Professional Documents
Culture Documents
PDB Activation Manual
PDB Activation Manual
Table of Contents
Pre Activation Steps ............................................................................................................................ 1
Power Activation.................................................................................................................................. 1
DC PSU Activation .............................................................................................................................. 2
48Vdc Power Supply to PDB............................................................................................................... 2
24Vdc Power Supply to Auxiliary Circuits ........................................................................................... 2
PLC Setup ........................................................................................................................................... 2
Reset to Factory Defaults ................................................................................................................ 2
PLC Site System Configuration ....................................................................................................... 3
Modem ......................................................................................................................................... 3
Pylon Lights.................................................................................................................................. 3
Air Conditioner.............................................................................................................................. 4
PSU .............................................................................................................................................. 4
Generator ..................................................................................................................................... 4
Power Analyzer ................................................................................................................................... 4
Phase monitoring relay........................................................................................................................ 5
Rhomberg SP-430 ........................................................................................................................... 6
Carlo Gavassi PPB02 ...................................................................................................................... 6
Confirmation..................................................................................................................................... 6
Aviation Lights (Dusk Switch, Current Monitor)................................................................................... 7
Light Sensor Activation .................................................................................................................... 8
Current Monitor Relay Activation ..................................................................................................... 8
Rhomberg SP-103........................................................................................................................ 8
Carlo Gavassi PIB01 .................................................................................................................... 8
Climate Unit Activation ........................................................................................................................ 9
Compressor Current Monitor Relay ................................................................................................. 9
Rhomberg SP-103........................................................................................................................ 9
Carlo Gavassi PIB01 .................................................................................................................... 9
High/Low Temperature Thermostats.................................................................................................10
Internal lights .....................................................................................................................................10
Motion detector..................................................................................................................................10
External light......................................................................................................................................11
Internal lights switch ..........................................................................................................................11
Power Sockets...................................................................................................................................11
Install SIM Card .................................................................................................................................11
Analogue Readings Confirmation......................................................................................................11
Warning
Leaving the label attached may result in malfunction since it blocks air circulation needed.
Power Activation
Having connected the Mains Input to the PDB Terminals 1X1 you have to adjust the mains distribution
switches according to the type of the Power Supply provided.
If the Power Supply is provided by the external Plug, the switches state should be:
Breaker/Switch Status
1F1 OFF
1SG1 0 (OFF)
1SG2 II (ON)
1F2 ON
DC PSU Activation
Turn on the Circuit Breaker 1F7 so as to provide the DC PSU with Power Supply.
Follow the DC PSU Instructions so as to set the unit in operation.
Warning
Confirm that the -48V DC wires to the Terminals 1X5.1 and 1X5.2 have the correct polarity:
• 1X5.1: +48 Vdc
• 1X5.2: 0 Vdc
PLC Setup
Press the “Reset to Factory Defaults” button. On the confirmation screen that appears select “Yes”.
On the “Enter Password” screen, touch the text box: “#####” and type: 2150.
Follow the instructions described in the next sections so as to configure the PLC Site Menu.
Modem
Modem
No Modem Installed Initially selected option, one of the following should be selected.
Modem GM29 Installed Select this option in case that the Modem installed is the Sony Ericsson.
Modem BenQ Installed Sselect this option in case that the Modem installed is the BenQ.
Modem Wavecom Installed Select this option in case that the Modem installed is the Wavecom.
Modem ADEM Installed Select this option in case that the Modem installed is the ADEM.
Modem Other Installed Not applicable, available for future use.
Pylon Lights
Pylon Lights
Initially selected option, leave it selected in case of site without Pylon
No Lights Installed
Lights installed.
Select this option in case that one pair of pylon lamps is installed and
1 Set Installed
that is connected to the PDB.
Select this option in case that one pair of pylon lamps is installed and
2 Set installed
that is connected to the PDB.
Air Conditioner
Air Conditioner 1
A/C 1 No A/C Select “Has A/C” in case that Air Conditioner is installed with the
Has A/C PLC Command Cable. Otherwise select “No A/C”.
F/C 1 A/C 1 Free Cooling Select “Has A/C1 Free Cooling” if Free Cooling is installed.
No A/C 1 Free Cooling Otherwise select “No A/C1 Free Cooling”
Air Conditioner 2
A/C 1 No A/C Select “No A/C”.
Has A/C
F/C 1 A/C 1 Free Cooling Select “No A/C 1 Free Cooling”.
No A/C 1 Free Cooling
PSU
PSU 1
Select this option in case that the PSU does not support serial
No PSU Installed
communication with the PLC or the connection is not implemented.
Select this option in case that of Sunlight DC PSU that is connected to the
Sunlight Installed
PLC via serial cable and communication is error free.
Select this option in case that of Raycap DC PSU that is connected to the
Raycap Installed
PLC via serial cable and communication is error free.
Select this option in case that of Antrice DC PSU that is connected to the
Antrice Installed
PLC via serial cable and communication is error free.
Other Installed Available for potential use
Has Second PSU
Select “No Second PSU”.
No Second PSU
Generator
PSU 1
No Generator Select this option in case that there is not Generator installed.
in case that there is Generator but the there is no Controller or the Controller
Generator No Controller
is not connected to the PLC.
Generator Other
available for potential use
Controller
Generator with AMF in case that the Generator Controller is AMF 5220 and is connected to the
5220 PLC.
Power Analyzer
Turn on the circuit breaker 1F3 so as to provide the Power Analyzer with power. The Power Analyzer
should be configured so as to communicate with the PLC.
To setup of the Lovato DMK-52 Power Analyzer perform the followings steps:
1. Press concurrently the buttons C and D for 5 to 10 seconds, until the display readings
change.
2. Use the A and B buttons to change the parameter value. Use also C and D buttons to select a
parameter.
3. Select the parameter No. 1 (P.1) and set the value to 20.0.
4. Select the parameter No. 41 (P.41) and set the value to 6.
5. Press concurrently the buttons C and D for 5 to 10 seconds, until the display readings
change.
Having performed the Power Analyzer activation, visit the PLC Touch Screen “Power Parameters”
monitor page so as to confirm that the Power Analyzer operation is normal. Form the PLC Touch
Screen Main page follow the path presented in the figure below at the left side. The right below figure
is presented on the Touch Screen. Confirm that the Voltage and Current Readings are at the normal
level.
Rhomberg SP-430
In order to calibrate the Rhomberg SP430 Phase Monitor Relay set the P1
adjustment switch to 10% that corresponds to the sensitivity of 3-phase
voltage imbalance.
Having turned on the 1F3 Circuit Breaker the LED 1 should lit on. If not,
confirm the followings:
• The PDB Input Voltage level is 400Vac ± 10%.
• Three Phase Voltage is provided with the right sequence.
Confirmation
Note
In order to confirm the proper operation of the Phase Monitor Relay (Rhomberg and Carlo
Gavassi) 3 Phase Power Supply is needed.
One Phase Power Supply looped in the circuits of the PDB can not be used for testing.
Having performed the Phase Monitor Activation steps, the “Electric Power Failure Alarm” should be at
normal status. In order to confirm this visit the “Alarm Output” page on the PLC Touch Screen
following the path presented in the left below figure. On the screen that appears, the “KA6 Electric
Power Failure” should be “OK”.
Warning
The Aviation Lights Activation steps described below require that a pair of Aviation Lights is
installed to the PDB following the Installation Manual. Also, the Primary Lamp should be
operational.
The following paragraphs describe the configuration of both Current Monitor Relays, Rhomberg SP-
103 and Carlo Gavassi XXX, that are used for the Pylon Lights control panel.
Rhomberg SP-103
While the Primary Lamp is activated the LED 1 should light.
If not confirm the following settings:
• S1: 1A
• S2: UL
• P1: 10% is recommended (not critical)
• P2: 20%
• P3: 5 s – half of the scale (not critical)
Internal lights
Confirm that the Circuit Breaker 1F5 is turned on.
By the time that the Door of the Shelter is opened (Door Switch Contact signal) the Internal Lights
should light on.
Motion detector
Confirm that the Circuit Breaker 1F5 is turned on.
Set the Motion Detector mode to “3 min”. By the time that a movement is detected outside of the
shelter the Motion Detector activates the red indicator at the front side of it. Also the PDB relay 1K14
as well as the PLC input 9 on card 1A4 are activated.
External light
Confirm that the Circuit Breaker 1F5 is turned on.
When the Dusk switch detects “Night” and the Motion Detector senses a movement, the External
Lights are activated.
Power Sockets
Turn the Circuit Breaker 1F15 to activate the PDB Schucko Socket 1XU1.
Turn the Circuit Breaker 1F4 to activate the Shelter Schucko Socket.
Use the following tables in order to confirm that the Indoor and Outdoor Thermometers as well as the
-48Vdc Power Supply to the PDB are properly connected. For example: Regarding the “Temp
External CH2” measurements, if the value presented in the Touch Screen is 1.663 V, according to the
table, the corresponding temperature is 25 oC. Use a thermometer so as to confirm that the PLC
reading in correct. Perform also this using a DC Voltage multimeter so as to confirm the “PSU1
48VDC” readings.
PSU 1 48Vdc – CH0
DC Volt Raw Value DC Volt Raw Value DC Volt Raw Value
55.0 7.857 V 51.0 7.286 V 47.0 6.714 V
54.9 7.843 V 50.9 7.271 V 46.9 6.700 V
54.8 7.829 V 50.8 7.257 V 46.8 6.686 V
54.7 7.814 V 50.7 7.243 V 46.7 6.671 V
54.6 7.800 V 50.6 7.229 V 46.6 6.657 V
54.5 7.786 V 50.5 7.214 V 46.5 6.643 V
54.4 7.771 V 50.4 7.200 V 46.4 6.629 V
54.3 7.757 V 50.3 7.186 V 46.3 6.614 V
54.2 7.743 V 50.2 7.171 V 46.2 6.600 V
54.1 7.729 V 50.1 7.157 V 46.1 6.586 V
54.0 7.714 V 50.0 7.143 V 46.0 6.571 V
53.9 7.700 V 49.9 7.129 V 45.9 6.557 V
53.8 7.686 V 49.8 7.114 V 45.8 6.543 V
53.7 7.671 V 49.7 7.100 V 45.7 6.529 V
53.6 7.657 V 49.6 7.086 V 45.6 6.514 V
53.5 7.643 V 49.5 7.071 V 45.5 6.500 V
53.4 7.629 V 49.4 7.057 V 45.4 6.486 V
53.3 7.614 V 49.3 7.043 V 45.3 6.471 V
53.2 7.600 V 49.2 7.029 V 45.2 6.457 V
53.1 7.586 V 49.1 7.014 V 45.1 6.443 V
53.0 7.571 V 49.0 7.000 V 45.0 6.429 V
52.9 7.557 V 48.9 6.986 V 44.9 6.414 V
52.8 7.543 V 48.8 6.971 V 44.8 6.400 V
52.7 7.529 V 48.7 6.957 V 44.7 6.386 V
52.6 7.514 V 48.6 6.943 V 44.6 6.371 V
52.5 7.500 V 48.5 6.929 V 44.5 6.357 V
52.4 7.486 V 48.4 6.914 V 44.4 6.343 V
52.3 7.471 V 48.3 6.900 V 44.3 6.329 V
52.2 7.457 V 48.2 6.886 V 44.2 6.314 V
52.1 7.443 V 48.1 6.871 V 44.1 6.300 V
52.0 7.429 V 48.0 6.857 V 44.0 6.286 V
51.9 7.414 V 47.9 6.843 V 43.9 6.271 V
51.8 7.400 V 47.8 6.829 V 43.8 6.257 V
51.7 7.386 V 47.7 6.814 V 43.7 6.243 V
51.6 7.371 V 47.6 6.800 V 43.6 6.229 V
51.5 7.357 V 47.5 6.786 V 43.5 6.214 V
51.4 7.343 V 47.4 6.771 V 43.4 6.200 V
51.3 7.329 V 47.3 6.757 V 43.3 6.186 V
51.2 7.314 V 47.2 6.743 V 43.2 6.171 V
51.1 7.300 V 47.1 6.729 V 43.1 6.157 V