Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Data sheet for three-phase motors

MLFB-Ordering data: 1LA8317-4PB80-Z


A61+A72+B02+K45+L97

Client order no.: Item no.:


Order no.: Consignment no.:
Offer no.: Project:
Remarks:

Electrical data: General data:


Frame size
Type data: 315

Power P Method of cooling


315 kW IC411 - self ventilated open-circuit cooled
Thermal class / utilisation Duty type Converter with du/dt filter or sine-
155(F) to 155(F)
wave filter
Rated voltage U D/Y Type of construction
400/690 VD/Y 50 Hz IM B3
Frequency f
50 Hz Degree of protection
IP55
Speed n
1488 1/min Total weight
1500 kg
Motor torque M
2022 Nm Coating
Standard paint finish
Current I VD VY
546 A 317 A Color
RAL 7030

Ratings: Type of explosion protection


none
Rated power PN:
315 kW Standards/specifications
IEC, DIN, ISO, VDE, EN
Thermal class / utilisation
155(F) to 155(F) Motor protection
Service factor 6x PT100 resistance thermometers integrated in the stator
1.00 winding
Rated speed nN
1488 1/min
Terminal box:
Rated torque MN
2022 Nm Type of terminal box
GT640
Rated current IN VD VY
Conductor cross section, max. (IEC)
546 A 317 A 185 mm²
Starting / rated current IA/IN
N/A Contact screw thread
M12
Breakdown/rated torque MK/MN Cable diameter from ... to …
2.80 41,0 ... 56,5

Starting / rated torque MA/MN Cable entry


2 x M72x2 + 2 x M20x1,5
N/A

Efficiency class in acc. to 60034-30-1/NEMA Special design:


none

Partial load P/PN A61 6x PT100 resistance thermometers integrated in the stator winding
5/4 4/4 3/4 2/4
A72 Installation of 2 screw-in PT100 resistance thermometers in a basic connection for
Efficiency η in % in acc. to IEC 60034-2-1 roller bearings
95,3 % 95,7 % 95,8 % 95,5 % Acceptance test certificate 3.1 acc. to EN 10204
B02
Power factor cos φ K45 Anti-condensation heating, 230V
0,87 0,87 0,83 0,73
L97 Auxiliary terminal box 1XB3 020
Mechanical data:
Moment of inertia Jmot
4.4 kg*m²
Rotor winding material
Al
Bearing DE deep-groove ball
6218 C3
bearing
Bearing NDE deep-groove ball
6218 C3 *
bearing
Direction of rotation
Both
Relubrication interval/quantity
6000 h / 40 g

Environmental conditions:
Coolant temperature KT
40 °C
* Standard: insulated bearing at NDE - VL0241
Installation altitude
1000 m
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Generated: 05.12.2016 08:05:21
Bestelldaten 1LA8317-4PB80-Z
Ordering data B02

Anlaufberechnung / Startup calculation

Eingabewerte / Input Values


Lastmomentverlauf Quadratic
VFD Load Characteristic
Starting Type
Motorbemessungsspannung (V) Stationäre Leistung nach Hochlauf (kW) 315
400 Stationary output after startup
Rated Voltage
Netzkurzschlussleistung (kVA) Ideales Netz Lastträgheitsmoment (kgm²) 0
Short-circuit power Ideal grid Load moment of inertia
Anlaufspannung (%) 90
Lastmoment Eingabetyp Absolute
Starting Voltage Type of load characteristic
Zul. Anzahl der Anläufe (Norm) IEC
Bezugsmoment (Nm) 0
Permissible number of consecutive starts Reference torque
Lastmoment bei 0% Drehzahl (Nm) 0
Load torque at 0% speed

Ausgabewerte / Calculation Results


Anlaufspannung Anlaufspannung
100% 90% 100% 90%
Startup voltage Startup voltage
Anzugsstrom/Bemessungsstrom (Ia/In) 8.1 7
Min. Beschleunigungsmoment (Nm) 3,518 2,432
Locked-rotor current/rated current Min. acceleration torque
Anzugsmoment/Bemessungsmoment (Ma/Mn) 1.9 1.4
Kippmoment (Nm) 7,112 5,384
Locked-rotor torque/rated torque Breakdown torque
Kippmoment/Bemessungsmoment (Mk/Mn) 3.5 2.7
Anlaufzeit (s) 0.19 0.27
Breakdown torque/rated torque Starting time
Anzahl der Starts (kalt) 3 3
Anzahl der Starts (warm) 2 2
Permissible number of consecutive starts (cold) Permissible number of consecutive starts (warm)

Anlaufdiagramm / Startup diagram