Professional Documents
Culture Documents
HATLAPA Deck CompressorTechnical Documentation 10.5574
HATLAPA Deck CompressorTechnical Documentation 10.5574
HATLAPA Deck CompressorTechnical Documentation 10.5574
Start
Technical Documentation
Screw Compressors
Technical Documentation
for
Screw Compressors Type HSC 15
of
Uetersener Maschinenfabrik
GmbH & Co. KG
Original 2010-12-08
25436 UETERSEN
GERMANY
Ref.-No.: 10.5574
Serial-No.: 10.5574 - 0
This technical documentation belong NOT in the office, but in the hands of the
operator
Technical Documentation
Screw Compressors
Table of Contents
2 Description of Compressor
3 Installation Drawing
4 Operating Instructions
5 Technical Indications
7 E-Diagram
8 Lubricating Instructions
9 Service
We recommend reading these instructions through carefully and becoming quite familiar
with the design and operation of the piston compressor before putting it into operation,
this will avoid damage through imporper handling.
Important Information on this
Documentation and Safety
Original 2010-12-08
Important Information on this Documentation and Safety
1 Information on Manuals
This manual includes all information necessary for guaranteeing the safety as well
as for the operation and maintenance of the equipment.
It is directed at instructed and trained personnel who are responsible for the
operation and maintenance of the equipment.
Only knowledge of this manual can ensure faultless and correct functioning of the
equipment, so its contents must be known to the responsible persons. The manual
should be kept so that the operating and maintenance personnel have access to it
at all times.
2 Copyright
The copyright for this technical documentation remains with HATLAPA.
This documentation is intended for the operator and their personnel only.
All rights reserved.
3 Guarantee
Original 2010-12-08
Guarantee and liability claims for damage to persons and/or objects are excluded,
if caused by one or several of the following circumstances:
− inappropriate use of the equipment,
− neglect of the provisions of this documentation,
− improper assembly, operation or maintenance,
− operation of the equipment with ineffective protective devices,
− arbitrary functional or constructive alteration of the equipment,
− removal of parts or installation of spare parts or additional components,
respectively, which have not been supplied or approved by HATLAPA,
− repairs which have not been authorised by HATLAPA,
− impact of foreign bodies in case of catastrophes or Force Majeure.
4 Designations
Persons are defined as follows:
− The operator is the (natural or legal) person on whose behalf the equipment
is used, e.g. the ship’s owner.
− Operating personnel are personnel trained for the respective work, and who
are authorised to operate the equipment and to remedy disturbances. The
operating personnel must be trained for the tasks they are entrusted with,
and meet the requirements necessary to handle the equipment.
− Assembling personnel are personnel trained for the respective work, and
who are authorised to assemble the equipment. They are able to carry out
the tasks assigned to them and to recognise possible dangers because of
their completed specialised training.
− Maintenance personnel are personnel trained for the respective work, and
who are authorised to maintain, adjust and modify the equipment. They are
able to carry out the tasks assigned to then and to recognise possible
dangers because of their completed specialist training.
− An electrician has electro-technical skills gained by respective education,
Original 2010-12-08
masters the legal regulations, and is assigned by the operator to carry out
work on their electrical equipment and appliances.
5 Signs Used
Sign for Danger
Danger!
This sign indicates specific behavioral patterns the non-observance of which is
highly dangerous, or which may lead to permanent bodily injury.
6 Intended Use
The compressor is exclusively designed for air compression. Any other use is
deemed as not being in compliance with the intended use and requires express
written approval from HATLAPA.
The intended use also includes compliance with all the regulations contained in this
technical documentation, the generally acknowledged rules of technology as well
as all the relevant laws, standards and regulations.
9 Safety Equipment
Danger!
Faulty safety equipment may put lives and equipment at risk.
All safety equipment must always be in a flawless and fully operational condition.
You must not make the safety equipment inoperative in any way.
If a piece of safety equipment is defective, the machine/system must not be
operated.
Only remove safety equipment if the machine/system has been isolated and
secured.
Perform regular checks on the safety equipment, in accordance with the
regulations in this documentation and the sub suppliers' documentation.
Long hair or loose clothing may get caught at the air intake filter.
When the compressor is in operation, maintain a safe distance to the compressor
housing!
Caution!
In automatic operation mode, the compressor starts automatically without warning.
The compressor housing and the pressure pipes become hot during operation.
Before beginning maintenance work, allow the compressor to cool down for
approx. 2 hours!
Caution!
Besides the information contained in this documentation, you must also observe
the regulations of the classification authorities and professional organisations in
order to determine the inspection and maintenance intervals.
After disassembly, always exchange self-locking nuts and gaskets. They are not
designed for repeat use.
If leaks occur at couplings which are sealed with resilient joint gaskets, the leaks
cannot be eliminated by retightening the coupling because the resilient joint
gaskets are damaged or hardened. Exchange the resilient joint gaskets.
Pay particular attention to cleanliness. Cover any openings to prevent the ingress
of dirt.
Ensure that tools, loose parts or cleaning cloths are not left in or on the
compressor.
Dispose of old oils and grease in an environmentally friendly manner in accordance
with national regulations.
15 Noise Protection
Refer to the technical data for information about the noise level.
Caution!
Make sure to wear ear protection in the vicinity of the compressor when it is in
operation.
16 Waste Disposal
The following substances which are caused by the operation of the
machine/system must be disposed of in an environmentally friendly manner, in
accordance with the applicable laws:
− used oils and grease as well as cloths with such substances on them;
− cleaning agents, and cloths with cleaning agents on them.
Original 2010-12-08
Belt Drive
Hatlapa Screw Compressors are belt-driven. Different pressures can be achieved due
to changing of pulley and belt. In addition, this facilitates smooth starting, absorbing
the ensuing starting torques effectively.
Motor IP 54, PTC-resistor and F-coiling offer complete control of the unit. Thanks to the
modern microprocessor-based control unit “PROCON” serving costs are minimized.
Super silent through noise protection also in cooling- and air discharge channel.
All components on base frame (frame as oil through executed) built as a ready to
connect air stations, included elastic machine feet, tubed and wired.
HATLAPA
Uetersener Maschinenfabrik
GmbH & Co. KG
Tornescher Weg 5 – 7,
25436 Uetersen
01_HSC_15_10.doc
Dimensions
Connection 1" i
Length x Bright x Height 805 x 695 x 1170 mm
Weight 346 kg
HATLAPA
Uetersener Maschinenfabrik
GmbH & Co. KG
Tornescher Weg 5 – 7,
25436 Uetersen Hatlapa Screw Compressor (opened)
01_HSC_15_10.doc
02.12.2002
Original 2010-12-08
HSC Electronic Control: Procon
Modification of Maintenance Intervals
Confirm
Confirm
Confirm
2. After this has been done the Alarm/Malfunction can be acknowledged by:
11.01.2007
Operating instructions
HATLAPA Screw Compressors
Original 2010-12-08
Type
7
12 24 13 10 25 6 8 20 3 21 22 1
Original 2010-12-08
23 4 28 5 27 26 2 19 9 16 17 11 18 15 14
8 9 10 11 12 13 14
°C bar
20 00
.
Original 2010-12-08
4 5 6 7 1 2 3
1 Power switch
2 Circuit-breaking key
3 Emergency stop
4 In the menu: One line up
Edit mode: Increase value
5 In the menu: One line down
Edit mode: Selection of the menu
6 In the menu: Call up information
Edit mode: Cancel value input
7 In the menu: Selection of the menu
Edit mode: Apply value
8 Permanent yellow: Base load sequencer operating mode
9 Permanent yellow: Remote operation
10 Permanent yellow: Automatic restart
11 Permanent green: Motor is running
Green flashing: Standby, motor can start automatically at any time
12 Blinking yellow: Maintenance
13 Blinking yellow: Warning
14 Red flashing: Type of malfunction
Component overview
PROCON control
3 Mounting ................................................ 3
3.1 Mounting conditions............................... 3
3.2 Compressed-air port ............................... 4
3.3 Electrical connection .............................. 4
3.4 Checking the rotating direction ............ 5
4 Operation................................................ 7
4.1 Safety instructions .................................. 7
4.2 Switching the unit on ............................. 7
4.3 Start-up after an extended idle time..... 7
4.4 Weekly check ........................................... 7
4.5 Switching the unit off ............................. 7
Original 2010-12-08
7 Maintenance schedule....................... 18
2.2 Storage
• Use mounting parts and devices down-
stream from the compressor which have Store the compressor in a dry location pro-
been designed for the maximum operating tected against weather influence. Ambient
overpressure of the compressor. temperature: -10°C to +50°C.
• In your capacity as proprietor, please en-
sure that all safety regulations are ob- Please order the HATLAPA conservation in-
served by the operating staff. structions in case of storage of over six
• Do not use the compressor as a climbing months.
aid.
For information on recommissioning
after an extended idle time, please re-
1.3 Description of symbols and fer to chapter 4.3.
notes
Danger
Mortal danger and risk of injury.
Caution
Damage to property.
1
B
Caution 2
Wrong mounting will cause damage to A
the compressor.
• Ensure sufficient ventilation of the
compressor room.
Original 2010-12-08
Fig. 3: Location
The overall length of all air intake and exhaust • Compressed-air lines, filters, aftercoolers
ducts must not exceed 4m; one baffle is per- and vessels must at their lowest spots be
missible. In case of conduits exceeding this equipped with an outlet for the condensa-
length or in case of several baffles, a booster tion water accumulated. These outlets
fan must be installed. In this case, please con- must allow to observe the draining con-
tact your technical adviser. densation water. Condensation water may
contain oil! In draining the condensation
For further information on the required venti- water, all applicable regulations on the
lation cross sections, please refer to the disposal of waste water must be complied
Technical Annex. with.
• Remove all securing devices before you
start to install the conduits.
Ground • Use only suitable connecting lines and
couplings which are designed for the in-
! Place the compressor on a horizontal and tended working pressure. Do not use any
plane surface. defect component.
• Supply lines must not be subjected to
The ground has to have a suitable load- stress or tension.
bearing capacity. HATLAPA offers special so-
lutions for inclined surfaces. Observe the technical data for the connection
of compressed air (cf. chapter “Technical an-
In order to reduce vibrations, HATLAPA rec- nex”).
ommends rubber-metal connections.
Caution
Fire hazard and damage to compressor
in case of wrong polarisation of the
motor (5 revolutions maximum in the
wrong direction of rotation!).
• Carry out the check of the rotating di-
rection as described below:
Caution
Overvoltages and undervoltages must not exceed the 10% mark.
This unit is intended for operation on a power supply network with a maximum system
impedance Zmax at the interconnection point (house service line), which is listed in the
table below in dependence of the performance. The user shall have to ensure that the
unit is operated only on a power supply network which meets these requirements. If and
when necessary, the local power supply company can provide information on the system
impedance.
400V-50Hz 3 ph 230V-50Hz 1 ph
Motor Motor Protection Protec- Motor Motor Protection Protec-
per- rated cur- – star- tion – di- per- rated cur- – star- tion – di-
formance rent delta rect start- formance rent delta rect start-
starting ing starting ing
kW A A A kW A A A
Original 2010-12-08
The supply line cross sections provided are recommended values for a maximum 50m line
length at 30°C. For fuse protection, use “slow-to-blow” or “gL” fuses.
• 220/240 V systems require a three-core 1P/N/PE cable.
• 380/400 V systems require a four-core 3P/PE cable for direct start.
• 380/400 V systems require for star-delta starting a five-core supply line 3P/N/PE.
4.1 Safety instructions ! Check oil level through oil gauge and top
up the oil if and when necessary (refer to
chapter 6.2 “Checking and topping up the
Danger oil level”).
Mortal danger caused by sudden start- ! Switch on the power switch.
up of the system. ! Press power switch (see fig. 2: operating
• Systems which are in the standby op- elements).
erating mode are liable to start auto- ! Signal lamp indicates readiness for opera-
matically at any time. tion.
! Compressor starts and after approx. 10sec.
• All parts installed behind the check valve starts load operation.
(e. g. aftercooler, pressure switch) are not ! Open ball valve.
released automatically from pressure.
• Not all transmission lines are de-energised In case of faults, please refer to chapter 8 ti-
when the system is switched off! tled “Trouble shooting” for more help.
• Before commissioning, ensure that no
person can be injured by the starting
compressor. 4.3 Start-up after an extended idle
• Never point compressed air at persons. time.
• Do not use compressed air for breathing
without corresponding treatment. During an extended idle time, the complete oil
• Use mounting parts and devices down- content flows into the compressed air / oil
stream from the compressor which have reservoir. If this has happened, the screw
Original 2010-12-08
been designed for the maximum operating compressor is not any more lubricated.
pressure of the compressor.
• Do not reach into the rotating wheels ! Dismount intake regulator.
when the compressor is operational. ! Fill approx. 1 litre compressor oil into the
• Touch the compressor system at the on air intake fitting.
and off switch only during and shortly af- ! Mount intake regulator.
ter operation. Hot surface can cause se-
vere injuries. Do not mix different types of oil. In
• Switch the compressor off immediately in choosing the oil you want to use, refer
case of faults. to the corresponding HATLAPA speci-
• Keep combustible materials away from fications (refer to chapter 6.2 “Check-
the compressor system. ing and topping up the oil level“).
• Operate the compressor only with suction
filter and if all parts of the casing are
closed.
• Operate the compressor only at the per- 4.4 Weekly check
missible operating pressure of the pres-
sure reservoir. • Check oil level of the compressor (refer to
• Tighten the screw connections of the chapter 6.2 “Checking and topping up the
pressure pipes. oil level“).
• Wear tight-fitting work cloths when han-
dling the compressor.
• Wear goggles and ear muffs when working 4.5 Switching the unit off
with compressed air.
• Wear a hair net to protect long hair and ! Press circuit-breaking key “0” (see fig. 2:
remove any lose jewellery. operating elements).
• Check the cables for damage in regular ! Switch off power switch.
intervals.
• Keep domestic animals and children away
from the compressor system.
• Switch the compressor off when not
needed.
All systems which are equipped with remote To reduce noise emissions.
control must bear a clearly visible label read-
ing as follows: “Warning! This system is re-
motely controlled and is liable to start at any Base load sequencer
time." In addition, persons operating remotely
controlled systems must ensure that the sys- Intelligent higher-order control system to con-
tem is not started during maintenance or re- trol several compressors depending on the
pair work. For this, a corresponding informa- actual compressed air consumption.
tion sign must be affixed to the remote control
unit.
Speed regulator
! Open ball valve.
! Press power switch (see fig. 2: operating
Adapts speed and thus also energy consump-
elements).
tion of the screw compressor to the actual
! Signal lamp indicates readiness for opera-
compressed air consumption.
tion.
! System is now ready to be operated via
remote control.
Water-cooling system
Rubber-metal connection
To reduce vibrations.
Line 8:
the display start with an “E” followed by a V-belt operating life. In the display “BE.”
two-digit malfunction code (refer to chapter alternates with the corresponding operat-
8.2 “Malfunction, PROCON control” and chap- ing life value. This line will appear only in
ter 8.3 “Warnings, PROCON control”) whereas case the V-belt is activated in the option
warnings start with an “A”. In addition, in menu. In addition, the maintenance LED
case of malfunction a malfunction LED will flashes.
light up; in case of a warning a warning LED • Line 9:
will light up. Software version, e. g. “PRO 1.00“ for Ver-
sion 1.00.
Information menu
5.3 Input of parameters
! To call up the first line of the information
menu, keep key 6 (→) pressed for one sec-
Selection menu
ond.
! The keys 4 and 5 (↑/↓) allow you to navi-
! In order to enter parameters, keep key 7
gate within the menu structure.
(↵) pressed for three seconds. “COD.000”
! Press key 6 (→) to exit the menu; alterna-
will appear in the display.
tively, the menu is also exited if no key has
! Enter the code for the desired menu using
been pressed for 3 minutes.
the keys 4 and 5 (↑/↓).
! Confirm by pressing key 7 (↵), and the first
• Line 1:
parameter of the selected menu is dis-
System pressure indicator. The system
played.
pressure is displayed in place of the net-
! In case an invalid code has been entered,
work pressure. “P2” will appear on the left
or key 6 (→) has been pressed, the routine
side of the display. This line will appear
returns to the initial display.
only in case the system pressure input is
activated in the option menu. In case an
incorrect system pressure value has been
obtained, the display will show “- - -”. Selection of parameters within a
• Line 2: menu
Hours of operation. Hours of operation are
indicated as five-digit figures. “R.“ will ap- ! The keys 4 and 5 (↑/↓) allow you to navi-
pear on the left side of the display (e. g. gate within the menu structure in the dis-
“R.23 456“ for 23456h). play modus.
! Press key 6 (→) to exit the menu; alterna- Oil filter C2.# ### 0-9999h 500*
tively, the menu is also exited if no key has operating
been pressed for 5 minutes. life
Oil sepa- C3.# ### 0-9999h 2000
rator op-
Editing parameters within a menu erating
life
! Press key 7 (↵) to modify parameters. You Oil oper- C4.# ### 0-9999h 500*
are then in the edit mode. This is indicated ating life
by the corresponding parameter value
V-belt op- C5.# ### 0-9999h 0
flashing.
erating (inac-
! The keys 4 and 5 (↑/↓) allow you now to
life tive)
modify the value.
! Press key 6 (→) to return to the display Shutdown C6. # 0=No No
mode, and retain the previous value. mainte- 1=Yes
! Press key 7 (↵) to save the current value nance
and to enter the next value that can be Tab. 3: Maintenance menu
modified.
* only first maintenance interval; the re-
In the event values have been modified maining intervals are 2000h
within one menu, storage of the new
values is signalled through a horizontal The maintenance intervals can be specified
bar (for one second). between 0-9999h while the input „0“ means
that this interval should not be edited. In this
place only the target values of the mainte-
Original 2010-12-08
Operating parameter menu (Code The pressure control is effected via an exter-
030) nal contact during programmed operation of
the base load sequencer.
Name Message Setting Factory
In case the remote control is activated the
range setting
start-up is effected via an external contact.
The control system reacts only to the positive
Base load B1. # 0=No No signal edge for start-up of the device. If there
sequencer 1=Yes is no input signal this means that the com-
operating pressor is switched off. In this case you can-
mode not use the keyboard to switch on or off the
Conti- B2. # 0=No No device.
nuous 1=Yes
operation The “continuous operation” parameter allows
to operate the compressor in the no-load op-
Remote B3. # 0=No No
eration mode and thus to prevent it from be-
operation 1=Yes
ing switched off.
Re-starts B4. # 0=No No
automa- 1=Yes You can specify two periods if the automatic
tically af- restart after voltage breakdown has been acti-
ter power vated. The power failure time specifies the
failure maximum allowable period of voltage break-
Power B5. ## 0-60s 1s down after which it is permitted to restart the
failure device. If this value is set to “0”, the device
time can be restarted at any time. The re-start de-
lay allows to prevent the compressor from re-
Original 2010-12-08
3s p2 00
. 3s cod 010 3s COD 020 3s Cod 030
System pressure (Option)
Edit:
be 999 Edit mode
V-belt operating life
Increase values Cancel:
Decrease values
pro . 100 Return to the basic mode
Software version Apply value without retaining all previous values
! Close cut-off valve at compressed air out- Checking the oil level
let 25 (see fig. 1: component overview).
! Shut down the system. ! Switch the compressor off and depressur-
! Switch off power switch. ise.
! Open slowly the screw plug of the com- ! Drain off the condensation water before
pressed air aftercooler 26 to release air you check the oil level (refer to chapter 6.5
pressure. “Draining the condensation water”).
! Wait until no more air exits the post- ! Unscrew oil filler neck 18 (see fig. 1: Com-
cooler, and tighten the screw plug. ponent overview) by approx. 1 turn to
! Wait until the remaining system is re- check whether pressure has been released
leased from pressure and has cooled completely.
down. ! Check oil level through oil gauge 17 (see
! Unscrew oil filler neck 18 by approx. 1 turn fig. 1: component overview).
to check whether pressure has been re- ! The oil level has to be within the min. /
leased completely. max. level.
! Wait until no more air exits the oil filler ! Check whether the oil has a milky discol-
neck 18, and tighten again oil plug. oration or contains water drops (for meas-
ures, please refer to chapter 8 titled “Trou-
ble shooting / Milky colour of the oil, water
drops in the oil”).
Ambient temperature
6.4 Changing oil filter
0 up to +25°C Permanently
higher than
25°C Danger
Scalding hazard by draining hot oil.
• Carefully and slowly remove the oil fil-
Viscosity ISO VG 46 ISO VG 68 ter.
class • Avoid skin contact with hot oil
Viscosity at 41 up to 51 61 up to 75
40 °C mm²/s mm²/s
Use only new oil filters; you cannot
Point of igni- > 200°C
clean a used oil filter.
tion
If you replace the oil filter while the oil
Pour point At least 5°C below lowest circuit is filled, up to 2l oil can escape
ambient temperature. the system.
Tab. 5: Types of oil Dispose of the oil filter according to
the applicable local environmental
We assume no warranty unless the lu- regulations.
bricants used in our screw compres-
sors show these essential characteris-
tics.
!
valve 15 while it is at operating tempera-
ture.
! Drain the condensation water into the ves- 6.9 Checking and changing the
sel until pure oil escapes. suction filter cartridge
! Close oil and condensation water drain
valve 15. ! Remove the cover of the suction filter 23
(see fig. 1: Component overview).
! In case of severe soiling, immediately re-
6.6 Cleaning the oil cooler and the place the suction filter (cf. list of
compressed-air aftercooler. HATLAPA spare parts in the chapter titled
“Technical annex”).
! Blow compressed air through the cooling ! Refit the cover of the suction filter.
fins of the oil cooler 27 and of the com-
pressed-air aftercooler 26 (see fig. 1: Com-
ponent overview) from the inside of the
machine until dust and deposits have dis-
appeared.
5
1 1
F
!
proportional controller 7 (see. fig. 1: Com- 2
ponent overview). 3
! Unscrew the nozzle behind.
! Clean nozzle, controller and hose.
! Screw in the nozzle.
! Fix the hose connection again.
7 Maintenance schedule
The intervals mentioned are experimental values. They can differ considerably
depending on the application conditions.
10 000 h1
4 000 h1
8 000 h1
Interval
2 000h1
6 000h1
500 h1
Application
Key:
8 Trouble shooting
Danger
Trouble shooting may be carried out only by trained experts or by staff members of
HATLAPA Company. In all actions, please observe the fundamental safety instructions
(cf. chapter 1), the safety instructions for operation (cf. chapter 4), and the safety instruc-
tions for maintenance (cf. chapter 6).
Fault at the electric connection. • Check the electric connection for under-
voltage and phase failure.
• Check the conductor cross section.
Ambient temperature is too high. • Improve the room ventilation.
• Select a cooler location.
Damage on the compressor • Check bearing of the compressor and
gear set.
Motor gets too hot due to high switching fre- • Check the pressure switching points.
quency.
Pressure detector has been set wrongly. • Check the pressure switching points.
The clamping connections have come lose. • Retighten the clamping connections.
Water accumulation in the oil vessel (operat- • Change the oil immediately.
ing temperature is not reached because of • Retrofit a standby heating (HATLAPA ac-
too short operation time) cessory item).
• Select warmer location.
• Check design of the compressor.
• Contact manufacturer as to oil specifica-
tions.
Water accumulation in the oil vessel • Change the oil immediately.
(caused by humid conditions). • Select dry location.
The wrong oil has been used. • Check the type of oil (cf. chapter 6.2
“Types of oil”), and replace, if and when
necessary.
The compressor is too hot. • See Table “Compressor turns too hot”.
Original 2010-12-08
Oil escapes through oil high-precision separa- • Check suction – compressor stage.
tor cartridge. • Check oil grade.
Pressure detector or relief valve is defective. • Check pressure detector and relief valve
at intake regulator and replace if neces-
sary.
Oil level too low. • Refill oil (refer to chapter 6.2 'Checking
and topping up the oil level').
Oil filter is clogged. • Replace oil filter cartridge.
Pressure detector is set at a too high rate. • Correct settings of pressure sensor.
Pressure sensor is defect. • Replace pressure sensor.
Safety valve is defective. • Replace safety valve.
Suction stop valve does not close completely. • Check springs of the suction stop valve.
Solenoid valve is defective. • Replace solenoid valve.
Oil high-precision separator cartridge is used • Replace oil high-precision separator car-
up. tridge.
Proportional controller nozzle is clogged • Clean proportional controller nozzle.
(only with proportional control).
Original 2010-12-08
Membrane in the adjust cylinder of the reduc- • Replace membrane and check control
ing damper is defective (depending on the pressure in the pressure control valve.
type of compressor)
The relief valve is defective. • Replace relief valve.
Pressure control valve is leaky. • Replace pressure control valve.
Abnormal noises
Any malfunction will cause the compressor to shut down. This will last until the cause of
the malfunction is eliminated and the corresponding message is acknowledged:
E01 Final temperature The value set under “Final temperature error” has
been reached or exceeded.
E02 Emergency stop Emergency stop key 4 has been pressed; or cable
break.
E03 Temperature of the motor. The temperature of the motor winding is too high; or
cable break.
E04 Direction of rotation Wrong direction of rotation; or cable break.
E05 Start temperature The final temperature is not higher than the value
set under “Start temperature”.
E06 Development of system The system pressure has not been developed within
pressure the set period. V-belt may have broken.
E07 Excess pressure The maximum allowable system pressure has been
exceeded.
Original 2010-12-08
In case of a warning, the compressor is not shut down automatically. The message is
acknowledged in the same fashion as with malfunction.
A01 Final temperature The value set under “Final temperature error” (-5°C)
has been reached or exceeded. If Error final tem-
perature is active the warning is reset automatically.
A021 Air filter differential pres- Air filter is clogged; or cable break.
sure
A03 Oil filter differential pres- Oil filter is clogged; or cable break.
sure
A041 Separator differential Defect in the oil separator; or cable break.
pressure
A11 Air filter service life Maintenance interval for the air filter has elapsed.
A12 Oil service life Maintenance interval for the oil has elapsed.
A13 Oil filter service life Maintenance interval for the oil filter has elapsed.
A14 Separator service life Maintenance interval for the separator has elapsed.
A15 V-belt service life Maintenance interval for the V-belt has elapsed.
Original 2010-12-08
1
Optional
HATLAPA
Uetersener Maschinenfabrik
GmbH & Co.
Tornescher Weg 5 – 7,
25436 Uetersen
Telefon: ++49 4122 711- 0
Telefax: ++49 4122 711 - 104
104482 HSC •
eMail info@hatlapa.de
Internet www.hatlapa.de
Technische Hinweise
Technical Indications
Technische Hinweise
Technical Indications
Original 2010-12-08
Schraubenkompressor
Screw Compressor
HSC
Technische Hinweise
Technical Indications
Zeichnungs-Nr.:
Drawing No.:
HSC
Original 2010-12-08
Operational description of
HATLAPA screw compressors HSC
Oil circuit:
Due to the pressure inside the oil and air reservoir (6) the oil is pressed back to the suction side of
the screw compression stage (3), passing through an oil filter (12).
The thermostatic valve (11) switches to its open position when the oil has reached its working
temperature. The temperature is held constant by regulating an oil flow through the largely
designed oil cooler (10).
The small amount of oil filtered from the compressed air inside of the oil fine filter (7) is sucked
back into the screw compression stage (3) through the oil drainage line (17). The throttle (19) is
installed to avoid a short circuit of the compressed air. The check valve (18) prevents oil being
pressed back into the fine filter (7) from the compression stage when the compressor is shut off.
Original 2010-12-08
In the unlikely case that the internal pressure becomes too high the safety valve (22) will protect
the system by blowing off the air.
For correct operation of the screw compression stage (3), of the oil flow and of the control valves
there has to be a minimum pressure inside the system between screw compression stage (3) and
minimum pressure valve (8). The minimum pressure valve (8) opens at approx. 4 bar(g).
If the final pressure in the network is reached the PROCON will switch the solenoid valve (15) into
the drawn position, as indicated in the piping diagram. This results in an open relief valve (14) and
a closed suction valve (2), as shown in the piping diagram. The compressor will continue idle
running for a certain period of time, as programmed in the PROCON (approx. 2 to 5 min.), without
delivering compressed air to the network. To hold the minimum system pressure there is a small
throttle inside of the suction valve (2), still allowing a small amount of air to be sucked in. The
same amount of air is flowing to the suction line through the relief valve (14).
If the minimum network pressure is not reached within the programmed time the PROCON stops
the compressor. The internal pipings are made pressureless by the opened relief valve (14) – up
to the minimum pressure valve (8) with check-valve.
If the network pressure is falling under the minimum value the PROCON will switch the solenoid
valve (15) which results in an open suction valve (2) and a closed relief valve (14). The
compressor will then start delivering its full amount of air into the network.
21.06.2005
Original 2010-12-08
178483
FLEXIBLE HOSE
INSTALLATION GUIDELINES
Flexible hoses are used for connecting a flexible mounted compressor assembly to a rigid
piping system. When a hose is installed, it must allow the compressor to move in all three
directions. See typical applications below, which show a single bend, to achieve this. The
diagrams apply to both air and water.
Note:
The following diagrams show flexible hoses with threaded end connections, however
flanged end connections may be supplied. These guidelines apply to the flexible part of
the hose, regardless of the type of end fitting supplied.
No pressure
High pressure
Original 2010-12-08
To allow the flexible part of the hose to move when pressurised, ensure no supporting
clamps are located on the bends.
incorrect correct
On installation, ensure that the flexible part of the hose is not twisted, this could result in
hose damage and, when pressurised, it could untwist, loosening the connections.
16.01.2006
122/Pitrowski 1/4
178483
FLEXIBLE HOSE
INSTALLATION GUIDELINES
incorrect correct
Use angle adaptors to eliminate tight bend radii and sharp twists occurring in the hose.
Original 2010-12-08
incorrect correct
If the installation bend radius is less than the minimum allowed, use angle adaptors to
eliminate tight bend radii.
16.01.2006
122/Pitrowski 2/4
178483
FLEXIBLE HOSE
INSTALLATION GUIDELINES
incorrect correct
Ensure the hose is installed with a smooth bend, avoiding any tight corners, which could
cause the flexible part of the hose to collapse.
Original 2010-12-08
incorrect correct
In a collinear application, do not install the hose in a straight line or with kinks, use angle
adaptors.
16.01.2006
122/Pitrowski 3/4
178483
FLEXIBLE HOSE
INSTALLATION GUIDELINES
incorrect correct
Ensure the hose is kept away from hot surfaces by using suitable clamps. High ambient
temperatures can reduce the life of the flexible part of the hose.
Original 2010-12-08
16.01.2006
122/Pitrowski 4/4
Safety Instructions for Hoses
1 General
Hose pipes are safety relevant parts which may endanger persons and the environment
in case of failure.
1.1 Installation and maintenance
During installation the hoses must in no way be damaged, bent, tw isted
or exerted to pressure. They must not be painted or have contact w ith
sharp objects!
For cleaning hose pipes and hoses ne ither aggressive cleaning agents
nor pressure cleaners may be used . They can damage the hose surface
resp. hose line!
HSC 11
HSC 15
Original 2010-12-08
06/05
Elektrischer Anschluß / Electrical connection Abluft
Outgoing air E
Zuleitungsquerschnitt
Cable cross section
G
Sicherung (träge)
Rated current
Type
Slow fuse
N
A A mm2
H
HSC 11 23 35 5G6 Z
U
Y
I
HSC 15 30 50 5G10
Der elektrische Anschluß und die Schutzmaßnahmen sind nach VDE und gemäß den Zusatz-
vorschriften des jeweiligen Elektrizitätswerkes von einer autorisierten Fachkraft auszuführen.
P
Die angegebenen Zuleitungsquerschnitte sind Richtwerte für eine max. Leitungslänge von 50m bei
einer Temperatur von 30°C.
S R D
T
The electric connection and the protecting measures have to be carried out by an authorized skilled
specialist from the relevant power station, according to the VDE and the additional regulations.
The mentioned sectional drawings of the incoming supply are guidelines for a max. line lenght of B M L F
50m with a temperature of 30°C.
Kühlluftmenge
Motorleistung
600 min.
Type 600 min.
Oil filling
Ölfüllung
Gewicht
Weight
kg kW l m3/h m
Incoming air
HSC 11 334 11 6 2200 4
Zuluft
C
HSC 15 346 15 6 3000 4
Ab einer Kanallänge von 4 m (Summe aus Ansaugkanal und Abluftkanal) wird der Einsatz eines
Ventilators notwendig. Dieser muß ebenfalls bei dem vorgegebenen Kühlluftvolumenstrom eine
Förderdifferenz von ca. 80-100 Pa erreichen.
G-Druckluftanschluß
From a channel lenght of 4m (sum from intake port and air discharge channel) a ventilator Outlet compressed air
will be necessary. This one must also reach, with the given air-cooling flow capacity, a Y-Netzanschluß 40 mm A
delivery difference of approx. 80-100 Pa. Cable inlet
Z-Kondensatablaß Rahmen
Abmessungen / Measurements Condensation water drain
L B H A C F K R S D T P U E G I Y M N Z
Type mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm Pg mm mm
Modell Nr. / Werkzeug Nr.
HSC 11
805 x 695 x 1170 160 575 410 -- 710 595 60 15 105 770 90 1" 670 21 200 265 1/4" Buchstabe Änderung Datum Name
HSC 15 Maßstab Datum Name Zeichn.Nr.
437 431
427
467
Original 2010-12-08
305
304
303
308
306
302 300
309
307 312
610
446
409
408
497
447
470
478
410
439
498
444
466 440 499
Original 2010-12-08
464
526 457
469
520 468
522 458
408 459
521
460
500
543
545
548
Werkstoff / Halbzeug / DIN
455
405
454
Original 2010-12-08
406
421
424
465
443
467
468 411
442 449
463
443 462
A
bis 30
±1
über 30
bis 120
±1
über 120
bis 315
±1
über 315
bis 1000
±2
über 1000
bis 2000
±3
über 2000
bis 4000
±4
bis 315
±20'
über 315
bis 1000
±15'
über 1000
±10'
anvertraut ist, sie darf weder
vervielfältigt, noch dritten Personen,
insbesondere Konkurenzfirmen ohne unsere
keitsgrad
fein
mittel
über 0,5 bis 3
±0,05
±0,1
über 3 bis 6
±0,05
±0,1
über 6 bis 30
±0,1
±0,2
bis 120
±0,15
±0,3
bis 400
±0,2
±0,5
bis 1000
±0,3
±0,8
bis 2000
±0,5
±1,2
bis 4000
±2
Oberflächenbehandlung Die
besonders geprüft
Maße werden Separator cpl.
B ±1 ±2 ±2 ±3 ±4 ±6 ±45' ±30' ±20' Erlaubnis mitgeteilt oder zugänglich grob ±0,2 ±0,3 ±0,5 ±0,8 ±1,2 ±2 ±3 ±4 Ersatz für
C ±1 ±3 ±4 ±6 ±8 ±11 ±1° ±45' ±30' gemacht werden. sehr grob ±0,5 ±1 ±1,5 ±2,5 ±4 ±6 ±8 HSC 4-15
Pos. pcs. Description Order-No. Pos. pcs. Description Order-No.
410 1 Separator 6970410 452 1 Screw connection 752057
405 4 Cylinder screw DIN912 M10x80 701027 454 1 Double nipple 6913454
406 4 Wheel disc DIN6797 J10,5 701407 455 1 Pipe 6913455
411 1 Valve housing 6913411 462 1 Screw 705500
421 1 Lock ring DIN471 A16 704007 463 1 Seal ring 703700
423 1 Seal 6913505 465 1 Screw 705522
424 1 O-Ring 707753 467 1 Screw 705526
442 1 Emergency valve 751032 468 1 Seal ring 703702
443 2 Seal ring 703701 539 1 air/oil separator box 758160
449 1 Screw connection 752001
Original 2010-12-08
A
bis 30
±1
über 30
bis 120
±1
über 120
bis 315
±1
über 315
bis 1000
±2
über 1000
bis 2000
±3
über 2000
bis 4000
±4
bis 315
±20'
über 315
bis 1000
±15'
über 1000
±10'
anvertraut ist, sie darf weder
vervielfältigt, noch dritten Personen,
insbesondere Konkurenzfirmen ohne unsere
keitsgrad
fein
mittel
über 0,5 bis 3
±0,05
±0,1
über 3 bis 6
±0,05
±0,1
über 6 bis 30
±0,1
±0,2
bis 120
±0,15
±0,3
bis 400
±0,2
±0,5
bis 1000
±0,3
±0,8
bis 2000
±0,5
±1,2
bis 4000
±2
Oberflächenbehandlung Die
besonders geprüft
Maße werden Separator cpl.
B ±1 ±2 ±2 ±3 ±4 ±6 ±45' ±30' ±20' Erlaubnis mitgeteilt oder zugänglich grob ±0,2 ±0,3 ±0,5 ±0,8 ±1,2 ±2 ±3 ±4 Ersatz für
C ±1 ±3 ±4 ±6 ±8 ±11 ±1° ±45' ±30' gemacht werden. sehr grob ±0,5 ±1 ±1,5 ±2,5 ±4 ±6 ±8 HSC 4-15
472
482
489 473
484
480
483 481
493
494
Original 2010-12-08
495
484
479 478
Werkstoff / Halbzeug / DIN
mit 55°-Einsatz
Modell Nr. / Werkzeug Nr.
A
bis 30
±1
über 30
bis 120
±1
über 120
bis 315
±1
über 315
bis 1000
±2
über 1000
bis 2000
±3
über 2000
bis 4000
±4
bis 315
±20'
über 315
bis 1000
±15'
über 1000
±10'
anvertraut ist, sie darf weder
vervielfältigt, noch dritten Personen,
insbesondere Konkurenzfirmen ohne unsere
keitsgrad
fein
mittel
über 0,5 bis 3
±0,05
±0,1
über 3 bis 6
±0,05
±0,1
über 6 bis 30
±0,1
±0,2
bis 120
±0,15
±0,3
bis 400
±0,2
±0,5
bis 1000
±0,3
±0,8
bis 2000
±0,5
±1,2
bis 4000
±2
Oberflächenbehandlung Die
besonders geprüft
Maße werden Oil-thermostat cpl.
B ±1 ±2 ±3 ±4 ±6 ±45' ±30' ±20' Erlaubnis mitgeteilt oder zugänglich grob ±0,2 ±0,3 ±0,5 ±0,8 ±1,2 ±2 ±3 ±4 Ersatz für
C ±1 ±3
±2
±4 ±6 ±8 ±11 ±1° ±45' ±30' gemacht werden. sehr grob ±0,5 ±1 ±1,5 ±2,5 ±4 ±6 ±8
HSC 4-15
Pos. pcs. Description Order-No. Pos. Description Order-No.
470 1 Oil thermostat compl. 6613470 481 Piston 6613481
472 1 O-ring 707703 482 Cylinder screw 701006
473 1 Inlet for Oil thermostat compl. 757817 483 O-ring 707753
476 1 Valve housing 6613476 484 Spring disc 703605
477 1 Double nipple 6633477 488 Screw connection 752107
478 1 Oil filter 7,5/10 bar 758102 489 Screw connection 752112
478 1 Oil filter 13/15 bar 758101 493 Cap 6613493
479 4 Cylinder screw DIN912 M6x75 701020 494 Screw 705500
480 1 Compression spring 6613480 495 Seal ring 703700
Original 2010-12-08
mit 55°-Einsatz
Modell Nr. / Werkzeug Nr.
A
bis 30
±1
über 30
bis 120
±1
über 120
bis 315
±1
über 315
bis 1000
±2
über 1000
bis 2000
±3
über 2000
bis 4000
±4
bis 315
±20'
über 315
bis 1000
±15'
über 1000
±10'
anvertraut ist, sie darf weder
vervielfältigt, noch dritten Personen,
insbesondere Konkurenzfirmen ohne unsere
keitsgrad
fein
mittel
über 0,5 bis 3
±0,05
±0,1
über 3 bis 6
±0,05
±0,1
über 6 bis 30
±0,1
±0,2
bis 120
±0,15
±0,3
bis 400
±0,2
±0,5
bis 1000
±0,3
±0,8
bis 2000
±0,5
±1,2
bis 4000
±2
Oberflächenbehandlung Die
besonders geprüft
Maße werden Oil-thermostat cpl.
B ±1 ±2 ±3 ±4 ±6 ±45' ±30' ±20' Erlaubnis mitgeteilt oder zugänglich grob ±0,2 ±0,3 ±0,5 ±0,8 ±1,2 ±2 ±3 ±4 Ersatz für
C ±1 ±3
±2
±4 ±6 ±8 ±11 ±1° ±45' ±30' gemacht werden. sehr grob ±0,5 ±1 ±1,5 ±2,5 ±4 ±6 ±8
HSC 4-15
730
729
709 731
745 738
717
728 707 703
726.1 727 719 708 705
720
726
733
725
710
735 702
Original 2010-12-08
730
706
704 730
712
701 715 737
716
713 738 732
750 714
711
725 736
721
739
722 724 740
Werkstoff / Halbzeug / DIN
721
722
Werkstoff / Halbzeug / DIN
701
Modell Nr. / Werkzeug Nr.
752 718
Buchstabe
Maßstab
Änderung
Datum Name Zeichn.Nr.
Datum Name
722 4 Spring disc 703605 752 1 Air filter with set 708977
723 1 Seal 6633736 750 1 Air filter 708988
724 3 Putting nippple 2707099 752 1 Air filter with set 758022
725 2 Double nipple 706340 Maintenance set incl.
790 1 69137901
726 1 Cap 66137254 704,705,706,707,710,715,718,727
7261 1 Relief valve complete 69157260
HSC 4 – 37
Original 2010-12-08
E03071606 b - 06/05
Original 2010-12-08
0 1 2 3 4 5 6 7 8 9
Vor Inbetriebnahme sind Spannung und Frequenz sowie die Einstellwerte der Before initial st arting, volt age and frequency as well as t he values at which motor protect ion Avant mise en service il faut vérifier la tension et f réquence ainsi que les valeurs de cosigne de
M ot orschut z und Zeitrelais zu prüfen. and t ime relay are set have to be checked. la protection du moteur et du relais temporisé.
Vor Inbetriebnahme und bei Wartungsarbeiten sind alle Kontakt schrauben nachzuziehen Before initial st arting and during maintenance works, all contact screws have t o be checked Avant mise en service et en cas de travaux d’entretien il f aut serrer les vis de contact, ou bien
bzw. auf festen Sitz zu kontrollieren. and retightened respectively. vérifier s’ils sont bien fixés.
Die Dimensionierung der Zuleit ung sowie alle ext ernen Verkabelungen erfolgt in Eigen- The dimensioning of the conducting cable as well as all external cables are the responsibility Le dimensionnement de la conduite d’alimentation, ainsi que de t ous les câblages externes, a
verantwortung der ausf ührenden Elekt rof irma. of the electrician ef fect ing the wiring. lieu en propre responsabilit é de la société électrique exécutant ces travaux.
Tiefe: 170mm
620mm
Gehäuse 01
housing 01
Carter 01
3Q1
Hauptschalter
Power switch
interrupteur
principal
PROCON A1
290mm
S1
Amperemeter
ammeter
amperemeter
3P1
L1
L2
L3
1
3F5 3F1
2
3T2 A 3P1
L50 /4.0
L51 /4.0
Bauseits
at site
2 4 6 95 97
3F0 * 3F6 11
1 3 5 96 98
3S1
12
5.2
L10 /7.0
L11 /4.0
PE /4.0
1X1 PE 1X1 PE
L1 L2 L3 PE
Einspeisung U1 V1 W1 PE W2 U2 V2
3/PE 50-60Hz/400-440V siehe Anhang
Sicherungseinsatz max.
Nennanschlußleistung M
Nennbetriebstrom
3
power supply Option
~
3/PE 50-60Hz/400-440V see attachment *
back up fuse max.
rating Motorstromrelais 3M1
current rated
motor power relais
Alimentation relais motorisé
3/PE 50-60Hz/400-440V voir annexe
Castouche fusible
puissance de branchement nominale
Courant en régime
PROCON - Steuerelektronik
PROCON - control electronic
PROCON - électronique de commande
230V 50Hz
3.9/ L11 L11
10V AC
3.9/ L61
19V AC
3.9/ L51
0V / 19V AC
3.9/ L50
0V / 10V AC
3.9/ L60
bl
sw
ga
br
gr-ge
0X3 0X2
4A1
13 12 11 10 9 8 7 6 5 4 3 2 1
0X1
Typ / type / Type :
PROCON Electronic
électronique PROCON
33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14
3.9/ PE PE /5.0
Versorg.spg. 12VDC
Motortemperatur Versorg.spg. 24VDC
PTC Digital Eingänge
supply voltage 12VDC supply voltage 24VDC
motor temp. PTC digital inputs
22 29
rt
ws
1X1 1 1X1 3 1X1 5 1X1 7 1X1 9 1X1 11 1X1 13
95 31 3 1 1 3 3
* 3F6 3S1
96 32 4 2 2 4 4
1 1
5R1 5R2
2 2
4.9/ PE PE /7.0
sw
br
rt
gr-ge
rs
bl
vi
ga
20 21 23 24 25 26 27 28
Option défaut PTC Option Option avertissement Option avertissement Option Option
réserve défaut PTC température du moteur défaut arrêt d'urgence avertissement filtre à air filtre à huile séparateur fin GLW: charge / marche à vide Xxx marche / arrêt
Druckfühler Druckfühler
pressure transductor pressure transductor
capteur de pression capteur de pression
6A0 6A1
P P
I I
1
6R1 -2 +1 A2 A1
2
1X1 15 16 S 1X1 17 18 S
gr-ge
br
sw
ws
ga
bl
14 15 16 17 18 19
Option
Schirmung Temperaturfühler Temperaturfühler Systemdruck Netzdruck Zuleitg.Druckfühler
Analog Eingänge KTY -20 bis +150°C KTY -20 bis +150°C 4-20mA 4-20mA 4-20mA
screening temp. transductor temp. transductor 0 bis 16 bar 0 bis 16 bar feed line
analog inputs KTY -20 bis +150°C KTY -20 bis +150°C system pressure line pressure pressure transductor
6 7 8 9 10 11 12
21 21
7K3 7K2
.6 .5
22 22
1X1
24
+ 1X1 27
* 7Y2 7Y1
- * 7Y3
A1 A1 A1
1X1 26 PE 1X1 26
7K2 7K3 7K1
0V 50Hz A2 A2 A2
3.9/ L10 L10
5.9/ PE PE
1X1 21 22 23
* Option * Option
(45/55/75kW) (Wasserkühlung)
(water-cooling)
Steuerventil Entlastungsventil 1 2 3.4 1 2 3.6 1 2 3.3 (refroidissement à l'eau)
control valve relief valve 3 4 3.5 3 4 3.6 3 4 3.3
soupape de distribution soupape de décharge 5 6 3.5 5 6 3.6 5 6 3.3
45/55/75kW Wasserstopventil
21 22 .6 21 22 .5 water stop valve
soupape d'arrêt d'eau
L11
3 3 11
7K1 7K1 7K4
4 4 14
21
7K1
1X1 22
24
A1 33
*7K4
A2 Stillstandheizung
Motor
230V
auxiliary heating
motor
1X1 26 PE
26
0V 50Hz
3.9/ L10 L10
5.9/ PE PE
29 30 31 32 27 28
W6A0
W0X5
W0X4
W0X1
W6R1
Leistenbezeichnung
Datum
Kabelname
Kabelname
1X1
Name
Norm
Gepr.
Datum
Bearb.
1
4mm²
Ziel-
Ziel-
nummer
Hall
Anschluß
Anschluß
5/03
Klemmen-
Seite/Pfad
Kabeltyp
Kabeltyp
bezeichnung
bezeichnung
Ers.f.
Kompressor / compressor
5R1 2 2 5.1
3
5R2 1 3 5.2
0X5 21 br
5R2 2 4 5.2
3S1 31
3 5 5.4
0X6 24 gr-ge
4 6 5.4
Ers.d.
1 7 5.5
4
0X6 25 rs
2 8 5.5
1 9 5.6
0X4 14 gr-ge
SH W6R1 SH S 6.3
Druckfühler pressure
transductor SH W6A0 SH S 6.5
0X6 26 bl
2 10 5.6
Ben.
5
Original 2010-12-08
3 11 5.7
0X6 27 vi
4 12 5.7
3 13 5.8
0X6 28 ga
4 14 5.8
1X1
0X4 15 br
1 6R1 2 15 6.3
6
0X4 16 sw
2 6R1 1 16 6.3
Druckfühler pressure 0X4 17 ws
transductor 1 6A0 -2 17 6.4
Druckfühler pressure 6A1 A1
transductor 2 6A0 +1 18 6.4
0X2 6
21 7.2
EDV Nr.:
0X2 7
22 7.2
7
0X2 8
23 7.2
0X3 9
7Y1 + 24 7.4
0X6 23 rt
3S1 32 25 5.3
3T1 0
E03071606 b
7Y1 - 26 7.4
SKP-E 4 - 75 kW
7K2 A2
Antrieb Kolbenkompressor
piston compressor drive 3M1 PE PE 3.4
8
Transformator 3T1 PE
transformer PE 3.7
4A1-0X1 1 gr-ge
PE 5.2
PE 5.2
Ort:
Anlage:
PE 5.3
PE 5.4
9
Blatt
Folge
PE 5.5
PE 5.6
8
Lubricating Instructions 177469
for HATLAPA HSC Rev. 08.10
Screw Compressors
1. General
Moving parts require the correct lubricant. Good quality lubrication oils increase the service life
of the compressor.
Please note: only the lubrication oil manufacturer knows his products thoroughly. Therefore, it is
advisable to contact him when making your choice.
Ask only the lubricant manufacturer for his recommendation! He is the expert.
Above all, compressor oils must have good lubrication properties for which their viscosity is
highly important. HATLAPA recommends lubrication oils within the following range:
ambient temperature 0 .. +25 °C constantly over 25 °C
(engine room of sea going ships)
viscosity class ISO VG 46 ISO VG 68
2 2
viscosity at 40°C 41 .. 51 mm /s 61 .. 75 mm /s
flash point > 200 °C > 200 °C
Original 2010-12-08
3. Guarantee
If lubrication oils are used which do not meet the requirements, damage to the compressor may
occur. This damage is not covered by HATLAPA's guarantee obligations.
4. Lubricant Examples
The following oils are examples which comply with the above specification:
BP ENERSYN RC-S 68
CASTROL AIRCOL SR-68
CHEVRON TEXACO (FAMM) CETUS PAO 68
ELF TOTAL FINA (Lubmarine) BARELF SM-68 / DACNIS SH-68
ESSO (ExxonMobil Marine) RARUS SHC-1026
MOBIL (ExxonMobil Marine)
SHELL CORENA AS-68
However, the oil properties are subject to change without notice by the
oil manufacturer. Also, the oil characteristics may vary depending on the
regional market. Therefore this list does not release the operator of the
compressor from verifying that the selected oil complies with the above
specification.
Service
1) Nome della nave (ev. nome precedente), numero di Costruzione e nome del Cantiere
Naval e
2) Numero di matricola e tipo del compressore (vedi targhetta)
3) Numero del pezzo di ricambio in base alla «Lista dei pezzi di ricambio»
4) Mezzo di trasporto, indirizzo di spedizione ed indirizzo di fatturazione desiderati
Service
In order to receive spare parts with the least possible delay, please get in touch with us
directly
Headquarters:
HATLAPA Uetersener Maschinenfabrik GmbH & Co. KG
Tornescher Weg 5-7
25436 Uetersen
GERMANY
Phone: +49 4122 711-0
Mobile: +49 172 9 813292
Fax: +49 4122 711-104 Sales
711-330 Service
info@hatlapa.de, http://www.hatlapa.de
o Australia CJA Marine Technology Pty Ltd Tel: +61 3 953213-97 / 953213-86
Unit 3, 136 Cochranes Road Fax: +61 3 953214-13
Moorabbin, Victoria 3189 info@cjamarine.com.au
xo Canada Marine and Offshore Canada Tel: +1 905 688 4922 (office)
29-113 Cushman Rd Fax: +1 905 688 9028
St. Catherines Cell: +1 905 650 3160
Ontario, L2M 6S9 roger@marineandoffshore.com
x China HATLAPA Shanghai Asia Pacific Pte Ltd Tel: +86 21 623296-71
No. 1211 Chang De Road Mobile: +86 137 0 17473 14
Room 1011, Baohua Building Fax: +86 21 623039-71
Shanghai 200060 hatlapa@online.sh.cn
Original 2010-12-08
xo Great Britain HATLAPA Marine Equipment Ltd Tel: +44 1202 8531-80
Discovery Court Business Centre Fax:+44 1202 8531-90
551-553 Wallisdown Road info@hatlapa-uk.com
Poole, Dorset BH12 5AG
xo Greece M.I.E. Co. Ltd. Tel: +30 210 4598-800
Kanari 1 Fax: +30 210 4539-234
18537 Piraeus commercial@mie.gr
o Greece INJEGOV Advanced Mechanical Services Ltd Tel: +30 210 4323600/1-2
Vipa Shistou, Road 2, OT3 Perama Fax: +30 210 43127-70
18863 Piraeus info@injegov.gr
x Singapore HATLAPA Asia Pacific Pte Ltd Tel: +65 65 628086 / 628088
German Centre, Unit 02-25 Mobile: +65 96 339381
25 International Business Park Fax: +65 65 628099
Jurong, Singapore 609916 info@hatlapa.com.sg