BELT DRIVEN CABINET FANS

CVST Series

Range of forward curved belt drive cabinet


fans designed for smoke extraction in
fire conditions and certified F400-120 (CE
marked). The casings are manufactured
F400-120 from galvanised sheet steel. Internally
lined with 7 mm thickness of melamine
thermo- acoustic insulation. All
models incorporate a single inlet low
pressure centrifugal fan mounted on
anti-vibration mounts and flexible
coupling at the discharge. Supplied as
standard in horizontal discharge (code H)
configuration with motor, pulley and belt
assembly on the left hand side of the unit
when viewed from the discharge outlet.

Motors
All motors are IP55, class F insulation.
Electrical supply:
Three phase 230/400V-50Hz, up to 3 kW.
400V-50Hz, for higher
motor powers.
(See characteristics chart).
All motor above 3 kW are mounted onto
an adjoining support frame.
All three phase motors are speed
controllable by frequency inverter.

Other versions on request


The belt-driven assembly can be supplied
at the right hand side of the unit (code R).
Vertical discharge (code V) configuration.
Two speed motors (4/8 and 4/6 poles).
Single phase motor (CVSB) up to 2,2 kW.
Double thickness side panels internally
lined with 17 mm thickness of fireproof
acoustic insulation (M0).

Specific applications
Vertical discharge models Low noise level Flexible coupling at the
Vertical discharge models Acoustic insulation of 7 mm discharge
available under request. thickness flame retardant To reduce vibration and
(M1) melamine foam reducing noise transmissions to the F400-120
Officially Continuous Parkings Commercial
the noise level significantly. installation. approved and
to EN12101-3 industrial
standard. kitchens
Certificate nº
0370-CPD-0966

Robustness Anti-vibration mounts


Quality finishing, with The fan is mounted on base
aluminium corners providing frame with silent-blocks to
a high robustness. reduce vibration and noise
transmissions to the
installation.

www.solerpalau.com Acoustic cabinet fans CVST


BELT DRIVEN CABINET FANS
CVST Series

Technical characteristics
Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency, etc.) match those of the intended
electrical supply.

Model Motor power (kW) Fan speed (r.p.m.) Weight *


Minimun Maximum Maximum Minimum Maximum Maximum (Kg)
(F400-120 version) (only standard version) (F400-120 version) (only standard version)
CVST 9/4 0,25 2,2 2,2 1200 2500 2500 49
CVST 10/6 0,37 2,2 3 1200 1850 2000 54
CVST 12/6 0,55 3 3 800 1800 1800 85
CVST 15/8 0,55 3 3 600 1200 1200 106
CVST 18/8 1,1 7,5 7,5 700 1200 1400 125
CVST 20/10 2,2 11 11 500 1300 1400 235
CVST 22/11 2,2 18,5 18,5 500 1200 1400 273
CVST 25/13 3 22 22 400 1000 1100 305
CVST 30/14 4 22 22 300 600 600 398
* With the most powerful motor option.

Motor powers (kw) for cvst product range


1 SPEED 4 POLES 0,25 0,37 0,55 0,75 1,1 1,5 2,2 3 4 5,5 7,5 11 15 18,5 22
4/6 POLES 0,25/0,09 - - 0,7/0,2 0,85/0,25 1,4/0,5 2,4/0,75 3,4/1,1 4/1,2 6,3/1,9 9/3 11/3,7 15/5 18,5/6,5 22/7,5
2 SPEED
4/8 POLES 0,25/0,06 0,37/0,07 0,55/0,09 0,75/0,12 1,1/0,18 1,5/0,25 2,2/0,37 3/0,55 4/0,75 5,5/1,1 7,5/1,5 11/2,8 15/3,8 18,5/4,8 22/5,3
NOTE: For 2 speed motors, the powers may have small variations depending on the motor manufacturer.

Dimensions (mm)

Model A B C D E F G H I J K L M
9/4 H 483 800 554 152 260 96 289 248 40 30 250 - -
9/4 V 483 800 554 152 260 96 311 268 40 30 250 - -
10/6 H 554 850 605 208 289 90 265 266 40 30 275 - -
10/6 V 554 850 605 208 289 94 341 296 40 30 275 - -
12/6 H 554 950 675 208 341 82 333 302 40 30 325 - -
12/6 V 554 950 675 208 341 82 381 337 40 30 325 - -
15/8 H 605 1018 775 258 403 88 307 343 40 30 402 - -
15/8 V 605 1018 775 258 403 88 431 379 40 30 402 - -
18/8 H 675 1250 900 268 479 88 389 395 40 30 470 - -
18/8 V 675 1250 900 268 479 88 505 447 40 30 470 - -
20/10 H 775 1350 1140 333 626 137 475 491 40 30 560 1510 80
20/10 V 775 1500 1018 333 626 137 678 562 40 30 560 1660 80
22/11 H 850 1500 1250 368 697 161 478 529 40 30 614 1660 80
22/11 V 850 1600 1086 368 697 161 718 612 40 30 614 1760 80
25/13 H 900 1600 1350 423 794 122 486 593 40 30 699 1760 80
25/13 V 900 1800 1190 423 794 122 788 669 40 30 699 1960 80
30/14 H 950 1900 1600 463 945 150 648 696 40 30 797 2060 80
30/14 V 950 2000 1390 463 945 150 899 792 40 30 797 2160 80

Acoustic cabinet fans CVST www.solerpalau.com


BELT DRIVEN CABINET FANS
CVST Series

Performance curves
– qv: Air volume in m3/h and m3/s.
– psf: Static pressure in mmWG and Pa.
– Dry air at 20ºC and 760 mmHg.
– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

psf psf CVST - 9/4


(Pa) (mmWG)

η%

50

59

55
1500 150

50
0,5 0,7
1

1000 0,3

40
100 1,5
900 90
800 80 0,2
700 70
P 2
kW

30
600 60 RPM

500 50 0,1

2500
400 40 2400

2200
300 95
30
2000
Lw
dB( A
A)
75
1800
200 90
20

1600
150 15
1400
85
80

100 10 1200
90 9
80 8
200 300 500 700 1000 1500 2000 3000 qv [m3/h]

0.07 0.1 0.2 0.3 0.5 0.7 1 qv [m3/s]

2 3 4 5 6 7 8 9 10 15 20 30 v m/s

0.3 0.5 0.7 1 2 3 5 7 10 20 30 50 Pd


mmWG
To obtain the sound power level spectrum subtract the correction values (dB(A)) shown in the table below at the corresponding octave average frequencies from the value provided in the product performance.

Hz 63 125 250 500 1000 2000 4000 8000


dB 26 19 11 9 4.1 5.4 11 16
Motor selection: to set the motor power to be installed, the absorbed power shown in the graph should be multiplied by a factor of 1,15.

www.solerpalau.com Acoustic cabinet fans CVST


BELT DRIVEN CABINET FANS
CVST Series

Performance curves
– qv: Air volume in m3/h and m3/s.
– psf: Static pressure in mmWG and Pa.
– Dry air at 20ºC and 760 mmHg.
– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

psf psf CVST - 10/6 Only standard version


(Pa) (mmWG) non-certified F400/120

η%

45

53

57

50
1000 100 1
900 0,7 1,4

40
90
800 80
700 0,5 2
70
P
600 kW
60

30
2,5
500 0,3
50 RPM

Lw
400 dB( A
40 A)
2000

1850
300 30 95
1800
75

1600

200 90
20
1400

150 15
85 1200

100 10
700 1000 1500 2000 3000 5000 qv [m3/h]

0.2 0.3 0.4 0.5 0.7 1 1.5 qv [m3/s]

4 5 6 7 8 9 10 15 20 26 30 v m/s

1 2 3 5 7 10 20 30 50 Pd
mmWG
To obtain the sound power level spectrum subtract the correction values (dB(A)) shown in the table below at the corresponding octave average frequencies from the value provided in the product performance.

Hz 63 125 250 500 1000 2000 4000 8000


dB 24 15 11 11 4.4 6 8 15

Motor selection: to set the motor power to be installed, the absorbed power shown in the graph should be multiplied by a factor of 1,15.

Acoustic cabinet fans CVST www.solerpalau.com


BELT DRIVEN CABINET FANS
CVST Series

Performance curves
– qv: Air volume in m3/h and m3/s.
– psf: Static pressure in mmWG and Pa.
– Dry air at 20ºC and 760 mmHg.
– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

psf psf CVST - 12/6 Only standard version


(Pa) (mmWG) non-certified F400/120

η%

50

55

58
2000 200

50
1500 1,5 2
150 3

40
1 4

1000 100
900 90
0,6
800 80

30
700 70 P RPM
kW
600 60
0,3
500 50
2000
400 40
100 1800

300 30 Lw 1600
dB( A
A)
95 1400
75
200 20

1200
150 15 90
80

1000
100 10
90 9 85
80 8
70 8000
7
600 800 1000 1500 2000 3000 5000 7000 qv [m3/h]

0.2 0.3 0.4 0.5 0.7 1 1.5 2 qv [m3/s]

3 4 5 6 7 8 9 10 15 20 30 v m/s

0.5 0.7 1 2 3 5 7 10 20 30 50 Pd
mmWG
To obtain the sound power level spectrum subtract the correction values (dB(A)) shown in the table below at the corresponding octave average frequencies from the value provided in the product performance.

Hz 63 125 250 500 1000 2000 4000 8000


dB 25 16 14 10 3.7 5.5 10 16

Motor selection: to set the motor power to be installed, the absorbed power shown in the graph should be multiplied by a factor of 1,15.

www.solerpalau.com Acoustic cabinet fans CVST


BELT DRIVEN CABINET FANS
CVST Series

Performance curves
– qv: Air volume in m3/h and m3/s.
– psf: Static pressure in mmWG and Pa.
– Dry air at 20ºC and 760 mmHg.
– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

psf psf CVST - 15/8 Only standard version


(Pa) (mmWG) non-certified F400/120

2000 200

64
63
η%

59

55
1500 150
2 3
1,5 4

1000 100
1

40
900 90 6
800 80 0,8
700 70 0,6
600 60 8

500 50 0,4
RPM
P

30
kW
400 40

0,2
300 30 1500
1400
100
1300
200 20 1200

75 95 1100
150 15
Lw 1000
dB A
(A)
900
100 10 90
90 9 800
80 8
80
70 7 85 700
60 6

50 5 600

40 4
1000 1500 2000 3000 5000 7000 10000 qv [m3/h]

0.3 0.4 0.5 0.7 1 1.5 2 3 qv [m3/s]

3 4 5 6 7 8 9 10 15 20 30 v m/s

0.5 0.7 1 1.5 2 3 4 5 7 10 20 30 50 70 Pd


mmWG
To obtain the sound power level spectrum subtract the correction values (dB(A)) shown in the table below at the corresponding octave average frequencies from the value provided in the product performance.

Hz 63 125 250 500 1000 2000 4000 8000


dB 21 10 12 8 4.4 7 11 16

Motor selection: to set the motor power to be installed, the absorbed power shown in the graph should be multiplied by a factor of 1,15.

Acoustic cabinet fans CVST www.solerpalau.com


BELT DRIVEN CABINET FANS
CVST Series

Performance curves
– qv: Air volume in m3/h and m3/s.
– psf: Static pressure in mmWG and Pa.
– Dry air at 20ºC and 760 mmHg.
– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

ps psf CVST - 18/8 Only standard version


(Pa) (mmWG) non-certified F400/120

2000 200

76

70
70
η%

60
2,5 3 4 6
1500 150 2
8

55
1,5 10

1000 100 1
900 90 P
kW RPM
800

45
80
700 0,6
70

600 60 1400
0,4 105
500 50 1300

1200
400 40
100 1100
80

300 Lw 1000
30 dB A
85 (A)

95 900

200 20 800

90
150 15 700

100 10
1000 2000 3000 5000 7000 10000 15000 20000 qv [m3/h]

0.3 0.4 0.5 0.7 1 1.5 2 3 4 5 qv [m3/s]

3 4 5 6 7 8 9 10 15 20 30 40 v m/s

0.3 0.5 0.7 1 2 3 5 7 10 20 30 50 70 Pd


mmWG
To obtain the sound power level spectrum subtract the correction values (dB(A)) shown in the table below at the corresponding octave average frequencies from the value provided in the product performance.

Hz 63 125 250 500 1000 2000 4000 8000


dB 24 11.5 13.4 8.2 4.9 6.2 9.3 16.5

Motor selection: to set the motor power to be installed, the absorbed power shown in the graph should be multiplied by a factor of 1,15.

www.solerpalau.com Acoustic cabinet fans CVST


BELT DRIVEN CABINET FANS
CVST Series

Performance curves
– qv: Air volume in m3/h and m3/s.
– psf: Static pressure in mmWG and Pa.
– Dry air at 20ºC and 760 mmHg.
– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

psf psf CVST - 20/10 Only standard version


(Pa) (mmWG) non-certified F400/120

76
η%

70

76

65
2000 200 10
4 6 8
3
1500 2,5

50
150
2

1,5
1000 100 RPM

40
900 90
800 1
80
700 70 0,8
1400
600 60 0,6 1300
P Lw
500 50 kW dB( A 1200
A)
0,4 100 1100
400 40
1000
300 30
95 900

800
200 20
90
700
75
150 15
85
600

100 10
90 9 500
80 80
8
70 7
1500 2000 3000 5000 7000 10000 20000 30000 qv [m3/h]

0.5 0.7 1 1.5 2 3 4 5 6 7 8 9 qv [m3/s]

3 4 5 6 7 8 9 10 15 20 30 40 v m/s

0.3 0.5 0.7 1 2 3 5 7 10 20 30 50 70 100 Pd


mmWG
To obtain the sound power level spectrum subtract the correction values (dB(A)) shown in the table below at the corresponding octave average frequencies from the value provided in the product performance.

Hz 63 125 250 500 1000 2000 4000 8000


dB 20 14 12 7 4.4 6.5 11 18

Motor selection: to set the motor power to be installed, the absorbed power shown in the graph should be multiplied by a factor of 1,15.

Acoustic cabinet fans CVST www.solerpalau.com


BELT DRIVEN CABINET FANS
CVST Series

Performance curves
– qv: Air volume in m3/h and m3/s.
– psf: Static pressure in mmWG and Pa.
– Dry air at 20ºC and 760 mmHg.
– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

psf psf CVST - 22/11 Only standard version


(Pa) (mmWG) non-certified F400/120

70
60
η%

50
15
10

60
2000 200 8

45
1500 150

4
RPM
1000 100 3

35
900 90
800 80 2 1400
700 70 P
kW 1300
600 105
60
1200
500 Lw
50 1 dB( A 1100
A)

400 40 100 1000

900
300 30

75 95 800

200 20 700
80
90
150 15
600

85
100 10 500
90 9
3000 5000 7000 10000 15000 20000 30000 40000 qv [m3/h]

0.7 1 1.5 2 3 4 5 7 10 qv [m3/s]

3 4 5 6 7 8 9 10 15 20 30 40 v m/s

0.5 0.7 1 2 3 5 7 10 20 30 50 70 100 Pd


mmWG
To obtain the sound power level spectrum subtract the correction values (dB(A)) shown in the table below at the corresponding octave average frequencies from the value provided in the product performance.

Hz 63 125 250 500 1000 2000 4000 8000


dB 21 15 12 7 4.2 6.7 11 17

Motor selection: to set the motor power to be installed, the absorbed power shown in the graph should be multiplied by a factor of 1,15.

www.solerpalau.com Acoustic cabinet fans CVST


BELT DRIVEN CABINET FANS
CVST Series

Performance curves
– qv: Air volume in m3/h and m3/s.
– psf: Static pressure in mmWG and Pa.
– Dry air at 20ºC and 760 mmHg.
– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

psf psf CVST - 25/13 Only standard version


(Pa) (mmWG) non-certified F400/120

62
60
η%

55
2000 200 14
10 20

55
8
7
1500 150
5

45
4
1000 100
3
900 90
800 80
2 RPM
700 70
P

37
600 60 kW

500 50 1100
1
1000
400 40
0,7 Lw
dB( A 900
A)
300 30
800
95

200 700
20
70
90
150 15 600

75 85
100 500
10
90 9
80 8 80
70 7 400
60 6
3000 5000 7000 10000 15000 20000 30000 50000 qv [m3/h]

1 1.5 2 3 4 5 7 10 14 qv [m3/s]

3 4 5 6 7 8 9 10 15 20 30 40 v m/s

0.5 0.7 1 2 3 5 7 10 20 30 50 70 100 Pd


mmWG
To obtain the sound power level spectrum subtract the correction values (dB(A)) shown in the table below at the corresponding octave average frequencies from the value provided in the product performance.

Hz 63 125 250 500 1000 2000 4000 8000


dB 18 15 11 8 4.4 6 11 18

Motor selection: to set the motor power to be installed, the absorbed power shown in the graph should be multiplied by a factor of 1,15.

Acoustic cabinet fans CVST www.solerpalau.com


BELT DRIVEN CABINET FANS
CVST Series

Performance curves
– qv: Air volume in m3/h and m3/s.
– psf: Static pressure in mmWG and Pa.
– Dry air at 20ºC and 760 mmHg.
– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

psf psf CVST - 30/14


(Pa) (mmWG)

60

62
η%

55
1000 100

55
900 90
5 7 10
800 80
700 70 4 14
600 60

45
3
500 50
2
400 40 P
kW 20

1
300 30 RPM

37
200 20 600
75 95
550
150 15 80 Lw
dB( A 500
A)

450
90
100 10
90 9 400
80 8
70 7 350
60 6 85

50 5 300

40 4
4000 5000 7000 10000 15000 20000 30000 50000 qv [m3/h]

1.5 2 3 4 5 6 7 8 9 10 15 qv [m3/s]

3 4 5 6 7 8 9 10 15 20 30 40 v m/s

0.5 0.7 1 2 3 5 7 10 20 30 50 70 Pd
mmWG
To obtain the sound power level spectrum subtract the correction values (dB(A)) shown in the table below at the corresponding octave average frequencies from the value provided in the product performance.

Hz 63 125 250 500 1000 2000 4000 8000


dB 17 17 12 9 4.8 5.1 10 17

Motor selection: to set the motor power to be installed, the absorbed power shown in the graph should be multiplied by a factor of 1,15.

www.solerpalau.com Acoustic cabinet fans CVST


BELT DRIVEN CABINET FANS
CVST Series

Accessories
CTI Model CTI Model cabinet A B
Pitched roof cover CTI-9/4 CVST-9/4 486 803
For outdoor mounted
installations. CTI-10/6 CVST-10/6 557 853
CTI-12/6 CVST-12/6 557 953
CTI-15/8 CVST-15/8 608 1021
CTI-18/8 CVST-18/8 678 1253
CTI-20/10 CVST-20/10 778 1353
CTI-22/11 CVST-22/11 854 1504
CTI-25/13 CVST-25/13 903 1603
CTI-30/14 CVST-30/14 953 1903
Dimensions (mm)

CVD (Discharge) – Model Discharge


CVA (Inlet) cabinet Model A B
Protection guards
Wire protection A CVST-9/4 CVD-9/4 IMP 263 155
guards for mounting CVST-10/6 CVD-10/6 IMP 292 211
on the discharge of CVST-12/6 CVD-12/6 IMP 344 211
the cabinets.
CVST-15/18 CVD-15/18 IMP 406 261
75
B CVST-18/8 275CVD-18/8 IMP 483 271
CVST-20/10 CVD-20/10 IMP 633 336
CVST-22/11 CVD-22/11 IMP 698 371
CVST-25/13 CVD-25/13 IMP 799 426
A CVST-30/14 CVD-30/14 IMP 950 466
Dimensions mm.

75
B 275

APC B Model A B
Circular inlet / outlet APC-10/6 ASP 277 337
protection guards.
°

APC-12/6 ASP 327 355


60

APC-15/8 ASP 404 395


ØA

APC-18/8 ASP 474 442


APC-22/11 ASP 616 512
70 100
APC-25/13 ASP 701 563
Dimensions (mm)

Acoustic cabinet fans CVST www.solerpalau.com