Professional Documents
Culture Documents
Detection and Isolation of Interturn Faults in Inductors of LCL Filter For Marine Electric Propulsion System
Detection and Isolation of Interturn Faults in Inductors of LCL Filter For Marine Electric Propulsion System
1, MARCH 2018
TABLE I
R EVIEW ON I NTERTURN FAULT D ETECTION T ECHNIQUES FOR I NDUCTORS
an early fault detection and isolation technique for converter- fault at the midpoint of the winding and is also influenced
side inductors of the LCL filter using the core-leakage flux is by load and supply voltages. Besides, six SCs are required
presented. for each phase winding to improve the fault detection sen-
Winding faults contribute to 30%–40% of the total fail- sitivity which results in complex interconnections. Gradual
ures of the inductors [6] which incur expensive downtime inductor degradation and winding fault detection using the
and in certain scenario catastrophic consequences. The low- core-leakage fluxes have been discussed in [19] and [20],
severity interturn fault is the predominant winding fault which respectively. The Hall-effect-based magnetic flux sensors are
eventually leads to the disastrous phase-to-phase or phase- used to detect the changes in the core-leakage fluxes at
to-ground fault. The interturn faults at a low-severity the outer limbs [19] and at the yoke center [20] during
level (1–5 turn short circuited) are difficult to detect as degradation and winding fault, respectively. The methodology
the change in voltages and currents encountered are very in [19] can detect the gradual inductance degradation from
small [6]–[8] which demands sensitive fault detection tech- 3% by using the coupled inductor’s core-leakage fluxes at the
niques. A survey of interturn fault detection techniques outer limbs which is not suitable for low-severity interturn
revealed that most of the techniques are for transformers and fault detection [20]. In [20], an online technique to detect
some of the techniques are directly applicable to the inductors. the high-severity interturn fault (29% of the total turns are
The techniques applicable to the inductors, their principles, shorted) using the core-leakage flux at the yoke center is
and disadvantages are listed in Table I. presented. Such a fault condition is critical which leads to
As the proposed methodology is based on the leakage complete winding damage within few seconds and increased
flux, the techniques proposed in [16]–[20] are discussed and downtime [6]–[8].
explained further. The search coils (SCs)-based technique From the literature review, it is evident that the leakage
to identify 1-turn and 5-turn faults have been presented flux-based interturn fault detection techniques for the inductors
in [16]–[18]. The technique can detect as low as 1-turn are proposed and validated under high level of fault severity.
fault. However, the methodology is unable to detect interturn Some of the techniques detect the low-severity interturn faults
234 IEEE TRANSACTIONS ON TRANSPORTATION ELECTRIFICATION, VOL. 4, NO. 1, MARCH 2018
where
Vaa fundamental phasor of the voltage
across the phase winding a-a ;
Ia , Ib , and Ic fundamental phasors of the terminal
currents of the phase windings a-a ,
b-b , and c-c , respectively;
Mba and Mca mutual inductances of the phase
winding a-a with respect to b-b
and c-c , respectively;
Raa , Rna , and Ri resistances of the phase winding
a-a , short-circuited turn n-a , and
external short-circuit resistor, Fig. 3. Total impedance variation of the inductor during interturn faults.
respectively;
L aa , L na , and L an inductances of the phase winding
a-a , short-circuited turn n-a , and Representing L an and L na of (3) in terms of turns ratio (4)
healthy turns a-n, respectively; gives the following equation:
kc coupling co-efficient between the
j ωL aa [1 + kc (a − 1)]
short-circuited turn n-a and the Z f = Z h − Rna +
a2
phase winding turns a-a ; ⎡ ⎤
j ωL aa [1+kc (a−1)]
If fundamental phasor of interturn fault Rna + + j ωM )
×⎣ ⎦. (5)
a2 f
current; j ωL aa
Ri + Rna + a 2
Mb f and Mc f mutual inductances of the
short-circuited turn n-a with respect As all the phase windings are on the same core, the coupling
to the healthy phase windings b-b coefficients between the short-circuited turn n-a and the phase
and c-c , respectively. windings b-b and c-c are the same as the coupling co-efficient
Substituting (2) in (1) gives the following equation: between the short-circuited turn and the phase winding
turns a-a . Besides, the inductances in all the three windings
Vaa of the inductor are almost the same. Therefore, the mutual
= Z f = Z h − [Rna j ω(L na kc L an L na )]
Ia inductance M f in (5) can be expressed in terms of phase
√ inductance L aa and turns ratio a as given by the following
Rna + j ω(L na + kc L an L na + M f )
× equation:
Ri + Rna + j ωL na
(3) j ωL aa [1 + kc (a − 1)]
Z f = Z h − Rna +
a2
where ⎡ ⎤
j ωL aa [1+kc (a−1)] j ωL aa
Rna + +
×⎣ a2 ⎦ (6)
Zf impedance of the inductor a
j ωL aa
under interturn fault; Ri + Rna + a 2
Fig. 4. Magnetic equivalent circuits of the coupled inductor. (a) Healthy condition. (b) Interturn fault condition.
The total core flux at the limb a under healthy operating phasor of the fluxes on limb a or c due to limb c or a
condition of the coupled inductor (ϕaT h ) is given by the MMFs under interturn fault condition of the coupled
following equation: inductor.
The total core fluxes at limb a, limb b, and limb c under
ϕaT h = ϕah − ϕbah − ϕcah interturn fault condition of the coupled inductor (ϕaT f , ϕbT f ,
N and ϕcT f ) are given by the following equations:
= (b (Ia − Ic ) + c (Ia − Ib )) (8)
T
ϕaT f = ϕa f − ϕba f − ϕca f
where Na = Nb = Nc = N.
N
Similarly, the total core flux at the limb b, ϕbT h and limb c, =
TF (b + c ) + T
ϕcT h under healthy operating condition of the coupled inductor
b (Ia − Ic ) + c (Ia − Ib )
are given by the following equations: × Nna (12)
− I f (b + c )
ϕbT h = ϕbh − ϕabh − ϕcbh N
ϕbT f = ϕb f − ϕab f − ϕcb f
N
= (a (Ib − Ic ) + c (Ib − Ia )) (9) N
T =
ϕcT h = ϕch − ϕach − ϕbch TF (b + c ) + T
N a (Ib − Ic ) + c (Ib − Ia )
= (a (Ic − Ib ) + b (Ic − Ia )) . (10) × Nna (13)
T +TF (Ib − Ic ) − I f c
N
The total core flux at the yoke center under healthy operating ϕcT f = ϕc f − ϕac f − ϕbc f
condition of the coupled inductor is given by the following N
equation: =
TF (b + c ) + T
ϕoT h = ϕaT h + ϕbT h + ϕcT h = 0. (11) a (Ic − Ib ) + b (Ic − Ia )
× Nna . (14)
From (8) and (10), the core flux at the outer limbs a and c +TF (Ic − Ib ) − I f b
N
depend on the terminal currents which is the function of The total core flux at the yoke center under interturn fault
loading and supply voltage unbalance conditions. However, condition of the coupled inductor is given by the following
from (11), the core flux at the yoke center is zero, irrespective equation:
of the supply voltage unbalance and loading conditions. But,
due to the magnetic asymmetry there will be a finite value ϕoT f = ϕaT f + ϕbT f + ϕcT f
of core flux at the yoke center. When there is an interturn N 2Nna
fault, the magnetic asymmetricity increases which in turn = − I f (b + c ) .
TF (b + c ) + T N
increase the core flux at the yoke center which is discussed (15)
in Section II-B2.
2) Core Flux During Interturn Fault Condition of the To simplify, the asymmetricity due to the reluctances are
Coupled Inductor: Fig. 4(b) presents the magnetic equivalent neglected and all the reluctances values are considered to be
circuit of the coupled inductor under interturn fault in the the same (Ra = Rb = Rc = R). Therefore, (12) and (15) can
limb a winding. The interturn fault leads to drop in the be expressed as follows:
voltage across the shorted turns due to the high turn-fault N 2Nna
current when compared to the terminal currents. The high turn- ϕaT f = 3Ia − If
(2TF + 3) N
fault current in the shorted turns generates MMF such that it
N 2Nna
opposes the main MMF generated by the terminal current of = 3Ia − If
(2TF + 3) N
that corresponding winding. Therefore, the reluctances faced
N
by the core fluxes increase due to the additional reluctance by (3Ia ) (16)
(2TF + 3)
turn fault [16]–[18], [21]–[23].
In Fig. 4(b), TF is the additional reluctance due to interturn N 4Nna
ϕoT f = − If
fault in the limb a winding; Nan and Nna are the total number (2TF + 3) N
of healthy and faulty turns in limb a winding; I ∗ = (Ia − I f ) N 4Nna
= − If (17)
is the fundamental phasor of the current in shorted turn; (2TF + 3) N
ϕaT f , ϕbT f , ϕcT f , and ϕoT f are the fundamental phasors of
where (Ia + Ib + Ic = 0), for a three-phase system.
the total fluxes in limbs a, b, c, and at yoke center under
interturn fault condition of the coupled inductor; ϕa f , ϕb f , From (16), the core flux at the outer limb a is a function of
and ϕc f are the fundamental phasors of the fluxes generated terminal current Ia . Therefore, the magnitude of the core flux
by the MMFs of the windings in limbs a, b, and c under at the outer limb a changes insignificantly under low-severity
interturn fault condition of the coupled inductor; ϕba f or ϕab f interturn fault conditions. However, the core flux at the yoke
is the fundamental phasor of the flux on limb a or b due to center is a function of interturn fault current I f and the number
limb b or a MMFs under interturn fault condition of the of shorted turns Nna as given by (17). Therefore, it is a robust
coupled inductor; and ϕca f or ϕac f is the fundamental indicator of interturn fault in any of the winding of the coupled
238 IEEE TRANSACTIONS ON TRANSPORTATION ELECTRIFICATION, VOL. 4, NO. 1, MARCH 2018
Fig. 5. Normalized core-leakage fluxes at the outer limb and yoke center for various degrees for interturn fault conditions. (a) Core-leakage flux at the outer
limb a. (b) Core-leakage flux at the yoke center.
inductors. It should be noted that (16) and (17) represent the the effect of turn fault is obscured by the terminal currents
core fluxes which are impractical to sense/measure as it flows which flows through the winding at the limb a as given by
inside the core. However, the core-leakage fluxes at the surface (18). Therefore, from (18) and Fig. 5(a), change in the core-
of the core can be easily sensed which reflect the characteristic leakage fluxes at the outer limbs during low-severity interturn
of the core flux. Therefore, the core fluxes (16) and (17) faults are insignificant which validates the developed model
can be represented by the core-leakage fluxes with leakage (18). From (19), it is evident that the core-leakage flux at the
coefficients corresponding to the location where the fluxes are yoke center during interturn fault condition is proportional to
sensed as given by the following equations: the fault current I f and the number of faulty turns Nna , which
emulates the core-leakage flux at the yoke center as a direct
2Nna
ϕaT f −l = ka f 3Ia − I f ka f (3Ia ) (18) indicator of interturn fault. From Fig. 5(b), the normalized
N
core-leakage fluxes at the yoke center increases for various
4Nna
ϕoT f −l = ko f − If (19) degrees of interturn faults under different loading conditions.
N The proposed technique is based on the abnormal change in the
Nka Nko core-leakage fluxes from healthy to interturn fault conditions.
where ka f = and ko f =
(2TF +3 ) (2TF +3 )
Therefore, the change in the trend of the core-leakage fluxes
where from healthy to interturn fault condition is important rather
ϕaT f −l fundamental phasor of the core-leakage flux than the absolute value. The trend of the experimental results
at the outer limb a under interturn fault agrees with the theoretical analysis carried out using the devel-
condition of the coupled inductor; oped models (18) and (19), thereby validating the developed
ϕoT f −l fundamental phasor of the core-leakage flux models.
at the yoke center under interturn fault
condition of the coupled inductor;
ka f and ko f leakage coefficients at the outer limb a and C. Comparison of the Grid Currents and the Core-Leakage
at the yoke center during interturn fault Flux at the Yoke Center During Interturn Fault Condition of
condition of the coupled inductor; the Coupled Inductor
ka and ko constants representing the leakage Fig. 3 presents the total impedance variation of the inductor
coefficients corresponding to the location under various interturn fault conditions. From Fig. 3, it can be
where the flux sensors are placed at the observed that during 1-turn, 2-turn, and 4-turn fault conditions,
outer limb a and at the yoke center. the total impedance variation is insignificant (<1%). However,
Fig. 5 presents the experimental results of the core-leakage for 6-turn fault the total impedance has reduced consider-
fluxes sensed/measured at the outer limb a and at the yoke ably (>1%). In the LCL filter, the inductors are in series with
center of the converter-side inductor of the MPS test rig. the load. Therefore, during 6-turn fault, input impedance of the
The measured values of core-leakage fluxes for various inter- AFER reduces considerably and leads to mild increase in the
turn fault severities under different loading conditions are grid currents which contribute to the active power consumed
normalized with respect to the core-leakage fluxes of the by short-circuited turn resistance. Hence, 6-turn fault can be
corresponding loading conditions and are presented in Fig. 5. detected using the grid currents. However, 6-turn fault is a
From Fig. 5(a), variations of the normalized core-leakage high-severity fault which is the result of gradual increase in
fluxes at the outer limb a for various degrees of interturn fault the fault severity from 1-turn fault. Therefore, the grid currents
under different loading conditions are minimal. The highest are not a reliable indicator of low-severity interturn fault
change being 8% for 4-turn fault at 34% of full load as shown conditions. However, the core-leakage flux at the yoke center
in Fig. 5(a). The change in the core-leakage fluxes at the outer of an inductor as represented by (19) is a robust indicator of
limb a under 1-turn and 2-turn fault is insignificant because low-severity interturn faults.
CHANDAR A. AND PANDA: DETECTION AND ISOLATION OF INTERTURN FAULTS IN INDUCTORS 239
TABLE III
S PECIFICATIONS OF THE E QUIPMENT AND S ENSORS U SED IN THE MPS T EST R IG
Fig. 7. Scaled-down MPS test rig. 1—AFE drive, 2—motor drive, 3—grid-side inductor, 4—converter-side inductor, 5—capacitors, 6—induction motor,
7—synchronous generator, 8—8.4-kW resistive load bank, 9—voltage stabilizer, 10—dSPACE1103, 11—amplifiers and fourth-order low-pass filter,
12—external short-circuit resistances, 13—Hall-effect flux sensor, 14—current sensors, 15—antialias filter, and 16—placement of flux sensors.
Fig. 8. Time-domain signal of (a) grid and dc-link voltages, (b) grid currents, (c) capacitor currents, and (d) converter-side inductor’s core-leakage fluxes at
full load (11.3 kW) condition of the AFER. (Core-leakage flux at the yoke center is multiplied by a factor of 10.)
the fundamental component of the core-leakage flux. Hence, that the magnitudes of the fundamental components of the
the magnitude of the fundamental component of a grid current core-leakage fluxes at the yoke center are changing for dif-
and core-leakage flux at the yoke center under 34% and 100% ferent loading conditions as that of the grid currents shown
for full-load capacity of the MPS test rig are presented in Fig. 9(a). Ideally, the magnitude of the core-leakage fluxes
in Fig. 9(a) and (b). From Fig. 9(b), it can be observed at the yoke center should be 0 as given by (11), but due to
CHANDAR A. AND PANDA: DETECTION AND ISOLATION OF INTERTURN FAULTS IN INDUCTORS 241
Fig. 9. Frequency spectrum of the (a) grid currents and (b) converter-side inductor core-leakage fluxes at 3.8 kW (34%) and 11.3 kW (100%). (Core-leakage
flux at the yoke center is multiplied by a factor of 10.)
magnetic asymmetricity there is a finite value and it increases conditions and is presented in Fig. 10. From Fig. 10, the fol-
with the increase in the terminal currents. Therefore, it is nec- lowing conclusions can be inferred.
essary to conduct a baseline measurement of the core-leakage 1) During 1-turn fault of the converter-side inductor,
fluxes at the yoke center for different loading conditions. the variation in the grid currents for different loading
Under healthy operating conditions of the converter-side conditions is insignificant as shown in Fig. 10(a). This
inductor, the magnitudes of the fundamental components of is mainly due to the very small change in the total
the grid currents and the core-leakage fluxes at the yoke center impedance of the converter-side inductor for 1-turn fault
for various loading conditions are extracted using FFT and condition as given by (6). However, the core-leakage
saved in the FLASH memory of digital signal processor (DSP). fluxes at the yoke center as given by (19) show a sub-
Under online operating conditions, the magnitudes of the fun- stantial increase in its magnitude as shown in Fig. 10(b)
damental components of the captured grid currents are checked and are a reliable indicator of 1-turn fault under different
with the grid current magnitudes saved in the DSP to identify loading conditions.
the loading condition. Then, the magnitude of the reference 2) Like 1-turn fault, 2-turn fault condition also shows
core-leakage flux corresponding to that loading condition is insignificant variation in the grid currents for different
extracted from the baseline measurements and compared with loading conditions as shown in Fig. 10(c). The core-
the magnitude of the core-leakage flux under online operating leakage fluxes at the yoke center show a substantial
condition to detect the interturn fault for that corresponding increase in its magnitude for different loading condi-
loading condition. The detailed discussion about the interturn tions as shown in Fig. 10(d). Besides, the core-leakage
fault detection using the baseline measurements is presented fluxes at the outer limb c show a mild increase in its
in Section IV-B. magnitude under different loading conditions as shown
in Fig. 10(d). However, the magnitude of the core-
A. Comparison of the Grid Currents and the Core-Leakage leakage fluxes at the yoke center is more than that of
Fluxes at the Outer Limbs and at the Yoke-Center During the core-leakage fluxes at the outer limb c.
Interturn Faults 3) During 4-turn fault condition, once again the core-
The AFER integrated with the LCL filter has grid currents leakage fluxes at the yoke center are a reliable and
and grid voltages sensors for closed loop operation. Therefore, robust indicator of turn fault as shown in Fig. 10(f).
any technique which utilizes only the existing sensors of There is a minor increase in the magnitude of the grid
the AFER to detect interturn fault in the inductors of the currents and the core-leakage fluxes at the outer limbs
LCL filter integrated with the AFER can be considered as as shown in Fig. 10(e) and (f), respectively. However,
sensor-less approach. Hence, a comparative study of the grid the substantial increase in the magnitude of the core-
currents and the core-leakage fluxes at the outer limbs of leakage fluxes at the yoke center clearly dominates the
the converter-side inductors are carried out to identify the increase in magnitude of the grid currents and the core-
best indicator of low-severity turn faults which is presented leakage fluxes at the outer limbs. From Fig. 10(e), it is
in this section. Fig. 10 presents the comparison of the grid evident that there is a finite increase in the magnitude of
currents and the core-leakage fluxes at the outer limbs and the fundamental component of the grid current for 4-turn
at the yoke center for 1-turn, 2-turn, and 4-turn faults at fault which is not observed for 1-turn and 2-turn fault
34% (3.8 kW), 73% (8.3 kW), and 100% (11.3 kW) of conditions as shown in Fig. 10(a) and (c), respectively.
the MPS full-load capacity. The grid currents and the core- This is mainly due to the substantial decrease in the total
leakage flux signals are captured at a sampling frequency impedance of the converter-side inductance for 4-turn
of 20 kHz for 0.5 s and FFT computation is carried out fault when compared to 1-turn and 2-turn fault as shown
using MATLAB. The magnitudes of the fundamental compo- in Fig. 3. The turn fault consumes additional active
nents are extracted, normalized with respect to the magnitudes power which is dissipated by the short-circuit resistance
under healthy operating condition for appropriate loading connected across the faulty turns. This increase in active
242 IEEE TRANSACTIONS ON TRANSPORTATION ELECTRIFICATION, VOL. 4, NO. 1, MARCH 2018
Fig. 10. Variation of grid currents and converter-side inductor core-leakage fluxes for 1-turn, 2-turn, and 4-turn fault under different load conditions.
(All the values are normalized with respect to healthy values at corresponding load conditions.) (a) Grid currents under 1-turn fault. (b) Core-leakage fluxes
under 1-turn fault. (c) Grid currents under 2-turn fault. (d) Core-leakage fluxes under 2-turn fault. (e) Grid currents under 4-turn fault. (f) Core-leakage fluxes
under 4-turn fault.
power leads to a mild increase in the magnitude of the flux at the yoke center to identify the loading conditions and to
grid currents as observed in Fig. 10(e). detect the interturn fault, respectively. The captured grid cur-
The experimental investigation of grid currents and rents and the core-leakage flux signals are amplified, filtered,
converter-side inductor core-leakage fluxes during the low- and then further processing is carried out. The framework has
severity interturn faults follow the analysis carried out using two different methods for reliable fault detection as shown
the developed analytical models. Both, the analytical model by dotted rectangles in Fig. 11. The primary fault detection
and the experimental results reveal that the core-leakage flux technique is based on the time-domain signal and the auxiliary
at the yoke center is a reliable indicator of as low as 1-turn fault detection technique on the frequency domain as shown
fault. Hence, using the core-leakage flux at the yoke center, in block 2 and block 3 of Fig. 11, respectively. In both the
a low-severity fault detection and isolation framework has been techniques, the grid currents tapped from the current sensors
proposed which is presented in Section IV-B. of the AFER are used to check the transient conditions such as
load switching, grid voltage, and grid frequency fluctuations
B. Proposed Low-Severity Interturn Fault Detection and as shown in block 1 of Fig. 11. The minimum time taken
Isolation Technique by the primary fault detection is 100 ms (five fundamental
The proposed framework for low-severity interturn fault cycles) which is discussed in detail later in this section.
detection and isolation technique is shown in Fig. 11. Therefore, within this time window of 100 ms, the generation
The framework utilizes the grid currents and the core-leakage of spurious trip signal due to momentary fluctuations in the
CHANDAR A. AND PANDA: DETECTION AND ISOLATION OF INTERTURN FAULTS IN INDUCTORS 243
TABLE IV
I NTERTURN FAULT D ETECTION T IME FOR
D IFFERENT F ILTER BANDWIDTHS
Fig. 13. (a) Grid voltages, (b) grid currents, (c) core-leakage fluxes at the outer limbs and yoke center, and (d) normalized core-leakage fluxes at the yoke
center for various loading conditions under stabilized/nonstabilized grid voltages.
in Table IV. Hence, it is better to fix the filter cutoff frequency The LVUR is due to the influence of asymmetrical loading
between 0.4 and 0.5 Hz for reliable fault detection with a on the distribution system of the laboratory and the decrease
reasonable fault trip time as shown by highlighted column in line voltages with respect to various loading conditions are
of Table IV. due to the additional voltage drop across the line impedance.
The recommended duration of the thermal short-circuit From Fig. 13(a), the servo stabilizer reduces the LVUR to
current rating for the dry type, series-connected inductor approximately 50%, the maximum LVUR being 1%. Due
is 1–3 s [26]. The maximum time taken by the proposed to the inherent LVUR, there is a current unbalance and is
technique to identify interturn fault is 0.51 s for 1-turn fault mildly affected by the LVUR conditions with/without servo
at 100% load condition of the MPS test rig as given in the stabilizer as shown in Fig. 13(b). The unbalance in the terminal
highlighted column of the Table IV. This value is 50% below currents of the coupled inductor causes change in the core-
the recommended minimum duration of the thermal short- leakage fluxes at the outer limbs as given by (18). This
circuit current rating (1 s) [26]. Hence, the proposed fault phenomenon is evident from the experimental results as shown
detection and isolation strategy can detect as low as 1-turn in Fig. 13(c), in which the core-leakage flux at the outer limb
fault within the duration as recommended by the IEEE Std c changes due to the change in the limb c terminal current.
C57.16-2011 [26]. Therefore, the core-leakage fluxes at the outer limbs are influ-
enced by the supply voltage unbalance conditions as shown
V. ROBUSTNESS OF THE P ROPOSED T ECHNIQUE in Fig. 13(c).
From (11), it evident that the core flux at the yoke center
A. Supply Voltage Unbalanced Conditions under healthy operating condition of the inductor is zero irre-
The supply voltage unbalance is inevitable in real world spective of loading and supply voltage unbalance conditions.
applications. Hence, the robustness of the proposed technique But, due to magnetic asymmetricities, there will be a small
under grid voltage unbalance is studied by conducting the value of core flux at the yoke center and it varies mildly
experiment with/without servo stabilizer. The servo stabilizer with respect to various loading and supply voltage unbalance
as shown in block 9 of Fig. 7 is used to stabilize the grid conditions as show in Fig. 13(c). Nonetheless, during interturn
voltages and reduce the line voltage unbalance ratio (LVUR). fault, the core flux at the yoke center changes drastically
Fig. 13(a) presents the grid voltage variations for various load- with respect to the healthy condition as shown in Fig. 13(d).
ing conditions with/without servo stabilizer. From Fig. 13(a), From Fig. 13(d), it is evident that the normalized core-leakage
there is a maximum LVUR of 1.8% for nonstabilized grid flux at the yoke center is greater than 30% for as small
voltages and the voltages decreases with respect to the load. as 1-turn fault under both stabilized and nonstabilized volt-
246 IEEE TRANSACTIONS ON TRANSPORTATION ELECTRIFICATION, VOL. 4, NO. 1, MARCH 2018
TABLE V
C OMPARISON OF D IFFERENT T ECHNIQUES FOR THE I NDUCTOR A BNORMALITY D ETECTION
[16] M. F. Cabanas et al., “A new online method based on leakage flux Subash Chandar A. (S’15) received the B.Tech.
analysis for the early detection and location of insulating failures in degree in electrical and electronics engineering from
power transformers: Application to remote condition monitoring,” IEEE the Pondicherry Engineering College, Puducherry,
Trans. Power Del., vol. 22, no. 3, pp. 1591–1602, Jul. 2007. India, and the M.Sc. degree in automation and
[17] F. Haghjoo and M. Mostafaei, “Flux-based method to diagnose and control from the Electrical and Computer Engineer-
identify the location of turn-to-turn faults in transformers,” IET Generat., ing Department, National University of Singapore,
Transm. Distrib., vol. 10, no. 4, pp. 1083–1091, Mar. 2016. Singapore, where he is currently pursuing the Ph.D.
[18] P. A. Venikar, M. S. Ballal, B. S. Umre, and H. M. Suryawanshi, “Search degree with the Electrical Machines and Drives
coil based online diagnostics of transformer internal faults,” IEEE Trans. Laboratory.
Power Del., vol. 32, no. 6, pp. 2520–2529, Dec. 2017. His current research interests include the develop-
[19] S. Chandar and S. K. Panda, “Degradation detection and diagnosis ment of condition monitoring and fault detection and
of inductors in LCL filter integrated with active front end rectifier,” diagnosis techniques for electrical machines.
IEEE Trans. Power Electron., vol. 33, no. 2, pp. 1622–1632, Feb. 2018,
doi: 10.1109/TPEL.2017.2685421.
[20] C. A. Subash, S. K. Panda, S. Nadarajan, and A. K. Gupta, “Winding
fault detection in coupled inductors using a single flux sensor,” in Proc.
42nd Annu. Conf. IEEE Ind. Electron. Soc., Florence, Italy, Oct. 2016,
pp. 1554–1559.
[21] V. Behjat and A. Vahedi, “Numerical modelling of transformers interturn
faults and characterising the faulty transformer behaviour under various
faults and operating conditions,” IET Electric Power Appl., vol. 5, no. 5,
pp. 415–431, May 2011.
[22] L. M. R. Oliveira and A. J. M. Cardoso, “Leakage inductances calcula-
tion for power transformers interturn fault studies,” IEEE Trans. Power Sanjib Kumar Panda (S’86–M’91–SM’01)
Del., vol. 30, no. 3, pp. 1213–1220, Jun. 2015. received the M.Tech. degree in electrical
[23] B. Kasztenny, M. Thompson, and N. Fischer, “Fundamentals of short- engineering from IIT Banaras Hindu University,
circuit protection for transformers,” in Proc. 63rd Annu. Conf. Protective Varanasi, India, in 1987, and the Ph.D. degree
Relay Eng., College Station, TX, USA, Mar./Apr. 2010, pp. 1–13. in electrical engineering from the University of
[24] M. M. Bech, F. Blaabjerg, and J. K. Pedersen, “Random modulation Cambridge, Cambridge, U.K., in 1991.
techniques with fixed switching frequency for three-phase power con- Since 1992, he has been holding a faculty
verters,” IEEE Trans. Power Electron., vol. 15, no. 4, pp. 753–761, position with the Department of Electrical and
Jul. 2000. Computer Engineering, National University of
[25] B. Zeng, Z. Teng, Y. Cai, S. Guo, and B. Qing, “Harmonic phasor Singapore, Singapore, and currently serving as an
analysis based on improved FFT algorithm,” IEEE Trans. Smart Grid, Associate Professor and the Director of the power
vol. 2, no. 1, pp. 51–59, Mar. 2011. and energy research area. He has authored over 300 peer-reviewed research
[26] IEEE Standard for Requirements, Terminology, and Test Code for Dry- papers, co-authored one book, and contributed to several book chapters and
Type Air-Core Series-Connected Reactors, IEEE Standard C57.16-2011 six patents.
(Revision of IEEE Std C57.16-1996), Feb. 2012, pp. 1–127. Dr. Panda served as an Associate Editor for several IEEE Transactions and
[27] Y. Jiang, J. Li, S. Pan, X. Zhang, P. Hu, and H. Zhang, “Research the Editor for the Journal of Power Electronics, South Korea. He has served
on the comparison analyses of three-phase discrete and integrated LC in various capacities for the IEEE Power Electronics and Drive Systems
filters in three-phase PV inverter,” Int. J. Photoenergy, vol. 2013, 2013, Conference and the IEEE International Conference on Sustainable Energy
Art. no. 217023, doi: 10.1155/2013/217023. Technologies Conference series.