Air distribution design

Project data :
Name of the project :
Customer :
Reference :
Designed by :
Information :

Air diffusion : Space :


length = 20.0m
Vol = 58.3 l/s width = 5.0m
10
height = 10.0m
floor = 100.0m2
9
volume = 1000.0m3
8

7
Placement :
6 X1 = 2.00m
X2 = 18.00m
5 X3 = 2.50m
X4 = 2.50m
4 nb = 1
db = 0.00m
H = 7.8m
3

0
0 2 4 6 8 10 12 14 16 18 20

Placement of nozzles : Definitions :


5.0 Vol [ l/s ] : Air flow rate at the nozzle
4.5 H1 [ m ] : Distance between ceiling and stand level
4.0 H2 [ m ] : Distance between ceiling and floor level
3.5 H [ m ] : Installation height of the nozzle / duct
3.0 A [ ° ] : Installation angle of the nozzle
2.5
2.0 vH1 [ m/s ] : Mean air velocity at the occupied zone level
1.5 vH2 [ m/s ] : Mean air velocity at the floor level
1.0 LW [ dB ] : Sound power level of the nozzle
0.5
0 LWA [ dB(A) ] : A-weighted sound power level of the nozzle
Lp [ dB ] : Sound pressure level in space
0 2 4 6 8 10 12 14 16 18 20
LpA [ dB(A) ] : A-weighted sound pressure level in space
dpt [ Pa ] : Total pressure drop at the nozzle

Placement :
X1 [ m ] : Distance from left wall
X2 [ m ] : Distance from right wall
X3 [ m ] : Distance from lower wall
X4 [ m ] : Distance from upper wall
nb [ ] : Number of nozzles along broad side of the space
db [ m ] : Distance along broad side of the space

Design criteria : Calculation results for cooling :


Optimal operative temperature : 22.0°C Nozzle type : VS-5 400
Supply air temperature : 15.0°C Nozzle air flow : Vol = 58.3l/s ( 209.9m3/h )
Temperature difference : -7.0°C Effective nozzle area : Aeff = 0.042m2
Permissible mean air velocity in Effective nozzle velocity : veff = 1.40m/s
occupied zone : 0.20m/s Mean air velocity at the occupied zone level : vH1 = 0.28m/s
Required supply air flow rate : 0.6l/s m2 floor Mean air velocity at the floor level : vH2 = 0.23m/s
Required supply air flow rate in space : 58l/s
Air change coefficient : 0.2/h
Sound pressure level : 20dB(A)
Sound increment : 0dB
Room reverberation time : 0.0s
Occupied zone : 1.8m

Nozzle :
Supply : One duct
Installation angle : -20°
Angle of the jet : 0°