WWW - Ubakus.de: Upper Floor Ceiling

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

All statements without guarantee

Upper floor ceiling Ceiling


created on 2.4.2021

Thermal protection Moisture proofing Heat protection


Wood moisture: +0,4% Temperature amplitude damping: 18
U = 0,22 W/(m²K) Dries 5 days phase shift: 10,3 h
Condensate: 44 g/m² Thermal capacity inside: 48 kJ/m²K
EnEV Bestand*: U<0,24 W/(m²K)

excellent insufficient excellent insufficient excellent insufficient

22 7
40 6
291,5

180 5
www.ubakus.de
24 4
3

Commercial use only with Plus-, PDF- or Profi-Option (from 2.99 € / month plus VAT).
12,5
12,5 1 2

80 650
48 682

1 Gypsum Fibreboard (12,5 mm) 4 Vapor retarder sd=5m 7 Spruce (22 mm)
2 Gypsum Fibreboard (12,5 mm) 5 Flexible wood fibre insulation board (180 mm)
3 Installation level (24 mm) 6 Stationary air (40 mm)

Impact of each layer and comparison to reference values


For the following figure, the thermal resistances of the individual layers were converted in millimeters insulation. The scale
refers to an insulation of thermal conductivity 0,039 W/mK.

Spruce, Installation level Spruce, Stationary air (unventilated)


Spruce, Flexible wood fibre insulation board Spruce Equivalent
insulation thickness
(WLS 039)

0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 mm

08 Ti 5 au 40 0,1
41 i ge 0,2 ub W U=
N r U= tand , 2 e Kf
DI O 95 nied s =0 W 0 N bau ,15 MV au a us
zV d Be nd au U G B 202 eu U=0 San ub ivh
hut stan EV ta ub rme EG 6N s E 55 Ne a ss
e s c Be En Bes Ne ä G
E V1 -Hau f W P
20 14 W K .
m
är EnE
V
20 nEV
E En iter au aßn
W - L ub
G 3 lm
GE
E Ne nze
Ei
W
Kf

Inside air : 20,0°C / 50% Thickness: 29,1 cm


Non-heated room: -5,0°C / 80% sd-value: 6,9 m Weight: 58 kg/m²
Surface temperature.: 18,1°C / -4,8°C Heat capacity: 83 kJ/m²K

*Comparison to the maximum U-value according to the german EnEV 2014/2016 for first-time installation or renewal of Oberste Geschossdecken Page 1
(Anlage 3, Tabelle 1, Zeile 4a).
All statements without guarantee

Upper floor ceiling, U=0,22 W/(m²K)

Temperature profile
Temperature profile
20 Temperature
18 Dew point
1
16 Condensate
2
14
12 3
Temperature [°C]

10 4 5 6 7
8
6
4
2
0
-2
-4
-6 www.ubakus.de
-8
0 50 100 150 200 250 300
Inside 0°C [mm]
www.ubakus.de

Commercial use only with Plus-, PDF- or Profi-Option (from 2.99 € / month plus VAT).
Outside 80 650

1 Gypsum Fibreboard (12,5 mm) 4 Vapor retarder sd=5m 7 Spruce (22 mm)
2 Gypsum Fibreboard (12,5 mm) 5 Flexible wood fibre insulation boa...
3 Installation level (24 mm) 6 Stationary air (40 mm)

Left:Temperature and dew-point temperature at the place marked in the right figure. The dew-point indicates the
temperature, at which water vapour condensates. As long as the temperature of the component is everywhere above the dew
point, no condensation occurs. If the curves have contact, condensation occurs at the corresponding position.
Right: The component, drawn to scale.

Layers (from inside to outside)


# Material λ R Temperatur [°C] Weight
[W/mK] [m²K/W] min max [kg/m²]
Thermal contact resistance* 0,100 18,1 20,0
1 1,25 cm
Gypsum Fibreboard 0,320 0,039 17,8 18,9 14,4
2 1,25 cm
Gypsum Fibreboard 0,320 0,039 17,5 18,7 14,4
3 2,4 cm
Installation level 0,150 0,160 15,9 18,5 0,0
2,4 cm
Spruce (6,6%) 0,130 0,185 15,7 17,5 0,7
4 0,05 cm
Vapor retarder sd=5m 0,220 0,002 15,7 17,8 0,1
5 18 cm
Flexible wood fibre insulation board 0,039 4,615 -3,3 17,8 8,0
22 cm
Spruce (Width: 8 cm) 0,130 1,692 -3,5 16,3 10,8
6 4 cm
Stationary air (unventilated) 0,250 0,160 -4,0 -1,9 0,0
7 2,2 cm
Spruce 0,130 0,169 -4,8 -3,5 9,9
Thermal contact resistance* 0,100 -5,0 -4,7
29,15 cm Whole component 4,590 58,4
*Thermal contact resistances according to DIN 6946 for the U-value calculation. Rsi=0,25 and Rse=0,04 according to DIN
4108-3 were used for moisture proofing and temperature profile.

Surface temperature inside (min / average / max): 18,1°C 18,7°C 18,9°C


Surface temperature outside (min / average / max): -4,8°C -4,8°C -4,7°C

Page 2
All statements without guarantee

Upper floor ceiling, U=0,22 W/(m²K)

Moisture proofing
For the calculation of the amount of condensation water, the component was exposed to the following constant climate for
90 days: inside: 20°C und 50% Humidity; outside: -5°C und 80% Humidity. This climate complies with DIN 4108-3.
Under these conditions, a total of 0,043 kg of condensation water per square meter is accumulated.This quantity dries in
summer in 5 days (Drying season according to DIN 4108-3:2018-10).

# Material sd-value Condensate Weight


[m] [kg/m²] [Gew.-%] [kg/m²]
1 1,25 cm Gypsum Fibreboard 0,16 - 14,4
2 1,25 cm Gypsum Fibreboard 0,16 - 14,4
3 2,4 cm Installation level 0,01 - 0,0
2,4 cm Spruce (6,6%) 0,48 - - 0,7
4 0,05 cm Vapor retarder sd=5m 5,00 - 0,1
5 18 cm Flexible wood fibre insulation board 0,18 - 8,0
22 cm Spruce (Width: 8 cm) 4,40 - - 10,8
6 4 cm Stationary air (unventilated) 0,01 0,043 0,0
7 2,2 cm Spruce 1,10 0,043 0,4 9,9
29,15 cm Whole component 6,87 0,043 58,4

Commercial use only with Plus-, PDF- or Profi-Option (from 2.99 € / month plus VAT).
Condensation areas
1 Condensate: 0,044 kg/m² Affected layers: Spruce, Stationary air (unventilated)

Humidity
The temperature of the inside surface is 18,1 °C leading to a relative humidity on the surface of 56%.Mould formation is not
expected under these conditions.
The following figure shows the relative humidity inside the component.

100 Relative humidity (%)


1 saturation point
90
2 Condensate
80
Relative humidity (%)

3
70 4 5 6 7
60
50
40 1
30
20
10 www.ubakus.de
0
0 50 100 150 200 250 300
Inside 0°C [mm]
www.ubakus.de Outside 80 650

1 Gypsum Fibreboard (12,5 mm) 4 Vapor retarder sd=5m 7 Spruce (22 mm)
2 Gypsum Fibreboard (12,5 mm) 5 Flexible wood fibre insulation boa...
3 Installation level (24 mm) 6 Stationary air (40 mm)

Notes: Calculation using the Ubakus 2D-FE method. Convection and the capillarity of the building materials
were not considered. The drying time may take longer under unfavorable conditions (shading, damp / cool
summers) than calculated here.

Page 3
All statements without guarantee

Upper floor ceiling, U=0,22 W/(m²K)

Heat protection
The following results are properties of the tested component alone and do not make any statement about the heat protection
of the entire room:

Temperature profile
This document has been generated by the U-value calculator on www.ubakus.de. If you are harmed by the free use of these contents, the service provider is only liable in case of

36 Temperature at 3pm, 11am and 7am


34 1 Temperature at 7pm, 11pm and 3am
intent and gross negligence on the part of the service provider. For further information, please refer to the terms and conditions at https://www.ubakus.de/agb

32 2 3
30 4 5 6 7 1 Gypsum Fibreboard (12,5 mm)
Temperature [°C]

28 2 Gypsum Fibreboard (12,5 mm)


26 3 Installation level (24 mm)
24 4 Vapor retarder sd=5m
5 Flexible wood fibre insulation board (180 mm)
22
6 Stationary air (40 mm)
20
7 Spruce (22 mm)
18

Commercial use only with Plus-, PDF- or Profi-Option (from 2.99 € / month plus VAT).
16
14
0 50 100 150 200 250 300
Inside [mm]
www.ubakus.de Outside

[°C] The surface temperature during the day


36 Outside
34 Inside
32
30
28
26
24
22
20
18
16
14 Phase shift: 10.3h
12 14 16 18 20 22 24 2 4 6 8 10 12
[time of day]
Top:Temperature profile within the component at different times. From top to bottom, brown lines: at 3 pm, 11 am and 7 am
and red lines at 7 pm , 11 pm and 3 am.
Bottom:Temperature on the outer ( red ) and inner ( blue ) surface in the course of a day. The arrows indicate the location of
the temperature maximum values . The maximum of the inner surface temperature should preferably occur during the
second half of the night.

Phase shift* 10,3 h Heat storage capacity (whole component): 83 kJ/m²K


Amplitude attenuation ** 17,7 Thermal capacity of inner layers: 48 kJ/m²K
TAV *** 0,057
* The phase shift is the time in hours after which the temperature peak of the afternoon reaches the component interior.
** The amplitude attenuation describes the attenuation of the temperature wave when passing through the component. A value of 10
means that the temperature on the outside varies 10x stronger than on the inside, e.g. outside 15-35 °C, inside 24-26 °C.
*** The temperature amplitude ratio TAV is the reciprocal of the attenuation: TAV = 1 / amplitude attenuation
Note: The heat protection of a room is influenced by several factors, but essentially by the direct solar radiation through windows and the
total amount of heat storage capacity (including floor, interior walls and furniture). A single component usually has only a very small
influence on the heat protection of the room.

The calculations presented above have been created for a 1-dimensional cross-section of the component.

Page 4

Powered by TCPDF (www.tcpdf.org)