with 1 MB. of configurable, nonvolatile memory for waveform,
event and log storage

Load Profiling
the 7500 ION provides 320 channels via 20 data recorders. Channel assignments are
configurable for historical trend recording of energy, demand, voltage, current, power
quality, or any other measured parameter. Trigger recorders based on time interval, calendar
schedule, alarm/event condition, or manually.

Página 3 de 5
Kay Electric CA PML ION 7500 PQ METERS ®

High-Speed Data Recording


High-speed “burst” recording (as fast as 1/2- cycle intervals) stores detailed characteristics
of disturbances or outages. Trigger recording by a user-defined setpoint, or from external
equipment. Gated recording logs data only during the critical event so that memory is
conserved.

Coincident Min/Max Recording


Log the values of key parameters or equipment conditions coincident with an extreme
condition, complete with date/time stamping. For example, record all feeder voltages and
currents at the moment a peak demand condition occurs.

Time Synchronization and GPS


A real-time clock allows internal events and data records to be date-stamped and time-
stamped to millisecond resolution. The clock can be synchronized to any one of three
sources:

_ The meter's internal crystal (+/- 50ppm)


_ The line frequency of the electrical network being metered
_ An external GPS receiver with an accuracy of +/- 1 millisecond The serial port used
for GPS time synchronization is dedicated exclusively as a GPS input.

Inputs/Outputs
Standard digital and optional analog I/O let you monitor a wide range of conditions, such as
flow rates, RPM, fluid levels, oil pressures and transformer temperatures. You can output
energy pulses to an RTU or perform equipment control operations.

Digital Inputs/Outputs
_ 8 digital inputs can monitor status or count pulses from external “volts free” dry
contact
_ 4 solid state relay output ports and 3 onboard relays can be controlled automatically
by internal setpoints or manually via a communications port

Página 4 de 5
Kay Electric CA PML ION 7500 PQ METERS ®

Specifications

Voltage Inputs Digital Inputs


_ Inputs:V1, V2, V3, V4, VREF _ 8 Inputs:S1-S8, SCOM Self-excited,
_ Rated Input: 347 LN/600 LL VAC RMS dry contact
_ Overload: 1500 VAC RMS continuous sensing, no external voltage required.
_ Dielectric Withstand: 3250 VAC RMS, 60Hz for 1 _ Minimum pulse width: 1msec
minute _ Maximum pulse rate: 20 pulses/sec.
_ Impedance: 5 M_/phase _ Scan Time: ½ cycle
_ Fault Capture: 1400 Vpeak _ Timing resolution: 1 ms
_ Isolation: 300 Vpeak for 10s, 60 Hz.
Current Inputs
_ Inputs: I1, I2, I3, I4, I5 Relays
_ Rated Inputs:1A or 10A RMS, Max voltage: 600V _ 3 Relays: R1 - R3
RMS _ Contacts: Form C
_ Overload: 50A (1A model) or 500 A (10A model) _ Rated voltage: 250 VAC / 30 VDC
RMS for 1 second, non-recurring _ Max. voltage: 380 VAC, 125 VDC
10A (1A model) or 20A (10A model) continuous _ Rated load @ 10 A AC/DC resistive,
_ Dielectric Withstand: 3250 VAC, 60Hz for 1 minuteRated
voltage: 7.5 A (AC) / 5 A (DC)
_ Starting current: 0.001A (1A ) or 0.005A (10A) RMS
_ Burden: 0.15 VA Inductive (p.f. =0.4)
_ Max. switching load: 2500 VA
Waveform Recording resistive, 1875 VA
_ Sampling Rate: 7600 ION, 256 samples/cycle from inductive (p.f. = 0.4)
47-63 Hz _ Turn-on time: 15 ms max
_ Dynamic range: Voltage Inputs: 14 bits effective _ Turn-off time: AC: 10ms max, DC: 5
(V1, V2, V3) ms max
_ Current Inputs: 18 bits effective (I1, I2, I3) _ Isolation: 5,000 VAC for 1 minute
_ Sampling Rate: 7500 ION, 128 samples/cycle _ Lifetime: 10,000,000 operations (no
_ Wave for recording options range from 16 load),100,000
samples/cycle (96 cycles) to 128 samples/cycle operations (rated voltage and load)
(14 cycles) _ Update Time: ½ cycle or 1-second