Professional Documents
Culture Documents
Service Manual: Split Inverter
Service Manual: Split Inverter
R2T
R1T M
R1T
R2T
M
R3T
Service Manual
Split Inverter
RX25GV1NB, RX35GV1NB
FTX25GV1NB, FTX35GV1NB
Daikin Europe NV
ESIE98–07
Table of Contents
1
1 Introduction
Part 1
System Outline 1-1
3
1 General Outline
2 Piping Layout
3 Wiring Layout
Table of Contents i
ESIE98–07
Part 2
1 Functional Description 2-1
1 General Functionality
Part 3
5 Troubleshooting 3-1
1 Troubleshooting
ii Table of Contents
ESIE98–07
Part 4
Commissioning and Test Run 4-1
Part 5
Maintenance 5-1
3 1 Maintenance
Appendix
Drawings
5 A-1
iv Table of Contents
ESIE98–07 Introduction
1 Introduction
Split Inverter The Split Inverter room air conditioners contain an outdoor unit RX25GV1NB controlling indoor unit
FTX25GV1NB or an outdoor unit RX35GV1NB controlling indoor unit FTX35GV1NB. They are
designed for cooling and heating applications. 3
Before starting up the unit for the first time, make sure it has been properly installed. Consult the
Installation manual and ‘Pre-Test Run Checks’ on page 4-3.
You will find the following tools at the back of the manual:
■ a list of drawings. Refer to Appendix Drawings.
■ an index. Refer to Index. 4
Usage of the The present service manual gives you all the information you need to do the necessary repair and
manual maintenance tasks for the Split Inverter room air conditioners. It is intended for and should only be
used by qualified engineers.
It is not intended to replace the technical know-how acquired through training and experience.
5
Using icons Icons are used to attract your attention to specific information. The meaning of each icon is described
in the table below:
Type of
Icon Description
information
Reference A ‘reference’ guides you to other places in this binder or in this manual,
where you will find additional information on a specific topic.
v
Introduction ESIE98–07
1 Using symbols The following symbols are used to clarify the troubleshooting part:
Symbol Description
5 LED is off
0 LED is on
9 Flashing LED
vi
ESIE98–07
1
Part 1
System Outline
3
Introduction This part outlines all the relevant elements in an installation of the Split Inverter room air conditioners.
Once all the elements of the installation are described in short and the installation set-up is understood,
3
a functional description of all elements will be given in the next parts of this book.
Part 1
1
1 General Outline
Introduction In this chapter you will find the outlook drawing and the installation outline of the indoor units
FTX25GV1NB, FTX35GV1NB and the outdoor units RX25GV1NB, RX35GV1NB.
3
Overview This chapter covers the following topics:
4 gas
drain
ø 9.5 mm
ø 18.0 mm
ø 12.7 mm
ø 18.0 mm
heat insulation
15 m
Cooling capacity The cooling capacity is based on indoor temperature of 27 °CDB, 19 °CWB and outdoor temperature
of 35 °CDB, 24 °CWB. Equivalent reference piping length 7.5 m.
Heating capacity The heating capacity is based on indoor temperature of 20 °CDB and outdoor temperature of 7 °CDB,
6 °CWB. Equivalent reference piping length 7.5 m.
Indoor units In the following table you will find the technical specifications for the indoor units:
1
Features FTX25GV1NB FTX35GV1NB
air flow rate cooling/heating H 7.5 m³/min 8.4 m³/min 7.9 m³/min 8.4 m³/min
motor output 13 W 13 W
power factor
temperature control
cooling/heating 95.1 %
microcomputer control
4
dimensions (HxWxD) 250 x 750 x 180 mm³
weight 7 kg
sound pressure cooling/heating 38/30 dBA 38/30 dBA 39/31 dBA 39/31 dBA
level (H/L) 5
1 Outdoor units In the following table you will find the technical specifications of the outdoor units:
model 1YC23ZXD
air flow rate cooling/heating 24.5/14.5 m³/min 21/12.5 m³/min 24.5/14.5 m³/min 21/12.5 m³/min
motor output 22 W
830 W
4.74 A
1,040 W
6.24 A
1,375 W
6.04 A
1,385 W
frequency 50 Hz
voltage 230 V
12 A
3
compressor rated load amperage (RLA) 3.16 A 5.96 A
Note The following list explains some of the items in the table above:
Indoor unit, The figure below displays the outlook of the indoor unit FTX25GV1NB and FTX35GV1NB:
FTX25GV1NB,
FTX35GV1NB
minimum
air flow operation space
50 MIN
60
minimum
service space
50 MIN
182 minimum
service space
750 180
4
name plate
250
terminal strip
3D007309A
ambient temperature thermistor
5
Outdoor unit The figure below displays the outlook of the outdoor unit RX25GV1NB and RX35GV1NB:
RX25GV1NB,
RX35GV1NB
420
100
150
50 operation space 50
209
279
295
150
470 113
50
695 72 10 245
300
100
50
DAIKIN
Model A
RX25GV1B ø 9.5
RX35GV1B ø 12.7
550
23
(ø 6.4 flare connection)
84 64
115 27
(ø A flare connection)
120
Part 1
1
2 Piping Layout
Introduction This chapter explains the different parts of the internal refrigeration circuit.
1
3 M
3 4
4 liquid pipe
3
gas pipe
5
Main parts The numbers in the table below refer to the numbers in the piping diagram above:
refrigeration circuit
N° Part name Function
1 Fan motor The fan motor is a phase controlled 5 step motor. An automatic con-
trol is available.
2 Heat exchanger The heat exchanger is of the multi louvre fin type. Hi-X-tubes and
coated waffle louvre fins are used.
3 Field piping The copper tube of the field piping depends on the model of the
connections indoor unit:
4 Muffler The muffler is used to absorb the refrigerant noise and is installed in
FTX35GV1NB and FTX25GV1ND.
Functional diagram
outdoor unit
The figure below displays the functional diagram of the refrigeration circuit of the outdoor units
RX25GV1B and RX35GV1NB: 1
R2T
9
R1T M
3
3
A
5 RX25GV1NB 9.5
RX35GV1NB 12.7
4
8 4
6.4 mm
6 A
7
R3T 8
1
cooling
heating 5
Main parts The numbers in the table below refer to the numbers in the piping diagram above.
refrigeration circuit
N° Part name Function
2 Heat exchanger The heat exchanger is of the multi louvre fin type. Hi-X-tubes and
coated waffle louvre fins are used.
4 Four-way valve The four-way valve is energized during cooling and defrosting.
5 Filter The filter collects impurities, which may enter the system during
installation and also avoids blockage of the capillaries and other
fine mechanical parts of the unit.
6 Muffler The muffler absorbs the refrigerant noise from the compressor.
7 Accumulator The accumulator separates the gas from the liquid in order to pro-
tect the compressor against liquid pumping.
8 Gas line stop valve The gas line stop valves are used as shut-off valves in case of a
pump-down. The gas line stop valves are equipped with connec-
tors to measure the pressure.
Part 1
1
3 Wiring Layout
Introduction This chapter guides you through the switch box and the wiring diagrams.
3.4 – Main PCB Layout for Indoor Units FTX25GV1NB and FTX35GV1NB
page 1-15
page 1-17
4
3.5 – Main PCB Layout for Outdoor Units RX25GV1NB and RX35GV1NB page 1-20
SSR1
C1R
C2R
3
PCB 2
TRM1
PCB 1
Functionality The following table explains the items in the drawing above:
Item Explanation
PCB 1 printed circuit board 1. Refer to ‘Main board PCB 1’ on page 1-20.
PCB 2 printed circuit board 2. Refer to ‘Main board PCB 2’ on page 1-21.
TRM1 transistor module. Refer to ‘Power transistor check’ on page 3-63,‘Power transis-
tor output current check’ on page 3-64 and ‘Power transistor output voltage
check’ on page 3-65.
FTX35GV1NB
FTX25GV1NB,
Wiring diagram
PCB2 H1
PCB3 PCB1
S25 S24
FU X1M
FTX35GV1NB:
SW7 S21 HA
S1
S7
S27 S26
signal receiver
S31 S32 S6
BLK
WHT
RED
t˚ t˚
R1T R2T
M M indoor
M1S M1F
1–15
5
4
3
1
5
4
3
1
RX25, 35GV1NB
C1R C2R
1–16
+ +
L1R
WHT
RX35GV1NB
RX25GV1NB,
Wiring Layout
WHT
WHT
WHT
Wiring diagram
RED BLU
MRM20
PCB1
X1M
1 1 RED
S MRM10
2 2 WHT HC7 HC8 HC12
indoor 3 3 BLK L
RED SSR1
Q5E Z1C V1 +
L
L N TAB1 TAB2 DB1
F1U BLK
N _
N
GRN/YLW E2 SA1
RX35GV1NB:
GRN/YLW CT1
E1 V2
FU
GRN/YLW
S94 HC10 3.15A
power supply PCB2 1
field wiring BLK +
AC 230V
C89 DB3
1 50Hz 4 HC11
_
YLW
S93 V3
1 HS2
BLK _
+
C82 HS1 TRM1
3
RED
MR MR MRC/W U V W
outdoor S91 S92
L H 1 WHT 1
S20
S70 8 5 3 1 BLK 1 6 1 3 1 2 1 6 U V W N
3 BLK 3 S80 S40 S90
1 4
Z2C S30
BLK
RED
ORG
WHT
Z3C
BLU
BLU
BLU
BLK
BLK
BLK
BLK
BLK
BLK
BRN
RED
RED
RED
YLW
ORG
WHT
M
1 M t t t
BRN
RED
Y1R
M1F
BLU
YLW
U N
Y1E
(outdoor) (disharge)
V W
(condenser) M1C
C82, C89, C1R, C2R: capacitor MRH, MRL, MRM10, MRM20: magnetic relay TRM1: transistor module
CT1: current transformer N: neutral V1, V2, V3: varistor
DB1, DB3: diode bridge PCB1, PCB2: printed circuit board X1M: terminal strip
F1U: field fuse Q1L: overload protector Y1E: electronic expansion valve coil
FU: fuse Q5E: field earth leak detector Y1R: reversing solenoid valve coil
L: live R1T-R3T: thermistor Z1C-Z3C: ferrite core
L1R: reactor S20-S94: connector
M1C: compressor motor SA1: surge arrester
M1F: fan motor SSR1: solid state relay
MRC/W: solid state relay TAB1, TAB2: connector
The following diagram shows the wirings and the electrical parts of the outdoor units RX25GV1NB and
ESIE98–07
3.4 Main PCB Layout for Indoor Units FTX25GV1NB and FTX35GV1NB
1
Main board PCB 1 The drawing below shows PCB 1 of the indoor units FTX25GV1NB and FTX35GV1NB:
SW2 S21
S32
S7
LED A
LED B
S6
S26 3
SW8
S24
S37
4
Symbol Description
Refer to ‘Wiring diagram FTX25GV1NB, FTX35GV1NB’ on page 1-15 for more information concerning
this PCB board.
1 Main board PCB 2 The drawing below shows PCB 2 of the indoor units FTX25GV1NB and FTX35GV1NB:
S36
S1
Symbol Description
4 S1 connector fan motor M1F
Refer to ‘Wiring diagram FTX25GV1NB, FTX35GV1NB’ on page 1-15 for more information concerning
this PCB board.
5
Main board PCB 3 The drawing below shows PCB 3 of the indoor units FTX25GV1NB and FTX35GV1NB:
S25
Symbol Description
Refer to ‘Wiring diagram FTX25GV1NB, FTX35GV1NB’ on page 1-15 for more information concerning
this PCB board.
Mail
Main board PCB 4 The drawing below shows PCB 4 of the indoor units FTX25GV1NB and FTX35GV1NB:
1
SW7 S31 WLU S27
Symbol Description
Refer to ‘Wiring diagram FTX25GV1NB, FTX35GV1NB’ on page 1-15 for more information concerning
4
this PCB board.
3.5 Main PCB Layout for Outdoor Units RX25GV1NB and RX35GV1NB
1
Main board PCB 1 The drawing below shows PCB 1 of the outdoor units RX25GV1NB and RX35GV1NB:
S30 S40
S80
S20
3 S2
S92
SW2
SW1
LED A
LED 1
4 LED 2
LED 3
LED 4
S90 S1 S50
Symbol Description
5 S1
S2
factory use
factory use
S20 connector for expansion valve of room Y1E
S30 (floating) connector for compressor motor M1C
S40 connector for overload protector Q1L
S50 cutting wire for long pipe
S80 connector for 4-way valve Y1R
S90 connector for outdoor ambient temperature thermistor R1T (1-2)
connector for outdoor heat exchanger thermistor R2T (3-4)
connector for discharge pipe thermistor R3T (5-6)
S92 communication connector between PCB 1 and PCB 2
SW1 forced operation switch (ON/OFF)
LED A
LED 1
fault indication
LED 2
LED 3
LED 4
Refer to ‘Wiring diagram RX25GV1NB, RX35GV1NB’ on page 1-16 for more information concerning
this PCB board.
Main board PCB 2 The drawing below shows PCB 2 of the outdoor units RX25GV1NB and RX35GV1NB:
1
S70 S93 S94
3
S91
Symbol Description
Refer to ‘Wiring diagram RX25GV1NB, RX35GV1NB’ on page 1-16 for more information concerning
this PCB board.
5
4
Part 2
Functional Description
2
Introduction This part gives more detailed information on the functions and controls in the unit. This information is
used as background information for troubleshooting.
3
What is in this part? This parts contains the following chapters:
Part 2
1
1 General Functionality
2
1.1 What Is in This Chapter
Introduction This chapter details on the control functions of the system. Understanding these functions is vital when
diagnosing a malfunction is related to the functional control.
3
Overview This chapter covers the following topics:
R2T
3 R1T M
R1T
R2T
M
4
R3T
cooling
heating
5
Frequency control The following table shows the thermistors that control the frequency:
Outdoor Indoor
Discharge Outdoor heat Indoor heat
switch box ambient ambient
Controls pipe exchanger exchanger
thermistor temperature temperature
thermistor thermistor thermistor
thermistor thermistor
Discharge tempera- _ 0 _ _ _ _
ture control. Refer
to page 2-23.
Freeze-up preven- _ _ _ _ 0 _
tion. Refer to
page 2-23.
Control tempera- 0 _ _ _ _ _
ture switch box.
Refer to page 2-26.
Maximum _ _ 0 _ _ _
frequency control in
function of outdoor
ambient
temperature. Refer
to page 2-23.
Outdoor Indoor
Controls
switch box
thermistor
Discharge
pipe
Outdoor heat
exchanger
ambient
temperature
ambient
temperature
Indoor heat
exchanger 1
thermistor thermistor thermistor
thermistor thermistor
Defrost. Refer to _ _ 0 0 _ 0
page 2-14.
1 Expansion valve
control
The following table shows the thermistors that control the expansion valve:
Disconnected High
Defrost Feed back
Thermistors Symbol discharge pipe discharge
operation control
control temperature
Overview The following table shows the different control modes of the Split inverter room air conditioners:
2
Mode Item
Dry keep
Heating
3
Defrosting (automatic)
Stop mode:
■ Pre-heat operation. Refer to ‘Pre-heat operation’ on page 2-21.
■ Stop 4
Forced operating mode Forced cooling
Forced heating
The outdoor unit retains the operating mode, when the thermostat is switched off.
Phase Description
4 1
2
The single phase power supply in AC is converted into DC.
The single phase power supply DC is converted into a three phase shopped DC voltage
with a variable frequency.
■ When the frequency increases, the rotation speed of the compressor increases
resulting in an increased refrigerant circulation. This leads to a higher amount of the
heat exchange per unit.
5 ■ When the frequency decreases, the rotation speed of the compressor decreases
resulting in a decreased refrigerant circulation. This leads to a lower amount of the
heat exchange per unit.
Drawing of inverter The following drawing shows a schematic view of the inverter principle:
max. freq.=108 Hz
Amount of heat high speed Amount of heat
exchanged (large) exchanged (large)
high f
power
power
AC
DC
low f
Amount of heat Amount of heat
exchanged (small) low speed exchanged (small)
min. freq.=15 Hz (cooling)
16 Hz (heating)
freq=cte 50 Hz freq=variable capacity=
60 Hz variable
3
Start seconds
60 120 300
■ Even during extreme cold weather, the high capacity is achieved. It is maintained even when the
■
outside temperature is 0°C.
Comfortable air conditioning
4
A detailed adjustment is integrated to ensure a fixed room temperature. It is possible to air
condition with a small room temperature variation.
■ Energy saving heating and cooling
Once the set temperature is reached, the energy saving operation enables to maintain the room
temperature at low power.
5
Frequency limits The following table shows the functions that define the minimum and maximum frequency:
Initial setting The initial frequency is automatically set in the following cases:
■ compressor start (except for defrost)
■ compressor start after defrost reset
■ change-over from cooling to heating based on the outdoor ambient temperature and discharge
pipe temperature.
1 Forced
cooling/heating
For more information, refer to ‘Forced mode’ on page 2-15.
operation
■
The swing compressor has 1 piston.
The innovative structure adapts the use of HFC-refrigerant by effective lubrication of sliding
2
surfaces. For rotary compressors, adaptation to HFC requires major modifications.
■ The compressor uses a DC motor.
Swing
2 Magnet
N
Iron
S
Iron is pulled towards the magnet.
3
Introduction The reluctance DC motor uses a neodymium magnet (= a magnet with a higher magnetic power than
the ferrite magnet) which produces a magnetic torque and a reluctance torque (= a rotating force
created by the change in the attraction between iron and magnet). The combined force generates a
powerful rotation. The motor is especially effective in saving energy consumption in the low frequency
4 range.
Motor efficiency The following drawing shows the difference in efficiency between the reluctance DC motor, the DC
motor and AC motor:
Reluctance DC motor
Motor efficiency (%)
5 90
80
Conventional DC motor
70
60 AC motor
50
Rotor structure The following drawings show the difference in structure between the conventional DC motor and the
reluctance DC motor: 1
Conventional DC motor Reluctance DC motor
N S
S 2
S N
N
N S S N
N
N S
S N
Iron
S
3
Neodymium
4
Principle Magnetic lines produced by electromagnets pass through iron easily but not through air or magnet.
When magnets are embedded deep into the rotor of a motor, the magnetic lines of force on the south
pole of the magnet extend tangentially. The bent magnetic lines evoke a force in order to straighten.
This creates a second rotating force which a conventional motor does not generate. Since this force
is generated by the difference in resistance against magnetic lines, it is called a reluctance torque.
5
Working The following drawing shows the working principle:
Iron
S
Rotating force
Condition Description
4 Conditions The following table shows the different conditions on which defrost control is based:
Conditions Description
5 2 ■
■
Tambient outdoor < 5 °C
Toutdoor heat exchanger < (-5 + Tambient outdoor x 0,4)
■ check if Tindoor heat exchanger decreases 6 times every 10 seconds
3 ■ Tambient outdoor ≥ 5 °C
■ Toutdoor heat exchanger < -3 °C
■ check if Tindoor heat exchanger decreases 6 times every 10 seconds
■ not in the 3-minute stand-by mode ■ not in the 3-minute stand-by mode
■ normal operation mode ■ normal operation mode 2
Conditions ■ outdoor unit off ■ outdoor unit off
■ no malfunction in the outdoor unit ■ no malfunction in the outdoor unit
■ forced mode: cooling mode. ■ forced mode: heating mode.
Press the forced operation switch SW2 to Press the forced operation switch SW2 to
start the following items: start the following items: 3
■ command frequency: 66 Hz ■ command frequency: 66 Hz
■ expansion valve opening: depending ■ expansion valve opening: depending
on capacity of operating room on capacity of operating room
Start
Adjustment ■ timer: 60-minute ■ timer: 60-minute
■
■
fan speed: H
swing flap: preservation of last setting
■
■
fan speed: H
swing flap: preservation of last setting
4
■ indoor adjustment: send forced mode ■ indoor adjustment: send forced mode
to unit. to unit.
Press the forced operation switch again Press the forced operation switch again
Reset
or after 60 minutes. or after 60 minutes.
5
The protective functions overrule the forced mode.
Diffuser The diffuser enables the air coming out of the indoor unit to reach all surfaces in cooling mode.
2
Heating mode During heating mode, the large flap enables direct warm air straight downwards. The diffuser presses
the warm air above the floor to reach the entire room.
Cooling mode During cooling mode, the diffuser retracts into the indoor unit. This enables a distribution of cooled air
Louvres The louvres, made of elastic synthetic resin, provide a wide range of airflow that guarantees a
comfortable air distribution.
4 Autoswing The following table explains the autoswing process for heating and cooling:
2 When the heat exchanger reaches 34°C or higher, the flap moves
to send air straight down. Refer to (a) in the drawing below.
4
Example The following example explains the difference between a swing-off start and a swing-on start for
heating mode.
Item Process
swing-off
start Swing OFF
Swing ON
Upper-limit swing position
(fully open) (20°)
Value in Value in
Value in memory
memory
Initial value or previous setting memory
Lower-limit swing position
(b)
Straight down air flow (80°)
Thermostat OFF Thermostat ON
Directed towards back wall (90°)
(a)
Closed
Operation ON
Item Process
1 swing-on Swing OFF Thermostat OFF (defrost start)
Upper-limit swing position
start (fully open) (20°) Value in
memory
Closed
Swing ON Operation STOP
■ The movements of the large and small flap are not linked. They move with a time delay of several
seconds.
3 ■ The diffuser and flaps cover the air outlet when the unit is not operating.
For more information about Hall IC, refer to ‘Hall IC check (A6)’ on page 3-60.
Phase steps Phase control and fan speed control contains 8 steps: LLL, LL, L, ML, M, HM, H and HH.
2
Step Cooling Heating Dry mode
LL
L
3
ML
MH
H 4
HH
= Within this range the airflow rate is automatically controlled when the AIRFLOW ADJUSTING
button is set to AUTOMATIC
When there is no operation and the night set mode turns on, the step is low. Refer to ‘Night set mode’
on page 2-21.
Automatic air flow The following drawing explains the principle of fan speed control for cooling:
control for cooling fan speed
M
+2˚C Temperature difference between
ML
+1.5˚C ambient and set temperature
+1˚C
L
+0.5˚C
Thermostat
setting
temperature Phase control
ON
OFF
28 °C 34 °C outdoor heat exchanger temperature
3 Fan off delay When the compressor turns off and Toutdoor ambient > 20 °C, the outdoor fan stays running at the same
speed for 30 seconds.
Fan speed modes The following table explains the fan control in normal and forced mode:
Forced H
Fan control in The following table explains the fan steps in cooling mode:
cooling mode
5 Tambient outdoor
Frequency
> 37 °C H H H
> 18 °C and ≤ 37 °C L H H
> 0 °C and ≤ 18 °C L L H
Fan control in The following table explains the fan steps in heating mode:
heating mode
Frequency
Tambient outdoor
≤ 44 Hz > 44 Hz
≤ 5 °C H H
> 5 °C L H
warm-up
2
control for
10˚C compressor
OFF ON OFF
3
Hot start function During defrosting or when the thermostat is on in heating mode, the indoor heat exchanger
temperature is measured to avoid cold draft.
Dry mode The dry mode removes humidity while maintaining the room temperature. The temperature and fan
cannot be regulated during dry mode.
ON point
0,5˚C
4
Frequency switching point
OFF point
5 min. 5 min.
Compressor control 5
Low Hz
55 Hz
Extra low Hz
Extra low Hz
Extra low Hz
Extra low Hz
Night set mode The night set mode is activated when the off timer is set. It switches the fan speed to low, to minimize
the noise.
2
Timer operation 1 hour later
Night set circuit on
Part 2
1.14 Frequency Control
Frequency The following table shows the different functions, which are controlled by decreasing or increasing the frequency:
controlled
functions Sensor
Function Why? How? Set Reset Malfunction
Thermistor
High fin temperature control switch box thermistor (R4T) To protect the switch box against a high By setting a high frequency T fin > 82 °C T fin > 75 °C -
temperature. limit.
Discharge temperature control discharge temperature To protect the compressor. By setting a high frequency T discharge pipe > 115 °C T discharge pipe < 107 °C T discharge pipe > 124 °C
thermistor (R3T) limit. UNIT STOP
Low outdoor temperature control outdoor ambient thermistor To avoid condensation in cooling mode. By setting a high frequency Toutdoor ambient < 25 °C T outdoor ambient > 33 °C -
(R1T) limit.
This control is not executed when
the unit is in forced cooling mode or in test
mode.
High pressure limitation in heat- ■ outdoor temperature To control the pressure. By setting a high frequency ■ heating mode ■ compressor stop -
ing thermistor (R1T) limit.
■ Toutdoor > 16 °C ■ timer delay (70 s) has
■ indoor heat exchanger passed
thermistor (R2T) ■ Tindoor heat exchanger >
22 °C
■ compressor on
Freeze-up prevention indoor heat exchanger To prevent the freezing up of the indoor By setting a high frequency ■ during cooling Tindoor heat exchanger > 13 °C Tindoor heat exchanger < 0 °C
thermistor (R2T) unit in cooling mode. limit. for 2 seconds (result: compressor stop)
■ 0 °C < Tindoor heat
exchanger < 13 °C
Peak cut off indoor heat exchanger To prevent an abnormal high temperature By setting a high frequency ■ during heating Tindoor heat exchanger < 50 °C Tindoor heat exchanger > 67 °C
thermistor (R2T) on the indoor heat exchanger in heating limit. for 2 seconds (result: compressor stop)
■ 50 °C < Tindoor heat
mode.
exchanger <67 °C
Control Expansion valve control is used to maintain a constant discharge pipe temperature and to regulate an equalized pressure in the system. The expansion valve is set by the frequency and the outdoor ambient temperature.
Initialization The expansion valve is initialized when the power is switched on. The initialization contains:
■ the closure of the expansion valve by 650 pulses (current opening = 0).
■ after closure of the expansion valve, it opens again by 150 pulses for normal working.
Limits The following table shows the limits of the expansion valve opening:
Sequence The following flowchart shows a simplified view of the expansion valve control:
power is on initialization compressor on open control feedback control compressor stop pressure equalization control
Open control The following table shows the functions of open control:
Sensor
Function Why? How? Set Reset
Thermistor
Expansion valve control discharge pipe thermistor To protect the compressor. By opening the expansion valve for 10 T discharge pipe > 112 °C T discharge pipe < 107 °C
during high discharge pipe (R3T) pulses every 30 seconds.
temperature
Disconnected The following table shows the functions of disconnected discharge thermistor control:
discharge
thermistor control Sensor
Function Why? How? Set Reset
Thermistor
Disconnected discharge ■ discharge pipe To detect disconnection of the By checking the difference between the T discharge pipe < Toutdoor during cooling T discharge pipe > Tcoil
pipe control thermistor (R3T) discharge pipe thermistor. discharge pipe temperature and the coil
■ outdoor heat exchanger
temperature. T discharge pipe > Toutdoor during heating
thermistor (R2T) This control is
executed 5 times before
■ indoor heat exchanger going into failure.
thermistor (R1T)
Feedback control The following table shows the functions of feedback control:
Sensor
Function Why? How? Set Reset
Thermistor
feedback control ■ discharge pipe To calculate an optimum discharge By checking the outdoor ambient - -
thermistor (R3T) temperature. temperature and the indoor heat
exchanger temperature in order to
■ outdoor heat exchanger
calculate an optimum discharge
(R1T)
temperature.
■ indoor heat exchanger
thermistor (R2T)
discharge temperature discharge pipe thermistor To protect the compressor. By reducing the frequency. ■ at compressor start: T discharge pipe >115 °C T discharge pipe < 107 °C
control (R3T)
■ at compressor stop: T discharge pipe >124 °C
Other control The following table shows the other different functions, which are not frequency or expansion valve controlled:
functions
Sensor
Function Why? How? Set Reset Malfunction
Thermistor
four-way valve - To cool and defrost. By energizing the coil of the ■ start of cooling operation ■ compressor stop -
operation four-way valve.
■ start of defrost operation ■ start of heating operation
■ forced cooling
fin temperature control switch box thermistor (R4T) To protect the inverter By switching off the compressor Tfin > 87 °C Tfin < 72 °C -
system. and turning on the outdoor fan into (FAN STOP)
H-mode.
switch box control switch box thermistor (R4T) To protect the inverter By switching the outdoor fan into ■ compressor off Tfin > 78 °C Tfin > 80 °C
system. H-mode. (FAN STOP)
■ Tfin > 78 °C
■ crankcase heater off
4
Part 3
Troubleshooting
Introduction The purpose of this chapter is to explain the fault codes on the remote controller and how you can trace
and correct errors.
3
What is in this part? This parts contains the following chapters:
Part 3
1
1 Troubleshooting
Introduction When a problem occurs, you have to check all possible faults. This chapter gives a general idea of
where to look for defects or causes.
Not all repair procedures are described. Some procedures are considered common practice.
3
Overview This chapter covers the following topics:
This is to protect the air conditioner. You should wait for about 3 minutes.
No direct hot air After starting the heating operation, hot air does not flow out directly.
You should wait 1 to 4 minutes, because the air conditioning is warming up to prevent cold draft.
Sounds Explanation
gissing sound The refrigerant flow stops or changes inside the unit.
snapping sound The indoor unit shrinks or expands slightly due to temperature
4 changes.
Heating operation The heating operation can stop suddenly emitting a flowing sound, because the system is defrosting.
stops suddenly You should wait for about 3 to 8 minutes.
5 Water or steam The following table explains why water or steam can escape out of the outdoor unit:
escapes out the
outdoor unit Case Explanation
heating mode The frost on the outdoor unit melts into water or steam
when the air conditioner is in defrost operation.
cooling or dry mode Moisture in the air condenses into water on the cool
surface of the outdoor unit piping and starts dripping.
The problem can be eliminated by insulating the
service valves and piping connections.
Mist escapes out Mist can come out the indoor unit, when the air in the room is cooled into mist by the cold air flow during
the indoor unit cooling operation.
Odour escapes out An odour can escape out of the indoor unit when smells of the room, furniture or cigarettes are
of the indoor unit absorbed into the unit and discharged with the air flow. You should:
■ Clean oil
■ Change filter
■ Check drain
If the problem is not solved, contact your dealer.
Case Explanation
1
After operation stop The outdoor fan continues rotating for another 30
seconds to cool the electronics.
While the air conditioner is not in When the outdoor temperature is 49 °C, the outdoor fan
operation starts rotating to protect the system.
Operation stops To protect the system, the air conditioner may stop operating on a sudden large voltage fluctuation. It
suddenly automatically starts operation in about 3 minutes.
(operation lamp on)
1.3 Safeties
1
Emergency button You can use the emergency button on the front panel of the indoor unit when the remote controller is
not available or its batteries have run out. Press the emergency button to start automatic mode
(automatic fan speed, temperature set point of 22 °C and preservation of the last swing flap position)
and press the button again to stop.
emergency button
3 Operation lamp The operation lamp flashes when the following errors are detected:
■ When the unit is disabled because of activation of a protection device or malfunction of the
thermistors. Refer to ‘Overview of Fault Indications on Indoor Units’ on page 3-23 and ‘Overview
of Fault Indications on Outdoor Units’ on page 3-35.
■ When a transmission error occurs between the indoor and outdoor unit.
Step Action
TIME
DOWN 2
UP
OFF TIMER
ON TIMER CANCEL
FAN
3
MODE
UP
OFF TIMER
Step Action
UP
OFF TIMER
4
5 Press the MODE button (1) again to go
to test mode (30 minutes). To end test FAN
mode directly, press the ON/OFF but- 1
ton. MODE
Step Action
FAN
3 MODE
4 2 Press the timer cancel button repeatedly until a continuous beep is produced.
3 Refer to ‘Overview of Fault Indications on Indoor Units’ on page 3-23 and ‘Overview of
Fault Indications on Outdoor Units’ on page 3-35 to analyse the fault.
Press the timer cancel button for 5 seconds to cancel the code display.
5 The code display also cancels itself when it is not pressed for 1 minute.
Part 3
1
2 Overview of General Problems
Introduction This chapter explains the troubleshooting sequence of problems that can occur without fault indication.
Begin
1
Check the power supply voltage.
Yes 4
Is the power cable 2.5 mm 2 and No
is it properly connected? Connect the correct cable.
Yes
5
Are the indoor-outdoor unit No
combinations correct? Connect matching units. Refer to 1-4.
Yes
Yes
Yes
No
Is the operation lamp
flashing? Refer to 3-6.
Yes
End
Charge an additional refrigerant amount of 20g/m for a pipe is longer than 10 m. When the pipe is
longer than 10m, cut jumper S50 refer to page 1-17.
5 Is the temperature
setting appropriate?
Refer to 4-7.
No
Switch the thermostat off.
Set the appropriate
temperature.
Is the indoor-outdoor No
unit combination Connect the matching units.
correct? Refer to1-4.
Yes
Yes
No
Is the unit capacity Replace or add a unit.
adequate for load?
Yes
Yes
End
Yes
Yes
Yes
5 Is the operation
space provided ?
Refer to 1-8.
No
Provide required space.
Yes
Yes
Yes
End
No
Yes
Is the sound generated by Add cushioning material on the
No
Yes
Are the pipes not Add cushioning material
properly connected? and secure with saddles.
4 No
No
No
No
No
Vacuum dry the unit and charge correct
amount of refrigerant.
End
Abnormal The air conditioner may malfunction with lightning or radio waves. To check, proceed as follows:
functioning
Step Action
3 Check the operation by trying to operate using the remote controller. If there is still no
operation, check the remote controller. Refer to ‘Overview of Fault Indications on Indoor
Units’ on page 3-23 and ‘Overview of Fault Indications on Outdoor Units’ on page 3-35.
coil
pilot body
3 piston
needle
bleed hole
piston body
4 tube to the
inside coil 3 2
tube to the
outside coil
compressor
suction tube to the
compressor
5 Normal cooling The following table explains the normal condition of the four-way valve in cooling mode:
Discharge Suction Tube to Tube to Left pilot back Right pilot front
tube tube inside coil outside coil capillary tube capillary tube
1 2 3 4 5 6
Normal heating The following table explains the normal condition of the four-way valve in heating mode:
Discharge Suction Tube to Tube to Left pilot back Right pilot front
tube tube inside coil outside coil capillary tube capillary tube
1 2 3 4 5 6
1 2 3 4 5 6 Description
Hot Cool Cool as Hot as Temperature Hot The pilot valve works correctly.
in in of valve There is dirt in one bleed hole. To
column column body resolve:
2 1
1
2
Deenergize the solenoid.
Raise the head pressure.
3
3 Reenergize the solenoid to
loosen the dirt.
4 If unsuccessful, remove the
valve and wash it out. Check
on air before reinstalling. If
there is still no movement,
4
replace the valve, add a new
strainer to the discharge tube
and mount the valve
horizontally.
The piston cup head leaks. To
resolve: 5
1 Stop the unit.
2 After pressure equalization,
restart with energized
solenoid.
3 If the valve shifts, reattempt
with the compressor on. If
there is no reversal, replace
the valve.
Hot Cool Cool as Hot as Temperature Temperature The pilot tubes are clogged. To
in in of valve of valve resolve:
column column body body
1 Raise the head pressure.
2 1
2 Operate the solenoid to free
the dirt.
3 If there is still no shift, replace
the valve.
Hot Cool Cool as Hot as Hot Hot Both parts of pilot are still open.
in in To resolve:
column column
1 Raise the head pressure.
2 1
2 Operate the solenoid to free
the partially clogged port.
3 If there is still no shift, replace
the valve.
Warm Cool Cool as Hot as Temperature Warm The compressor is defective.
in in of valve
column column body
2 1
Hot Warm Warm Warm Temperature Hot There is not enough pressure
of valve differential at start of stroke or
body not enough flow to maintain the
pressure differential. To resolve:
1 Check the unit for correct
operating pressure and
charge.
2 Raise the head pressure.
3 If there is still no shift, replace
3 the valve.
There is body damage. Replace
the valve.
Hot Warm Warm Hot Hot Hot Both parts of pilot are still open.
To resolve:
4 1
2
Raise the head pressure.
Operate the solenoid to free
the partially clogged port.
3 If there is still no shift, replace
the valve.
Hot Hot Hot Hot Temperature Hot There is body damage. Replace
5 of valve
body
the valve.
The valve hung up at mid-stroke.
The pumping volume of the
compressor is not sufficient to
maintain the reversal. To
resolve:
1 Raise the head pressure.
2 Operate the solenoid.
3 If there is still no shift, replace
the valve.
Hot Hot Hot Hot Hot Hot Both parts of pilot are still open.
To resolve:
1 Raise the head pressure.
2 Operate the solenoid to the
free partially clogged port.
3 If there is still no shift, replace
the valve.
1 2 3 4 5 6 Description
Hot Cool Hot as Cool as Temperature Warmer At the end of the slide, the piston
in in of valve than valve needle is leaking. To resolve:
column 1 column 1 body body
1 Operate the valve several
times.
2 Recheck.
3 If there is an excessive leak,
replace the valve.
Hot Cool Hot as Cool as Warmer than Warmer The piston needle and pilot nee-
3 in
column 1
in
column 1
valve body than valve
body
dle are leaking. To resolve:
1 Operate the valve several
times.
2 Recheck.
3 If there is an excessive leak,
replace the valve.
4
Part 3
1
3 Overview of Fault Indications on Indoor Units
Introduction In the first stage of the troubleshooting sequence it is important to interpret the fault indication on the
remote controller display. This will help you to find the cause of the problem for the indoor units.
■ The fault indication of the indoor unit has priority on the outdoor unit.
3
■ Some of the faults are not directly indicated on the remote controller, because they need to be
generated several times. If you want to check immediately, you can check the LED indication on
the indoor PCB.
LED indication The following table shows the LED indication of the indoor unit:
normal 9 9 -
fault 1 8 8 Error method 1 on this page.
fault 2 0 ✽ Error method 2 on this page.
fault 3 9 0 Error method 3 on the following
3 page.
Error method 1 The indoor unit evaluates the zero-cross detection of the power supply.
Error generation 1 The error is generated when there is no zero-cross detection for ± 10s.
4
Causes The following list shows the possible causes:
■ Faulty indoor PCB 1 or PCB 2.
■ Faulty connector connection (S36/S37).
No
Is it connected Correct the connection.
properly?
Yes
End
Error method 2 The internal program checks the working of the microcomputer to detect this error.
Error generation 2 The error is generated when the microcomputer program does not function properly.
Yes
No
3
Is the grounding
proper? Provide proper grounding.
Yes
Error method 3 The system checks the communication signal between the indoor and outdoor unit.
5
Error generation 3 The error is generated when the transmission circuit remains on.
Causes The cause for this error can be a faulty indoor unit PCB 1.
LED indication The following table shows the LED indication of the indoor unit
normal 9 9
fault 9 9
During the cooling operation, freeze-up preven- During the cooling operation, the error is
tion is activated according to the temperature generated when Tindoor heat exchanger < 0°C.
detected by the indoor heat exchanger thermis-
tor (R2T).
4 During the heating operation, high pressure During the heating operation, the error is
control is activated according to the temperature generated when Tindoor heat exchanger > 67°C.
detected by the indoor heat exchanger thermis-
tor (R2T).
Yes
Check the intake air filter.
Yes 3
Check the dust accumulation
on the indoor heat exchanger.
No
Is it clean? Clean the heat exchanger.
Yes 4
Check the indoor heat exchanger
thermistor R2T.
No
Is the amount of
Recharge correct amount.
refrigerant correct?
Yes
End
LED indication The following table shows the LED indication of the indoor unit:
normal 9 9
fault 9 9
Error method During fan motor operation, hall IC detects the rotation speed to determine abnormal fan motor
3 operation.
Error generation During maximum fan motor speed, the error is generated when the detected speed is less than 50%
of the power full mode.
No
Does the fan rotate? Rotate the fan by hand.
Yes
Is there an output?
No Replace the fan
motor or indoor
3
PCB 2.
Yes
Check the fan motor voltage between the red and black wire of S1.
No
Is the voltage 130V? Replace indoor
PCB 2. 4
Yes
Replace the fan motor.
No
Does it rotate
smoothly?
Replace the fan
motor. 5
Yes
Yes
Yes
End
LED indication The following table shows the LED indication of the indoor unit:
normal 9 9
fault 9 9
Error method The relation between the temperatures detected by the thermistors and the resistance of the
3 thermistors is used to determine the errors.
Error generation During compressor operation, the error is generated when the thermistor input is more than 4.96 V or
less than 0.04 V.
Begin
No
Is it connected
properly? Correct the connection.
Yes
No
Replace the thermistor.
Is it normal?
(Replace the PCB.)
Yes
Replace the PCB to which the thermistor is
connected.
End
LED indication The following table shows the LED indication of the indoor unit:
normal 9 9
fault 8 ✽
Check LED B.
Yes
No
3 Is the power supply voltage
230V AC with a fluctuation of
10%?
Correct the power supply voltage.
Yes
4 Is it discolored
or cracked ?
No
Replace the varistor V1.
Yes
5 Is there conductivity?
No
Replace the fuse.
Yes
No
Does the same LED
indication appear again? Check the grounding.
Yes
Is the grounding No Provide proper
Check the connection between proper? grounding.
indoor PCB 1 and indoor PCB 2.
Yes
Yes
No
Is it approximately Replace indoor PCB 2.
5V± – 0.5V?
Yes
End
LED indication The following table shows the LED indication of the indoor unit:
normal 9 9
fault 9 8
Error method The data received from the outdoor unit through the indoor-outdoor signal transmission is checked to
detect transmission errors. 3
Error generation The error is generated when the data from the outdoor unit cannot be received normally or when the
content of the data is abnormal.
■
‘Power supply waveform check’ on page 3-62.
Indoor-outdoor signal transmission error due to a broken connection wire between the indoor and
5
the outdoor units.
Begin
Check the connection wires between the indoor and outdoor unit.
Yes
Check the voltage of the connection wires between the indoor and outdoor unit.
(between 1-2, 2-3)
3 Is the voltage No
different from 0 V? Replace the wires.
Yes
4
No
Is LED A Troubleshoot the outdoor unit. Refer to 3-35.
flashing?
Yes
5 Refer to 3-62.
No
Is there disturbance? Replace PCB 1 and PCB 2 of the indoor unit.
Yes
End
Part 3
1
4 Overview of Fault Indications on Outdoor Units
Introduction In the first stage of the troubleshooting sequence, it is important to interpret the fault indication on the
remote controller display. This will help you to find the cause of the problem for the outdoor units.
■ The fault indication of the indoor unit has priority. Refer to ‘Overview of Fault Indications on Indoor
3
Units’ on page 3-23.
■ Some of the faults are not directly indicated on the remote controller, because they need to be
generated several times. If you want to check immediately, you can check the LED indication on
the indoor PCB.
LED indication The following table shows the LED indication of the outdoor unit:
Condition LED A (green) LED 1 (red) LED 2 (red) LED 3 (red) LED 4 (red)
normal 9 8 8 8 8
fault 9 8 8 0 0
Error method The input current checked by the current transformer and the frequency control are used to detect gas
3 shortage.
Error generation The error is generated during a check of the input current, when:
I input< [12/256 (A/Hz) x foperating-1.75] when foperating > 74 Hz for a period of 14 seconds.
The timer automatically resets when one of the following errors does not occur within a period of 60
minutes of accumulated runtime after the first error generation:
■ overload activation E5
■ radiation fin temperature rise L4
5 ■ gas shortage detection U0
■ compressor start-up error E6
■ current transformer error H8
■ thermistor abnormality J3.
Begin
1
Check the discharge pipe thermistor R3T.
No
No
3
Are there oil stains at the Yes
Correct the pipe flare. Replace the refrigerant.
joints of the connection
Replace the union joint.
pipes?
No
Are there oil stains on Yes Yes Check and correct the shield of
4
Is the compressor
the pipes inside the the power transistor TRM1.
vibration excessive?
unit? Replace the damaged pipe.
No
No
Check and correct the pipe contact.
Check the current transformer CT1.
Refer to 3-62.
Replace if damaged.
5
Yes
Is it abnormal? Correct it.
No
Yes
Does the gas shortage Replace the compressor.
occur again?
No
End
LED indication The following table shows the LED indication of the outdoor unit:
Condition LED A (green) LED 1 (red) LED 2 (red) LED 3 (red) LED 4 (red)
normal 9 8 8 8 8
fault 9 0 8 8 0
Error method The error is detected by a momentary voltage drop, an irregular compressor rotation due to power
3 failure, or by overvoltage detection circuit on PCB.
Error generation The system shuts down when the error is confirmed 16 times.
The timer automatically resets when the compressor operates normally for 8 seconds.
5 ■
■
Broken circuit pattern on outdoor PCB 1.
Malfunction of capacitors C1R and C2R.
■ Faulty compressor.
■ Malfunction of the solid state relay SSR1 on outdoor PCB 1. Refer to ‘SSR1 check’ on page 3-68.
Begin
1
Switch the power off and back on again to
restart the equipment.
No
End
LED indication The following table shows the LED indication of the outdoor unit:
Condition LED A (green) LED 1 (red) LED 2 (red) LED 3 (red) LED 4 (red)
normal 9 8 8 8 8
fault 9 0 8 0 8
Error method Internal protection of the compressor is detected using the open condition of the internal protector of
3 the compressor.
Error generation The error is generated when the internal protection activation is sent from the internal protection circuit
to the microcomputer. The contact opens at 120 °C ± 3 °C and closes at 95°C ± 10°C.
The system shuts down when the activation of the internal protector is detected 2 times.
4 The timer automatically resets when one of the following errors does not occur within a period of 60
minutes of accumulated runtime after the first error generation:
■ the radiation fin temperature rise L4
■ gas shortage detection U0
■ compressor start-up error E6.
5
Causes The following list shows the possible causes:
■ Overload activation due to insufficient refrigerant.
■ Error detection due to a faulty overload contact.
■ Overload activation due to a faulty 4-way valve. Refer to ‘Faulty Four-way Valve’ on page 3-18.
■ Error detection due to a faulty connector S40.
■ Detection error due to a broken wire in the internal protector Q1L shield.
■ Detection error due to faulty outdoor PCB 1.
■ Error detection due to insufficient vacuuming in the pipes.
Is there No
Replace the overload protector Q1L.
conductivity?
Yes
Is it connected
No
3
properly? Correct the connection.
Yes
4
overload protector shield.
Is there No
conductivity? Repair the shield.
Yes
Yes
End
LED indication The following table shows the LED indication of the outdoor unit:
Condition LED A (green) LED 1 (red) LED 2 (red) LED 3 (red) LED 4 (red)
normal 9 8 8 8 8
fault 9 0 8 0 8
Error method The error is detected through the discharge pipe thermistor R3T.
3
Error generation The error is generated when the discharge pipe thermistor is disconnected.
The timer automatically resets when no other abnormality occurs within a period of 60 minutes of
4 accumulated runtime after the first error generation.
LED indication The following table shows the LED indication of the outdoor unit:
Condition LED A (green) LED 1 (red) LED 2 (red) LED 3 (red) LED 4 (red)
normal 9 8 8 8 8
fault 9 8 0 0 8
Error method Compressor start-up errors are detected using the rotation data from the motor windings of the
compressor 3
Error generation The error is generated when the compressor tries to restart 16 times within a time range of 60 minutes.
No
Are the stop
Fully open them.
valves open?
Yes
3 Is it normal?
No
Switch off the power to check the
electric conduction of reactor L1R.
Yes
No
Is there
conductivity? Replace reactor L1R.
Are the electrical
4 connections towards the
compressor and control
circuit correctly?
No
Correct it.
Yes
Yes No
Is the wire connected
Correct it.
properly?
Check the power transistor TRM1.
Refer to 3-63.
5 No
Yes
Yes
Yes
Yes
End
LED indication The following table shows the LED indication of the outdoor unit:
Condition LED A (green) LED 1 (red) LED 2 (red) LED 3 (red) LED 4 (red)
normal 9 8 8 8 8
fault 9 8 8 8 0
Error method During compressor operation, the radiation fin temperature rise is detected using the temperature of
the radiation switch box thermistor R4T. 3
Error generation During compressor operation, the error is generated when Tradiation fin > 87 °C.
The timer automatically resets when one of the following errors does not occur within a period of 60
minutes of accumulated runtime after the first error generation:
4
■ the radiation fin temperature rise L4
■ gas shortage detection U0
■ compressor start-up error E6.
No
Does the error indication
appear again?
Yes
4 Yes
Is the temperature more than Check for looseness of the power transistor
No TRM1 and the fin installation.
87˚C (operation halt
temperature)? If they are securely mounted, replace outdoor
PCB 1 or power transistor TRM1.
Yes
Yes
Yes
End
LED indication The following table shows the LED indication of the outdoor unit:
Condition LED A (green) LED 1 (red) LED 2 (red) LED 3 (red) LED 4 (red)
normal 9 8 8 8 8
fault 9 0 0 8 8
Error method Current transformer errors are detected using the operating frequency of the compressor and the input
current of CT1. 3
Error generation The error is generated when the operating frequency of the compressor is more than 56 Hz and the
current transformer input is less than 0.08 V.
The system shuts down when the current transformer error is generated 4 times.
4
Causes The following list shows the possible causes:
■ Faulty power transistor TRM1.
■ broken wire or faulty connection of internal wiring.
■ Faulty reactor L1R.
■ Faulty outdoor PCB 1. 5
Begin
No
No
4 Is the voltage
Yes
Check the connector connection.
324 VDC?
No
Switch the power off. Is it not connected Yes
properly? Correct it.
No
Check the rectifiers DB1 and DB3.
Refer to 3-67.
Yes
Are they normal? Replace outdoor PCB 1.
No
Replace the rectifier DB1 and DB2.
End
LED indication The following table shows the LED indication of the indoor unit:
Condition LED A (green) LED 1 (red) LED 2 (red) LED 3 (red) LED 4 (red)
normal 9 8 8 8 8
fault 9 8 0 0 0
Error method The output overcurrent is detected by the current flowing in the current transformer CT1.
3
Error generation The error is generated when the output overcurrent detection circuit sends an output overcurrent
signal to the microcomputer.
The timer automatically resets when the compressor operates for 8 minutes without low voltage, fan
lock or output overcurrent.
4
Causes The following list shows the possible causes:
■ Overcurrent due to a faulty power transistor TRM1.
■
■
Overcurrent due to a faulty internal wiring.
Overcurrent due to a faulty power supply voltage.
5
■ Overcurrent due to a faulty outdoor PCB 1.
■ Overcurrent due to a closed stop valve.
■ Overcurrent due to a faulty compressor.
■ Overcurrent due to a faulty installation condition.
No
No Causes:
- momentary power supply voltage drop.
- excessively large load on the compressor
Check the power transistor TRM1. Refer to 3-63. motor.
- short circuit in the electrical circuit due to a
4 Is it Yes
defective contact.
No
5
Are the outputs of phases Yes
U, V and W unbalanced? Replace outdoor PCB 1.
(± 2%)
No
No
No
Check the discharge
pressure. Refer to 3-67.
End
LED indication The following table shows the LED indication of the indoor unit:
Condition LED A (green) LED 1 (red) LED 2 (red) LED 3 (red) LED 4 (red)
normal 9 8 8 8 8
fault 9 8 0 8 0
Error method During compressor operation, the input overcurrent is checked by the input current detected by the
current transformer CT1. 3
Error generation During compressor operation, the error is generated when the input current remains above 17 A for
2.5 seconds.
No
Is the measured value
higher than 17A? Replace outdoor PCB 1.
Yes
3 No
Is it normal? Replace outdoor PCB 1.
Yes
Check the power transistor output voltage.
Refer to 3-65.
4
No
Are the U, V and W
phases in balance? Replace outdoor PCB 1.
(± 0.2%)
Yes
Yes
End
LED indication The following table shows the LED indication of the indoor unit:
Condition LED A (green) LED 1 (red) LED 2 (red) LED 3 (red) LED 4 (red)
normal 9 8 8 8 8
fault 9 0 0 8 0
Error method During compressor operation, the electrical box temperature rise is detected by the radiation switch
box thermistor R4T. 3
Error generation During compressor’s non-operating period, the error is generated when the radiation switch box
thermistor temperature reaches 80 °C.
Begin
Does the error Yes Check the radiation switch box thermistor R4T.
occur again? Refer to 3-61.
3 abnormal ?
No
4
No
Check the looseness of the power transistor TRM1
and fin installation.
If they are securely mounted, replace outdoor PCB 1.
No
No
Yes
Is there
Replace outdoor PCB 2. (faulty capacitor)
conductivity?
No
End
LED indication The following table shows the LED indication of the indoor unit:
Condition LED A (green) LED 1 (red) LED 2 (red) LED 3 (red) LED 4 (red)
normal 9 8 8 8 8
fault 0 - - - -
Error method The internal program checks the working of the microcomputer to detect this error.
3
Error generation The error is generated when the microcomputer program does not function properly.
Begin
5
Switch the power on again.
No
Is the LED indication off? Replace outdoor PCB 1.
Yes
Is the No
grounding Provide proper grounding.
properly?
Yes
End
LED indication The following table shows the LED indication of the indoor unit:
Condition LED A (green) LED 1 (red) LED 2 (red) LED 3 (red) LED 4 (red)
normal 9 8 8 8 8
fault 9 0 0 8 8
Error method The temperatures detected by the thermistors are used to determine this error.
3
Error generation The error is generated when the thermistor input is more than 4.96 V or less than 0.04 V.
4 ■
■
Faulty connector connection.
Faulty thermistor.
■ Faulty outdoor PCB 1.
Begin
Is it connected No
Correct the connection.
properly?
Yes
No
Is it normal? Replace the thermistor.
Yes
End
LED indication The following table shows the LED indication of the indoor unit:
Condition LED A (green) LED 1 (red) LED 2 (red) LED 3 (red) LED 4 (red)
normal 9 8 8 8 8
fault 8 _ _ _ _
■
Display disabled by faulty power supply.
Faulty signal transmitting-receiving circuit of outdoor PCB 1.
5
■ Microcomputer program is in abnormal condition due to an external factor like noise, momentary
voltage drop, momentary power failure, etc.
■ Faulty outdoor PCB 1.
No
Is it 230V? Correct the power supply.
Yes
Check fuse FU of outdoor PCB 1.
No
Is there conductivity? Replace the fuse.
Yes
No Replace the
Is there conductivity? varistors.
Yes
Check the power supply of outdoor PCB 1.
4 Is the voltage No
Replace outdoor PCB 1.
approximately 5 V±0.5V?
Yes
Switch the power off and on again.
Yes
No
Is it properly connected? Correct it.
Yes
Replace indoor PCB 2.
End
Part 3
1
5 Additional Checks and Repair for Troubleshooting
Introduction This chapter explains how you have to check the units to execute good troubleshooting.
page 3-69
4
5.5 – Repair for Outdoor Units page 3-82
Step Action
Purple (signals)
2
3 3 Blue (grounding)
4 Rotate the fan one turn by hand and measure the generated pulses between pin 2 and 3
4 of S7.
If then
the measured voltage between pin 1 and 3 does replace indoor PCB 1.
5 not equal 5 V
the generated pulses do not equal 3 pulses replace the fan motor.
the measured voltage does not equal 5 V and replace indoor PCB 1.
the generated pulses do not equal 3 pulses
Indoor PCB 2 Check the indoor PCB2 output voltage when fault code U4 appears on the display.
output voltage
check (U4) To check the output voltage of indoor PCB 2, proceed as follows:
Step Action
2 Measure the voltage between pin 4 and 6 and between pin 4 and 7.
5V
7
12V
6
3 Zero cross
Check the thermistor resistance when fault code P4, J3, J6, or H9 appears on the display.
Thermistor
resistance check 1
(P4, J3, J6, H9) To check the resistance of the thermistors, proceed as follows:
Step Action
For more information about these sensors, refer to ‘Wiring Diagrams’ on page 1-15
and ‘Functions of Thermistors’ on page 2-4.
3
r
Teste
4 Check that the measured values correspond with the values in the table below.
4
Temperature Resistor value
°C kΩ
-20 211 5
-15 150
-10 116.5
-5 88
0 67.2
5 51.9
10 40
15 31.8
20 25
25 20
30 16
35 13
40 10.6
45 8.7
50 7.2
5A
2 min. Time
3
Power supply The following table explains how to check the power supply waveform:
waveform check
Step Action
Power transistor
check
To check the power transistor TRM1, proceed as follows:
1
Before checking, make sure that the voltage between (+) and (-) of the power transistor is
approximately 0 V.
Step Action
Capacitor voltage To check the voltages of the capacitors C1R and C2R, proceed as follows:
check
Step Action
5
1 Operate the unit for several minutes.
When you shut down the unit using the remote controller, the capacitors discharge.
This causes inaccurate measurement.
3 Measure between (+) and (-) of the power transistor TRM1 using a multi-tester
(DC-mode).
The voltage of the capacitors is measured between (+) and (-) of the power transis-
tor TRM1, while the (+) and (-) of the capacitors are connected to the (+) and (-) of the
transistor.
During operation, the voltage of the capacitors C1R and C2R is 280 V.
1 Power transistor
output current
To check the output current of the power transistor, proceed as follows:
2 Snap a clamp meter around the red (U), yellow (V) or blue (W) wires inside the compres-
sor to measure the current.
Do not short-circuit the terminals of the red, yellow and blue wires.
Do not touch the terminals of the red, yellow and blue wires when the power is on.
3 4 When the output frequency has stabilized, measure the output current of each phase.
If then
the output currents of each phase are balanced the situation is normal.
If the compressor stops before the output frequency stabilizes, measure the output
voltage. Refer to ‘Power transistor output voltage check’ on page 3-65.
Power transistor
output voltage
To check the output voltage of the power transistor TRM1, proceed as follows:
1
check Step Action
2 Connect a multi-meter between the red (U) and blue (W) wire on the compressor to meas-
ure the voltage:
Compressor
Red
Blue
Yellow Multi-meter
AC voltage range
3
Do not short-circuit the terminals of the red, yellow and blue wires.
Do not touch the terminals of the red, yellow and blue wires when the power is on.
4
Conduct forced cooling.
Measure the voltage between the operation start (when the fans start rotating) and
4
operation halt caused by a current transformer fault (after 15 seconds).
9 Compare the voltages U-V, U-W and V-W with the solid line below:
V
abnormal
185 V
normal
100 V
abnormal
15 seconds t
start
If then
one of the voltages is not similar to the volt- check the cable between the power
ages on the solid line above transistor and the compressor. If this
is normal, replace outdoor PCB 1.
1 Refrigerant system
check
To check the refrigerant system, proceed as follows:
Begin
No
No
No
4 End
Is the minimum space for all air Change the position of the air
Yes
passage around the suction and discharge grille or change the
discharge areas regarded? installation location.
Refer to 1-8.
No
Does the discharged air from Yes Change the position of the air
possible other outdoor units cause discharge grille or the installation
an increase of the suction location.
air temperature?
No
No
No
Check the outdoor ambient temperature R1T.
This temperature must be lower than 43˚C.
End
Orange
Yellow
Black
Red
Negative (-) terminal of Positive (+) terminal of
Normal
analog tester analog tester
resistance
range
Unacceptable
resistance 3
Positive terminal (+) for Negative terminal (-) for range
digital tester digital tester
kΩ to MΩ 0 or ∞
∞ 0
4
∞ 0
kΩ to MΩ 0 or ∞
When the part is damaged, remove the terminal conductivity compound. Before installing a new
rectifier, replace it by new compound. 5
Discharge pressure To check the discharge pressure, proceed as follows:
check Begin
Is the discharge No
pressure high? Replace the compressor.
Yes
Yes
Yes
No
Are the heat exchanger and
Replace the compressor.
air filter dirty?
Yes
Clean them. Refer to 3-69.
End
1 SSR1 check To check the solid state relay SSR1, proceed as follows:
SSR1
5
4 Take out the filters by pushing
them a little upwards and then
downwards.
4
3 Detach the filter element.
5 In a dusty environment, it
is recommended to replace the
filters every three months.
To open or close
the service cover
To open or close the service cover or to change the settings at installation site, proceed as follows:
1
Step Action Drawing
In a dusty environment,
clean the filter once every two
weeks to save energy.
3
2 Disengage the three catches of
the electrical box.
5
3 Remove the box cover.
4 Disconnect connector S6 of
indoor PCB 1.
PCB1
5 Remove connector S7 on
1
indoor PCB 1 and S1 on indoor
PCB 2.
3
8 Remove the lamp house and
indoor PCB 3.
5
9 Disengage hook of lamp house
and open it upward.
1 Removal of swing
motor
To remove the swing motor, proceed as follows:
1 Removal of
electrical box
To remove the electrical box, proceed as follows:
4
2 Disconnect S1, S7 and S6 of
the electrical box.
3
5 Disengage the catch at the top
side.
1 Removal of fan
rotor and motor
To remove the fan rotor and motor, proceed as follows:
5 3
nector terminal.
4
Hook
5
7 Remove motor.
1 Removal of
electrical parts
To remove the electrical parts, proceed as follows:
S80
4
9 Lift up the electrical parts box.
4
Reactor
cover
4
4 Remove the screw to take off
the reactor cover.
Reactor
4
Part 4
Commissioning and Test Run
Introduction Commissioning and test run are well known practices in service engineering. This part offers a
systematic approach to test-run checks and test values which will guarantee a high quality installation
3
and operation of the units. It is therefore recommended to read the chapters in this part with attention.
Part 4
1
1 Pre-Test Run Checks
Introduction To assure proper operation of the unit, this chapter explains how to check before running the unit.
4
Test run checks To execute a test run, make sure that following points are checked:
Checkpoints Otherwise...
5 Are all air inlets and outlets of the indoor and outdoor
units unobstructed?
Poor cooling.
Poor heating.
Have the connections been checked for gas leakage? Poor cooling.
Poor heating.
Is the earth wire installed according to the applicable Dangerous if electric leakage occurs.
local standard?
Make sure to set the address switch on PCB 1 of the indoor unit. Refer to ‘Main board PCB 1’ on
page 1-17.
Drawing The following drawing shows the location of the address switch:
3
address switch
Part 4
1
2 Test Run & Operation Data
Introduction The following drawings and tables give an overview of the measurements that you can do. Use it as a
guideline during commissioning.
For the location of the measurement points, we refer to the piping and wiring diagrams in Part 1.
3
Overview This chapter covers the following topics:
During heating During heating mode, the operating conditions must be as follows:
3 mode
Items Operating modes If the operation is out of this range:
4 During drying mode During drying mode, the operating conditions must be as follows:
5 Indoor humidity 80 %
and start dripping.
Off period Turn the breaker off if you are not using the air conditioner for a long period.
Cooling mode The following drawing shows the operation range in cooling mode:
50
43
40
3
continuous operation
pull-down period
Outdoor temperature
(°CDB)
30
4
21
10
0
10 15 20 23 28 30 5
Indoor temperature
(°CWB)
Heating mode The following drawing shows the operation range in heating mode:
20
15
Outdoor temperature
(°CWB) 10
continuous operation
7
warming-up period
-10
10 14 20 28 30
Indoor temperature
(°CDB)
Step Action
1 Press the ON/OFF button of the remote controller to switch on the system.
TEMP
TIME 2
4 UP
DOWN
OFF TIMER
ON TIMER CANCEL
FAN 3
MODE
3 Wait until the test mode terminates (approximately 60 minutes) and switches
automatically into normal mode.
If the system is not used for a certain time, switch off the circuit breaker to avoid unnecessary power
consumption.
4
Part 5
Maintenance
Introduction Preventive maintenance should be set up for operation at maximum capacity or to avoid damage. The
following chapters explain how to or when to maintain the units.
3
What is in this part? This part contains the following chapters:
Part 5
1 Maintenance
5
1.1 What Is in This Chapter
Introduction This chapter explains some basic procedures that you can use for maintenance of the indoor units.
Make sure that the power supply is turned off and turn the breaker off.
Air filter Check whether the air filter is Clean the filter and dry it A dirty filter results in
clean. with a vacuum cleaner. poor capacity.
Refer to ‘Cleaning the air
The unit must be filters’ on page 3-69.
turned off when you change
the filter.
Indoor heat Check whether the heat Clean with low pressure A dirty heat
3 exchanger exchanger is dirty. water and a vacuum
cleaner.
exchanger results in
poor capacity.
Fan rotor Check whether the rotor is Remove the rotor and A dirty rotor results in
clean. clean with water. unbalance.
Make sure it is
dry.
Noise level Check whether there is no Find the problem, refer It can result in a
5 Drain
abnormal noise.
Unblock it.
higher noise level.
A blocked drain
not blocked. results in water
leakage.
Drain pump Check whether the operation Repair it. A faulty drain pump
(if installed) of the drain pump is normal. results in water
leakage.
Outdoor heat Check whether the Clean with low pressure A dirty heat exchanger
exchanger heat exchanger is water and dry it with a results in poor capacity.
clean. vacuum cleaner.
Noise level Check whether there is Find the problem, refer It can result in a higher
no abnormal noise . to ‘Sounds’ on page 3-4. noise level.
Drain (heat Check whether the Remove dirt. A blocked drain results in
pump) drain hole is free. water leakage.
Drain pump
(if installed)
Check whether the
operation of the drain
Repair it. A faulty drain pump results
in water leakage.
5
pump is normal.
Pressure, Compare with previous resolve the problem. It can result in poor
voltage, current maintenance. operation of the unit.
and temperature.
4
Appendix
Drawings
Introduction In order to find quickly the drawings inserted in this manual, appendix B offers a list with all the
drawings.
3
Drawings table The following table shows the page and description of all the drawings:
A
3 Step Flow page 2-17
Index
This index is set up in three columns. In the first column you will find references to the item in general. 1
In the second column you will find references to the indoor units and in the third column to the outdoor
units.
FTX25GV1NB RX25GV1NB
General index
FTX35GV1NB RX35GV1NB
Symbols
- . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-51, 3-53
✽ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-24, 3-31
✽ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-55, 3-57
3
A
A1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-24
A5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-26
A6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-28
abnormal functioning . . . . . . . . . . . . . . . . . . . . . . k 3-17
abnormal operation sound and vibration . . . . . . . k 3-15
accumulator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
4
additional checks. . . . . . . . . . . . . . . . . . . . . . . . . k 3-59
additional control parameters . . . . . . . . . . . . . . . . k 2-8
address switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-5
air flow
automatic control for cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-19
automatic control for heating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-19
air purifying filter
cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-69
5
maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-4
replacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-70
working principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-69
ambient temperature thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
ambient temperature thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
autoswing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-16
Index i
ESIE98–07
1 General index
FTX25GV1NB RX25GV1NB
FTX35GV1NB RX35GV1NB
C
C1R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-14
C2R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-14
C4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-30
C9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-30
capacitor voltage check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-63
casing maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-5
check
capacitor voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-63
current transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-62
discharge pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-67
Hall IC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-60
ii Index
ESIE98–07
General index
FTX25GV1NB RX25GV1NB 1
FTX35GV1NB RX35GV1NB
D
defrost
control . . . . . . . . . . . . . . . . . . . . . . . . k 2-5, 2-14
start conditions . . . . . . . . . . . . . . . . . . . . . k 2-14
working conditions. . . . . . . . . . . . . . . . . . . k 2-14
diffuser. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-16
dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-8
discharge pipe
disconnected control . . . . . . . . . . . . . . . . . k 2-24
temperature abnormality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-42
thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
discharge pressure check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-67
discharge temperature control. . . . . . . . . . . . . . . k 2-23
disconnected discharge pipe control . . . . . . . . . . k 2-24
disconnected discharge thermistor control . . . . . k 2-24
3
drain
maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-4
maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-5
drain pump
maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-4
maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-5
dry mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-21 4
E
E5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-40
E6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-43
electrical box
removing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-78
temperature rise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-53
5
electrical connections
maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-4
maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-5
electrical parts removing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-84
electrical specifications . . . . . . . . . . . . . . . . . . . . . k 1-7
emergency operation. . . . . . . . . . . . . . . . . . . . . . . k 3-6
expansion valve
control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-6
feedback control . . . . . . . . . . . . . . . . . . . . k 2-25
initialization . . . . . . . . . . . . . . . . . . . . . . . . k 2-24
limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-24
main control. . . . . . . . . . . . . . . . . . . . . . . . k 2-24
motor operated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
open control . . . . . . . . . . . . . . . . . . . . . . . k 2-24
sequence. . . . . . . . . . . . . . . . . . . . . . . . . . k 2-24
Index iii
ESIE98–07
1 General index
FTX25GV1NB RX25GV1NB
FTX35GV1NB RX35GV1NB
F
F3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-42
fan
control in cooling mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-20
control in heating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-20
motor abnormality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-28
motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
off delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-20
propeller maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-5
removing motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-80
removing motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-82
4 - . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-51
✽ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-24, 3-31
✽ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-55, 3-57
A1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-24
A5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-26
A6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-28
C4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-30
C9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-30
5 E5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-40
E6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-43
F3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-42
H8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-47
H9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-56
J3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-56
J6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-56
L4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-45
L5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-49
P4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-56
U0. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-36
U2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-38
U4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-31, 3-33
fault indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-8
fault indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-23
fault indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-35
faulty LED indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-23
faulty PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-24, 3-31
faulty PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-57
faulty power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-31
feedback control . . . . . . . . . . . . . . . . . . . . . . . . . k 2-25
field piping connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
flap
autoswing . . . . . . . . . . . . . . . . . . . . . . . . . k 2-16
cooling mode . . . . . . . . . . . . . . . . . . . . . . . k 2-16
heating mode. . . . . . . . . . . . . . . . . . . . . . . k 2-16
wide-angle . . . . . . . . . . . . . . . . . . . . . . . . . k 2-16
forced cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-15
forced heating . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-15
forced mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-15
forced operating mode. . . . . . . . . . . . . . . . . . . . . . k 2-7
four-way valve
faulty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-18
function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
operation compensation . . . . . . . . . . . . . . k 2-26
operation . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-26
iv Index
ESIE98–07
General index
FTX25GV1NB RX25GV1NB 1
FTX35GV1NB RX35GV1NB
structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-18
freeze-up prevention . . . . . . . . . . . . . . . . . . k 2-4, 2-23
freeze-up prevention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-26
frequency
control . . . . . . . . . . . . . . . . . . . . . . . . k 2-4, 2-23
initial setting . . . . . . . . . . . . . . . . . . . . . . . . k 2-9
limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-9
parameters . . . . . . . . . . . . . . . . . . . . . . . . . k 2-8
principle. . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-8
functional
control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-3
description. . . . . . . . . . . . . . . . . . . . . . . . . . k 2-1
diagram refrigeration circuit. . . . . . . . . . . . k 1-10
diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11 3
functioning abnormal . . . . . . . . . . . . . . . . . . . . . . k 3-17
G
gas detection fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-36
gas line stop valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
general functionality . . . . . . . . . . . . . . . . . . . . . . . k 2-3
general outline. . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-3
4
H
H8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-47
H9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-56
Hall IC check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-60
heat exchanger
5
function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-4
maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-5
thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
heat pump drain maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-5
heating operation stops . . . . . . . . . . . . . . . . . . . . . k 3-4
high pressure
control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-26
limitation heating . . . . . . . . . . . . . . . . k 2-5, 2-23
hot start function . . . . . . . . . . . . . . . . . . . . . . . . . k 2-21
I
input overcurrent error. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-51
installation check . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-4
installation condition check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-66
insufficient gas detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-36, 3-38
insulation maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-5
inverter
drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-8
features . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-9
principle. . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-8
J
J3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-56
J6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-56
Index v
ESIE98–07
1 General index
FTX25GV1NB RX25GV1NB
FTX35GV1NB RX35GV1NB
L
L4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-45
L5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-49
layout piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-9
location of thermistors . . . . . . . . . . . . . . . . . . . . . . k 2-4
louvre . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-16
low temperature control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-23
low voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-38
M
3 main circuit overvoltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
main PCB layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
main PCB layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-17
k 3-38
k 1-20
4 efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-12
operated expansion valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
reluctance . . . . . . . . . . . . . . . . . . . . . . . . . k 2-12
k 1-11
5 N
night set mode . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-21
no direct hot air . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4
no direct operation start . . . . . . . . . . . . . . . . . . . . . k 3-4
no operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-10
noise level
maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-4
maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-5
normal operating mode . . . . . . . . . . . . . . . . . . . . . k 2-7
vi Index
ESIE98–07
General index
FTX25GV1NB RX25GV1NB 1
FTX35GV1NB RX35GV1NB
O
odour escapes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4
off period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-8
opening service cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-71
operating mode
forced . . . . . . . . . . . . . . . . . . . . . . . . k 2-7, 2-15
main . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-7
normal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-7
operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-7
operation
abnormal sound and vibration. . . . . . . . . . k 3-15
lamp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-6
stop through breaker . . . . . . . . . . . . . . . . . k 3-13
stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-17
operation data
3
cooling mode. . . . . . . . . . . . . . . . . . . . . . . . k 4-8
drying mode . . . . . . . . . . . . . . . . . . . . . . . . k 4-8
general . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-8
heating . . . . . . . . . . . . . . . . . . . . . . . . k 4-8, 4-9
main . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-7
operation range
cooling mode. . . . . . . . . . . . . . . . . . . . . . . . k 4-9 4
cooling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-9
heating mode . . . . . . . . . . . . . . . . . . . . . . . k 4-9
operation space. . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-8
operation stops . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-5
outlook drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-8
outlook drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-8
outlook drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-8
output current error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-49 5
output voltage check PCB 2 . . . . . . . . . . . . . . . . k 3-60
overload activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-40
Index vii
ESIE98–07
1 General index
FTX25GV1NB RX25GV1NB
FTX35GV1NB RX35GV1NB
P
P3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-56
P4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-56
PCB 1
connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-17
functionality . . . . . . . . . . . . . . . . . . . . . . . . k 1-14
PCB 2
check output voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-60
connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-18
functionality . . . . . . . . . . . . . . . . . . . . . . . . k 1-14
PCB 3 connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-18
PCB 4 connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-19
4 layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-9
piping diagram
main parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
main parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
refrigeration circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
poor cooling or heating effect . . . . . . . . . . . . . . . k 3-12
power supply
fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-31
viii Index
ESIE98–07
General index
FTX25GV1NB RX25GV1NB 1
FTX35GV1NB RX35GV1NB
R
R1T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
R1T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
R2T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
R2T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
R3T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
R4T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
radiation fin temperature rise. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-45
reactor removing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-87
recommended temperature setting . . . . . . . . . . . . k 4-8
rectifier check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-67
refrigerant distribution control . . . . . . . . . . . . . . . . k 2-6
refrigerant system check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-66
refrigeration circuit
functional diagram. . . . . . . . . . . . . . . . . . . k 1-10
3
main parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
main parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
reluctance DC motor . . . . . . . . . . . . . . . . . . . . . . k 2-12
remote controller
setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-5
removing
test run . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-10
4
electrical box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-78
electrical parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-84
fan motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-80
fan motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-82
fan rotor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-80
PCB. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-72
propeller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-82
reactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-87 5
swing motor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-76
repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-59
repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-69
repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-82
replacing air purifying filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-70
resistance check thermistor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-61
rotor structure . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-13
S
safeties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-6
service check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-6
service cover
closing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-71
opening . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-71
service space . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-8
setting remote controller . . . . . . . . . . . . . . . . . . . . k 4-5
signal transmission error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-33
sounds. . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4, 3-15
specifications
electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-7
technical . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-4
SSR1 check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-68
SSR1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-14
steam escape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4
step flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-17
swing compressor . . . . . . . . . . . . . . . . . . . . . . . . k 2-11
swing motor removing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-76
switch box
control . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-26
layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-14
thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
Index ix
ESIE98–07
1 General index
FTX25GV1NB RX25GV1NB
FTX35GV1NB RX35GV1NB
T
technical specifications . . . . . . . . . . . . . . . . . . . . . k 1-4
temperature
maintenance . . . . . . . . . . . . . . . . . . . . . . . . k 5-6
recommended setting . . . . . . . . . . . . . . . . . k 4-8
test run
checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-4
from remote controller . . . . . . . . . . . . . . . . k 4-10
main. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-7
thermistor
abnormality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-30
abnormality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-56
U
U0. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-36, 3-38
5 U2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-38
U4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-31, 3-33
V
valve
expansion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
gas line stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
voltage
low . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-38
maintenance . . . . . . . . . . . . . . . . . . . . . . . . k 5-6
W
water escape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4
wide-angle flap. . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-16
wiring
diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-15, 1-16
diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-16
layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-13
x Index