Professional Documents
Culture Documents
4364 Ie3 Fs 90 180 MM Manual en
4364 Ie3 Fs 90 180 MM Manual en
4364 Ie3 Fs 90 180 MM Manual en
3. MOTOR INSTALLATION 10
3.3 Placing the geared pulley or half coupling on the motor’s shaft extension 11
3.5.5
Anti-condensation heaters 15
5. MOTOR MAINTENANCE 22
7. ATTACHMENTS 28
1. SPECIFICATION AND USE 5
This operating manual has been created for three-phase squirrel-cage single and dual speed induction motors,
with shaft height above the mounting feet’s surface of: 80, 90, 100, 112, 132, 160, 180 and 200 mm, designed
to drive various types of machines and appliances. The manual also describes special motors designed to be
mated to a frequency converter with an external cooling unit and brakes.
Motors are adapted for indoor and outdoor use.
This manual is not valid for explosion-proof motors marked with the „Ex” symbol.
Design characteristics
X – not available
6
Electric motors are produced according to the current directives and norms:
Requirements Norms
International marking Polish marking
1. Low Voltage directive 2006/95/CE (LVD)
2. Machinery Directive * 2006/42/CE (MD)
3. Electromagnetic compatibility 2004/108/CE (EMC)
EN 60034-1 PN-EN 60034-1
IEC 60072-1 PN-IEC 72-1
4. Electric requirements EN 60034-2-1 PN-EN 60034-2-1
EN 60034-9 PN-EN 60034-9
EN 60034-12 PN-EN 60034-12
IEC 60072-1, EN 50347 PN-IEC 72-1, PN-EN 50347
EN 60034-5 PN-EN 60034-5
5. Mechanical requirements EN 60034-6 PN-EN 60034-6
EN 60034-7 PN-EN 60034-7
EN 60034-14 PN-EN 60034-14
6. Environmental requirements RoHS - UE Directive no. 2002/95/EC „Restriction on Hazardous
Substances”
7. Quality Management System (certificate no. 27992) ISO 9001 PN-ISO 9001
* - by design the machines considered as components. Conformity to the requirements, provided that the installation is set up
correctly by the tool’s manufacturer.
Motor operating parameters and assembly dimensions are included in the specification sheet.
8 Rotating
rotating electrical electricalmanufactured
machines machines manufactured
accordingaccording to PN –EN-60034-7.
to PN –eN-60034-7.
IM 1001 IM B3 IM 1011 IM V5
IM 1051 IM B6 IM 1031 IM V6
* - *forces
- forces listed
listed in the
in the chart
chart andand applied
applied to to
thethe middle
middle ofof
thethe shaft
shaft neck'slength.
neck’s length.
ATTENTION! When lifting drive units always use lifting handles designed for this purpose.
Motors shouldbebetransported
Motors should transported packaged,
packaged, in roofed
in roofed vehicles,
vehicles, avoiding
avoiding suddensudden
shocksshocks and impact,
and impact, secured secured
against
against mechanical damage and humidity. Packaging should adequately protect the
mechanical damage and humidity. Packaging should adequately protect the motor from mechanical damage motor from mechanical
during
transport.during transport.
damage
When lifting
When lifting the
the motor
motor or
or moving
movingititwithout
withoutthe
thepackaging,
packaging,useusethe
thelifting eye
lifting bolt
eye located
bolt locatedat at
thethe
toptop
of of
thethe
frame in
frame
the middle part of the motor. Do not attach the rope to motor elements which stick out, such as
in the middle part of the motor. Do not attach the rope to motor elements which stick out, such as the terminal the terminal box,
mounting feet, shaft neck, etc.
box, mounting feet, shaft neck, etc.
Motor should be stored in a storage space, where:
Motor
dust, should
fumes beand
stored in vapours
acrid a storageand
space,
otherwhere:
aggressive chemical fumes which can damage the isolation or the
• dust, fumes
cover cannotand acrid vapours and other aggressive chemical fumes which can damage the isolation or the
enter;
maximum
cover relative humidity does not exceed 80 at 20°C;
cannot enter;
in case ofrelative
• maximum motorshumidity
with heating
doesornot
antiexceed
condensation elements, they can be plugged into mains,
80 at 20°C;
temperature of the surroundings is between -10°C and +40°C,
• in case of motors with heating or anti condensation elements, they can be plugged into mains,
no vibrations occur.
• temperature of the surroundings is between -10°C and +40°C,
•It no vibrationstooccur.
is important protect processed surfaces of motors in storage from atmospheric impact, by covering them with
thick grease or easily removable anti-corrosion paint.
It is important to protect processed surfaces of motors in storage from atmospheric impact, by covering them
with thick grease or easily removable
After storinganti-corrosion
a motor for a paint.
period of three years, its bearings should be replaced
ATTENTION!
for new ones, or the greasing should be replaced.
3. MOTOR INSTALLATION.
Prior to starting any work on the motor, make sure that it is unplugged from
ATTENTION!
Motor cover cannot
should enter; in a storage space, where:
be stored
temperature
maximum
dust, fumes of theacrid
relative
and surroundings
humidityvapoursdoesand is
notbetween
exceed -10°C and chemical
80 at 20°C;
other aggressive +40°C, fumes which can damage the isolation or the
in no vibrations
case of occur.
motors
cover cannot enter; with heating or anti condensation elements, they can be plugged into mains,
temperature
maximum of thehumidity
relative surroundings does is notbetween
exceed -10°C and +40°C,
80 at 20°C;
It
is inimportant
no to protect
vibrations
case occur.
of motors withprocessed
heating orsurfaces of motors elements,
anti condensation in storage they
fromcanatmospheric
be plugged impact, by covering them with
into mains,
thick grease or easily removable anti-corrosion
temperature of the surroundings is between -10°C and +40°C, paint.
10 It
is noimportant to protect
vibrations occur. processed surfaces of motors in storage from atmospheric impact, by covering them with
thick grease or easily removable anti-corrosion
After storing a motorpaint. for a period of three years, its bearings should be replaced
ATTENTION!
It is important to protect processed surfaces of greasing
motors in should
storagebe from atmospheric impact, by covering them with
for new ones, or the replaced.
thick grease or easily removable anti-corrosion paint.
After storing a motor for a period of three years, its bearings should be replaced
3. ATTENTION!
MOTOR INSTALLATION. for new ones, or the greasing should be replaced.
3. MOTOR ATTENTION!INSTALLATION After storing a motor for a period of three years, its bearings should be replaced
Prior to starting any work on the motor, make sure that it is unplugged from
3. MOTOR INSTALLATION.
ATTENTION! for new ones, or the greasing should be replaced.
mains.
3. MOTOR INSTALLATION. Prior to starting any work on the motor, make sure that it is unplugged from
ATTENTION!
3.1 Inspecting the motor mains.prior to the assembly.
Prior to starting any work on the motor, make sure that it is unplugged from
Before starting ATTENTION!
the motor, mains. check:
3.1 whether
3.1 Inspecting
Inspecting
the motorthe
themotormotor
complies prior toyour
prior
with the
toassembly.
the assembly
order,
Before
Before whether the
starting motor's
the motor, rated
starting the motor, check: check:voltage confirms with the network voltage,
• 3.1
whether Inspecting
whether
whether the
the
themotor the
motor motor
hasn't
motorcomplies prior
been
complieswith to the
damaged
with your assembly.
your order,during
order, transportation or storage;
• whether
whether
whether
Before the
starting
the motor's
themotor’s
motor's
the motor, rotor
rated
rated rotates
check: freely
voltageconfi
voltage confirms(turn it
rms with themanually),
the network
networkvoltage,
voltage,
whetherwhether the motor
the surrounding
hasn'tbeen temperature
been damaged in during
the location of the motor's installation does not exceed + 40°C, (for
• whether the motor hasn’t complies with your order,
damaged during transportation
transportationororstorage;
storage;
whethermaritimethe motors,+45°C
motor's rotorratedorrotates
+50°C,freely
voltage according
confirms to
(turnwith the maritime
it manually),
the network association
voltage, regulations),
• whether the motor’s rotor rotates freely (turnforit proper
manually),
whetherwhether free flow ofhasn't
the motor
the surrounding cooling air,damaged
necessary
temperature
been in during
the location operation ofstorage;
of the motor's
transportation or the installation
motor, will be provided,
does not exceed + 40°C, (for
• whether the
maritimethe surrounding
motors,+45°C temperature
orrotates
+50°C,freely in
accordingthe location
the maritime association regulations), not exceed + 40°C, (for
of the motor’s installation does
whether motor's rotor (turn toit manually),
maritime
whether motors,+45°C
free flow of Minimal
the surrounding or +50°C,
cooling distance between
air, according
necessary
temperature in theforthe
to the end
proper
location the
of motor's
maritime
operation
the offrame
association
motor's and other elements:
regulations),
the installation
motor, will be provided,
does not exceed + 40°C, (for
• maritime whether free
fl ow for
of shaft
coolingheightair, 90 mm
necessary – 15 mm
motors,+45°C or +50°C, according to the maritime association regulations),will be provided,
for proper operation of the motor,
whether free flow of for shaft
Minimal
cooling air,height
distance 100 and
between
necessary forthe112 mmthe
end
proper – 20 mmofframe
motor's
operation and other
the motor, elements:
will be provided,
for for shaft
shaft height
height 132,
90 mm 160 – and
15 180
mm mm – 40 mm
Minimal distance between the end the motor’s frame and other elements:
Minimalfor shaft heightbetween
distance 100 andthe 112end
mmthe – 20 mm frame and other elements:
motor's
• fortightness
shaft height
of all90 mm
mounting – 15 mm on the
screws
for shaft height 132,90motor.
mm 160 – and 180 mm – 40 mm
15 mm
• for shaft height 100 and 112 mm – 20 mm
for shaft height 100 and 112 mm – 20 mm
•3.2
fortightnessChecking
shaft height of
of all the
132, 160
mountinginsulation
forand
screws
shaft 180 resistance.
mmthe
on
height – 40 mmand 180 mm – 40 mm
motor.
132, 160
•Inspection
tightnessofofthe all mounting
insulation's screws
conditionon the motor.
should be done prior to starting the motor, if moistness of the winding is
3.2 tightness
suspected, Checking
or of
afterofmounting
all athe insulation
lengthy screws
standstillresistance.
onorthe motor.period (about 6 months).
storage
3.2 Checking
Inspection of the of the insulation
insulation's condition resistance
should be done prior to starting the motor, if moistness of the winding is
3.2 Checking
Insulation
suspected, or the ofathe
resistance
after insulation
should
lengthy be resistance.
measured
standstill using be
or should
storage 500V
period direct current.
(about 6 months).
Inspection of insulation’s condition done prior to starting the motor, if moistness of the winding is
Inspection oforthe
suspected, insulation's
after a lengthy condition
standstill should be done
or storage period prior to starting
(about the motor, if moistness of the winding is
6 months).
Insulation
suspected,resistance
or after a should
lengthy be
During, measured
and directly
standstill usingafter
or storage 500V direct
measuring
period current.
(about 6 the insulation resistance, harmful voltage is
months).
ATTENTION! present in the terminals, therefore it is forbidden to touch them. In order to remove
Insulation resistance should the be measured
threat of directlyusing 500V
electrocution, direct
itdirect
is current.to discharge the winding.
necessary
Insulation resistance should be measured
During, and usingafter
500Vmeasuring current.
the insulation resistance, harmful voltage is
ATTENTION! present in the terminals, therefore it is forbidden to touch them. In order to remove
The minimal value of the the threat
During, and
insulationof directly
electrocution,
resistanceafter it is necessary
in measuring
regard to the to discharge
theframe
insulation thephases
winding.
resistance,
or between harmful voltage is
in the temperature
La resistenza dell’isolamento
ATTENTION! present deve
in essere
the misurata
terminals, con unaitcorrente
therefore is continua
forbidden to di 500V.
touch them. In order to remove
of 25°C ± 15°C for a new or repaired motor is 10 MΩ .
The minimal value of the theinsulation
threat of electrocution, it is necessary
resistance in regard to the frame to discharge
or between thephases
winding.in the temperature
While
of 25°Cthe motorforis ainnew
± 15°C operation, the motor
or repaired insulation resistance
is 10 MΩ . may drop, however, it cannot be below the critical
the
The minimal
insulation
minimal value of
resistance
value of the
the insulation
value, resistance
whichresistance
insulation is a productininregard
regard totothe
of inter-wirethe frame oror
supply
frame between
voltage
between phases
and
phases in the
constant
in the tempera-
coefficient
temperature
ture
While
of ofthe
25°C 25°C ± 15°C
motor
± 15°C for
foris ainnew aor
new
operation, orthe
repairedrepaired motor
insulation
motor is 10
. MΩ.
resistance
is 10 MΩ may drop, however, it cannot be below the critical
insulation resistance value, which is a product of inter-wire supply voltage and constant coefficient
the motor
While the motor isis ininoperation,
operation,thetheinsulation
insulationresistance
resistancemay maydrop,drop,however,
however, it cannot
it cannot be be below
below thethe critical
critical in-
insulation
sulation resistance
resistance value,
value, which
which is a is a product
product of inter-wire
of inter-wire supplysupply
voltagevoltage and constant
and constant coefficient
coefficient 0.5MΩ/
kV. In case of a motor powered by a frequency converter, the minimal value of the motor’s insulation resistance
is 1 MΩ. During the measurement, the winding should be in operating temperature.
An example of a motor powered from a 3 x 400V network: 0,4kV x 0,5MΩ/kV= 0,2 MΩ.
If the expected winding resistance falls below the level of the critical resistance value, the motor should be im-
mediately taken out of service and the cause of the lowered resistance value - moistness, pollution, damage,
etc - removed. After the repair or drying, the conditions of insulation should be checked again.
During the drying process, create conditions necessary to remove moisture from the winding, i.e. at least, take
off the cover of the terminal box in order to make the exchange of air with the interior of the motor possible. For
motor sizes 132, 160 and 180, there is a possibility to drain the condensate by unscrewing the drain plugs instal-
led in the bearing brackets. The recommended drying temperature is 60 to 80°C. The motor should be dried until
insulation resistance reaches its minimal value (2-8h).
3.3 Placing the geared pulley or half coupling on the motor’s shaft extension
Prior to placing the geared pulley or the half coupling on the motor’s shaft extension:
• remove any possible injury marks from the shaft extension,
• remove protective paint from the shaft extension,
• lightly cover the shaft extension with grease,
• clean anti-corrosion layer from the flange disc,
Placing the geared /wedged/ pulley or the half coupling should be done with the use of an appropriate tool, as
shown in fig. 1 – using the threaded centre hole of the shaft extension.
Fig1
If necessary, heat up the coupling hub or the pulley /belt, geared/ to about 80°C.
In no special equipment is available, the heated up coupling or geared pulley can be hammered on using a sui-
table sleeve, simultaneously supporting the opposite shaft extension, so the force from the hits is transferred to
the support, not the bearings.
After putting the belt, wedged, geared pulley or half coupling on the shaft extension, secure it from sliding off the
shaft using a screw with a washer, screwed in the threaded centre hole of the shaft extension.
When connecting the motor to the driven appliance using a coupling, particular attention needs to be given to
the concentricity of shafts: the motor and of the driven machine’s shafts – as shown in fig. 2.
For belt drives, it is recommended to use transmissions with wedge belts, which have:
When connecting the motor to the driven appliance using a coupling, particular attention needs to be given to the
concentricity
When of shafts: the
connecting motor
the and
motor to of
thethe driven
driven machine's
appliance shafts
using – as shown
a coupling, in fig.attention
particular 2. needs to be given to the
concentricity of shafts: the motor and of the driven machine's shafts – as shown in fig. 2.
For belt• drives,
smalleritslide,
is recommended to use transmissions with wedge belts, which have:
12 smaller slide,
•For
quieter
belt drives,
quieter it is recommended to use transmissions with wedge belts, which have:
operation,
operation,
§ smaller
• lower slide,
belt tension.
lower § belt tension.
quieter operation,
§ lower belt tension.
Lower
Lower belt belt tension
tension results results in arisk
in a lower lower risk of damaging
of damaging motor's motor’s
bearing bearing
from thefrom
drivethe drive side.
side.
Lower belt tension results in a lower risk of damaging motor's bearing from the drive side.
CorrectCorrect
assembly and appropriately
assembly balanced
and appropriately coupling
balanced element
coupling have have
element a significant effect
a significant on the
effect drive's
on the drive’s
vibrations and
Correct quite
assemblyoperation.
and
vibrations and quite operation. appropriately balanced coupling element have a significant effect on the drive's
vibrations and quite operation.
Fig.2 Fig.2
MotorMotor
orientation
orientation
Each has
Each motor motor has a plate
a rating ratingattached
plate attached to its frame.
to its frame. This rating
This rating plate plate includes
includes information
information suchsuchas: as:
Each motorvoltage
supply has a rating
– plate attached
permissible deviation to±5%
its frame.
not This rating
requiring plate includes
decreasing the information such as:
power;
supply voltage – permissible deviation ±5% not requiring decreasing the power;
§
supply•§ supply
supply
voltagevoltage
voltage – frequency
frequency permissible
– permissibledeviation
– permissible ±5%
deviation not
±2%requiring
deviation notdecreasing
±2%requiring
not requiring the power;
decreasing
decreasing the power;
the power;
•§ supply
connection voltage
connection
of offrequency
the 3-phase
the 3-phase winding– permissible
winding
in a star in a(Y)deviation
star
or(Y) or±2%
a delta (∆);not(∆);
a delta requiring decreasing the power;
input input current
•§ connection
current atload.
of the
at rated rated
3-phase load.winding in a star (Y) or a delta (∆);
• input current at rated load.
The boxThe box contains
contains a terminala terminal
board boardwith 3withor 63terminals.
or 6 terminals.Power Power
cables cables
should should
be led beinledtointheto terminal
the terminal
boxbox through
through
stuffing
stuffingTheboxes boxes
orcontainsor glands.
glands.aThe The
screwed screwed
in cable in cable inlets should prevent water and dust from entering the terminal box
during box operation. terminal
Stuffing box board
throttle with
range3 inlets should prevent
oris6included
terminals. in Powerwater
attachmentcables and
no.
dust be
should
1.
fromledentering
in to thethe terminal
terminal boxbox
throu-
during operation.
gh stuffileadsng Stuffing
boxes orbox throttle
glands. Therange
screwed is included
in cable ininlets
attachment
should no. 1. water and dust from entering the terminal
prevent
Power Power
leads shouldshould have ahave cable a cable tips. Torque
tips. Torque values, values, with
with which which the nuts
the nuts and screws
and screws of the of electric
the electric connections
connections
box
should during
be operation.
tightened, areStuffi
listednginbox throttle range
attachment no. 2. is included in attachment no. 1.
should be tightened, are listed in attachment no. 2.
Detailed
Power rulesshould
regarding installing
cable electric motors are given inwhichPN-E-05012.
Detailed rules leads
regarding have
installing a electric tips.
motors Torqueare values,
given inwithPN-E-05012. the nuts and screws of the electric connections
should be tightened, are listed in attachment no. 2.
3.5.1 Direct
Detailed rules(DOL) starting.
regarding installing electric motors are given in PN-E-05012.
3.5.1 Direct (DOL) starting.
Each motor is adapted for direct starting.
Each motor is adapted for direct starting.
In case of a 3-terminal board, motor is designed for one voltage, which is indicated on the rating plate. Direct start
In case3.5.1
of a
can take
Direct
3-terminal (DoL)
place by
starting.
board, motor
plugging is designed
directly into the formains,
one voltage, which sure
after making is indicated
that theon the rating
inter-wire plate.ofDirect
voltage start is
the mains
can takeEach placemotor by plugging
is adapted directly
for into
direct
equal to the rated voltage of the connected motor. the
starting. mains, after making sure that the inter-wire voltage of the mains is
equal toInthecase rated
of avoltage of theboard,
3-terminal connected
motormotor. is designed for one voltage, which is indicated on the rating plate. Direct
start
In case canoftake place byboard,
a 6-terminal plugging usingdirectly into the mains,
the connectors suppliedafter making
with sure create
the motor, that thea inter-wire
correct phase voltage of the
match, mains
meaning
In caseisYofequal
ora ∆,
6-terminal
and
to the board,
connect
rated the using
power
voltage the
of connectors
supply
the supplied
motor. with
to the terminals
connected the motor, to
in accordance create a correct phase
the connection diagrammatch, meaning
attached with the
Y or ∆, motor
and connect
– attachmentthe power
no. 4.supply to the terminals in accordance to the connection diagram attached with the
motor – attachment no. 4.
Fig. 3
Nel disegno 4a è illustrato il sistema di alimentazione di un motore dotato di protezione termica che prevede
sensori termici a contatto.
14 An example of the power supply system of a motor with thermal protection using thermocontacts is presented
in drawing 4a.
Fig. 4
Nei sensori
In bimetal termicisensors
temperature bimetallici
withcon contatto
normally normalmente
closed chiuso
contact, the la continuità
continuity of the del circuito
circuit deve
should be essere
checkedcontrollata
in a
freddo,
cold state, con
with una corrente
current non superiore
not exceeding alla operating
the sensor’s corrente di esercizio
current. del higher
Current sensore. Una
than corrente
rated currentsuperiore
can cau- a quella
nominale
se damage puòthermal
to the causare danni allaofprotezione
protection termica dell’avvolgimento.
the winding.
Sensori a termistore PTC.
PTC-resistor sensors.
Tre termistori PTC si trovano nell’avvolgimento del motore e sono collegati in serie (fig. 5), ognuno in una fase
Threediversa.
PTC-resistors are located in the motor’s winding, connected in series (Fig. 5). Each one is placed in a
different phase.
Fig. 5
Sensor outlets should not be connected directly to the contactor’s terminals. They should be connected to the
Le uscite dei sensori non devono essere collegate direttamente ai terminali del contattore, ma a quelli del relè
resistance relay’s(es.
resistenza terminals
RRx-12).(forNel
example:
disegnoRRx-12). An example
n. 4b è illustrato of the power
il sistema supply system
di alimentazione di unof a motor
motore withviene
in cui ther-utilizzato
mal protection
un resistoreusing
PTCPTC-resistors is presented
per la protezione termica. in drawing no. 4b.
Dati parameters
Technical tecnici del resistore PTC STM
of PTC-resistor STM140140EK:
EK:
resistenza:
• resistance:
• TN = 140ºC ♦ TN = 140ºC
• for temp 20°C to♦TN-20Kper -temp
20 Ωda 250 Ωa T N-20K – da 20 Ω a 250 Ω
to 20°C
♦ per temp TN-5K - <550 Ω
• for temp TN-5K - <550 Ω
♦ per temp TN+K5 - >1330 Ω
• for temp TN+K5 - >1330
♦ perΩtemp TN+15K - >4000 Ω
• for temp TN+15K - nominale
corrente >4000 Ω - ≤2,5V-
• rated
current - ≤2,5V-
corrente max – 30V-
resistenza
• max current – 30V-elettrica dell’isolamento – 2,5kV
• electric resistance of the insulation – 2.5kV
3.5.5 Scaldiglie anticondensa.
Le scaldiglie sono usate per evitare la formazione di condensa all’interno del motore. La condensa può formarsi
quando il motore rimane a lungo inattivo in un ambiente umido. In tal caso basta accendere le scaldiglie per
THREE-PHASEqualche ora prima
SQUIRREL-CAGE di avviare
INDUCTION MOTORS il motore; ad asciugatura completata, controllare il valore della resistenza di
isolamento citato nel capitolo 3.2 oppure tenere le scaldiglie accese per tutto il periodo di inattività.
3.5.5 Anti-condensation heaters 15
Anti-condensation heaters are used in cases of a risk of steam condensation inside the motor. The effect of ste-
am condensation can take place during long-term standstill of a cold motor in humid air. In such a case, turn on
the heaters for a few hours prior to starting the motor, and after drying check the insulation resistance value as
described in chapter 3.2 or keep the heaters turned on during the whole standstill period.
For motor sizes 132, 160 and 180, there is a possibility to drain the condensate by unscrewing the drain plugs
installed in the bearing brackets.
Do not power the heaters while the motor is in operation.
Standard heaters: 2 heaters, 25W each, running on 230V current with three leads.
When connected parallel, the power supply current may amount to 200-240V, and connecting in series allows for
powering the heaters with 400-480V current.
The maximum number of consecutive starts is dependent on the degree of starting difficulty and limited by the
maximum temperature increase for the given heat resistance class of insulation.
While the motor is in operation, systematically check the correctness of such operations as:
• the state of motor heating up on its frame – in some types of motors, the temperature increase of the frame
can reach as much as 70K;
• correct functioning of bearings – which is manifested by quiet, even humming,
• whether there are no excessive vibrations of the motor,
• the condition of the motor’s coupling with the powered machine,
• current input shouldn’t exceed the nominal value.
Normal, stable work can take place with current fluctuation not exceeding ±5% of the rated current and ±2% of
the rated frequency.
La regolazione della velocità di rotazione, in base alla coppia, può avvenire solo nell’intervallo indicato nel grafi-
co n. 1, mentre la coppia
Adjustment massima
of rotational dei motori
speed, depending a induzione
on the contake
load torque, can ventilazione esterna,
place only in scope in base
presented in thealla frequenza della
graph
corrente fornita, è indicata
no. 1, and nel grafico
the maximum n. of
load torque Il funzionamento
2. induction nel campo
motors with external arancione
cooling, depending dipende dal tipo
on the frequency of e dalle impo-
supplied current, is presented in graph no. 2. Operation in orange field is dependent on kind and settings of frequency
stazioni delconverter.
convertitore di frequenza.
Grafico n. 1
Graph no. 1
Grafico
Graph no. 2 n. 2
Analysing the formula: notice that the increase of rotational speed, while maintaining a
constant torque, must be accompanied by an increase of power. With speeds exceeding the rated speed, the
Dall’analisithe
Analysing della
increase formula
of power
formula: would cause an increase of si
evince
thenotice che the
current that
drawn l’aumento
by the motor,della
increase which velocità dispeed,
causes motor
of rotational rotazione,
overheating.
whilemantenendo
maintaininguna
For this reason, in rotational speed higher than the rated speed, the load torque on the shaft needs to be lowered.
coppia costante,
a constant While
torque, deve essere
mustthebemotor
operating
accompagnato
accompanied by an
in rotational speed
da un
increase
higher
aumento
of power.
than the rated
della
With
speed, pay
potenza.
speeds
attention
In presenza
exceeding
to the current drawn
di
the velocità superiori
rated speed,
by the the a
quella nominale, l’aumento della potenza comporterebbe
motor, and make sure that it is not higher than the rated current. un aumento della corrente consumata dal motore, con
conseguente Whilesurriscaldamento
the motor is operated di quest’ultimo.
in speeds higher thatQuindi
the rated se la the
speed, velocità
level of di rotazione
noise è maggiore
and vibrations di quella nominale,
increases, and
the life span of bearings can be shorter. Attention: do not exceed the rotational speed listed in chart.
occorre ridurre la coppia sull’albero. Se il motore ruota a una velocità maggiore di quella nominale, controllare che
la corrente Aconsumata non sia
method of eliminating maggiore
these della
unfavourable corrente
effects can be: nominale.
THREE-PHASE SQUIRREL-CAGE INDUCTION MOTORS
L’uso del motore
usingadU/dt
unafilters,
velocità
whichdi rotazione
smooth out the maggiore
rate of outputdi quella nominale può comportare un aumento del livello del
voltage,
blocking the frequencies in the inverter, in which the unfavourable effects take place,
increase of power would cause an increase of the current drawn by the motor, which causes motor overheating. 17
For this reason, in rotational speed higher than the rated speed, the load torque on the shaft needs to be lowered.
While operating the motor in rotational speed higher than the rated speed, pay attention to the current drawn by
the motor, and make sure that it is not higher than the rated current.
While the motor is operated in speeds higher that the rated speed, the level of noise and vibrations increases,
and the life span of bearings can be shorter. Attention: do not exceed the rotational speed listed in chart.
The gap between the core and the Remove any dirt and adjust.
shifted brake armature is higher than
0.06mm in places.
Axial run-out of the brake lock's front in Adjust the perpendicularity of the lock
relation to the shaft's axis is higher than in relation to the shaft's axis through as-
0.05mm. sembly or machining
Brake power supply voltage too low Increase the power supply voltage.
(HZg, HYg) U<0.9Uzn
Small, obstructed flow of air cooling the Improve brake cooling.
brake.
Brake's operation too intense. Decrease the number of switchings per
hour.
DEFECT CAUSE SOLUTION
Drop of the braking torque in the The brake's air gap has exceeded its Adjust the gap.
20
brake (regards motors with a brake). maximum value.
Brake pad lining worn out. Replace the brake disk.
Brake's friction surface polluted. Clean, replace the greasy brake disk.
Damaged brake springs. Replace the springs.
Current intensity asymmetry in the Asymmetry of the power supply voltage. Check and remove the cause of the
power leads. power supply voltage asymmetry.
A short circuit in the stator's winding Find and remove the short circuit (rewind
or a short circuit to the frame (to the the motor).
ground).
A break in the motor's connection or Find and remove the break.
winding.
Damage on the rotor cage. Replace the rotor.
Motor takes too long to gain speed Overloading. Decrease the load
and/or draws too much current. Low voltage during starting. Check whether the leads have an appro-
priate size.
Incorrect convertor settings. Correct the settings.
Squirrel-cage rotor damaged. Replace the rotor for a new one.
The voltage used is too low. Contact the power supply company in
order to increase the power level.
Incorrect direction of rotation. Incorrect phase order. Reverse the connections in the motor or
on the switchboard.
Overcurrent releases are activated The rotor or the ventilator seizes up. Find and remove the mechanical damage
during the motor's start (rotor, pulley, coupling, ventilator, and ca-
refully balance).
A short circuit with the frame (the Find and remove the short circuit (rewind
ground). the motor).
A break in the motor's connection or Find and remove the break.
winding.
Collegare il motore nel modo corretto.
Grinding The ventilator rubs against the cover. Eliminate the friction.
The fan is hitting the cover. Clean the fan and the cover, check the
fan's mounting on the shaft.
Looseness on the base plate. Tighten the clamping screws.
Noisy operation. Uneven air gap. Check and correct the bracket or bea-
ring mounting.
Spinning parts not balanced. Find and remove the mechanical damage
(rotor, pulley, coupling, ventilator, and ca-
refully balance).
Belt tension too high. Adjust the motor orientation and belt
tension
Incorrect coupling of the motor with the Replace the bearings. Adjust the motor
driven machine. orientation and belt tension
Brake buzzing while switching the A break in the brake's electromagnet
Replace the electromagnet.
motor off circuit.
Break in the lead supplying power to the
Remove the damage.
brake.
Brake's air gap has exceeded its maxi-
Adjust the gap.
mum value.
5. MOTOR MAINTENANCE
5. MOTOR
In order MAINTENANCE.
to maintain the motor in full technical efficiency, it is necessary to remove all defects noticed during
In order toon
operation maintain the motor
an ongoing basis.in full technical efficiency, it is necessary to remove all defects noticed during
operation
Regardlesson of
anthe
ongoing basis.
above, every working motor should be subjected to periodic maintenance inspections. Time
Regardless of the above, every working motor should be subjected to periodic maintenance inspections. Time
periods between maintenances, running and major repairs, are dependent on the conditions of motor’s work.
periods between maintenances, running and major repairs, are dependent on the conditions of motor's work.
In order to attempt any type of work related with the motor or its elements,
ATTENTION!
especially prior to taking off protective covers, prior to directly touching moving
parts or parts which can be under current, unplug the motor and all additional and
support circuits from the mains.
AFTER A MAIN INSPECTION AND ANY EVENTUAL REPAIRS OF THE MOTOR'S WINDING, CHECK THE
CONDITION OF THE WINDING'S INSULATION AS DESCRIBED IN CHAPTER 3.2.
THREE-PHASE SQUIRREL-CAGE INDUCTION MOTORS
Additionally, in motors with brakes, inspect the brake elements. A detailed description of the brakes is included in
AFTER A MAIN INSPECTION AND ANY EVENTUAL REPAIRS OF THE MOTOR’S WINDING, CHECK THE 23
CONDITION OF THE WINDING’S INSULATION AS DESCRIBED IN CHAPTER 3.2.
Additionally, in motors with brakes, inspect the brake elements. A detailed description of the brakes is included in
attachment no. 5. In case of a large number of switchings, inspect the brakes more often than every 6 months.
All defects noticed during the inspection should be removed, and worn out parts replaced with new ones.
It is recommended to renew the protective layers.
Fig. 6
Fig. 7
Fig. 7
Fig. 8
Fig.(also
Attention: For motors with a gripped bearing fig. 9 and 10, 8 regards vertical motors), prior to the disassembly of
THREE-PHASE SQUIRREL-CAGE INDUCTION
the bearing it is necessary to:MOTORS
Attention: For motors with a gripped bearing fig. 9 and 10, (also regards vertical motors), prior to the disassembly of
Attention: For motors with a gripped bearing fig. 9 and 10, (also regards vertical motors), prior to the disassem- 25
bly of the bearing it is necessary to:
• remove 3 screws mounting the bearing cover (4) and remove the rotor’s spring clip (3) (this also regards mo-
tors with a closed bearing chamber - see fig. 9)
• remove the spring clip in the bearing brackets (3) and rotor (4) (this also regards motors with a open bearing
chamber – see fig. 10).
Fig. 9 Fig. 10
In case of a motor with a brake (fig. 11), prior to the disassembly of the motor it is necessary to disassemble the
brake (19).
In case of motors with an external ventilation system (fig. 12), external ventilation (10) is disassembled along with
the cover.
Fig. 11
26
Fig. 12
Fig. 12
Fig. 13 Fig. 14
Fig. 13 Fig. 14
Disassembly of the motor's terminal box is done in accordance with drawing no. 13. Depending on the type of
Disassembly of terminal
motor, following the motor's
box terminal boxavailable:
settings are is done in accordance with drawing no. 13. Depending on the type of
motor, following terminal box settings are available:
Fig. 15 Fig. 16
Attachment no. 2. Torque values for the tightness of nuts and screws
Thread M4 M5 M6 M8 M10 M12 M16
Torque va- Min. 0,8 1,8 2,7 5,5 9 14 27
lue in [Nm] Max. 1,2 2,5 4 8 13 20 40
Connection in a ∆ Connection in a Y
2. 3-phase dual-speed general use motors (single-winding), for example, 2p=4/2, 8/4:
4. 3-phase dual-speed ventilator motor (single-winding), for example 2p=4/2W, 8/4W – motor marking ending in
„W":
GEAR 1 2p=4(8)(12) GEAR 2 2p=2(4)(6)
Connection in a Y Connection in a YY
ATTENTION! Do not supply power to the external cooling or the brake using the frequency converter.
30 6. 3-phase single-speed motors:
7. Diagram of supplying power to external cooling – in standard versions, motors have a separate external cooling
box.
a) type H brake
a) type H brake
A condition of correct functioning of the brake is to maintain perpendicularity of the surface on which the brake
rests, in relation to the motor’s axis.
Mounting the brake on the motor with an adapted bearing bracket and motor’s shaft takes place using three
clamping screws (4), spaced 3x120°. Next, the shaft is put on the central spring (5), which is rested on the be-
aring’s inner ring. Tightly screw in the clamping screw (7) to the motor’s shaft and put on the fan (3), which is led
on the internal diameter and a key channel.
Put the special washer (6) on the fan (3) and the clamping screw (7), and tighten the nut self-locking (8) until a 0.2
air gap is set (see chart 1).
Put on the gasket ring (9) between the frame (electromagnet (1)) and armature, than cover the brake with the
motor’s cover.
Chart 1
TYPE H-63 H-71 H-80 H-90 H-100 H-112 H-132 H-160
rated gap
0,2 ±0,05 0,2 ±0,05 0,2 ±0,05 0,2 ±0,05 0,2 ±0,1 0,2 ±0,1 0,2 ±0,1 0,2 ±0,1
„a”
Brakes are very simple to assemble. Mount the gear (6) on the shaft and secure from axial displacement with a
spring clip. After putting the brake disk (5) on the gear, mount the brake using clamping screws (10) to the mo-
tor’s bearing cover, mounting plate (7) or wall of the mated device. If the brake has blocking elements (14), they
should be removed after mounting the brake. Check the air gap „a” value, which should be equal to the „a nom”
value listed in chart 2. In case of finding a discrepancy, adjust the gap as described in paragraph 3. Put on the
brake cover.
Disassembly should be done in reverse order.
Chart 2
TYPE HPS06 HPS08 HPS10 HPS12 HPS14 HPS16 HPS18 HPS20 HPS25
a nom. 0,2 ±0,05 0,2 ±0,05 0,2 ±0,05 0,3 ±0,05 0,3 ±0,05 0,3 ±0,05 0,3 ±0,05 0,3 ±0,05 0,3±0,05
a max. 0,5 0,5 0,5 0,7 0,8 1,0 1,0 1,2 1,4
H(Z,Y)g brakes are very simple to assemble. Mount the gear (1) on the shaft and secure from axial displacement
with a spring clip. After putting the brake disk (7) on the gear, mount the brake using clamping screws to the
motor’s bearing bracket or wall of the mated device. Use cast iron or steel as the friction surface. If case of diffi-
culties creating a friction surface on the mated device, use a mounting plate (9).
When the DC brake needs to be connected to an AC source, two rectifying circuits are used. The attachable coil
of the brake’s electromagnet circuit can be detached on the direct or alternating current side.
When switching off the voltage, the magnetic field causes that the coil's current flows through the rectifying diode
andWhen
falls switching off the voltage,
slowly. Magnetic field is the magnetic
reduced field causes
gradually, whichthat the coil’s
causes current flows
a lengthened through
period of thethe rectifying
brake's diode
operation,
which means a delayed increase of the braking torque. If the working time is insignificant,
and falls slowly. Magnetic field is reduced gradually, which causes a lengthened period of the brake’s operation, the brake should be
When switching
connected on theoffalternating
the voltage, the magnetic
current side, field
since no causes
other that the coil's
protection for thecurrent
coil flows
and thethrough
contactstheis rectifying
needed. diode
When
andwhich
falls means aMagnetic
slowly.off,delayed increase
field is actof the braking
reduced gradually,torque.
whichIf the working
causes time is insignifi
a lengthened periodcant, thebrake's
of the brake should be
operation,
being switched
connected on thesupply circuits
alternating as unidirectional
current side, since nodiodes.
other protection for the coil and the contacts is needed.
which means a delayed increase of the braking torque. If the working time is insignificant, the brake should be
When being
connected switched off, supply
on the currentcircuits act asnounidirectional diodes.
- SWITCHING OFFalternating
ON THE DIRECT side, since
CURRENT SIDEother protection for the coil and the contacts is needed. When
being switched off, supply circuits act as unidirectional diodes.
- SWITCHING OFF ON THE DIRECT CURRENT SIDE
- SWITCHING OFF ON THE DIRECT CURRENT SIDE
Coil's current is broken between the coil and the power supply (rectifying) circuit. Magnetic field is reduced very
quickly, brake's operation time is short, in consequence, the braking torque increases quickly. When tripping on the
side of direct current in the coil, high peak voltage is generated causing faster wearing out of contacts due to
Coil's current
sparking. is broken
In order between
to protect the coil
the coil and peak
the power supply (rectifying) circuit. Magnetic
from fifield is reduced very
Coil’s brake's
quickly, current is broken
operation between
time is theagainst
short, coil
in
voltage
and the power
consequence, the
and to
supply
braking
protect the
(rectifying)
torque
contacts
circuit.
increases Magnetic
quickly.
excessive
When
wear,very
eld is tripping
reduced on
the
the
rectifying
quickly,circuits
brake’s have protection
operation time allowing
is short, to
in connect the brake
consequence, the on the direct
braking current
torque side. quickly. When tripping on
increases
side of direct current in the coil, high peak voltage is generated causing faster wearing out of contacts due to
the side oforder
sparking. directto
current in the coil, high peak voltage is generated causing faster wearing out of contacts due to
b) H(Z,Y)gIntype brakeprotect the coil against peak voltage and to protect the contacts from excessive wear, the
rectifying circuits
sparking. have
In order toprotection
protect the allowing to connect
coil against the brake
peak voltage onto
and the direct the
protect current side. from excessive wear, the
contacts
rectifying circuits have protection allowing to connect
Connecting the brake is done according to the above drawing. the brake on the direct current side.
b) H(Z,Y)g type brake
b) H(Z,Y)g type brake
Connecting the brake is done according to theL1 L2
above drawing. L3
BRAKE
Air gap „a” increases as a result of the brake disk (5) wearing out. The appropriate initial „a nom.” value of the
gap can be restored by screwing in the adjustment screws (11) into the frame (1). When adjusting, loosen the
clamping screws (10), use a gap gauge inserted between the armature and the frame by screwing in the adjust-
ment screws (11), set the air gap to the rated value. Tighten the clamping screws (10) – total stiffening of the
attachment point is achieved by countering it with adjustment screws, meaning by unscrewing them to the limit
with the mounting plate of the surface of the mated device.
Correct work of the brake is ensured when the S and S1 gaps have correct values.
Gap values:
S nom = 0.4 mm S max = 1.4 mm S 1 = 2 mm
In case of exceeding the listed S max value, adjust the air gap immediately. In order to do this:
- remove the rubber band (12),
- loosen the screws (10) and (13) clamping the brake, unscrewing them half a turn,
- through openings in the cover (11), tighten the adjustment screws (3) to the bearing ring (6) by about 2 mm 2mm
- place a gap gauge with thickness of S nom +/- 0.05 mm in the gap between the electromagnet’s core (5) and
the armature (2).
- using clamping screws, press the core to the armature so that the gap gauge can be taken out with little re-
sistance and with the same resistance insert it in gaps every 120 degrees from the place of initial measurement,
- unscrew adjustment screws so they rest on the mounting plate or the motor’s bearing bracket, or another ma-
ted device,
- tighten the brake’s clamping screws and check the size of gap S,
- in brakes with a manual release lever (14), self-locking nuts (15) must be set so that their distance from the
armature plate S 1=2mm is maintained when the armature is shifted, i.e. when S = 0.
5. Periodic inspections