Idoc - Pub - Distance Relay Setting Calculation
Idoc - Pub - Distance Relay Setting Calculation
E
NA
ME CALCULATION FOR THE RELAY REL670
: distace relay setting
System Particulars
A Line Parameters
1 Rated Line Voltage in KV 400
2 Line Length in kms 55
3 Max. Power Flow in the Line in MVA 600.00
4 Positive seqence Resistance in ohms/km 0.0298
5 Positive Sequence Reactance in ohms/km 0.332
6 Zero sequence Resistance in ohms/km 0.1619 Assumed
7 Zero sequence reactance in ohms/km 1.24 as 50% of
8 Zero Sequence Mutual Resistance in ohms/km 0.2281 zero
9 Zero Sequence Mutual Reactance in ohms/km 0.622 sequence
impedanc
B Adjoining Line parameters e
a) Shortest Line
1 Length of shortest line in kms 52
2 Positive Sequence Resistance in ohms/km 0.0298
3 Positive Sequence Reactance in ohms/km 0.332
4 Zero Sequence Resistance in ohms/km 0.1619
5 Zero sequence Reactance in ohms/km 1.24
b) Longest Line
1 Length of longest line 70
2 Positive Sequence Resistance in ohms/km 0.0298
3 Positive Sequence Reactance in ohms/km 0.332
4 Zero Sequence Resistance in ohms/km 0.1619
5 Zero sequence Reactance in ohms/km 1.24
c) Transformer
1 Transformer Impedance in pu N/A
2 Transformer MVA N/A
3 Positive Sequence Resistance in ohms/km N/A
4 Positive Sequence Reactance in ohms/km N/A
5 Zero Sequence Resistance in ohms/km N/A
6 Zero sequence Reactance in ohms/km N/A
d) Shortest Line (Reverse)
1 Length of shortest line in kms 52
2 Positive Sequence Resistance in ohms/km 0.0298
3 Positive Sequence Reactance in ohms/km 0.332
4 Zero Sequence Resistance in ohms/km 0.1619
5 Zero sequence Reactance in ohms/km 1.24
C Source Impedance
FAULT MVA at Local-End (Maximum) 20000
1 FAULT MVA at Local-End (Minimum) 18000
FAULT MVA at Local-End 19000
FAULT MVA at Remote-End (Maximum) 18000
FAULT MVA at Remote-End (Minimum)
( When BC at S/S O is off, this feeder acts as a 16000
2 radial feeder
radial feeder and there will not be any infeed from
the remote end. 17000
3 Source impedance angle in deg 80
4 Angle in radians 1.3968
5 Positive Sequence Resistance at local end, in ohms 0.000
6 Positive Sequence Reactance at local end, in ohms 8.600
7 Positive Sequence Resistance at remote end, in ohms 0.000
8 Positive Sequence Reactance at remote end, in ohms 9.200
D CT/PT Detail
1 CT primary rating in A 3000
2 CT secondary rating in A 1
3 PT primary rating in V 400000
4 PT secondary rating in V 110
E Relay Detail
1 Rated Current in A 1
2 Rated Voltage in V 110
SYSTEM PARAMETERS
Fault Resistance in primary for phase - earth faults 20 Assumed
Fault Resistance in primary for phase - earth faults 25 Assumed
Fault Resistance in primary for phase - earth faults 30 Assumed
Fault Resistance in primary for phase - phase faults 5 Assumed
Fault Resistance in primary for phase - phase faults 8 Assumed
Fault Resistance in primary for phase - phase faults 10 Assumed
Imp Ratio = CTR/PTR 0.825
zone-1 setting - % of the protected line 80%
zone 2 setting - % of the shortest adjoining line 50%
zone53setting
zone setting--%
%of
ofthe
theadjacent
longest adjoining line in reverse
shortest line 120%
direction 25%
Line Impedance in secondary
1 Positive seqence Resistance in ohms 1.3522
2 Positive Sequence Reactance in ohms 15.065
3 Zero sequence Resistance in ohms 7.346
4 Zero sequence reactance in ohms 56.265
5 Zero Sequence Mutual Resistance in ohms 10.35
6 Zero Sequence Mutual Reactance in ohms 28.223
7 Line Angle 85
Shortest Line (Forward)
1 Positive Sequence Resistance in ohms 1.278
2 Positive Sequence Reactance in ohms 14.243
3 Zero Sequence Resistance in ohms 6.946
4 Zero sequence Reactance in ohms 53.196
Shortest Line (Reverse)
1 Positive Sequence Resistance in ohms 1.27842
2 Positive Sequence Reactance in ohms 14.2428
3 Zero Sequence Resistance in ohms 6.94551
4 Zero sequence Reactance in ohms 53.196
Zone-2 setting
1 Positive seqence Resistance in ohms 1.9912
2 Positive Sequence Reactance in ohms 22.1865
3 Zero sequence Resistance in ohms 26.344 13.7445 10.819
4 Zero sequence reactance in ohms 125.198 63.5175 82.863
5 Fault Resistance (ph-ph) 10.5824
6 Fault Resistance (ph-e) 30.7338
Zone-3 setting
1 Positive seqence Resistance in ohms 3.4174
2 Positive Sequence Reactance in ohms 38.0726
3 Zero sequence Resistance in ohms 39.266 20.1586 18.566
4 Zero sequence reactance in ohms 198.643 93.159 142.197
5 Fault Resistance (ph-ph) 15.0848
6 Fault Resistance (ph-e) 40.116933
Zone-5 setting
1 Positive seqence Resistance in ohms 0.319605
2 Positive Sequence Reactance in ohms 3.5607
3 Zero sequence Resistance in ohms 1.7363775
4 Zero sequence reactance in ohms 13.299
5 Fault Resistance (ph-ph) 4.76421
6 Fault Resistance (ph-e) 16.02315
The General Fault Criterion is an overall impedance measuring element with a very high reach and a
long time delay for its tripping function.The GFC can be operated in two modes - the under impedance
mode and the over current mode.In the under impedance mode, the GFC characteristic should, in
general, cover all the impedance measuring zones used for distance protection, regardless of their
directionality. Normally set to 2 times of zone-3 with a limit on the resistive direction so that the
characteristics does not enter the load area.
The reach of the Inner characteristic in the resistive and reactive direction are set so that the inner
characteristic covers completely all the distance protection zones, which are to be blocked by the PSD
function. AtReactive
least 10% of additional
Reach safety
of the Inner margin is considered
characteristic of the Power
swing blocking
Resistive Reachelement = 1.1*X3
of the Inner characteristic of the Power 45.68712
swing blocking
Reactive Reachelement=1.1(2R3+Rf)
of the Outer characteristic of the Power 18.10176
swing blocking element
Resistive Reach of the Outer characteristic of the Power 57.1089
swing blocking element 22.6272
LINE NAME : distace relay setting