SIERRA LEONE
Volume 1 of 2
1
Table of Contents
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
3
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 5
Contents
A. General ............................................................................................................................. 7
1. Scope of Bid .................................................................................................................. 7
2. Source of Funds ............................................................................................................ 7
3. Fraud and Corruption .................................................................................................... 8
4. Eligible Bidders ............................................................................................................ 8
5. Eligible Plant and Installation Services ...................................................................... 11
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 6
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 7
A. General
1. Scope of Bid 1.1 In connection with the Specific Procurement Notice - Request for
Bids (RFB), specified in the Bid Data Sheet (BDS), the
Employer, as specified in the BDS, issues this bidding document
for the Design, Supply and Installation of Plant as specified in
Section VII, Employer’s Requirements. The name, identification
and number of lots (contracts) of this RFB are specified in the
BDS.
1.2 Throughout this bidding document:
(a) the term “in writing” means communicated in written form
(e.g. by mail, e-mail, fax, including if specified in the
BDS, distributed or received through the electronic-
procurement system used by the Employer) with proof of
receipt;
(b) if the context so requires, “singular” means “plural” and vice
versa; and
(c) “Day” means calendar day, unless otherwise specified as
“Business Day.” A Business Day is any day that is an
official working day of the Borrower. It excludes the
Borrower’s official public holidays.
2. Source of 2.1 The Borrower or Recipient (hereinafter called “Borrower”)
Funds indicated in the BDS has applied for or received financing
(hereinafter called “funds”) from the World Bank (hereinafter
called “the Bank”) in an amount specified in BDS, toward the
project named in BDS. The Borrower intends to apply a portion
of the funds to eligible payments under the contract(s) for which
this bidding document is issued.
2.2 Payment by the Bank will be made only at the request of the
Borrower and upon approval by the Bank in accordance with the
terms and conditions of the Loan (or other financing) Agreement.
The Loan (or other financing) Agreement prohibits a withdrawal
from the loan account for the purpose of any payment to persons
or entities, or for any import of goods, equipment, plant, or
materials, if such payment or import is prohibited by a decision
of the United Nations Security Council taken under Chapter VII
of the Charter of the United Nations. No party other than the
Borrower shall derive any rights from the Loan (or other
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 8
3. Fraud and 3.1 The Bank requires compliance with the Bank’s Anti-Corruption
Corruption Guidelines and its prevailing sanctions policies and procedures
as set forth in the WBG’s Sanctions Framework, as set forth in
Section VI.
3.2 In further pursuance of this policy, bidders shall permit and shall
cause their agents (where declared or not), subcontractors,
subconsultants, service providers, suppliers, and their personnel,
to permit the Bank to inspect all accounts, records and other
documents relating to any initial selection process,
prequalification process, bid submission, proposal submission
and contract performance (in the case of award), and to have
them audited by auditors appointed by the Bank.
4. Eligible Bidders 4.1 A Bidder may be a firm that is a private entity, a state-owned
enterprise or institution subject to ITB 4.6, or any combination of
such entities in the form of a joint venture (JV) under an existing
agreement or with the intent to enter into such an agreement
supported by a letter of intent. In the case of a joint venture, all
members shall be jointly and severally liable for the execution of
the entire Contract in accordance with the Contract terms. The
JV shall nominate a Representative who shall have the authority
to conduct all business for and on behalf of any and all the
members of the JV during the Bidding process and, in the event
the JV is awarded the Contract, during contract execution. Unless
specified in the BDS, there is no limit on the number of
members in a JV.
4.2 A Bidder shall not have a conflict of interest. Any Bidder found
to have a conflict of interest shall be disqualified. A Bidder may
be considered to have a conflict of interest for the purpose of this
Bidding process, if the Bidder:
(a) directly or indirectly controls, is controlled by or is under
common control with another Bidder; or
(b) receives or has received any direct or indirect subsidy from
another Bidder; or
(c) has the same legal representative as another Bidder; or
(d) has a relationship with another Bidder, directly or through
common third parties, that puts it in a position to influence
the Bid of another Bidder, or influence the decisions of the
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 9
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 12
6.3 Unless obtained directly from the Employer, the Employer is not
responsible for the completeness of the document, responses to
requests for clarification, the Minutes of the pre-Bid meeting (if
any), or Addenda to the bidding document in accordance with
ITB 8. In case of any contradiction, documents obtained directly
from the Employer shall prevail.
6.4 The Bidder is expected to examine all instructions, forms, terms,
and specifications in the bidding document and to furnish with its
Bid all information or documentation as is required by the
bidding document.
7. Clarification of 7.1 A Bidder requiring any clarification of the bidding document
Bidding shall contact the Employer in writing at the Employer’s address
Document, Site indicated in the BDS or raise his enquiries during the pre-Bid
Visit, Pre-Bid meeting if provided for in accordance with ITB 7.4. The
Meeting Employer will respond in writing to any request for clarification,
provided that such request is received prior to the deadline for
submission of Bids within a period specified in the BDS. The
Employer shall forward copies of its response to all Bidders who
have acquired the bidding document in accordance with ITB 6.3,
including a description of the inquiry but without identifying its
source. If so specified in the BDS, the Employer shall also
promptly publish its response at the web page identified in the
BDS. Should the clarification result in changes to the essential
elements of the bidding document, the Employer shall amend the
bidding document following the procedure under ITB 8 and ITB
23.2.
7.2 The Bidder is advised to visit and examine the site where the
plant is to be installed and its surroundings and obtain for itself
on its own responsibility all information that may be necessary
for preparing the Bid and entering into a Contract for the
provision of Plant and Installation Services. The costs of visiting
the site shall be at the Bidder’s own expense.
7.3 The Bidder and any of its personnel or agents will be granted
permission by the Employer to enter upon its premises and lands
for the purpose of such visit, but only upon the express condition
that the Bidder, its personnel, and agents will release and
indemnify the Employer and its personnel and agents from and
against all liability in respect thereof, and will be responsible for
death or personal injury, loss of or damage to property, and any
other loss, damage, costs, and expenses incurred as a result of the
inspection.
7.4 If so specified in the BDS, the Bidder’s designated
representative is invited to attend a pre-Bid meeting and/or a site
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 13
C. Preparation of Bids
9. Cost of Bidding 9.1 The Bidder shall bear all costs associated with the preparation
and submission of its Bid, and the Employer shall not be
responsible or liable for those costs, regardless of the conduct or
outcome of the Bidding process.
10. Language of 10.1 The Bid, as well as all correspondence and documents relating to
Bid the Bid exchanged by the Bidder and the Employer, shall be
written in the language specified in the BDS. Supporting
documents and printed literature that are part of the Bid may be
in another language provided they are accompanied by an
accurate translation of the relevant passages in the language
specified in the BDS, in which case, for purposes of
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 14
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 15
12. Letter of Bid 12.1 The Letter of Bid and Price Schedules shall be prepared, using
and Price the relevant forms furnished in Section IV, Bidding Forms. The
Schedules forms must be completed as instructed in each form without any
alterations to the text, and no substitutes shall be accepted except
as provided under ITB 21.3. All blank spaces shall be filled in
with the information requested.
13. Alternative 13.1 Unless otherwise specified in the BDS, alternative Bids shall not
Bids be considered.
13.2 When alternatives to the Time Schedule are explicitly invited, a
statement to that effect will be included in the BDS, and the
method of evaluating different time schedules will be described
in Section III, Evaluation and Qualification Criteria.
13.3 Except as provided under ITB 13.4 below, Bidders wishing to
offer technical alternatives to the Employer’s requirements as
described in the bidding document must also provide: (i) a price
at which they are prepared to offer a Plant meeting the
Employer’s requirements; and (ii) all information necessary for a
complete evaluation of the alternatives by the Employer,
including drawings, design calculations, technical specifications,
breakdown of prices, and proposed installation methodology and
other relevant details. Only the technical alternatives, if any, of
the Bidder with the Most Advantageous Bid conforming to the
basic technical requirements shall be considered by the
Employer.
13.4 When Bidders are invited in the BDS to submit alternative
technical solutions for specified parts of the facilities, such parts
will be identified in the BDS, as will the method for their
evaluation, and described in Section VII, Employer’s
Requirements.
14. Documents 14.1 To establish the eligibility of the Plant and Installation Services
Establishing the in accordance with ITB 5, Bidders shall complete the country of
Eligibility of the origin declarations in the Price Schedule Forms, included in
Plant and Section IV, Bidding Forms.
Installation
Services
15. Documents 15.1 To establish its eligibility and qualifications to perform the
Establishing the Contract in accordance with Section III, Evaluation and
Eligibility and Qualification Criteria, the Bidder shall provide the information
Qualifications requested in the corresponding information sheets included in
of the Bidder Section IV, Bidding Forms.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 16
16. Documents 16.1 The Bidder shall furnish the information stipulated in Section IV,
Establishing the Bidding Forms in sufficient detail to demonstrate substantial
Conformity of responsiveness of the Bidders’ proposal to the work requirements
the Plant and and the completion time.
Installation
Services 16.2 For major items of Plant and Installation Services as listed by the
Employer in Section III, Evaluation and Qualification Criteria,
which the Bidder intends to purchase or subcontract, the Bidder
shall give details of the name and nationality of the proposed
Subcontractors, including manufacturers, for each of those items.
In addition, the Bidder shall include in its Bid information
establishing compliance with the requirements specified by the
Employer for these items. Quoted rates and prices will be
deemed to apply to whichever Subcontractor is appointed, and no
adjustment of the rates and prices will be permitted.
16.3 The Bidder shall be responsible for ensuring that any
Subcontractor proposed complies with the requirements of ITB
4, and that any plant, or services to be provided by the
Subcontractor comply with the requirements of ITB 5 and ITB
15.1.
17. Bid Prices and 17.1 Unless otherwise specified in the BDS, Bidders shall quote for
Discounts the entire Plant and Installation Services on a “single
responsibility” basis. The total Bid price shall include all the
Contractor’s obligations mentioned in or to be reasonably
inferred from the bidding document in respect of the design,
manufacture, including procurement and subcontracting (if any),
delivery, construction, installation and completion of the Plant.
This includes all requirements under the Contractor’s
responsibilities for testing, pre-commissioning and
commissioning of the plant and, where so required by the
bidding document, the acquisition of all permits, approvals and
licenses, etc.; the operation, maintenance and training services
and such other items and services as specified in the bidding
document, all in accordance with the requirements of the General
Conditions. Items against which no price is entered by the Bidder
will not be paid for by the Employer when executed and shall be
deemed to be covered by the prices for other items.
17.2 Bidders are required to quote the price for the commercial,
contractual and technical obligations outlined in the bidding
document.
17.3 Bidders shall give a breakdown of the prices in the manner and
detail called for in the Price Schedules included in Section IV,
Bidding Forms.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 17
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 18
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 21
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 22
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 23
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 24
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 25
in the BDS.
26.7 The Employer shall neither discuss the merits of any Bid nor
reject any Bid (except for late Bids, in accordance with ITB
24.1).
26.8 The Employer shall prepare a record of the Bid opening that shall
include, as a minimum:
(a) the name of the Bidder and whether there is a withdrawal,
substitution, or modification;
(b) the Bid Price, per lot if applicable, including any discounts;
(c) any alternative Bids; and
(d) the presence or absence of a Bid Security or a Bid-Securing
Declaration.
26.9 The Bidders’ representatives who are present shall be requested
to sign the record. The omission of a Bidder’s signature on the
record shall not invalidate the contents and effect of the record.
A copy of the record shall be distributed to all Bidders.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 26
28. Clarification of 28.1 To assist in the examination, evaluation, and comparison of the
Bids Bids, and qualification of the Bidders, the Employer may, at its
discretion, ask any Bidder for a clarification of its Bid. Any
clarification submitted by a Bidder that is not in response to a
request by the Employer shall not be considered. The
Employer’s request for clarification and the response shall be in
writing. No change in the prices or substance of the Bid shall be
sought, offered, or permitted, except to confirm the correction of
arithmetic errors discovered by the Employer in the evaluation of
the Bids, in accordance with ITB 32.
28.2 If a Bidder does not provide clarifications of its Bid by the date
and time set in the Employer’s request for clarification, its Bid
may be rejected.
29. Deviations, 29.1 During the evaluation of Bids, the following definitions apply:
Reservations,
and Omissions (a) “Deviation” is a departure from the requirements specified
in the bidding document;
(b) “Reservation” is the setting of limiting conditions or
withholding from complete acceptance of the requirements
specified in the bidding document; and
(c) “Omission” is the failure to submit part or all of the
information or documentation required in the bidding
document.
30. Determination 30.1 The Employer’s determination of a Bid’s responsiveness is to be
of based on the contents of the Bid itself, as defined in ITB11.
Responsiveness
30.2 A substantially responsive Bid is one that meets the requirements
of the bidding document without material deviation, reservation,
or omission. A material deviation, reservation, or omission is
one that:
(a) if accepted, would:
(i) affect in any substantial way the scope, quality, or
performance of the Plant and Installation Services
specified in the Contract; or
(ii) limit in any substantial way, inconsistent with the
bidding document, the Employer’s rights or the
Bidder’s obligations under the proposed Contract; or
(b) if rectified, would unfairly affect the competitive position
of other Bidders presenting substantially responsive Bids.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 27
30.3 The Employer shall examine the technical aspects of the Bid in
particular, to confirm that all requirements of Section VII,
Employer’s Requirements have been met without any material
deviation, reservation, or omission.
30.4 If a Bid is not substantially responsive to the requirements of the
bidding document, it shall be rejected by the Employer and may
not subsequently be made responsive by correction of the
material deviation, reservation, or omission.
31. Nonmaterial 31.1 Provided that a Bid is substantially responsive, the Employer
Nonconformitie may waive any nonconformity in the Bid that does not constitute
s a material deviation, reservation or omission.
31.2 Provided that a Bid is substantially responsive, the Employer
may request that the Bidder submit the necessary information or
documentation, within a reasonable period of time, to rectify
nonmaterial nonconformities in the Bid related to documentation
requirements. Requesting information or documentation on such
nonconformities shall not be related to any aspect of the price of
the Bid. Failure of the Bidder to comply with the request may
result in the rejection of its Bid.
31.3 Provided that a Bid is substantially responsive, the Employer
shall rectify quantifiable nonmaterial nonconformities related to
the Bid Price. To this effect, the Bid Price shall be adjusted, for
comparison purposes only, to reflect the price of a missing or
non-conforming item or component in the manner specified in
the BDS.
32. Correction of 32.1 Provided that the Bid is substantially responsive, the Employer
Arithmetical shall correct arithmetical errors on the following basis:
Errors
(a) where there are errors between the total of the amounts
given under the column for the price breakdown and the
amount given under the Total Price, the former shall
prevail and the latter will be corrected accordingly;
(b) where there are errors between the total of the amounts of
Schedule Nos. 1 to 4 and the amount given in Schedule
No. 5 (Grand Summary), the former shall prevail and the
latter will be corrected accordingly; and
(c) if there is a discrepancy between words and figures, the
amount in words shall prevail, unless the amount expressed
in words is related to an arithmetic error, in which case the
amount in figures shall prevail subject to (a) and (b) above.
32.2 Bidders shall be requested to accept correction of arithmetical
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 28
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 29
Low Bids combination with other elements of the Bid, appears so low that
it raises material concerns as to the capability of the Bidder to
perform the Contract for the offered Bid Price.
37.2 In the event of identification of a potentially Abnormally Low
Bid, the Employer shall seek written clarifications from the
Bidder, including detailed price analyses of its Bid price in
correlation to the subject matter of the contract, scope, proposed
methodology, schedule, allocation of risks and responsibilities
and any other requirements of the bidding document.
37.3 After evaluation of the price analyses, in the event that the
Employer determines that the Bidder has failed to demonstrate its
capability to deliver the contract for the offered tender price, the
Employer shall reject the Bid.
38. Unbalanced or 38.1 If the Bid that is evaluated as the lowest evaluated cost is, in the
Front Loaded Employer’s opinion, seriously unbalanced or front loaded the
Bids Employer may require the Bidder to provide written
clarifications. Clarifications may include detailed price analyses
to demonstrate the consistency of the Bid prices with the scope
of works, proposed methodology, schedule and any other
requirements of the bidding document.
38.2 After the evaluation of the information and detailed price
analyses presented by the Bidder, the Employer may:
(a) accept the Bid; or
(b) if appropriate, require that the total amount of the
Performance Security be increased, at the expense of the
Bidder, to a level not exceeding twenty percent (20%) of
the Contract Price; or
(c) reject the Bid.
39. Eligibility and 39.1 The Employer shall determine to its satisfaction whether the
Qualification of Bidder that is selected as having submitted the lowest evaluated
the Bidder cost and substantially responsive Bid is eligible and meets the
qualifying criteria specified in Section III, Evaluation and
Qualification Criteria.
39.2 The determination shall be based upon an examination of the
documentary evidence of the Bidder’s qualifications submitted
by the Bidder, pursuant to ITB 15.1.The determination shall not
take into consideration the qualifications of other firms such as
the Bidder’s subsidiaries, parent entities, affiliates,
subcontractors (other than Specialized Subcontractors if
permitted in the bidding document) or any other firm(s) different
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 31
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 32
42. Notification of 42.1 The Employer shall send to each Bidder the Notification of
Intention to Intention to Award the Contract to the successful Bidder. The
Award Notification of Intention to Award shall contain, at a minimum,
the following information:
(a) the name and address of the Bidder submitting the
successful Bid;
(b) the Contract price of the successful Bid;
(c) the names of all Bidders who submitted Bids, and their Bid
prices as readout, and as evaluated;
(d) a statement of the reason(s) the Bid (of the unsuccessful
Bidder to whom the notification is addressed) was
unsuccessful, unless the price information in c) above
already reveals the reason;
(e) the expiry date of the Standstill Period; and
(f) instructions on how to request a debriefing and/or submit a
complaint during the standstill period.
F. Award of Contract
43. Award Criteria 43.1 Subject to ITB 40, the Employer shall award the Contract to the
successful Bidder. This is the Bidder whose Bid has been
determined to be the Most Advantageous Bid. This is the Bid of
the Bidder that meets the qualification criteria and whose Bid has
been determined to be:
(a) substantially responsive to the bidding document; and
(b) the lowest evaluated cost.
44. Notification of 44.1 Prior to the expiration of the Bid Validity Period, and upon
Award expiry of the Standstill Period, specified in ITB 41.1 or any
extension thereof, and upon satisfactorily addressing any
complaint that has been filed within the Standstill Period, the
Employer shall notify the successful Bidder, in writing, that its
Bid has been accepted. The notification of award (hereinafter and
in the Contract Forms called the “Letter of Acceptance”) shall
specify the sum that the Employer will pay the Contractor in
consideration of the execution of the contract (hereinafter and in
the Conditions of Contract and Contract Forms called “the
Contract Price”).
44.2 Within ten (10) Business Days after the date of transmission of
the Letter of Acceptance, the Employer shall publish the
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section I – Instructions to Bidders (ITB) 33
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section II – Bid Data Sheet (BDS) 37
A. General
ITB 1.1 The reference number of the Request for Bids (RFB) is: SL-EDSA-119619-
CW-RFB
The Employer is: Electricity Distribution and Supply Authority (EDSA)
The name of the RFB is: Supply and Installation of 33kV Sub-transmission
Lines and 33/11kV Primary Substations (Lot 1-2)
The number and identification of lots (contracts)comprising this RFB is:
The bid is in two (2) lots as detailed below and bidders may bid for any one
lot or both lots:
• Lot 1: Supply and Installation of 33/11kV Primary Substations in
Freetown (Lot 1)
• Lot 2: Supply and Installation of 33kV Sub Transmission Lines in
Freetown (Lot 2)
ITB 2.1 The Borrower is: The Government of the Republic of Sierra Leone
The amount of the financing is: USD 50,000,000.00
The name of the Project is: Energy Sector Utility Reform Project
Additional Financing (ESURP AF)
ITB 4.1 Maximum number of members in the Joint Venture (JV) shall be: No limit.
ITB 4.5 A list of debarred firms and individuals is available on the Bank’s external
website: http://www.worldbank.org/debarr.
B. Bidding Document
ITB 7.1 For Clarification of Bid purposes only, the Employer’s address is:
Attention: Emmanuel Ozigbo
Address: No 5, High broad Street, Murray Town
City: Freetown
Country: Sierra Leone
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section II – Bid Data Sheet (BDS) 38
Telephone:
Electronic mail address: ozigboemmanu@gmail.com;
Cc:gobarichard@gmail.com; aleksandarnikolic@edsa.sl;
mohamedfofanah@edsa.sl; pchamfya@gmail.com, francisnyama@edsa.sl,
edwardparkinson@edsa.sl
Requests for clarification should be received by the Employer no later than:
twenty-eight (28) days prior to the deadline for submission of bids.
Web page: none
ITB 7.4 A Pre-Bid meeting will take place at the following date, time and place:
Date: January 13, 2020
Time: 10:00 Hours GMT
Place: No 5, High broad Street, Murray Town, Freetown in the
Conference Room
A site visit conducted by the Employer shall be organized on the same day.
C. Preparation of Bids
ITB 10.1 The language of the Bid is: English.
All correspondence exchange shall be in English language.
Language for translation of supporting documents and printed literature is
English.
ITB 11.1 (j) The Bidder shall submit the following additional documents in its Bid:
a. Preliminary Contractor’s Environment and Social Management Plan
(C-ESMP) based on the ESMP in the ESHIA Report prepared by the
employer
b. Preliminary dimensioned Drawings to demonstrate bidders
understanding of the scope works (based on the drawings in the bidding
document) including:
• Substation Single Line Diagrams
• Substation equipment layout
• Steel Tubular Pole Top Structure Arrangement
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section II – Bid Data Sheet (BDS) 39
ITB 13.4 Alternative technical solutions shall be permitted for the following parts of
the Plant and Installation Services: N/A as further detailed in the
Specification.
If alternative technical solutions are permitted, the evaluation method will
be as specified in Section III, Evaluation and Qualification Criteria.
The Technical Proposal shall also include the following additional documents:
ITB16.1
Code of Conduct (ESHS)
The Bidder shall submit its Code of Conduct that will apply to its employees
and subcontractors, to ensure compliance with its Environmental, Social, Health
and Safety (ESHS) obligations under the contract. If not available, its Code of
Conduct must be submitted during the first month of contract effectiveness
In addition, the Bidder shall detail how this Code of Conduct will be
implemented. This will include how it will be introduced into conditions of
employment/engagement, what training will be provided, how it will be
monitored and how the Contractor proposes to deal with any breaches.
The Contractor shall be required to implement the agreed Code of Conduct
upon contract award.
Code of Conduct for Gender Based Violence (GBV) / Sexual Exploitation
and Abuse (SEA)
The Bidder shall submit its Code of Conduct that will apply to its employees
and subcontractors, to ensure compliance with its GBV/SEA Framework
obligations under the contract.
In addition, the Bidder shall develop GBV/SEA prevention and response action
plan that is acceptable by the Employer.
Management Strategies and Implementation Plans (MSIP) to manage the
(ESHS) risks
The Bidder shall submit Management Strategies and Implementation Plans
(MSIP) to manage the following key Environmental, Social, Health and Safety
(ESHS) risks:
• Gender based violence and sexual exploitation and abuse (GBV/SEA)
prevention and response action plan;
• Grievance Redress Mechanism;
• Health and Safety Management Plan, to ensure health and safety of
workers; including use of protective clothing; HIV/AIDS awareness and
prevention, including sensitization and counselling; drug and substance
abuse, and avoidance of child labour and child abuse;
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section II – Bid Data Sheet (BDS) 40
ITB 17.5 (a) Place of destination: Shall be an area to be secured and maintained by the
and (d) contractor for the period of the works. It may be located close to the
named place of final destination as stated below
Final destination (Project Site):
Lot1: Substation sites at Freetown 161, Aberdeen, Falcon Bridge, Cline
Town, Jui, Waterloo and Regent
Lot2: various lines routes specified under scope of works under Section
VII “Employer’s Requirements”
ITB 17.7 The prices quoted by the Bidder shall not be subject to adjustment during
the performance of the Contract.
ITB 18.1 The Bidder is not required to quote in the currency of the Employer’s
Country the portion of the Bid price that corresponds to expenditures
incurred in that currency.
ITB 19.3 (a) The Bid price shall be adjusted by the following factor(s): N/A
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section II – Bid Data Sheet (BDS) 41
ITB 21.1 In addition to the original of the Bid, the number of copies is:
Three (3) plus a soft copy in a flash drive. The Flash disk shall be
enclosed in the envelope marked “copy” in accordance with the ITB 21.1
and should contain UNEDITABLE COPY of both TECHNICAL &
FINANCIAL PROPOSAL. In the event of any discrepancies between the
original and the electronic copy, the original shall prevail
ITB 21.3 The written confirmation of authorization to sign on behalf of the Bidder
shall consist of: a Notarized Power of Attorney.
ITB 26.6 The Letter of Bid and Price Schedules shall be initialed by two
representatives of the Employer conducting Bid opening.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section II – Bid Data Sheet (BDS) 42
ITB 31.3 The adjustment shall be based on the highest price of the item or component
as quoted in other substantially responsive Bids. If the price of the item or
component cannot be derived from the price of other substantially
responsive Bids, the Employer shall use its best estimate.
ITB 33.1 The currency that shall be used for Bid evaluation and comparison purposes
to convert (at the selling exchange rate) all Bid prices expressed in various
currencies into a single currency is: Sierra Leone Leones (SLL)
The source of exchange rate shall be: The Central Bank of Sierra Leone at
http://www.bsl.gov.sl.
The date for the exchange rate shall be: 7 days prior to the bid opening date
ITB 35.4 (f) The adjustments shall be determined using the following criteria, from
amongst those set out in Section III, Evaluation and Qualification Criteria:
[refer to Section III, Evaluation and Qualification Criteria; insert
complementary details if necessary]
(a) Deviation in Time for Completion: No.;
(b) Life cycle costs: the projected operating and maintenance costs
during the life of the goods or equipment Yes;
(c) Functional Guarantees of the Facilities Yes;
(d) Work, services, facilities, etc., to be provided by the Employer No;
ITB 46.1 The successful Bidder shall not submit the Beneficial Ownership Disclosure
Form.
ITB 48.1 The procedures for making a Procurement-related Complaint are detailed in
the “Procurement Regulations for IPF Borrowers (Annex III).” If a Bidder
wishes to make a Procurement-related Complaint, the Bidder should submit
its complaint following these procedures, in writing (by the quickest means
available, that is either by email or fax), to:
For the attention: Francis Nyama
Title/position: Deputy Director General
Employer: Electricity Distribution and Supply Authority (EDSA)
Email address francisnyama@edsa.sl
In summary, a Procurement-related Complaint may challenge any of the
following:
1. the terms of the Bidding Documents; and
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section II – Bid Data Sheet (BDS) 43
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section III – Evaluation and Qualification Criteria 45
This Section contains all the criteria that the Employer shall use to evaluate Bids and qualify
Bidders. No other factors, methods or criteria shall be used other than those specified in this
bidding document.
The Bidder shall provide all the information requested in the forms included in Section IV,
Bidding Forms.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section III – Evaluation and Qualification Criteria 46
Table of Criteria
1. Evaluation .......................................................................................................................... 47
1.1 Technical Evaluation .................................................................................................... 47
1.2 Economic Evaluation .................................................................................................... 49
1.3 Multiple Contracts (ITB 35.6) ...................................................................................... 50
2. Qualification ...................................................................................................................... 52
1 Eligibility ......................................................................................................................... 52
2. Historical Contract Non-Performance ............................................................................ 53
3 Financial Situation ........................................................................................................... 55
4 Experience........................................................................................................................ 58
2.5 Personnel ....................................................................................................................... 61
2.6 Equipment ..................................................................................................................... 62
2.7 Subcontractors............................................................................................................... 63
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section III – Evaluation and Qualification Criteria 47
The Employer shall use the criteria and methodologies listed in this Section to evaluate Bids.
By applying the criteria and methodologies, the Employer shall determine the Most
Advantageous Bid. This is the Bid of the Bidder that meets the qualification criteria and
whose Bid has been determined to be:
(a) substantially responsive to the bidding document; and
(b) the lowest evaluated cost.
1. Evaluation
1.1 Technical Evaluation
In addition to the criteria listed in ITB 35.2 (a) – (c) the following factors shall apply:
(a) the adequacy of the technical proposals (i) – (vii) and meeting the requirement
proposal below:
i. Site Organization: Requirement is for hierarchical organization chart indicating
head office and field personnel that would be involved in the Management and
Construction works;
ii. Method Statement: Adequate narrative detailing the sequence and methods to
carry out the works in strict adherence to the specifications and the
Environmental and Social Safeguard policies of the Bank including:
• Design, Supply & Installation: Substation, and equipment design procedure,
the procedure for procurement of major equipment and materials, procedure
for civil & installation work;
• Quality control measures: Adequate narration of specific quality control
measures at design, manufacture, erection, installation, testing and
commissioning stages of the project. The presentation shall include
recruitment/selection of the subcontractors/sub suppliers if any and how they
will be supervised;
• Environment, Social, Health and Safety (ESHS) Management Strategy and
Implementation Plans (C-ESMP): The preliminary Contractor’s
Environmental, Health and Social Management Plan should include an
identification of expected Environmental, Health and safety hazards, and
mitigation measures that will be adopted to ensure that the projects are
completed without accidents, and with minimum negative impact on the
environment. Bidders shall prepare their preliminary C-ESMP based on the
ESMP in the ESHIA report prepared by EDSA and reflect industry best
practice and standards. The ESHIA report would be made available to
prospective bidders;
• Workers’ ESHS Code of Conduct: Adequacy of statement on ESHS Code of
Conduct that will apply to the employees and sub-contractors of the
contractor, and details of how it will be enforced. The code of conduct will
include the bidder’s declared statement against sexual exploitation and abuse
(SEA) involving workers and women/young girls in the local communities. The
declared statement is expected to be incorporated in contracts for workers
and be enforced as such.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section III – Evaluation and Qualification Criteria 48
•
iii. Mobilization Schedule: Provision of mobilization schedule in the form of bar
chart showing the schedule for undertaking the activities leading to contract
effectiveness and the sequence of mobilizing personnel and work items to site
iv. Construction Schedule: Requirement is for construction schedule in a bar chart
form showing the sequence for undertaking the key events from notification of
award through construction up until commissioning, handover and defect liability
period. The activities should include but not limited to the period for site testing,
detailed designs, civil works, procurement of materials, manufacturing,
delivering, installation of equipment, testing, commissioning and hand over
(provision of as-built-documentation);
v. Plant: Must meet minimum requirements in the Technical Schedules (Technical
Data Sheets) of the major plant and equipment provided in Section IV Bid Forms.
Bidders shall provide duly completed all Technical Schedules (Technical Data
Sheets) with detailed information of offered materials and equipment, in which all
required information, should be filled completely and signed. Technical Schedules
(Technical Data Sheets) shall be signed and stamped by the Bidder. Bids not
having duly completed all Technical Schedules (Technical Data Sheets) for all the
listed plant shall be rejected. Any deviation from technical requirements shall be
clearly stated/marked by the Bidders and shall be subject to Employer’s
acceptance or rejection.
(b) The offered equipment shall already have been Type Tested, where the specifications
call for the equipment to be type tested. Bidders shall attach copies of Type Test
Certificates and Reports and technical documents (catalogue, brochures, drawings.) of
each major item offered with their bids. The validity of the type test referred to in this
section will be for the Type Test conducted not earlier than the last ten (10) years,
calculated from the date of bid opening. Type Test Reports shall be carried out by a
laboratory independent of the manufacturer or with the witness of independent laboratory.
Accreditation certificate for the testing laboratory shall be submitted with the bid.
Tested plant (equipment/material) in Type Test Reports shall have the same code/ country
/ manufacturer and technical parameters as offered plant (equipment/material). Type
Tests of non-conforming plant (materials/equipment) shall not be accepted.
The major equipment for which Type Test reports are required are (as applicable to each
lot):
• Power Transformers (161/33kV 35/40MVA, 33/11kV 20/26MVA) or of similar
capacities)
• 161kV outdoor equipment (Circuit Breakers, Lightening Arrestors, Disconnect
Switches, Voltage Transformers, Current Transformers)
• 33kV outdoor equipment (Circuit Breakers, Lightening Arrestors, Disconnect
Switches, Voltage Transformers, Current Transformers)
• 33kV and 11kV indoor Air Insulated Switchgears and Vacuum Circuit Breakers
• Protection relays and Bay Protection and Control Units (BCPUs)
• 33kV XLPE Cables
• 11kV XLPE Cables
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section III – Evaluation and Qualification Criteria 49
Power Transformer
For the purposes of evaluation, The Transformer Losses (at the ONAN central Tap
rating) offered by Bidders shall be capitalized and evaluated in accordance with the
technical specification for the transformers in volume II of this bidding document.
Transformer Losses (in kW) offered by Bidders in the Technical Schedules for the
ONAN rating at central Tap (and also in the form FUNC) shall be multiplied by the
Employer’s Unit Capitalized Costs of Losses and the results added to the Bid Price for
the purpose of evaluation only as follows:
Pi = N x (kNL * NL + kLL * LL)
Where: Pi = Total Capitalized Cost in US $ of a transformer type i
N = Number of transformers of type i
NL = Quoted Guaranteed No-load loss in kW
LL = Quoted Guaranteed Load loss in kW
kLL = Unit Load Loss Capitalized Cost = $2,800/kW
kNL = Unit No Load Loss Capitalized Cost = $6,500/kW
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section III – Evaluation and Qualification Criteria 50
The sum of capitalized cost all the types of transformers shall be added to the evaluated
price to obtain the Adjusted Evaluated Cost
Transformers offered by Bidders whose Losses exceed the figures in the table 1.2 below
shall be rejected.
Power Transformers
Functional Guarantees shall be for transformer losses stated in the Technical Data Sheet and
in the form FUNC by the bidder. The maximum allowable losses (without any positive
tolerance) for the transformers are specified in the technical specifications and tabulated in
Table 1.2 above
(d) Work, services, facilities, etc., to be provided by the Employer
Not Applicable.
(e) Sustainable procurement
Not Applicable
(f) Alternative technical solutions for specified parts
Not Applicable
(g) Specific additional criteria
The relevant evaluation method, if any, shall be as follows:
Any adjustments in price that result from the above procedures shall be added, for purposes
of comparative evaluation only, to arrive at an “Evaluated Bid Price.” Bid prices quoted by
bidders shall remain unaltered.
1.3 Multiple Contracts (ITB 35.6)
If in accordance with ITB 1.1, Bids are invited for more than one lot, the contract will be
awarded to the Bidder or Bidders offering a substantially responsive Bid(s) and the lowest
evaluated cost to the Employer for combined lots, subject to the selected Bidder(s) meeting
the required qualification criteria Section III, Evaluation and Qualification Criteria for a lot or
combination of lots as the case may be.
In determining Bidder or Bidders that offer the total lowest evaluated cost to the Employer,
after considering all possible combination of lots, the Employer shall apply the following
steps in sequence:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section III – Evaluation and Qualification Criteria 51
(a) evaluate individual lots to determine the substantially responsive Bids and
corresponding evaluated costs;
(b) for each lot, rank the substantially responsive Bids starting from the lowest evaluated
cost for the lot;
(c) apply to the evaluated costs listed in b) above, any applicable discounts/price reductions
offered by a Bidder (s) for the award of multiple contracts based on the discounts and
the methodology for their application offered by the respective Bidder; and
(d) determine contract award on the basis of the combination of lots that offer the total
lowest evaluated cost to the Employer.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
52 Section III - Evaluation and Qualification Criteria
2. Qualification
Factor 1 Eligibility
Criteria
Bidder Documentation
Sub-Factor
Requirement Single Joint Venture (existing or intended) Required
Entity All members Each At least one
combined Partner Partner
1.1 Nationality Nationality in accordance with Must meet must meet Must meet N/A Form ELI –1.1 and
ITB 4.4. requirement requirement requirement 1.2, with
attachments
1.2 Conflict of No- conflicts of interests as Must meet must meet Must meet N/A Letter of Bid
Interest described in ITB 4.2 requirement requirement requirement
1.3 Bank Not having been declared Must meet must meet Must meet N/A Letter of Bid
Ineligibility ineligible by the Bank as requirement requirement requirement
described in 4.5.
1.4 State Owned Compliance with conditions of Form ELI –1.1 and
Must meet Must meet Must meet
Enterprise or Institution ITB 4.6 N/A 1.2, with
requirement requirement requirement
attachments
1.5 Ineligibility Not having been excluded as a Must meet must meet Must meet N/A Letter of Bid
based on a United result of the Borrower’s country requirement requirement requirement
Nations resolution or laws or official regulations, or
Borrower’s country law by an act of compliance with
UN Security Council resolution,
in accordance with ITB 4.8and
Section V.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines (Lot 1-2) – Volume 1 of 2
Section III - Evaluation and Qualification Criteria 53
1
Nonperformance, as decided by the Employer, shall include all contracts where (a) nonperformance was not challenged by the contractor, including through referral to the dispute resolution
mechanism under the respective contract, and (b) contracts that were so challenged but fully settled against the contractor. Nonperformance shall not include contracts where Employers decision was
overruled by the dispute resolution mechanism. Nonperformance must be based on all information on fully settled disputes or litigation, i.e. dispute or litigation that has been resolved in accordance
with the dispute resolution mechanism under the respective contract and where all appeal instances available to the Bidder have been exhausted.
2
This requirement also applies to contracts executed by the Bidder as JV member.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines (Lot 1-2) – Volume 1 of 2
54 Section III - Evaluation and Qualification Criteria
3
The Bidder shall provide accurate information on the related Letter of Bid about any litigation or arbitration resulting from contracts completed or ongoing under its execution over the last five years.
A consistent history of awards against the Bidder or any member of a joint venture may result in failure of the Bid.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines (Lot 1-2) – Volume 1 of 2
Section III - Evaluation and Qualification Criteria 55
2.4 Declaration: Declare any civil work Must make N/A Each must Form CON-3
Environmental, contracts that have been the make the N/A ESHS
Social, Health, and suspended or declaration. declaration. Performance
Safety (ESHS) past terminated and/or Where there Where there Declaration
performance performance security are are
called by an employer Specialized Specialized
for reasons related to Sub- Sub-
the non-compliance of contractor/s, contractor/s,
any environmental, or the the
social (including Specialized Specialized
sexual exploitation Sub- Sub-
and abuse (SEA) and contractor/s contractor/s
gender based violence must also must also
(GBV)), or health or make the make the
declaration. declaration.
safety requirements or
safeguard in the past
five years
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines (Lot 1-2) – Volume 1 of 2
56 Section III - Evaluation and Qualification Criteria
3.1 Financial Submission of audited balance Must meet N/A Must meet N/A Form FIN – 3.1 with
Capabilities sheets or if not required by the requirement requirement attachments
law of the Bidder’s Country,
other financial statements
acceptable to the Employer, for
the last Three [3] years (2016,
2017 & 2018) years to
demonstrate the current
soundness of the Bidders
financial position and its
prospective long term
profitability.
Criteria:
a. TA/TL Ratio should be
consistently ≥ 1.25 for the
3 yrs.
b. CA/CL Ratio should be
Consistently ≥ 1.20 for the
3 yrs.
3.2Average Annual Minimum average annual Must meet Must meet Must meet Must meet Form FIN –3.2
Turnover turnover in supply & requirement requirement [40÷(n-1)] % of sixty percent
installation of transmission and the requirement (60%) of the
or distribution network requirement
(where n =
equipment and materials of
number of JV
US$14.6 million for Lot 1 and
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines (Lot 1-2) – Volume 1 of 2
Section III - Evaluation and Qualification Criteria 57
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines (Lot 1-2) – Volume 1 of 2
58 Section III - Evaluation and Qualification Criteria
Factor 4 Experience
Criteria
Bidder
Sub-Factor Joint Venture (existing or intended) Documentation
Requirement Single Required
Entity All members Each member At least one member
combined
4.1General Experience Experience in supply & installation of Must meet N / A Must meet N/A Form EXP-4.1
transmission and or distribution network requirement requirement
equipment and materials under contracts in
the role of contractor, subcontractor, or
management contractor for at least the last 5
years starting 1st January 2013.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines (Lot 1-2) – Volume 1 of 2
Section III - Evaluation and Qualification Criteria 59
4.2(a)Specific (a)Participation as contractor, joint venture Must meet Must meet N/A Must meet at least two Form EXP 4.2(a)
Experience member4, management contractor, or requirement requirements6 contracts involving any of
subcontractor, in at least two (2) contracts the following key
within the last five (5) years, each with a activities:
value of at least US$7.6 million for Lot 1 • Detail Engineering
and US$6.8 million for Lot 2, that have been design services
successfully and substantially5completed • installation services
and that are similar to the proposed Plant
and Installation Services at least one of
which must have been in a developing
country with conditions similar to Sierra
Leone.
The similarity of the contracts shall be based
on the following:
Lot 1: Design, Supply & Installation of
primary substations with ratio 33/11kV or
above with at least 5No 33kV or higher
outdoor bays, 5No 33/11kV, 10MVA (or
higher) power transformers and 6No MV
Indoor Switchgears.
4
For contracts under which the Bidder participated as a joint venture member or sub-contractor, only the Bidder’s share, by value, shall be considered to meet this requirement
5
Substantial completion shall be based on 80% or more plant and installation completed under the contract.
6
In the case of JV, the value of contracts completed by its members shall not be aggregated to determine whether the requirement of the minimum value of a single contract has been met. Instead,
each contract performed by each member shall satisfy the minimum value of a single contract as required for single entity. In determining whether the JV meets the requirement of total number of
contracts, only the number of contracts completed by all members each of value equal or more than the minimum value required shall be aggregated.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines (Lot 1-2) – Volume 1 of 2
60 Section III - Evaluation and Qualification Criteria
4.2(b) Specific (b) For the above or other contracts executed Must meet Must meet N/A Must meet at least one Form EXP-4.2(b)
Experience during the period stipulated in 4.2(a) above, requirement requirements7 key activity listed in the
a minimum experience in the following key s first column of this 4.2
activities: b)-(a) & (b)
Lot 1
a. Engineering and design of sub
transmission (substation of voltage 33kV
and above) network
b. Supply and installation of:
• 3 No. 33/11kV Primary Substation
Building
• 5No. 33/11kV 10MVA (or above) Power
Transformers
• 4No. HV Outdoor line and transformer
bays
• 6No. 33kV or 11kV Indoor AIS
switchgears
Lot2
a. Engineering and design of sub
transmission (lines of voltage 33kV and
above) network
b. Supply and installation of:
• Towers/ Steel Tubular Poles: for
minimum 45km of 33kV line
• Stringing (Conductor 150mm2 and
above): for minimum 45km of 33kV
line
Any of the above key activities may also be
met through a specialized subcontractor
7
In the case of JV, the value of contracts completed by its members shall not be aggregated to determine whether the requirement of the minimum value of a single contract has been met. Instead, each
contract performed by each member shall satisfy the minimum value of a single contract as required for single entity. In determining whether the JV meets the requirement of total number of contracts,
only the number of contracts completed by all members each of value equal or more than the minimum value required shall be aggregated.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines (Lot 1-2) – Volume 1 of 2
Section III - Evaluation and Qualification Criteria 61
2.5 Personnel
The Bidder must demonstrate that it will have the personnel for the key positions that
meet the following requirements:
Experience (years)
In Written
Position As manager and spoken
in similar South
Total of similar English
works Sahara
works
Africa
Lot 1
Contractor’s Representative 15 10 8 - Fluent
Manager based on site (At least B.Sc./
12 8 5 3 Fluent
B. Tech in Elect. Eng.)
Substation Engineer (B.Sc. /B. Tech
8 5 - 2 Fluent
in Elect Eng.)
Construction Engineer (B.Sc./B. Tech 2
8 5 - Fluent
in Civil Eng.)
Substation Supervisor (B.Sc. /B. Tech, -
8 5 - Fluent
HND in Elect Eng.)
Environmental Safeguard officer 5 - - 1 Fluent
Social Safeguard officer 5 1 Fluent
Health and Safety Officer 5 - - 1 Fluent
Lot 2
Contractor’s Representative 15 10 8 - Fluent
Manager based on site (At least B.Sc./
12 8 5 3 Fluent
B. Tech in Elect/ Civil Eng.)
Construction Engineer (B.Sc./B. Tech 2
8 5 - Fluent
in Civil Eng.)
Transmission Lines Supervisor (B.Sc. -
8 5 - Fluent
/B. Tech, HND in Elect/ Civil Eng.)
Environmental Safeguard officer 5 - - 1 Fluent
Social Safeguard officer 5 - - 1 Fluent
Health and Safety Officer 5 - - 1 Fluent
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section III – Evaluation and Qualification Criteria 62
The Bidder shall provide details of the proposed personnel and their experience
records in the relevant Forms included in Section IV, Bidding Forms.
2.6 Equipment
The Bidder must demonstrate that it will have access to the key Contractor’s
equipment listed hereafter:
Item Description of Plant and Equipment Minimum number Is this equipment owned
No. to be used required or is it to be hired?
Lot 1
1 Circuit breaker analyzer test kit 1
Substation Test and Measuring
2 equipment (Primary and Secondary 1
Injection Test sets)
3 HV testing equipment 1
4 Partial discharge test equipment 1
5 Relay testing equipment 1
6 Power transformer testing 1
equipment
7 CT’s/VT’s testing equipment 1
8 Megger 2
9 Earth resistance tester 1
10 Oil analyzer equipment 1
11 Contact resistance test equipment 1
12 Transformer Oil Treatment Plant 1
13 Cable stand 1
14 Cable rollers Sufficient
Lot2
1 Stringing machine 1
2 Cable Stand 3
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section III - Evaluation and Qualification Criteria 63
3 HV testing equipment 1
4 Earth resistance tester 1
5 Testing and splicing equipment for 2
FO cables
6 Total Station equipment for survey 1
7 Rollers for conductor stringing Sufficient
8 Compressors (for excavation in 2
rocky areas)
The Bidder shall provide further details of proposed items of equipment using the relevant
Form in Section IV.
2.7 Subcontractors
Subcontractors/manufacturers for the following major items of supply or services
(‘Specialized Subcontractors’) must meet the following minimum criteria, herein listed for
that item:
No.
Description of Plant outside
Requirement Unit Total
for Supply under Bid Supplier'
s country
LOT1
Requirement is for a power transformer of at least
161/33kV Power 132kV voltage level and of at least 35/40MVA
No. 100 50
Transformer ONAN/ONAF rating manufactured in last 20 years
and in trouble free operation for at least 5 years
Requirement is for a power transformer of at least
33/11kV Power 33kV voltage level and of at least 10/13MVA
No. 500 300
Transformer ONAN/ONAF rating manufactured in last 20 years
and in trouble free operation for at least 5 years
Requirement is for Indoor AIS Switchgear panels
Indoor Switchgear with Vacuum Circuit Breakers up to 33kV,
No. 500 300
Panel manufactured in last 20 years and in trouble free
operation for at least 5 years8
161kV SF6 Live Tank Requirement is for CB of at least 132kV No. 100 50
Circuit Breakers manufactured in last 20 years and in trouble free
8
AIS Indoor Switchgears manufactured by Crompton Greeves and recently supplied to EDSA does not meet this
requirement and so EDSA shall not accept offers for indoor switchgears from this manufacturer
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section III – Evaluation and Qualification Criteria 64
Lot2
Steel Tubular Poles Requirement is for Steel Tubular Poles designed for No. 3,000 1,000
direct burial and capable of carrying at least 265
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section III - Evaluation and Qualification Criteria 65
Failure to comply with this requirement will result in rejection of the subcontractor.
In the case of a Bidder who offers to supply and install major items of supply under the
contract that the Bidder did not manufacture or otherwise produce, the Bidder shall provide
the manufacturer’s authorization, using the form provided in Section IV, showing that the
Bidder has been duly authorized by the manufacturer or producer of the related plant and
equipment or component to supply and install that item in the Employer’s Country. The
Bidder is responsible for ensuring that the manufacturer or producer complies with the
requirements of ITB 4 and 5 and meets the minimum criteria listed above for that item.
The items for which Manufacturer’s Authorization is required are the following:
• Power Transformers (161/33kV 35/40MVA, 33/11kV 20/26MVA)
• 161kV outdoor equipment (Circuit Breakers, Lightening Arrestors, Disconnect
Switches, Voltage Transformers, Current Transformers)
• 33kV outdoor equipment (Circuit Breakers, Lightening Arrestors, Disconnect
Switches, Voltage Transformers, Current Transformers)
• 33kV and 11kV indoor Air Insulated Switchgears
• 33kV and 11kV vacuum Circuit Breakers
• Protection relays and Bay Protection and Control Units (BCPUs)
• 33kV XLPE Cables
• 11kV XLPE Cables
• LV and Control Cables
• Lattice Towers
• Tubular Steel Poles
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section III – Evaluation and Qualification Criteria 66
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 67
Table of Forms
Letter of Bid........................................................................................................................... 70
Preamble ................................................................................................................................ 73
Price Schedules for Lot 1: Supply and Installation of 33/11kV Primary Substations in
Freetown ................................................................................................................................ 76
Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad ....................... 77
Schedule No. 2. Plant and Mandatory Spare Parts Supplied from Within the Employer’s
Country ............................................................................................................................... 94
Schedule No. 3. Design Services ..................................................................................... 110
Schedule No. 4. Installation and Other Services.............................................................. 111
Schedule No. 5. Grand Summary .................................................................................... 133
Schedule No. 6. Recommended Spare Parts .................................................................... 134
Price Schedules for Lot 2: Supply and Installation of 33 Sub Transmission Lines in
Freetown .............................................................................................................................. 135
Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad ..................... 136
Schedule No. 2. Plant and Mandatory Spare Parts Supplied from Within the Employer’s
Country ............................................................................................................................. 148
Schedule No. 3. Design Services ..................................................................................... 159
Schedule No. 4. Installation and Other Services.............................................................. 160
Schedule No. 5. Grand Summary .................................................................................... 174
Schedule No. 6. Recommended Spare Parts .................................................................... 175
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 68
Proposed Subcontractors for Major Items of Plant and Installation Services ............. 318
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 69
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 70
Letter of Bid
Date of this Bid submission: [insert date (as day, month and year) of Bid submission]
RFB No.: [insert number of RFB process]
Alternative No.:[insert identification No if this is a Bid for an alternative]
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 71
BDS 23.1 (as amended if applicable), and it shall remain binding upon us and may be
accepted at any time before the expiration of that period;
(h) Performance Security: If our Bid is accepted, we commit to obtain a Performance
Security in accordance with the bidding document;
(i) One Bid Per Bidder: We are not submitting any other Bid(s) as an individual Bidder,
and we are not participating in any other Bid(s) as a Joint Venture member, and meet
the requirements of ITB 4.3, other than alternative Bids submitted in accordance with
ITB 13;
(j) Suspension and Debarment: We, along with any of our subcontractors, suppliers,
consultants, manufacturers, or service providers for any part of the contract, are not
subject to, and not controlled by any entity or individual that is subject to, a temporary
suspension or a debarment imposed by the World Bank Group or a debarment imposed
by the World Bank Group in accordance with the Agreement for Mutual Enforcement
of Debarment Decisions between the World Bank and other development banks.
Further, we are not ineligible under the Employer’s Country laws or official regulations
or pursuant to a decision of the United Nations Security Council;
(k) State-owned enterprise or institution: [select the appropriate option and delete the
other] [We are not a state-owned enterprise or institution] / [We are a state-owned
enterprise or institution but meet the requirements of ITB 4.6];
(l) Commissions, gratuities and fees: We have paid, or will pay the following
commissions, gratuities, or fees with respect to the Bidding process or execution of the
Contract: [insert complete name of each Recipient, its full address, the reason for
which each commission or gratuity was paid and the amount and currency of each
such commission or gratuity]
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 72
(o) Fraud and Corruption: We hereby certify that we have taken steps to ensure that no
person acting for us or on our behalf engages in any type of Fraud and Corruption.
Name of the Bidder: *[insert complete name of person signing the Bid]
Name of the person duly authorized to sign the Bid on behalf of the Bidder: **[insert
complete name of person duly authorized to sign the Bid]
Title of the person signing the Bid: [insert complete title of the person signing the Bid]
Signature of the person named above: [insert signature of person whose name and
capacity are shown above]
Date signed [insert date of signing] day of [insert month], [insert year]
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 73
1. The Price Schedules are divided into separate Schedules (as per ITB 17.4) as follows:
Lot1: Supply and Installation of 33/11kV Primary Substations in Freetown (Lot 1)
Schedule No. 1 Plant and Equipment (including Mandatory Spare Parts) Supplied from
Abroad
Schedule No. 2 Plant and Equipment (including Mandatory Spare Parts) Supplied from
within the Employer’s Country
Schedule No. 3 Design Services
Schedule No. 4 Installation Services
Schedule No. 5 Grand Summary
Schedule No. 6 Recommended Spare Parts
Lot2: Supply and Installation of 33kV Sub transmission Lines in Freetown (Lot 1-2)
Schedule No. 1 Plant and Equipment (including Mandatory Spare Parts) Supplied from
Abroad
Schedule No. 2 Plant and Equipment (including Mandatory Spare Parts) Supplied from
within the Employer’s Country
Schedule No. 3 Design Services
Schedule No. 4 Installation Services
Schedule No. 5 Grand Summary
Schedule No. 6 Recommended Spare Parts
2. The Schedules do not generally give a full description of the plant and equipment to be
supplied and the services to be performed under each item. Bidders shall be deemed to
have read the Technical Specifications and other sections of the bidding documents and
reviewed the Drawings to ascertain the full scope of the requirements included in each
item prior to filling in the rates and prices. The entered rates and prices shall be deemed
to include for the full scope as aforesaid, including overheads and profit.
3. If bidders are unclear or uncertain as to the scope of any item, they shall seek clarification
in accordance with the Instructions to Bidders in the bidding documents prior to
submitting their bid.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 74
Pricing
4. Prices shall be filled in indelible ink, and the Bidder shall initial any alterations necessary
due to errors, etc.
As specified in the Bid Data Sheet and Special Conditions of Contract, prices shall be
fixed and firm for the duration of the Contract, or prices shall be subject to adjustment in
accordance with the corresponding Appendix (Price Adjustment) to the Contract
Agreement.
5. Bid prices shall be quoted in the manner indicated and, in the currencies, specified in the
Instructions to Bidders in the bidding documents.
For each item, bidders shall complete each appropriate column in the respective
Schedules, giving the price breakdown as indicated in the Schedules.
Prices given in the Schedules against each item shall be for the scope covered by that
item as detailed in the Technical Specifications, Drawings or elsewhere in the bidding
documents.
6. Where there are errors between the total of the amounts given under the column for the
price breakdown and the amount given under the Total Price, the former shall prevail,
and the latter will be corrected accordingly.
Where there are errors between the total of the amounts of Schedule Nos. 1 to 4 and the
amount given in Schedule No. 5 (Grand Summary), the former shall prevail, and the latter
will be corrected accordingly.
Where there are discrepancies between amounts stated in figures and amounts stated in
words, the amounts stated in words shall prevail.
7. Payments will be made to the Contractor in the currency or currencies indicated under
each respective item.
8. Items left blank will be deemed to have been included in other items. The TOTAL for
each Schedule and the TOTAL of the Grand Summary shall be deemed to be the total
price for executing the Facilities and sections thereof in complete accordance with the
Contract, whether or not each individual item has been priced.
9. When requested by the Employer for the purposes of making payments or part payments,
valuing variations or evaluating claims, or for such other purposes as the Employer may
reasonably require, the Contractor shall provide the Employer with a breakdown of any
composite or lump sum items included in the Schedules.
10. At the time the Contract is awarded, the Employer reserves the right to increase or
decrease the quantity of Plant and Installation Services originally specified in the Price
Schedules below, provided the change in the evaluated bid price does not exceed ±15%,
and without any change in the unit prices or other terms and conditions of the bid and the
Bidding Documents.
11. The guaranteed characteristics of the facilities to be supplied shall be indicated to confirm
the conformity and compatibility of the facilities.
12. Full compensation for furnishing all working drawings and As-Built drawings shall be
considered as included in prices paid for the contract items of work to which such
drawings relate and no additional compensation will be allowed thereof.
13. Bidders shall take note of the following in pricing for Schedule No. 1 of all lots
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 75
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 76
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 77
Unit
Total Price2
Qty Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
Schedule A: FREETOWN 161kV SUBSTATION (Please refer to relevant S/S drawings)
A1 161kV SWITCHYARD
161/33kV, 35/40MVA, ONAN/ONAF, YNyn0
A1.1 Transformer c/w On Load Tap Changer No 1
(OLTC), HV and LV Surge Arresters
161kV, 630A, 31.5 kA, 3s, SF6 Circuit Breaker
A1.2 with remote and local control (set of 3-phase) Set 1
c/w steel supporting structures
1
Bidders shall enter a code representing the country of origin of all imported plant and equipment.
2
Specify currency. Create and use as many columns for Unit Price and Total Price as there are currencies.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 78
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit
Total Price2
Qty Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
161kV Post Insulators c/w clamps, connectors,
A2.2 No 24
etc.
Connection to gantries: Conductors, clamps,
A2.3 Lot 1
insulators, earthing, etc.
Metering, Protection & Control Panel boards with control switches (Local/Remote, Close/Open), Alarm
A3 system, Digital Indication Metering (Ammeter, Voltmeter, Thermometer), Secondary Injection test
facilities etc. fully wired to include but not limited to the following:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 79
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit
Total Price2
Qty Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
33kV O/D 1250A, 25kA 3s Motorized Bus
A4.2 Isolator (set of 3-phase) with Earth Switch c/w Set 6
with support structures
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 80
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit
Total Price2
Qty Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
Upgrade and Extension of existing Substation
A7.2 Lightening protection system complete as per Lot 1
detailed Scope of Works
Upgrade and Extension of Existing Substation
A7.3
earthing system complete consisting of:
- 95sq. mm stranded bare cupper conductor m 600
- 30 x 3mm cupper flat tapes m 120
- 20mm diameter and 3.0 meters long earth
rods No 25
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 81
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit
Total Price2
Qty Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
Transformer Incomer Cubicle with 12kV,
2500A Vacuum Circuit Breaker c/w Current
Transformers, Protection Relays and
B2.1 No 2
Capacitive insulator with voltage indicator,
measuring equipment. etc. as per detailed
Scope of Works.
Feeder Cubicle with 12kV, 630A Vacuum
Circuit Breaker c/w Current Transformers,
Protection Relays, Controls and 3-Phase
B2.2 No 6
Ammeter and Capacitive insulator with voltage
indicator, measuring equipment. etc. as per
detailed Scope of Works.
Bus Sectionalizer Cubicle with 12kV, 2500A
Vacuum Circuit Breaker c/w Current
Transformers (two sets for bus differential
B2.3 No 1
protection), Protection Relays and controls,
measuring equipment. etc. as per detailed
Scope of Works.
Station Transformer Cubicle with 12kV, 630A
Vacuum Circuit Breaker c/w Current
Transformers, Protection Relays, Controls, 3-
B2.4 No 1
Phase Ammeter and Capacitive insulator with
voltage indicator, measuring equipment. etc. as
per detailed Scope of Works.
Measuring panel c/w Voltage transformer and
B2.5 Busbar earthing switch and measuring No 2
equipment. etc. as per detailed Scope of Works.
B3 TRANSFORMERS
33/11kV, 20/26MVA, ONAN/ONAF, Dyn11
Transformer c/w On-load tap changer (OLTC ±
B3.1 No 1
8 steps), HV and LV surge arresters, TPI and
AVR panel
Station Service Transformer: 11/0.4kV,
B3.2 100KVA, ONAN, Dyn11 c/w no-load tap No 1
changer ±2 steps, Outdoor
B4 AC AND DC SUPPLY
110V DC/100A Battery Charger, Rectifier
B4.1 No 2
complete with Redundancy system
110V DC 100Ah Battery Bank (Capacity to be
B4.2 No 2
enough for whole station)
Complete DC Distribution Panel with auto
B4.3 selection breaker to accommodate the two DC No 1
source. 100 A
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 82
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit
Total Price2
Qty Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
Complete AC Distribution Panel for Station
B4.4 Auxiliary supply 400/230V, 50Hz, 100A, 16 No 1
way
B5 POWER, AUXILIARY & CONTROL CABLES & ACCESSORIES
2
1Cx300mm 33kV, XLPE/SWA/PVC Cu to
B5.1 m 300
connect from B1.2 to B3.1
1Cx300mm2 33kV, XLPE/SWA/PVC Cu to
B5.2 connect from 1.1 to Freetown 161 Incomer m 480
Feeder
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 83
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit
Total Price2
Qty Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
complete
B6.4 Fire detection and protection system Lot 1
B7 HVAC
B7.1 5HP Free stand Type Split AC No 4
Schedule C: CLINE TOWN 33/11KV SUBSTATION (Please refer to relevant S/S drawings)
33KV SWITCHGEAR (33kV, 25kA for 3s, 1250A Single Bus bars, INDOOR METAL-CLAD
C1
SWITCHGEAR LINEUP COMPRISING :)
Line/Feeder Cubicle with 36kV, 1250A
Vacuum Motorized Circuit Breaker c/w
Current Transformers, Voltage transformer,
C1.1 Protection Relays, Controls, and 3-Phase No 4
Ammeter, Capacitive insulator with voltage
indicator, measuring equipment. etc. as per
detailed Scope of Works.
Transformer Cubicle with 36kV, 1250A
Vacuum Motorized Circuit Breaker c/w
Current Transformers, Voltage transformer,
Protection Relays and Controls, Multi-
C1.2 No 2
functional meter (A, V), 3-phase 4 - wire
Energy and KVA demand Meter, Capacitive
insulator with voltage indicator, measuring
equipment. etc. as per detailed Scope of Works.
Bus Sectionalizer Cubicle with 36kV, 1250A
Vacuum Motorized Circuit Breaker c/w
Current Transformers (two sets for bus
C1.3 No 1
differential protection), Protection Relays and
Controls, measuring equipment. etc. as per
detailed Scope of Works.
Measuring panel c/w Voltage transformer and
C1.4 Busbar earthing switch and measuring No 2
equipment. etc. as per detailed Scope of Works.
C2 TRANSFORMERS
33/11kV, 20/26MVA, ONAN/ONAF, Dyn11
Transformer c/w On-load tap changer (OLTC ±
C2.1 No 1
8 steps), HV and LV surge arresters, TPI and
AVR panel
C3 POWER, AUXILIARY & CONTROL CABLES & ACCESSORIES
2
1Cx300mm 33kV, XLPE/SWA/PVC Cu to
C3.1 m 300
connect from C1.2 to C3.1
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 84
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit
Total Price2
Qty Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
1Cx300mm2 33kV, XLPE/SWA/PVC Cu for
C3.2 m 1,200
connection to feeders
33kV Cable single core Termination kits (set of
C3.3 No 10
3-phase, 300mm2)
Cables for auxiliary Systems c/w Terminations
C3.4 Lot 1
& Markings
Protection & Control Cables C/W Terminations
C3.5 Lot 1
& Markings
Schedule D: FALCON BRIDGE 33/11KV SUBSTATION (Please refer to relevant S/S drawings)
33KV SWITCHGEAR (33kV, 25kA for 3s, 1250A Single Bus bars, INDOOR METAL-CLAD
D1
SWITCHGEAR LINEUP COMPRISING :)
Line/Feeder Cubicle with 36kV, 1250A
Vacuum Motorized Circuit Breaker c/w
Current Transformers, Voltage transformer,
D1.1 Protection Relays, Controls, and 3-Phase No 4
Ammeter, Capacitive insulator with voltage
indicator, measuring equipment. etc. as per
detailed Scope of Works.
Transformer Cubicle with 36kV, 1250A
Vacuum Motorized Circuit Breaker c/w
Current Transformers, Voltage transformer,
Protection Relays and Controls, Multi-
D1.2 No 2
functional meter (A, V), 3-phase 4 - wire
Energy and KVA demand Meter, Capacitive
insulator with voltage indicator, measuring
equipment. etc. as per detailed Scope of Works.
Bus Sectionalizer Cubicle with 36kV, 1250A
Vacuum Motorized Circuit Breaker c/w
Current Transformers (two sets for bus
D1.3 No 1
differential protection), Protection Relays and
Controls, measuring equipment. etc. as per
detailed Scope of Works.
Measuring panel c/w Voltage transformer and
D1.4 Busbar earthing switch and measuring No 2
equipment. etc. as per detailed Scope of Works.
D2 TRANSFORMERS
33/11kV, 20/26MVA, ONAN/ONAF, Dyn11
Transformer c/w On-load tap changer (OLTC ±
D2.1 No 1
8 steps), HV and LV surge arresters, TPI and
AVR panel
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 85
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit
Total Price2
Qty Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
D3 AC AND DC SUPPLY
110V DC/100A Battery Charger, Rectifier
D3.1 complete to be coupled as Redundancy with No 1
existing DC system
110V DC 100Ah Battery Bank (Capacity to be
D3.2 No 1
enough for whole station)
D3.3 Complete DC Distribution Panel, 100 A No 1
Complete AC Distribution Panel for Station
D3.4 Auxiliary supply 400/230V, 50Hz, 100A, 16 No 1
way
D4 POWER, AUXILIARY & CONTROL CABLES & ACCESSORIES
2
1Cx300mm 33kV, XLPE/SWA/PVC Cu to
D4.1 m 450
connect from D1.2 to D2.1
1Cx300mm2 33kV XLPE/SWA/PVC Cu for
D4.2 m 1,200
connection to feeders
1Cx300mm2 11kV, XLPE/SWA/PVC Cu (laid
4 cores per phase) from D2.1 to existing 11kV
D4.3 m 600
switchgear transformer incomer (Only one
transformer to be connected in this contract)
33kV Cable single core Termination kits (set of
D4.4 No 10
3-phase, 300mm2)
11kV Cable single core Termination kits (set of
D4.5 No 8
3-phase, 300mm2)
Cables for auxiliary Systems c/w Terminations
D4.6 Lot 1
& Markings
Protection & Control Cables C/W Terminations
D4.7 Lot 1
& Markings
D5 MISCELLANEOUS WORKS
Substation Earth grid complete to be meshed
D5.1 Lot 1
with existing
D5.2 Outdoor lighting for switchyard Lot 1
Substation Lightening protection system
D5.3 Lot 1
complete
D5.4 Fire detection and protection system Lot 1
D6 HVAC
D6.1 5HP Free stand Type Split AC No 4
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 86
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit
Total Price2
Qty Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 87
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit
Total Price2
Qty Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
Feeder Cubicle with 12kV, 630A Vacuum
Circuit Breaker c/w Current Transformers,
Protection Relays, Controls and 3-Phase
E2.2 No 8
Ammeter and Capacitive insulator with voltage
indicator, measuring equipment. etc. as per
detailed Scope of Works.
Bus Sectionalizer Cubicle with 12kV, 2500A
Vacuum Circuit Breaker c/w Current
Transformers (two sets for bus differential
E2.3 No 1
protection), Protection Relays and controls,
measuring equipment. etc. as per detailed
Scope of Works.
Station Transformer Cubicle with 12kV, 630A
Vacuum Circuit Breaker c/w Current
Transformers, Protection Relays, Controls, 3-
E2.4 No 1
Phase Ammeter and Capacitive insulator with
voltage indicator, measuring equipment. etc. as
per detailed Scope of Works.
Measuring panel c/w Voltage transformer and
E2.5 Busbar earthing switch and measuring No 2
equipment. etc. as per detailed Scope of Works.
E3 TRANSFORMERS
33/11kV, 20/26MVA, ONAN/ONAF, Dyn11
Transformer c/w On-load tap changer (OLTC ±
E3.1 No 1
8 steps), HV and LV surge arresters, TPI and
AVR panel
Station Service Transformer: 11/0.4kV,
E3.2 100KVA, ONAN, Dyn11 c/w no-load tap No 1
changer ±2 steps, Outdoor
E4 AC AND DC SUPPLY
110V DC/100A Battery Charger, Rectifier
E4.1 No 2
complete with Redundancy system
110V DC 100Ah Battery Bank (Capacity to be
E4.2 No 2
enough for whole station)
Complete DC Distribution Panel with auto
E4.3 selection breaker to accommodate the two DC No 1
source. 100 A
Complete AC Distribution Panel for Station
E4.4 Auxiliary supply 400/230V, 50Hz, 100A, 16 No 1
way
E5 POWER, AUXILIARY & CONTROL CABLES & ACCESSORIES
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 88
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit
Total Price2
Qty Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
1Cx300mm2 33kV, XLPE/SWA/PVC Cu to
E5.1 m 300
connect from E1.2 to E3.1
1Cx300mm2 33kV XLPE/SWA/PVC Cu for
E5.2 m 1,800
connection to feeders
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 89
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit
Total Price2
Qty Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 90
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit
Total Price2
Qty Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
Feeder Cubicle with 12kV, 630A Vacuum
Circuit Breaker c/w Current Transformers,
Protection Relays, Controls and 3-Phase
F2.2 No 8
Ammeter and Capacitive insulator with voltage
indicator, measuring equipment. etc. as per
detailed Scope of Works.
Bus Sectionalizer Cubicle with 12kV, 2500A
Vacuum Circuit Breaker c/w Current
Transformers (two sets for bus differential
F2.3 No 1
protection), Protection Relays and controls,
measuring equipment. etc. as per detailed
Scope of Works.
Station Transformer Cubicle with 12kV, 630A
Vacuum Circuit Breaker c/w Current
Transformers, Protection Relays, Controls, 3-
F2.4 No 1
Phase Ammeter and Capacitive insulator with
voltage indicator, measuring equipment. etc. as
per detailed Scope of Works.
Measuring panel c/w Voltage transformer and
F2.5 Busbar earthing switch and measuring No 2
equipment. etc. as per detailed Scope of Works.
F3 TRANSFORMERS
33/11kV, 20/26MVA, ONAN/ONAF, Dyn11
Transformer c/w On-load tap changer (OLTC ±
F3.1 No 1
8 steps), HV and LV surge arresters, TPI and
AVR panel
Station Service Transformer: 11/0.4kV,
F3.2 100KVA, ONAN, Dyn11 c/w no-load tap No 1
changer ±2 steps, Outdoor
F4 AC AND DC SUPPLY
110V DC/100A Battery Charger, Rectifier
F4.1 No 2
complete with Redundancy system
110V DC 100Ah Battery Bank (Capacity to be
F4.2 No 2
enough for whole station)
Complete DC Distribution Panel Complete
F4.3 with auto selection breaker to accommodate the No 1
two DC source. 100 A
Complete AC Distribution Panel for Station
F4.4 Auxiliary supply 400/230V, 50Hz, 100A, 16 No 1
way
F5 POWER, AUXILIARY & CONTROL CABLES & ACCESSORIES
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 91
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit
Total Price2
Qty Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
1Cx300mm2 33kV, XLPE/SWA/PVC Cu to
F5.1 m 300
connect from F1.2 to F3.1
1Cx300mm2 33kV XLPE/SWA/PVC Cu for
F5.2 m 1,800
connection to feeders
1Cx300mm2 11kV, XLPE/SWA/PVC Cu (laid
F5.3 4 cores per phase) from F3.1 to F2.1 (Only one m 600
transformer to be connected in this contract)
3Cx240mm2 11kV XLPE/SWA/PVC Cu for
F5.4 m 800
connection to feeders
3Cx70mm2 11kV XLPE/SWA/PVC Cu for
F5.5 m 70
connection to Station Transformer
4Cx70mm2 0.4kV XLPE/SWA/PVC Cu for
F5.6 m 100
connection to Station Transformer to LV panel
33kV Cable single core Termination kits (set of
F5.7 No 14
3-phase, 240mm2)
11kV Cable Termination kits (set of 3-phase,
F5.8 No 16
240mm2)
11kV Cable single core Termination kits (set of
F5.9 No 8
3-phase, 300mm2)
11kV Cable Termination kits (set of 3-phase,
F5.10 No 2
70mm2)
0.4kV Cable Termination kits (set of 3-phase,
F5.11 No 2
70mm2)
Cables for auxiliary Systems c/w Terminations
F5.12 Lot 1
& Markings
Protection & Control Cables C/W Terminations
F5.13 Lot 1
& Markings
F6 MISCELLANEOUS WORKS
F6.1 Substation Earth grid complete Lot 1
F6.2 Outdoor lighting for switchyard Lot 1
Substation Lightening protection system
F6.3 Lot 1
complete
F6.4 Fire detection and protection system Lot 1
F7 HVAC
F7.1 5HP Free stand Type Split AC No 4
Sub-Total (Schedule F) carried to Summary
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 92
1 Bidders shall enter a code representing the country of origin of all imported plant and equipment.
2 Specify currency. Create and use as many columns for Unit Price and Total Price as there are currencies.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 93
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 94
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 95
SCHEDULE No. 2: Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 96
SCHEDULE No. 2: Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
A5 AC AND DC SUPPLY
A5.1 DC Distribution Panel 110V DC No 1
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 97
SCHEDULE No. 2: Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 98
SCHEDULE No. 2: Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 99
SCHEDULE No. 2: Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Schedule C: CLINE TOWN 33/11KV SUBSTATION (Please refer to relevant S/S drawings)
33KV SWITCHGEAR (33kV, 25kA for 3s, 1250A Single Bus bars, INDOOR METAL-CLAD
C1
SWITCHGEAR LINEUP COMPRISING :)
Line/Feeder Cubicle with 36kV, 1250A Vacuum
Motorized Circuit Breaker c/w Current
Transformers, Voltage transformer, Protection
C1.1 No 4
Relays, Controls, and 3-Phase Ammeter, Capacitive
insulator with voltage indicator, measuring
equipment. etc. as per detailed Scope of Works.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 100
SCHEDULE No. 2: Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Schedule D: FALCON BRIDGE 33/11KV SUBSTATION (Please refer to relevant S/S drawings)
33KV SWITCHGEAR (33kV, 25kA for 3s, 1250A Single Bus bars, INDOOR METAL-CLAD
D1
SWITCHGEAR LINEUP COMPRISING :)
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 101
SCHEDULE No. 2: Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
D3 AC AND DC SUPPLY
110V DC/100A Battery Charger, Rectifier complete
D3.1 to be coupled as Redundancy with existing DC No 1
system
110V DC 100Ah Battery Bank (Capacity to be
D3.2 No 1
enough for whole station)
D3.3 Complete DC Distribution Panel, 100 A No 1
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 102
SCHEDULE No. 2: Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 103
SCHEDULE No. 2: Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 104
SCHEDULE No. 2: Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 105
SCHEDULE No. 2: Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 106
SCHEDULE No. 2: Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 107
SCHEDULE No. 2: Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 108
SCHEDULE No. 2: Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 109
1 Specify currency in accordance with specifications in Bid Data Sheet under ITB 18.1
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 110
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 111
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 112
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
For Transformer Panel: Protection: 87T, 50/51,
50N/51N, Automatic Voltage Regulator (AVR),
auxiliary relays and secondary injection test
A3.1 Set 1
facilities for the 161/33kV, 35/40MVA Power
Transformers, Multi-functional meter, 3-phase 4
- wire Energy and KVA demand Meter etc.
For 33kV Line Panels: Protection: 67/50/51,
67N/50N/51N, 79 and secondary test injection
A3.2 Set 3
facilities, Multi-functional meter, 3-phase 4 -
wire Energy Meter
For 33kV Bus Section Panel: Protection:
87/67/50/51, 67N/50N/51N, 79 and secondary
A3.3 Set 1
test injection facilities, Multi-functional meter,
3-phase 4 - wire Energy Meter
33kV Low Impedance type bus bar protection
(LIBBP) with integrated Breaker Fail Protection,
A3.4 Set 1
3-phase OC and EF protection and under and
over voltage protection relays
Settlement metering system for the new 33kV
A3.5 incomer from new 161/33kV Power Lot 1
Transformer.
Integration of Protection system with existing
A3.6 system, Control & Auxiliary Cable Systems Lot 1
(Including Terminations & Markings)
Upgrade and extension of existing Substation
A3.7 Event and Data Recording System as per Lot 1
detailed Scope of Works
A4 33kV SWITCHYARD
33kV O/D 1250A, 25kA 3s Motorized Line
A4.1 Isolator (set of 3-phase) with Earth Switch c/w Set 4
with support structures
33kV O/D 1250A, 25kA 3s Motorized Bus
A4.2 Isolator (set of 3-phase) with Earth Switch c/w Set 6
with support structures
33kV O/D 1250A, 25kA 3s SF6 Circuit Breaker
A4.3 with remote and local control (set of 3-phase) Set 5
c/w with support structures
33kV O/D Current Transformer (set of 3-phase)
A4.4 Set 6
(400-800/1/1/1A) c/w support structures
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 113
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
33kV O/D Voltage Transformer (set of 3-phase)
A4.5 Set 1
c/w support structures
33kV O/D 1250A, 25kA, 3s Rigid Bus bar c/w
A4.6 Set 1
Support Structure
33kV O/D Surge Arrester (set of 3-phase) c/w all
A4.7 Set 5
accessories
33kV Post Insulators c/w clamps, connectors,
A4.8 No 40
etc.
A5 AC AND DC SUPPLY
A5.1 DC Distribution Panel 110V DC No 1
A5.2 AC Distribution Panel, 100A, 230/400 V - 50Hz No 1
A6 POWER, AUXILIARY & CONTROL CABLES & ACCESSORIES
2
300mm 33kV, single core XLPE/SWA/PVC Cu
A6.1 (laid 1 core per phase) to connect feeders to the m 900
OH Line feeders
300mm2 33kV, single core XLPE/SWA/PVC Cu
A6.2 (laid 2 cores per phase) to connect item A1.1 to m 150
item A4.1
33kV Cable Termination kits (set of 1-phase,
A6.3 No 30
300mm2)
Cables for auxiliary Systems c/w Terminations
A6.4 Lot 1
& Markings
Protection & Control Cables C/W Terminations
A6.5 Lot 1
& Markings
A7 MISCELLANEOUS WORKS
Upgrade and Extension of existing Outdoor
A7.1 lighting for switchyard as per detailed Scope of Lot 1
Works
Upgrade and Extension of existing Substation
A7.2 Lightening protection system complete as per Lot 1
detailed Scope of Works
Upgrade and Extension of Existing Substation
A7.3
earthing system complete consisting of:
- 95sq. mm stranded bare cupper conductor m 600
- 30 x 3mm cupper flat tapes m 120
- 20mm diameter and 3.0 meters long earth
No 25
rods
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 114
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
A8 CIVIL WORKS
A8.1 Substation Embankment Works
Demolishing of old equipment foundation &
A81.1. m3 20
structures and removal of debris from site
Excavate top soil from site and haul to spoil
A8.1.2 m3 150
heaps or dispose as directed
Excavate in any material except rock and haul to
A8.1.3 m3 150
spoil heaps or dispose as directed
Provide, lay and compact to any specified depth
A8.1.4 approved fill material in substation embankment m3 225
not exceeding 150mm thickness per layer.
A8.1.5 Outdoor Cable Trench with Concrete covers m 75
Supply and spreading of 40-60mm chippings of
A8.1.6 m3 55
100mm thickness to cover substation
Equipment Foundations including designs, excavation, rebar works, formwork, lean concrete, concrete,
A8.2
backfilling and compacting for the:
161/33kV, 35/40MVA Power Transformer
A8.2.1 No 1
including Firewall and Oil collection pit
A8.2.2 161kV, 630A, 31.5 kA, 3s, SF6 Circuit Breaker No 1
161kV, 1250A, 31.5kA, 3s disconnect with
A8.2.3 No 1
switch
161kV, 1250A, 31.5kA, 3s Pantograph break
A8.2.4 Set 2
disconnect (set of 3 phase)
A8.2.5 161kV O/D Current Transformer No 1
A8.2.6 161kV Voltage Transformers No 1
A8.2.7 161kV Surge Arrester (set of 3-phase) No 1
A8.2.8 161kV Post Insulators Lot 1
33kV O/D 1250A, 25kA 1s Motorized Line
A8.2.9 No 7
Isolator with Earth Switch
A8.2.10 33kV O/D 1250A, 25kA 1s SF6 Circuit Breaker No 5
A8.2.11 33kV O/D Current Transformer No 6
33kV O/D Voltage Transformer (set of 3-phase)
A8.2.12 No 1
c/w support structures
33kV O/D 1250A, 25kA, 1s Motorized Bus
A8.2.13 No 3
Isolator
A8.2.14 33kV O/D Surge Arrester No 5
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 115
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
A8.2.15 33kV Post Insulators (set of 3-phase) Lot 1
Sub-Total (Schedule A) carried to Summary
Schedule B: ABERDEEN 33/11KV SUBSTATION (Please refer to relevant S/S drawings)
33KV SWITCHGEAR (33kV, 25kA for 3s, 1250A Single Bus bars, INDOOR METAL-CLAD
B1
SWITCHGEAR LINEUP COMPRISING :)
Line/Feeder Cubicle with 36kV, 1250A Vacuum
Motorized Circuit Breaker c/w Current
Transformers, Voltage transformer, Protection
B1.1 Relays, Controls, and 3-Phase Ammeter, No 2
Capacitive insulator with voltage indicator,
measuring equipment. etc. as per detailed Scope
of Works.
Transformer Cubicle with 36kV, 1250A Vacuum
Motorized Circuit Breaker c/w Current
Transformers, Voltage transformer, Protection
Relays and Controls, Multi-functional meter (A,
B1.2 No 2
V), 3-phase 4 - wire Energy and KVA demand
Meter, Capacitive insulator with voltage
indicator, measuring equipment. etc. as per
detailed Scope of Works.
Bus Sectionalizer Cubicle with 36kV, 1250A
Vacuum Motorized Circuit Breaker c/w Current
Transformers (two sets for bus differential
B1.3 No 1
protection), Protection Relays and Controls,
measuring equipment. etc. as per detailed Scope
of Works.
Measuring panel c/w Voltage transformer and
B1.4 Busbar earthing switch and measuring No 2
equipment. etc. as per detailed Scope of Works.
11KV SWITCHGEAR (11kV, 25kA for 3s, 2500A Single Bus bars, INDOOR METAL-CLAD
B2
SWITCHGEAR LINEUP COMPRISING :)
Transformer Incomer Cubicle with 12kV, 2500A
Vacuum Circuit Breaker c/w Current
B2.1 Transformers, Protection Relays and Capacitive No 2
insulator with voltage indicator, measuring
equipment. etc. as per detailed Scope of Works.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 116
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
Feeder Cubicle with 12kV, 630A Vacuum
Circuit Breaker c/w Current Transformers,
Protection Relays, Controls and 3-Phase
B2.2 No 6
Ammeter and Capacitive insulator with voltage
indicator, measuring equipment. etc. as per
detailed Scope of Works.
Bus Sectionalizer Cubicle with 12kV, 2500A
Vacuum Circuit Breaker c/w Current
Transformers (two sets for bus differential
B2.3 No 1
protection), Protection Relays and controls,
measuring equipment. etc. as per detailed Scope
of Works.
Station Transformer Cubicle with 12kV, 630A
Vacuum Circuit Breaker c/w Current
Transformers, Protection Relays, Controls, 3-
B2.4 No 1
Phase Ammeter and Capacitive insulator with
voltage indicator, measuring equipment. etc. as
per detailed Scope of Works.
Measuring panel c/w Voltage transformer and
B2.5 Busbar earthing switch and measuring No 2
equipment. etc. as per detailed Scope of Works.
B3 TRANSFORMERS
33/11kV, 20/26MVA, ONAN/ONAF, Dyn11
Transformer c/w On-load tap changer (OLTC ±
B3.1 No 1
8 steps), HV and LV surge arresters, TPI and
AVR panel
Station Service Transformer: 11/0.4kV,
B3.2 100KVA, ONAN, Dyn11 c/w no-load tap No 1
changer ±2 steps, Outdoor
B4 AC AND DC SUPPLY
110V DC/100A Battery Charger, Rectifier
B4.1 No 2
complete with Redundancy system
110V DC 100Ah Battery Bank (Capacity to be
B4.2 No 2
enough for whole station)
Complete DC Distribution Panel with auto
B4.3 selection breaker to accommodate the two DC No 1
source. 100 A
Complete AC Distribution Panel for Station
B4.4 Auxiliary supply 400/230V, 50Hz, 100A, 16 No 1
way
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 117
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
B5 POWER, AUXILIARY & CONTROL CABLES & ACCESSORIES
1Cx300mm2 33kV, XLPE/SWA/PVC Cu to
B5.1 m 300
connect from B1.2 to B3.1
1Cx300mm2 33kV, XLPE/SWA/PVC Cu to
B5.2 connect from 1.1 to Freetown 161 Incomer m 480
Feeder
1Cx300mm2 11kV, XLPE/SWA/PVC Cu (laid 4
B5.3 cores per phase) from B3.1 to B2.1 (Only one m 600
transformer to be connected in this contract)
3Cx240mm2 11kV XLPE/SWA/PVC Cu for
B5.4 m 900
connection to feeders
3Cx70mm2 11kV XLPE/SWA/PVC Cu for
B5.5 m 70
connection to Station Transformer
4Cx70mm2 0.4kV XLPE/SWA/PVC Cu for
B5.6 m 100
connection to Station Transformer to LV panel
33kV Cable single core Termination kits (set of
B5.7 No 4
3-phase, 300mm2)
11kV Cable Termination kits (set of 3-phase,
B5.8 No 12
240mm2)
11kV Cable single core Termination kits (set of
B5.9 No 8
3--phase, 300mm2)
11kV Cable Termination kits (set of 3-phase,
B5.10 No 2
70mm2)
0.4kV Cable Termination kits (set of 3-phase,
B5.11 No 2
70mm2)
Cables for auxiliary Systems c/w Terminations
B5.12 Lot 1
& Markings
Protection & Control Cables C/W Terminations
B5.13 Lot 1
& Markings
B6 MISCELLANEOUS WORKS
B6.1 Substation Earth grid complete Lot 1
B6.2 Outdoor lighting for switchyard Lot 1
Substation Lightening protection system
B6.3 Lot 1
complete
B6.4 Fire detection and protection system Lot 1
B7 HVAC
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 118
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
B7.1 5HP Free stand Type Split AC No 4
B8 CIVIL WORKS
B8.1 Substation Embankment Works
Demolishing of old equipment foundation &
B81.1. m3 15
structures and removal of debris from site
Excavate top soil from site and haul to spoil
B8.1.2 m3 200
heaps or dispose as directed
Excavate in any material except rock and haul to
B8.1.3 m3 400
spoil heaps or dispose as directed
Provide, lay and compact to any specified depth
B8.1.4 approved fill material in substation embankment m3 600
not exceeding 150mm thickness per layer.
Substation Perimeter Drainage System, Lump
B8.1.5 LS 1
Sum
Perimeter Fencing (Block Wall) as per detailed
B8.1.6 m 150
Scope of Works
B8.1.7 Outdoor Cable Trench with Concrete covers m 45
Supply and spreading of 40-60mm chippings of
B8.1.8 m3 55
100mm thickness to cover substation
B8.2 Substation Buildings
Construct New Substation Building (ref. Dwg
B8.2.1 LS 1
No. ESURP/AF/ABN/02), Lump Sum
Construct New Customer Service Building (ref.
B8.2.2 Dwg No. ESURP-AF-ABN-02), Lump Sum per LS 1
Substation
Lighting & Small Power Electrical Installation
B8.2.3 LS 1
Lump Sum per Substation
Mechanical Installation (cold water, sewage,
B8.2.4 LS 1
sanitary appliances) Lump Sum per Substation
Equipment Foundations including designs, excavation, rebar works, formwork, lean concrete, concrete,
B8.3
backfilling and compacting for the:
33/11kV, 20/26MVA Power Transformer
B8.3.1 including Firewall, Oil collection pit and Chain No 1
link fence
11/0.4kV, 100KVA Station Service Transformer
B8.3.2 No 1
including Oil collection pit and Chain link fence
B8.4 Road Works
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 119
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
Construction of 10m x75m bitumen surface
B8.4.1 access road from the main highway to Aberdeen Lot 1
Substation site
Construction of internal road and parking space
B8.4.2 Lot 1
(ref. Dwg. No. ESURP/AF/ABN/02)
Sub-Total (Schedule B) carried to Summary
Schedule C: CLINE TOWN 33/11KV SUBSTATION (Please refer to relevant S/S drawings)
33KV SWITCHGEAR (33kV, 25kA for 3s, 1250A Single Bus bars, INDOOR METAL-CLAD
C1
SWITCHGEAR LINEUP COMPRISING :)
Line/Feeder Cubicle with 36kV, 1250A Vacuum
Motorized Circuit Breaker c/w Current
Transformers, Voltage transformer, Protection
C1.1 Relays, Controls, and 3-Phase Ammeter, No 4
Capacitive insulator with voltage indicator,
measuring equipment. etc. as per detailed Scope
of Works.
Transformer Cubicle with 36kV, 1250A Vacuum
Motorized Circuit Breaker c/w Current
Transformers, Voltage transformer, Protection
Relays and Controls, Multi-functional meter (A,
C1.2 No 2
V), 3-phase 4 - wire Energy and KVA demand
Meter, Capacitive insulator with voltage
indicator, measuring equipment. etc. as per
detailed Scope of Works.
Bus Sectionalizer Cubicle with 36kV, 1250A
Vacuum Motorized Circuit Breaker c/w Current
Transformers (two sets for bus differential
C1.3 No 1
protection), Protection Relays and Controls,
measuring equipment. etc. as per detailed Scope
of Works.
Measuring panel c/w Voltage transformer and
C1.4 Busbar earthing switch and measuring No 2
equipment. etc. as per detailed Scope of Works.
C2 TRANSFORMERS
33/11kV, 20/26MVA, ONAN/ONAF, Dyn11
Transformer c/w On-load tap changer (OLTC ±
C2.1 No 1
8 steps), HV and LV surge arresters, TPI and
AVR panel
C3 POWER, AUXILIARY & CONTROL CABLES & ACCESSORIES
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 120
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
1Cx300mm2 33kV, XLPE/SWA/PVC Cu to
C3.1 m 300
connect from C1.2 to C3.1
1Cx300mm2 33kV, XLPE/SWA/PVC Cu for
C3.2 m 1,200
connection to feeders
33kV Cable single core Termination kits (set of
C3.3 No 10
3-phase, 300mm2)
Cables for auxiliary Systems c/w Terminations
C3.4 Lot 1
& Markings
Protection & Control Cables C/W Terminations
C3.5 Lot 1
& Markings
Sub-Total (Schedule C) carried to Summary
Schedule D: FALCON BRIDGE 33/11KV SUBSTATION (Please refer to relevant S/S drawings)
33KV SWITCHGEAR (33kV, 25kA for 3s, 1250A Single Bus bars, INDOOR METAL-CLAD
D1
SWITCHGEAR LINEUP COMPRISING :)
Line/Feeder Cubicle with 36kV, 1250A Vacuum
Motorized Circuit Breaker c/w Current
Transformers, Voltage transformer, Protection
D1.1 Relays, Controls, and 3-Phase Ammeter, No 4
Capacitive insulator with voltage indicator,
measuring equipment. etc. as per detailed Scope
of Works.
Transformer Cubicle with 36kV, 1250A Vacuum
Motorized Circuit Breaker c/w Current
Transformers, Voltage transformer, Protection
Relays and Controls, Multi-functional meter (A,
D1.2 No 2
V), 3-phase 4 - wire Energy and KVA demand
Meter, Capacitive insulator with voltage
indicator, measuring equipment. etc. as per
detailed Scope of Works.
Bus Sectionalizer Cubicle with 36kV, 1250A
Vacuum Motorized Circuit Breaker c/w Current
Transformers (two sets for bus differential
D1.3 No 1
protection), Protection Relays and Controls,
measuring equipment. etc. as per detailed Scope
of Works.
Measuring panel c/w Voltage transformer and
D1.4 Busbar earthing switch and measuring No 2
equipment. etc. as per detailed Scope of Works.
D2 TRANSFORMERS
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 121
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
33/11kV, 20/26MVA, ONAN/ONAF, Dyn11
Transformer c/w On-load tap changer (OLTC ±
D2.1 No 1
8 steps), HV and LV surge arresters, TPI and
AVR panel
D3 AC AND DC SUPPLY
110V DC/100A Battery Charger, Rectifier
D3.1 complete to be coupled as Redundancy with No 1
existing DC system
110V DC 100Ah Battery Bank (Capacity to be
D3.2 No 1
enough for whole station)
D3.3 Complete DC Distribution Panel, 100 A No 1
Complete AC Distribution Panel for Station
D3.4 Auxiliary supply 400/230V, 50Hz, 100A, 16 No 1
way
D4 POWER, AUXILIARY & CONTROL CABLES & ACCESSORIES
1Cx300mm2 33kV, XLPE/SWA/PVC Cu to
D4.1 m 450
connect from D1.2 to D2.1
1Cx300mm2 33kV XLPE/SWA/PVC Cu for
D4.2 m 1,200
connection to feeders
1Cx300mm2 11kV, XLPE/SWA/PVC Cu (laid 4
cores per phase) from D2.1 to existing 11kV
D4.3 m 600
switchgear transformer incomer (Only one
transformer to be connected in this contract)
33kV Cable single core Termination kits (set of
D4.4 No 10
3-phase, 300mm2)
11kV Cable single core Termination kits (set of
D4.5 No 8
3-phase, 300mm2)
Cables for auxiliary Systems c/w Terminations
D4.6 Lot 1
& Markings
Protection & Control Cables C/W Terminations
D4.7 Lot 1
& Markings
D5 MISCELLANEOUS WORKS
Substation Earth grid complete to be meshed
D5.1 Lot 1
with existing
D5.2 Outdoor lighting for switchyard Lot 1
Substation Lightening protection system
D5.3 Lot 1
complete
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 122
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
D5.4 Fire detection and protection system Lot 1
D6 HVAC
D6.1 5HP Free stand Type Split AC No 4
D8 CIVIL WORKS
D8.1 Substation Embankment Works
Demolishing of old equipment foundation &
D81.1. m3 100
structures and removal of debris from site
Excavate top soil from site and haul to spoil
D8.1.2 m3 200
heaps or dispose as directed
Excavate in any material except rock and haul to
D8.1.3 m3 400
spoil heaps or dispose as directed
Provide, lay and compact to any specified depth
D8.1.4 approved fill material in substation embankment m3 600
not exceeding 150mm thickness per layer.
Substation Perimeter Drainage System, Lump
D8.1.5 LS 1
Sum
Perimeter Fencing (Chain Link) as per detailed
D8.1.6 m 150
Scope of Works
D8.1.7 Outdoor Cable Trench with Concrete covers m 45
Supply and spreading of 40-60mm chippings of
D8.1.8 m3 55
100mm thickness to cover substation
D8.2 Substation Buildings
Construct New 33kV Switchgear Substation
D8.2.1 Building (ref. Dwg No. ESURP/AF/FB/02 and LS 1
ESURP/AF/FB/03), Lump Sum per Substation
Lighting & Small Power Electrical Installation
D8.2.2 LS 1
Lump Sum per Substation
Mechanical Installation (cold water, sewage,
D8.2.3 LS 1
sanitary appliances) Lump Sum per Substation
Equipment Foundations including designs, excavation, rebar works, formwork, lean concrete, concrete,
D8.3
backfilling and compacting for the:
33/11kV, 20/26MVA Power Transformer
D8.3.1 including Firewall, Oil collection pit and Chain No 1
link fence
11/0.4kV, 100KVA Station Service Transformer
D8.3.2 No 1
including Oil collection pit and Chain link fence
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 123
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
D8.4 Road Works
Construction of 10m x75m bitumen surface
D8.4.1 access road from the main highway to Aberdeen Lot 1
Substation site
D8.4.2 Construction of internal road and parking space Lot 1
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 124
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
Measuring panel c/w Voltage transformer and
E1.5 Busbar earthing switch and measuring No 3
equipment. etc. as per detailed Scope of Works.
11KV SWITCHGEAR (11kV, 25kA for 3s, 2500A Single Bus bars, INDOOR METAL-CLAD
E2
SWITCHGEAR LINEUP COMPRISING :)
Transformer Incomer Cubicle with 12kV, 2500A
Vacuum Circuit Breaker c/w Current
E2.1 Transformers, Protection Relays and Capacitive No 2
insulator with voltage indicator, measuring
equipment. etc. as per detailed Scope of Works.
Feeder Cubicle with 12kV, 630A Vacuum
Circuit Breaker c/w Current Transformers,
Protection Relays, Controls and 3-Phase
E2.2 No 8
Ammeter and Capacitive insulator with voltage
indicator, measuring equipment. etc. as per
detailed Scope of Works.
Bus Sectionalizer Cubicle with 12kV, 2500A
Vacuum Circuit Breaker c/w Current
Transformers (two sets for bus differential
E2.3 No 1
protection), Protection Relays and controls,
measuring equipment. etc. as per detailed Scope
of Works.
Station Transformer Cubicle with 12kV, 630A
Vacuum Circuit Breaker c/w Current
Transformers, Protection Relays, Controls, 3-
E2.4 No 1
Phase Ammeter and Capacitive insulator with
voltage indicator, measuring equipment. etc. as
per detailed Scope of Works.
Measuring panel c/w Voltage transformer and
E2.5 Busbar earthing switch and measuring No 2
equipment. etc. as per detailed Scope of Works.
E3 TRANSFORMERS
33/11kV, 20/26MVA, ONAN/ONAF, Dyn11
Transformer c/w On-load tap changer (OLTC ±
E3.1 No 1
8 steps), HV and LV surge arresters, TPI and
AVR panel
Station Service Transformer: 11/0.4kV,
E3.2 100KVA, ONAN, Dyn11 c/w no-load tap No 1
changer ±2 steps, Outdoor
E4 AC AND DC SUPPLY
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 125
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
110V DC/100A Battery Charger, Rectifier
E4.1 No 2
complete with Redundancy system
110V DC 100Ah Battery Bank (Capacity to be
E4.2 No 2
enough for whole station)
Complete DC Distribution Panel with auto
E4.3 selection breaker to accommodate the two DC No 1
source. 100 A
Complete AC Distribution Panel for Station
E4.4 Auxiliary supply 400/230V, 50Hz, 100A, 16 No 1
way
E5 POWER, AUXILIARY & CONTROL CABLES & ACCESSORIES
1Cx300mm2 33kV, XLPE/SWA/PVC Cu to
E5.1 m 300
connect from E1.2 to E3.1
1Cx300mm2 33kV XLPE/SWA/PVC Cu for
E5.2 m 1,800
connection to feeders
1Cx300mm2 11kV, XLPE/SWA/PVC Cu (laid 4
E5.3 cores per phase) from E3.1 to E2.1 (Only one m 600
transformer to be connected in this contract)
3Cx240mm2 11kV XLPE/SWA/PVC Cu for
E5.4 m 800
connection to feeders
3Cx70mm2 11kV XLPE/SWA/PVC Cu for
E5.5 m 70
connection to Station Transformer
4Cx70mm2 0.4kV XLPE/SWA/PVC Cu for
E5.6 m 100
connection to Station Transformer to LV panel
33kV Cable single core Termination kits (set of
E5.7 No 14
3-phase, 300mm2)
11kV Cable Termination kits (set of 3-phase,
E5.8 No 16
240mm2)
11kV Cable single core Termination kits (set of
E5.9 No 8
3-phase, 300mm2)
11kV Cable Termination kits (set of 3-phase,
E5.10 No 2
70mm2)
0.4kV Cable Termination kits (set of 3-phase,
E5.11 No 2
70mm2)
Cables for auxiliary Systems c/w Terminations
E5.12 Lot 1
& Markings
Protection & Control Cables C/W Terminations
E5.13 Lot 1
& Markings
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 126
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
E6 MISCELLANEOUS WORKS
E6.1 Substation Earth grid complete Lot 1
E6.2 Outdoor lighting for switchyard Lot 1
Substation Lightening protection system
E6.3 Lot 1
complete
E6.4 Fire detection and protection system Lot 1
E7 HVAC
E7.1 5HP Free stand Type Split AC No 4
E8 CIVIL WORKS
E8.1 Substation Embankment Works
Demolishing of old equipment foundation &
E81.1. m3 20
structures and removal of debris from site
Excavate top soil from site and haul to spoil
E8.1.2 m3 200
heaps or dispose as directed
Excavate in any material except rock and haul to
E8.1.3 m3 400
spoil heaps or dispose as directed
Provide, lay and compact to any specified depth
E8.1.4 approved fill material in substation embankment m3 600
not exceeding 150mm thickness per layer.
Substation Perimeter Drainage System, Lump
E8.1.5 LS 1
Sum
Perimeter Fencing (Block Wall) as per detailed
E8.1.6 m 150
Scope of Works
E8.1.7 Outdoor Cable Trench with Concrete covers m 45
Supply and spreading of 40-60mm chippings of
E8.1.8 m3 55
100mm thickness to cover substation
E8.2 Substation Buildings
Construct New Substation Building (ref. Dwg
E8.2.1 No. ESURP/AF/JUI/02), Lump Sum per LS 1
Substation
Construct New Customer Service Building,
E8.2.2 LS 1
Lump Sum per Substation
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 127
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
Mechanical Installation (cold water, sewage,
E8.2.4 LS 1
sanitary appliances) Lump Sum per Substation
Equipment Foundations including designs, excavation, rebar works, formwork, lean concrete, concrete,
E8.3
backfilling and compacting for the:
33/11kV, 20/26MVA Power Transformer
E8.3.1 including Firewall, Oil collection pit and Chain No 1
link fence
11/0.4kV, 100KVA Station Service Transformer
E8.3.2 No 1
including Oil collection pit and Chain link fence
E8.4 Road Works
Construction of 10m x75m bitumen surface
E8.4.1 access road from the main highway to Aberdeen Lot 1
Substation site
Construction of internal road and parking space
E8.4.2 Lot 1
(ref. Dwg. No. ESURP/AF/JUI/02)
Sub-Total (Schedule E) carried to Summary
Schedule F: WATERLOO 33/11KV SUBSTATION (Please refer to relevant S/S drawings)
33KV SWITCHGEAR (33kV, 25kA for 3s, 1250A Double Bus bars, INDOOR METAL-CLAD
F1
SWITCHGEAR LINEUP COMPRISING :)
Line/Feeder Cubicle with 36kV, 1250A
Vacuum, Motorized Circuit Breaker c/w two no.
of bus bar selection motorized isolator switches,
Current Transformers, Voltage transformer,
F1.1 No 6
Protection Relays, Controls, and 3-Phase
Ammeter, Capacitive insulator with voltage
indicator, measuring equipment. etc. as per
detailed Scope of Works.
Transformer Cubicle with 36kV, 1250A Vacuum
Motorized Circuit Breaker c/w two nos. of bus
bar selection motorized isolator switches,
Current Transformers, Voltage transformer,
F1.2 Protection Relays and Controls, Multi-functional No 2
meter (A, V), 3-phase 4 - wire Energy and KVA
demand Meter, Capacitive insulator with voltage
indicator, measuring equipment. etc. as per
detailed Scope of Works.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 128
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
Bus Sectionalizer Cubicle with 36kV, 1250A
Vacuum Motorized Circuit Breaker c/w Current
Transformers (two sets for bus differential
F1.3 No 1
protection), Protection Relays and Controls,
measuring equipment, measuring equipment. etc.
as per detailed Scope of Works.
Bus Coupler Cubicle with 36kV, 1250A Vacuum
Motorized Circuit Breaker c/w Current
Transformers (two sets for bus differential
F1.4 No 2
protection), Protection Relays and Controls,
measuring equipment, measuring equipment. etc.
as per detailed Scope of Works.
Measuring panel c/w Voltage transformer and
F1.5 Busbar earthing switch and measuring No 3
equipment. etc. as per detailed Scope of Works.
11KV SWITCHGEAR (11kV, 25kA for 3s, 2500A Single Bus bars, INDOOR METAL-CLAD
F2
SWITCHGEAR LINEUP COMPRISING :)
Transformer Incomer Cubicle with 12kV, 2500A
Vacuum Circuit Breaker c/w Current
F2.1 Transformers, Protection Relays and Capacitive No 2
insulator with voltage indicator, measuring
equipment. etc. as per detailed Scope of Works.
Feeder Cubicle with 12kV, 630A Vacuum
Circuit Breaker c/w Current Transformers,
Protection Relays, Controls and 3-Phase
F2.2 No 8
Ammeter and Capacitive insulator with voltage
indicator, measuring equipment. etc. as per
detailed Scope of Works.
Bus Sectionalizer Cubicle with 12kV, 2500A
Vacuum Circuit Breaker c/w Current
Transformers (two sets for bus differential
F2.3 No 1
protection), Protection Relays and controls,
measuring equipment. etc. as per detailed Scope
of Works.
Station Transformer Cubicle with 12kV, 630A
Vacuum Circuit Breaker c/w Current
Transformers, Protection Relays, Controls, 3-
F2.4 No 1
Phase Ammeter and Capacitive insulator with
voltage indicator, measuring equipment. etc. as
per detailed Scope of Works.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 129
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
Measuring panel c/w Voltage transformer and
F2.5 Busbar earthing switch and measuring No 2
equipment. etc. as per detailed Scope of Works.
F3 TRANSFORMERS
33/11kV, 20/26MVA, ONAN/ONAF, Dyn11
Transformer c/w On-load tap changer (OLTC ±
F3.1 No 1
8 steps), HV and LV surge arresters, TPI and
AVR panel
Station Service Transformer: 11/0.4kV,
F3.2 100KVA, ONAN, Dyn11 c/w no-load tap No 1
changer ±2 steps, Outdoor
F4 AC AND DC SUPPLY
110V DC/100A Battery Charger, Rectifier
F4.1 No 2
complete with Redundancy system
110V DC 100Ah Battery Bank (Capacity to be
F4.2 No 2
enough for whole station)
Complete DC Distribution Panel Complete with
F4.3 auto selection breaker to accommodate the two No 1
DC source. 100 A
Complete AC Distribution Panel for Station
F4.4 Auxiliary supply 400/230V, 50Hz, 100A, 16 No 1
way
F5 POWER, AUXILIARY & CONTROL CABLES & ACCESSORIES
1Cx300mm2 33kV, XLPE/SWA/PVC Cu to
F5.1 m 300
connect from F1.2 to F3.1
1Cx300mm2 33kV XLPE/SWA/PVC Cu for
F5.2 m 1,800
connection to feeders
1Cx300mm2 11kV, XLPE/SWA/PVC Cu (laid 4
F5.3 cores per phase) from F3.1 to F2.1 (Only one m 600
transformer to be connected in this contract)
3Cx240mm2 11kV XLPE/SWA/PVC Cu for
F5.4 m 800
connection to feeders
3Cx70mm2 11kV XLPE/SWA/PVC Cu for
F5.5 m 70
connection to Station Transformer
4Cx70mm2 0.4kV XLPE/SWA/PVC Cu for
F5.6 m 100
connection to Station Transformer to LV panel
33kV Cable single core Termination kits (set of
F5.7 No 14
3-phase, 240mm2)
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 130
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
11kV Cable Termination kits (set of 3-phase,
F5.8 No 8
240mm2)
11kV Cable single core Termination kits (set of
F5.9 No 16
3-phase, 300mm2)
11kV Cable Termination kits (set of 3-phase,
F5.10 No 2
70mm2)
0.4kV Cable Termination kits (set of 3-phase,
F5.11 No 2
70mm2)
Cables for auxiliary Systems c/w Terminations
F5.12 Lot 1
& Markings
Protection & Control Cables C/W Terminations
F5.13 Lot 1
& Markings
F6 MISCELLANEOUS WORKS
F6.1 Substation Earth grid complete Lot 1
F6.2 Outdoor lighting for switchyard Lot 1
Substation Lightening protection system
F6.3 Lot 1
complete
F6.4 Fire detection and protection system Lot 1
F7 HVAC
F7.1 5HP Free stand Type Split AC No 4
F8 CIVIL WORKS
F8.1 Substation Embankment Works
Demolishing of old equipment foundation &
F81.1. m3 15
structures and removal of debris from site
Excavate top soil from site and haul to spoil
F8.1.2 m3 200
heaps or dispose as directed
Excavate in any material except rock and haul to
F8.1.3 m3 400
spoil heaps or dispose as directed
Provide, lay and compact to any specified depth
F8.1.4 approved fill material in substation embankment m3 600
not exceeding 150mm thickness per layer.
Substation Perimeter Drainage System, Lump
F8.1.5 LS 1
Sum
Perimeter Fencing (Block Wall) as per detailed
F8.1.6 m 150
Scope of Works
F8.1.7 Outdoor Cable Trench with Concrete covers m 45
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 131
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning,
installation, testing, commissioning, etc. and should include rates or prices for local transportation to named place
of final destination, insurance and other services incidental to delivery of the plant, all labor, contractor’s
equipment, temporary works, materials, consumables and all matters and things of whatsoever nature, including
operations and maintenance services, the provision of operations and maintenance manuals, training, etc. as
necessary for the proper execution of the installation and other services, including all taxes, duties, levies and
charges payable in the Employer’s country
Total Total
Unit WHT Unit Price1
Qty
Price1 (10.5%) Price
Item DESCRIPTION Unit
[4] = [5] =
[1] [2] [3]
[2]+[3] [1]x[4]
Supply and spreading of 40-60mm chippings of
F8.1.8 m3 55
100mm thickness to cover substation
F8.2 Substation Buildings
Construct New Substation Building (ref. Dwg
F8.2.1 No. ESURP/AF/WTL/02), Lump Sum per LS 1
Substation
Construct New Customer Service Building,
F8.2.2 LS 1
Lump Sum per Substation
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 132
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 133
Name of Bidder
Signature of
Bidder
1
Specify currency in accordance with ITB 18. Create and use as many columns for Foreign Currency
requirement as there are foreign currencies
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 134
Name of Bidder
Signature of Bidder
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 135
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 136
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 137
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit Total
Qty Price2 Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
33kV Surge Arrestor (Set of 3No) c/w brackets and
A4.3 Set 2
clamps
A5 Spares
A5.1 33kV Polymeric post insulator (3 phase set) Set 14
33kV Polymeric tension insulator set including
A5.2 Set 12
fittings and hardware (3 phase set)
265sq.mm Aluminium Alloy Conductor (AAC) -
A5.3 km 2.5
Insulated (19.1kV)
Sub-Total (Schedule A) carried to Summary
Schedule B: 33kV Transmission Line from Freetown 161 S/S to Falcon Bridge S/S
33kV, Double Circuit Distribution Pole c/w:
a. X-Arms (double)
B1
b. 33kV Post or Tension Insulators
c. OPGW Support Structure
Intermediate Pole Top Structure (0 - 5°), Dwg No.
B1.1 No 32
ESURP/AF/POLE/33/DC/INT)
Light Angle Pole Top Structure (5o - 20°), Dwg
B1.2 No 5
No. ESURP/AF/POLE/33/DC/TA)
Medium Angle Pole Top Structure (20o - 60°),
B1.3 No 10
Dwg No. ESURP/AF/POLE/33/DC/TA)
Large Angle/Dead end/Terminal Pole Top
B1.4 Structure (60o - 90°), Dwg No. No 5
ESURP/AF/POLE/33/DC/TA)
B2 33kV Stay equipment
Stay Equipment complete with pole bracket,
B2.1 clamps, guy rod, bolts and nuts, etc. 33kV Stay Set 40
Insulator and Stay Wire and Stay Block
B2.2 Flying Stay Complete with pole & Accessories No 4
B3 Conductors and OPGW
265mm2 Aluminium Alloy Conductor (AAC) -
B3.1 km 12.2
Insulated (19.1kV)
265mm2 Aluminium Alloy Conductor (AAC) –
B3.2 km 4.3
bare conductor
Optical Ground Wire OPGW (32 fibers) complete
B3.3 km 2.8
(including joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w
B3.4 35sq.mm insulated Cu Conductor, Earth Rod & Set 52
Clamp
Approach fiber optic cable to link the substation
B3.5 m 200
and the OPGW joint box on the terminal pole
B3.6 OPGW joint box c/w termination Set 4
B4 Cable Works
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 138
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit Total
Qty Price2 Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
3x(1x300mm2) 33kV, single core
B4.1 m 900
XLPE/SWA/PVC Cu Cable (route length)
33kV Cable Termination kits (set of 1-phase,
B4.2 Set 24
300mm2), outdoor
33kV Surge Arrestor (Set of 3No) c/w brackets and
B4.3 Set 4
clamps
B5 Spares
B5.1 33kV Polymeric post insulator (3 phase set) Set 7
33kV Polymeric tension insulator set including
B5.2 Set 5
fittings and hardware (3 phase set)
265sq.mm Aluminium Alloy Conductor (AAC) -
B5.3 km 1
Insulated (19.1kV)
Sub-Total (Schedule B) carried to Summary
Schedule C: 33kV Transmission Line from Falcon Bridge S/S to Cline Town S/S
33kV, Double Circuit Distribution Pole c/w:
a. X-Arms (double)
C1
b. 33kV Post or Tension Insulators
c. OPGW Support Structure
Intermediate Pole Top Structure (0 - 5°), Dwg No.
C1.1 No 39
ESURP/AF/POLE/33/DC/INT)
Light Angle Pole Top Structure (5o - 20°), Dwg
C1.2 No 11
No. ESURP/AF/POLE/33/DC/TA)
Medium Angle Pole Top Structure (20o - 60°),
C1.3 No 6
Dwg No. ESURP/AF/POLE/33/DC/TA)
Large Angle/Dead end/Terminal Pole Top
C1.4 Structure (60o - 90°), Dwg No. No 3
ESURP/AF/POLE/33/DC/TA)
C2 33kV Stay equipment
Stay Equipment complete with pole bracket,
C2.1 clamps, guy rod, bolts and nuts, etc. 33kV Stay Set 40
Insulator and Stay Wire and Stay Block
C2.2 Flying Stay Complete with pole & Accessories No 5
C3 Conductors and OPGW
265mm2 Aluminium Alloy Conductor (AAC) -
C3.1 km 14
Insulated (19.1kV)
265mm2 Aluminium Alloy Conductor (AAC) –
C3.2 km 6.0
bare conductor
Optical Ground Wire OPGW (32 fibers) complete
C3.3 km 3.3
(including joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w
C3.4 35sq.mm insulated Cu Conductor, Earth Rod & Set 59
Clamp
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 139
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit Total
Qty Price2 Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
Approach fiber optic cable to link the substation
C3.5 m 200
and the OPGW joint box on the terminal pole
C3.6 OPGW joint box c/w termination Set 4
C4 Cable Works
3x(1x300mm2) 33kV, single core
C4.1 m 900
XLPE/SWA/PVC Cu Cable (route length)
33kV Cable Termination kits (set of 1-phase,
C4.2 Set 24
300mm2), outdoor
33kV Surge Arrestor (Set of 3No) c/w brackets and
C4.3 Set 4
clamps
C5 Spares
C5.1 33kV Polymeric post insulator (3 phase set) Set 8
33kV Polymeric tension insulator set including
C5.2 Set 6
fittings and hardware (3 phase set)
265sq.mm Aluminium Alloy Conductor (AAC) -
C5.3 km 1.1
Insulated (19.1kV)
Sub-Total (Schedule C) carried to Summary
Schedule D: 33kV Transmission Line from Cline Town S/S to Blackhall Road S/S
33kV, Double Circuit Distribution Pole c/w:
a. X-Arms (double)
D1
b. 33kV Post or Tension Insulators
c. OPGW Support Structure
Intermediate Pole Top Structure (0 - 5°), Dwg No.
D1.1 No 13
ESURP/AF/POLE/33/DC/INT)
Light Angle Pole Top Structure (5o - 20°), Dwg
D1.2 No 2
No. ESURP/AF/POLE/33/DC/TA)
Medium Angle Pole Top Structure (20o - 60°),
D1.3 No 4
Dwg No. ESURP/AF/POLE/33/DC/TA)
Large Angle/Dead end/Terminal Pole Top
D1.4 Structure (60o - 90°), Dwg No. No 3
ESURP/AF/POLE/33/DC/TA)
D2 33kV Stay equipment
Stay Equipment complete with pole bracket,
D2.1 clamps, guy rod, bolts and nuts, etc. 33kV Stay Set 18
Insulator and Stay Wire and Stay Block
D2.2 Flying Stay Complete with pole & Accessories No 2
D3 Conductors and OPGW
265mm2 Aluminium Alloy Conductor (AAC) -
D3.1 km 2.4
Insulated (19.1kV)
265mm2 Aluminium Alloy Conductor (AAC) –
D3.2 km 5.5
bare conductor
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 140
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit Total
Qty Price2 Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
Optical Ground Wire OPGW (32 fibers) complete
D3.3 km 1.3
(including joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w
D3.4 35sq.mm insulated Cu Conductor, Earth Rod & Set 24
Clamp
Approach fiber optic cable to link the substation
D3.5 m 200
and the OPGW joint box on the terminal pole
D3.6 OPGW joint box c/w termination Set 2
D4 Cable Works
3x(1x300mm2) 33kV, single core
D4.1 m 900
XLPE/SWA/PVC Cu Cable (route length)
33kV Cable Termination kits (set of 1-phase,
D4.2 Set 24
300mm2), outdoor
33kV Surge Arrestor (Set of 3No) c/w brackets and
D4.3 Set 4
clamps
D5 Spares
D5.1 33kV Polymeric post insulator (3 phase set) Set 3
33kV Polymeric tension insulator set including
D5.2 Set 2
fittings and hardware (3 phase set)
265sq.mm Aluminium Alloy Conductor (AAC) -
D5.3 km 0.5
Insulated (19.1kV)
Sub-Total (Schedule D) carried to Summary
Schedule E: 33kV Transmission Line from Jui S/S to Regent S/S
33kV, Single Circuit Distribution Pole c/w:
a. X-Arms (single circuit)
E1
b. 33kV Post or Tension Insulators
c. OPGW Support Structure
Intermediate Pole Top Structure (0 - 5°), Dwg No.
E1.1 No 184
ESURP/AF/POLE/33/SC/INT)
Light Angle Pole Top Structure (5o - 20°), Dwg
E1.2 No 24
No. ESURP/AF/POLE/33/SC/AS)
Medium Angle Pole Top Structure (20o - 60°),
E1.3 No 32
Dwg No. ESURP/AF/POLE/33/SC/AS)
Large Angle/Dead end Top Structure (60o - 90°),
E1,4 No 4
Dwg No. ESURP/AF/POLE/33/SC/AS)
Terminal Pole Top Structure (Dwg No.
E1.5 No 2
ESURP/AF/POLE/33/SC/TE)
E2 33kV Stay equipment
Stay Equipment complete with pole bracket,
E2.1 clamps, guy rod, bolts and nuts, etc. 33kV Stay Set 124
Insulator and Stay Wire and Stay Block
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 141
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit Total
Qty Price2 Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
E2.2 Flying Stay Complete with pole & Accessories No 22
E3 Conductors and OPGW
265mm2 Aluminium Alloy Conductor (AAC) –
E3.1 km 44.5
bare conductor
Optical Ground Wire OPGW (32 fibers) complete
E3.2 km 45
(including joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w
E3.3 35sq.mm insulated Cu Conductor, Earth Rod & Set 264
Clamp
Approach fiber optic cable to link the substation
E3.4 m 200
and the OPGW joint box on the terminal pole
E3.5 OPGW joint box c/w termination Set 4
E4 Cable Works
3x(1x300mm2) 33kV, single core
E4.1 m 450
XLPE/SWA/PVC Cu Cable (route length)
33kV Cable Termination kits (set of 1-phase,
E4.2 Set 12
300mm2), outdoor
33kV Surge Arrestor (Set of 3No) c/w brackets and
E4.3 Set 2
clamps
E5 Spares
E5.1 33kV Polymeric post insulator (3 phase set) Set 35
33kV Polymeric tension insulator set including
E5.2 Set 20
fittings and hardware (3 phase set)
265sq.mm Aluminium Alloy Conductor (AAC) -
E5.3 km 4.9
Insulated (19.1kV)
Sub-Total (Schedule E) carried to Summary
Schedule F: 33kV Transmission Line from Wellington S/S to Jui S/S
F1 33kV, Double Circuit Lattice Towers (Narrow base, basic - height 19m) for 400sq.mm AAC
Double Circuit Tower Type SS (Suspension, Dwg
F1.1 No 16
No. ESURP/AF/TOW/33/DC/SS) of basic height
Double Circuit Tower Type SS (Suspension, Dwg
F1.2 No. ESURP/AF/TOW/33/DC/SS) with 3M No 8
extension
Double Circuit Tower Type SS (Suspension, Dwg
F1.3 No. ESURP/AF/TOW/33/DC/SS) with 6M No 2
extension
Double Circuit Tower Type ST1 (Tension, Dwg
F1.4 No 20
No. ESURP/AF/TOW/33/DC/ST) of basic height
Double Circuit Tower Type ST1 (Tension, Dwg
F1.5 No. ESURP/AF/TOW/33/DC/ST) with 3M No 10
Extension
Double Circuit Tower Type ST1 (Tension, Dwg
F1.6 No 1
No. ESURP/AF/TOW/33/DC/ST) with 6M
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 142
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit Total
Qty Price2 Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
Extension
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 143
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit Total
Qty Price2 Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
Schedule G: 33kV Transmission Line from Jui S/S to Waterloo S/S
G1 33kV, Double Circuit Lattice Towers (Narrow base, basic - height 19m) for 400sq.mm AAC
Double Circuit Tower Type SS (Suspension, Dwg
G1.1 No 45
No. ESURP/AF/TOW/33/DC/SS) of basic height
Double Circuit Tower Type SS (Suspension, Dwg
G1.2 No. ESURP/AF/TOW/33/DC/SS) with 3M No 21
extension
Double Circuit Tower Type SS (Suspension, Dwg
G1.3 No. ESURP/AF/TOW/33/DC/SS) with 6M No 3
extension
Double Circuit Tower Type ST1 (Tension, Dwg
G1.4 No 30
No. ESURP/AF/TOW/33/DC/ST) of basic height
Double Circuit Tower Type ST1 (Tension, Dwg
G1.5 No. ESURP/AF/TOW/33/DC/ST) with 3M No 10
Extension
Double Circuit Tower Type ST1 (Tension, Dwg
G1.6 No. ESURP/AF/TOW/33/DC/ST) with 6M No 3
Extension
G1.7 Double Circuit Tower Type DE of basic height No 4
Double Circuit Tower Type Specially designed for
G1.8 No 1
90 deg Angle
G2 Conductors and OPGW
G2.1 265mm2 Aluminium Alloy Conductor (AAC) km 118.8
G2.2 Vibration dampers for 265mm2 AAC No 1,572
Optical Ground Wire OPGW (32 fibers) complete
G2.3 km 18.5
(including joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w
G2.4 35sq.mm insulated Cu Conductor, Earth Rod & Set 131
Clamp
Approach fiber optic cable to link the substation
G2.5 m 400
and the OPGW joint box on the terminal pole
G2.6 OPGW joint box c/w termination Set 4
G3 33kV Insulators & Fittings Designed for 265mm2 AAC
33kV Polymeric suspension insulator sets including
G3.1 Set 450
fittings and hardware
33kV Polymeric tension insulator set including
G3.2 Set 672
fittings and hardware
G4 Counterpoise Grounding
Counterpoise grounding additional to the standard
G4.1 No 26
grounding
G5 Cable Works
3x(1x300mm2) 33kV, single core
G5.1 m 900
XLPE/SWA/PVC Cu Cable (route length)
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 144
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit Total
Qty Price2 Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
33kV Cable Termination kits (set of 1-phase,
G5.2 Set 24
300mm2), outdoor
33kV Surge Arrestor (Set of 3No) c/w brackets and
G5.3 Set 4
clamps
G6 Spares
33kV Polymeric suspension insulator sets including
G6.1 Set 90
fittings and hardware
33kV Polymeric tension insulator set including
G6.2 Set 134
fittings and hardware
G6.3 265sq.mm Aluminium Alloy Conductor (AAC) km 11.9
Sub-Total (Schedule G) carried to Summary
Schedule H: 33kV Transmission Line from Blackhall Road S/S to Wellington S/S
H1 Conductors and OPGW
H1.1 265mm2 Aluminium Alloy Conductor (AAC) km 27.4
H1.2 Vibration dampers for 265mm2 AAC No 672
Optical Ground Wire OPGW (32 fibers) complete
H1.3 km 8.4
(including joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w
H1.4 35sq.mm insulated Cu Conductor, Earth Rod & Set 56
Clamp
Approach fiber optic cable to link the substation
H1.5 m 200
and the OPGW joint box on the terminal pole
H1.6 OPGW joint box c/w termination Set 4
H2 33kV Insulators & Fittings Designed for 265mm2 AAC
33kV Polymeric suspension insulator sets including
H2.1 Set 98
fittings and hardware
33kV Polymeric tension insulator set including
H2.2 Set 148
fittings and hardware
H3 Counterpoise Grounding
Counterpoise grounding additional to the standard
H3.1 No 12
grounding
H4 Cable Works
3x(1x300mm2) 33kV, single core
H4.1 m 450
XLPE/SWA/PVC Cu Cable (route length)
33kV Cable Termination kits (set of 1-phase,
H4.2 Set 24
300mm2), outdoor
33kV Surge Arrestor (Set of 3No) c/w brackets and
H4.3 Set 4
clamps
H5 Spares
33kV Polymeric suspension insulator sets including
H5.1 Set 20
fittings and hardware
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 145
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit Total
Qty Price2 Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
33kV Polymeric tension insulator set including
H5.2 Set 30
fittings and hardware
H5.3 265sq.mm Aluminium Alloy Conductor (AAC) km 2.7
Sub-Total (Schedule H) carried to Summary
Schedule I: Upgrade of 33kV Transmission Line Between Freetown 161 S/S, Blackhall Road S/S and Wilberforce S/S
(Provisional amount subject to analysis/adequacy assessment of existing towers and foundations)
I1 33kV, Double Circuit Lattice Towers
Reinforcement of existing Intermediate (IMP) (0 –
I1.1 1 degree) Double Circuit lattice Tower Complete No 15
with all accessories
Reinforcement of existing Light Angle (1 – 15
I1.2 degrees) Double Circuit Tower Complete with all No 15
accessories
Reinforcement of existing Intermediate (IMP) (0 –
I1.3 1 degree) Double Circuit lattice Tower Complete No 81
with all accessories
Reinforcement of existing Heavy Angle (IMP) (16
I1.4 – 90 degree) Double Circuit Tower Complete with No 35
all accessories
Reinforcement of existing Terminal Double Circuit
I1.5 Tower Complete with 33kV Lightening arrestors No 6
and all accessories
Reinforcement of existing Section Double Circuit
I1.6 No 60
Tower Complete with all accessories
I2 Conductors and OPGW
I2.1 265mm2 Aluminium Alloy Conductor (AAC) km 138.0
I2.2 Vibration dampers for 265mm2 AAC No 2,544
Optical Ground Wire OPGW (32 fibers) complete
I2.3 km 24.0
(including joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w
I2.4 35sq.mm insulated Cu Conductor, Earth Rod & Set 212
Clamp
Approach fiber optic cable to link the substation
I2.5 m 400
and the OPGW joint box on the terminal pole
I2.6 OPGW joint box c/w termination Set 6
I3 33kV Insulators & Fittings Designed for 265mm2 AAC
33kV Polymeric suspension insulator sets including
I3.1 Set 90
fittings and hardware
33kV Polymeric tension insulator set including
I3.2 Set 2,364
fittings and hardware
I4 Counterpoise Grounding
Counterpoise grounding additional to the standard
I4.1 No 22
grounding
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 146
SCHEDULE No. 1: Plant, Equipment and Mandatory Spare Parts Supplied from Abroad
Unit Total
Qty Price2 Price2
Item DESCRIPTION Code1 Unit CIP2 CIP2
[3] =
[1] [2]
[1]x[2]
I5 Cable Works
3x(1x300mm2) 33kV, single core
I5.1 m 1,350
XLPE/SWA/PVC Cu Cable (route length)
33kV Cable Termination kits (set of 1-phase,
I5.2 Set 36
300mm2), outdoor
33kV Surge Arrestor (Set of 3No) c/w brackets and
I5.3 Set 6
clamps
I6 Spares
33kV Polymeric suspension insulator sets including
I6.1 Set 18
fittings and hardware
33kV Polymeric tension insulator set including
I6.2 Set 473
fittings and hardware
I6.3 265sq.mm Aluminium Alloy Conductor (AAC) km 13.8
Sub-Total (Schedule I) carried to Summary
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 147
1 Bidders shall enter a code representing the country of origin of all imported plant and equipment.
2 Specify currency. Create and use as many columns for Unit Price and Total Price as there are currencies.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 148
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 149
SCHEDULE No. 2: Plant, Equipment and Mandatory Spare Parts Supplied from Within the Employer’s Country
EXW EXW
Qty Unit Total
Item DESCRIPTION Unit Price1 Price1
[3] =
[1] [2]
[1]x[2]
33kV Polymeric tension insulator set including fittings and
A5.2 Set 12
hardware (3 phase set)
265sq.mm Aluminium Alloy Conductor (AAC) - Insulated
A5.3 km 2.5
(19.1kV)
Sub-Total (Schedule A) carried to Summary
Schedule B: 33kV Transmission Line from Freetown 161 S/S to Falcon Bridge S/S
33kV, Double Circuit Distribution Pole c/w:
a. X-Arms (double)
B1
b. 33kV Post or Tension Insulators
c. OPGW Support Structure
Intermediate Pole Top Structure (0 - 5°), Dwg No.
B1.1 No 32
ESURP/AF/POLE/33/DC/INT)
Light Angle Pole Top Structure (5o - 20°), Dwg No.
B1.2 No 5
ESURP/AF/POLE/33/DC/TA)
Medium Angle Pole Top Structure (20o - 60°), Dwg No.
B1.3 No 10
ESURP/AF/POLE/33/DC/TA)
Large Angle/Dead end/Terminal Pole Top Structure (60o - 90°),
B1.4 No 5
Dwg No. ESURP/AF/POLE/33/DC/TA)
B2 33kV Stay equipment
Stay Equipment complete with pole bracket, clamps, guy rod,
B2.1 bolts and nuts, etc. 33kV Stay Insulator and Stay Wire and Stay Set 40
Block
B2.2 Flying Stay Complete with pole & Accessories No 4
B3 Conductors and OPGW
265mm2 Aluminium Alloy Conductor (AAC) - Insulated
B3.1 km 12.2
(19.1kV)
B3.2 265mm2 Aluminium Alloy Conductor (AAC) – bare conductor km 4.3
Optical Ground Wire OPGW (32 fibers) complete (including
B3.3 km 2.8
joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w 35sq.mm
B3.4 Set 52
insulated Cu Conductor, Earth Rod & Clamp
Approach fiber optic cable to link the substation and the OPGW
B3.5 m 200
joint box on the terminal pole
B3.6 OPGW joint box c/w termination Set 4
B4 Cable Works
3x(1x300mm2) 33kV, single core XLPE/SWA/PVC Cu Cable
B4.1 m 900
(route length)
B4.2 33kV Cable Termination kits (set of 1-phase, 300mm2), outdoor Set 24
B4.3 33kV Surge Arrestor (Set of 3No) c/w brackets and clamps Set 4
B5 Spares
B5.1 33kV Polymeric post insulator (3 phase set) Set 7
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 150
SCHEDULE No. 2: Plant, Equipment and Mandatory Spare Parts Supplied from Within the Employer’s Country
EXW EXW
Qty Unit Total
Item DESCRIPTION Unit Price1 Price1
[3] =
[1] [2]
[1]x[2]
33kV Polymeric tension insulator set including fittings and
B5.2 Set 5
hardware (3 phase set)
265sq.mm Aluminium Alloy Conductor (AAC) - Insulated
B5.3 km 1
(19.1kV)
Sub-Total (Schedule B) carried to Summary
Schedule C: 33kV Transmission Line from Falcon Bridge S/S to Cline Town S/S
33kV, Double Circuit Distribution Pole c/w:
a. X-Arms (double)
C1
b. 33kV Post or Tension Insulators
c. OPGW Support Structure
Intermediate Pole Top Structure (0 - 5°), Dwg No.
C1.1 No 39
ESURP/AF/POLE/33/DC/INT)
Light Angle Pole Top Structure (5o - 20°), Dwg No.
C1.2 No 11
ESURP/AF/POLE/33/DC/TA)
Medium Angle Pole Top Structure (20o - 60°), Dwg No.
C1.3 No 6
ESURP/AF/POLE/33/DC/TA)
Large Angle/Dead end/Terminal Pole Top Structure (60o - 90°),
C1.4 No 3
Dwg No. ESURP/AF/POLE/33/DC/TA)
C2 33kV Stay equipment
Stay Equipment complete with pole bracket, clamps, guy rod,
C2.1 bolts and nuts, etc. 33kV Stay Insulator and Stay Wire and Stay Set 40
Block
C2.2 Flying Stay Complete with pole & Accessories No 5
C3 Conductors and OPGW
265mm2 Aluminium Alloy Conductor (AAC) - Insulated
C3.1 km 14
(19.1kV)
C3.2 265mm2 Aluminium Alloy Conductor (AAC) – bare conductor Km 6
Optical Ground Wire OPGW (32 fibers) complete (including
C3.3 km 3.3
joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w 35sq.mm
C3.4 Set 59
insulated Cu Conductor, Earth Rod & Clamp
Approach fiber optic cable to link the substation and the OPGW
C3.5 m 200
joint box on the terminal pole
C3.6 OPGW joint box c/w termination Set 4
C4 Cable Works
3x(1x300mm2) 33kV, single core XLPE/SWA/PVC Cu Cable
C4.1 m 900
(route length)
C4.2 33kV Cable Termination kits (set of 1-phase, 300mm2), outdoor Set 24
C4.3 33kV Surge Arrestor (Set of 3No) c/w brackets and clamps Set 4
C5 Spares
C5.1 33kV Polymeric post insulator (3 phase set) Set 8
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 151
SCHEDULE No. 2: Plant, Equipment and Mandatory Spare Parts Supplied from Within the Employer’s Country
EXW EXW
Qty Unit Total
Item DESCRIPTION Unit Price1 Price1
[3] =
[1] [2]
[1]x[2]
33kV Polymeric tension insulator set including fittings and
C5.2 Set 6
hardware (3 phase set)
265sq.mm Aluminium Alloy Conductor (AAC) - Insulated
C5.3 km 1.1
(19.1kV)
Sub-Total (Schedule C) carried to Summary
Schedule D: 33kV Transmission Line from Cline Town S/S to Blackhall Road S/S
33kV, Double Circuit Distribution Pole c/w:
a. X-Arms (double)
D1
b. 33kV Post or Tension Insulators
c. OPGW Support Structure
Intermediate Pole Top Structure (0 - 5°), Dwg No.
D1.1 No 13
ESURP/AF/POLE/33/DC/INT)
Light Angle Pole Top Structure (5o - 20°), Dwg No.
D1.2 No 2
ESURP/AF/POLE/33/DC/TA)
Medium Angle Pole Top Structure (20o - 60°), Dwg No.
D1.3 No 4
ESURP/AF/POLE/33/DC/TA)
Large Angle/Dead end/Terminal Pole Top Structure (60o - 90°),
D1.4 No 3
Dwg No. ESURP/AF/POLE/33/DC/TA)
D2 33kV Stay equipment
Stay Equipment complete with pole bracket, clamps, guy rod,
D2.1 bolts and nuts, etc. 33kV Stay Insulator and Stay Wire and Stay Set 18
Block
D2.2 Flying Stay Complete with pole & Accessories No 2
D3 Conductors and OPGW
265mm2 Aluminium Alloy Conductor (AAC) - Insulated
D3.1 km 2.4
(19.1kV)
D3.2 265mm2 Aluminium Alloy Conductor (AAC) – bare conductor Km 5.5
Optical Ground Wire OPGW (32 fibers) complete (including
D3.3 km 1.3
joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w 35sq.mm
D3.4 Set 24
insulated Cu Conductor, Earth Rod & Clamp
Approach fiber optic cable to link the substation and the OPGW
D3.5 m 200
joint box on the terminal pole
D3.6 OPGW joint box c/w termination Set 2
D4 Cable Works
3x(1x300mm2) 33kV, single core XLPE/SWA/PVC Cu Cable
D4.1 m 900
(route length)
D4.2 33kV Cable Termination kits (set of 1-phase, 300mm2), outdoor Set 24
D4.3 33kV Surge Arrestor (Set of 3No) c/w brackets and clamps Set 4
D5 Spares
D5.1 33kV Polymeric post insulator (3 phase set) Set 3
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 152
SCHEDULE No. 2: Plant, Equipment and Mandatory Spare Parts Supplied from Within the Employer’s Country
EXW EXW
Qty Unit Total
Item DESCRIPTION Unit Price1 Price1
[3] =
[1] [2]
[1]x[2]
33kV Polymeric tension insulator set including fittings and
D5.2 Set 2
hardware (3 phase set)
265sq.mm Aluminium Alloy Conductor (AAC) - Insulated
D5.3 km 0.5
(19.1kV)
Sub-Total (Schedule D) carried to Summary
Schedule E: 33kV Transmission Line from Jui S/S to Regent S/S
33kV, Single Circuit Distribution Pole c/w:
a. X-Arms (single circuit)
E1
b. 33kV Post or Tension Insulators
c. OPGW Support Structure
Intermediate Pole Top Structure (0 - 5°), Dwg No.
E1.1 No 184
ESURP/AF/POLE/33/SC/INT)
Light Angle Pole Top Structure (5o - 20°), Dwg No.
E1.2 No 24
ESURP/AF/POLE/33/SC/AS)
Medium Angle Pole Top Structure (20o - 60°), Dwg No.
E1.3 No 32
ESURP/AF/POLE/33/SC/AS)
Large Angle/Dead end Top Structure (60o - 90°), Dwg No.
E1.4 No 4
ESURP/AF/POLE/33/SC/AS)
Terminal Pole Top Structure (Dwg No.
E1.5 No 2
ESURP/AF/POLE/33/SC/TE)
E2 33kV Stay equipment
Stay Equipment complete with pole bracket, clamps, guy rod,
E2.1 bolts and nuts, etc. 33kV Stay Insulator and Stay Wire and Stay Set 124
Block
E2.2 Flying Stay Complete with pole & Accessories No 22
E3 Conductors and OPGW
E3.1 265mm2 Aluminium Alloy Conductor (AAC) – bare conductor km 44.5
Optical Ground Wire OPGW (32 fibers) complete (including
E3.2 km 45
joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w 35sq.mm
E3.3 Set 264
insulated Cu Conductor, Earth Rod & Clamp
Approach fiber optic cable to link the substation and the OPGW
E3.4 m 200
joint box on the terminal pole
E3.5 OPGW joint box c/w termination Set 4
E4 Cable Works
3x(1x300mm2) 33kV, single core XLPE/SWA/PVC Cu Cable
E4.1 m 450
(route length)
E4.2 33kV Cable Termination kits (set of 1-phase, 300mm2), outdoor Set 12
E4.3 33kV Surge Arrestor (Set of 3No) c/w brackets and clamps Set 2
E5 Spares
E5.1 33kV Polymeric post insulator (3 phase set) Set 35
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 153
SCHEDULE No. 2: Plant, Equipment and Mandatory Spare Parts Supplied from Within the Employer’s Country
EXW EXW
Qty Unit Total
Item DESCRIPTION Unit Price1 Price1
[3] =
[1] [2]
[1]x[2]
33kV Polymeric tension insulator set including fittings and
E5.2 Set 20
hardware (3 phase set)
265sq.mm Aluminium Alloy Conductor (AAC) - Insulated
E5.3 km 4.9
(19.1kV)
Sub-Total (Schedule E) carried to Summary
Schedule F: 33kV Transmission Line from Wellington S/S to Jui S/S
F1 33kV, Double Circuit Lattice Towers (Narrow base, basic - height 19m) for 400sq.mm AAC
Double Circuit Tower Type SS (Suspension, Dwg No.
F1.1 No 16
ESURP/AF/TOW/33/DC/SS) of basic height
Double Circuit Tower Type SS (Suspension, Dwg No.
F1.2 No 8
ESURP/AF/TOW/33/DC/SS) with 3M extension
Double Circuit Tower Type SS (Suspension, Dwg No.
F1.3 No 2
ESURP/AF/TOW/33/DC/SS) with 6M extension
Double Circuit Tower Type ST1 (Tension, Dwg No.
F1.4 No 20
ESURP/AF/TOW/33/DC/ST) of basic height
Double Circuit Tower Type ST1 (Tension, Dwg No.
F1.5 No 10
ESURP/AF/TOW/33/DC/ST) with 3M Extension
Double Circuit Tower Type ST1 (Tension, Dwg No.
F1.6 No 1
ESURP/AF/TOW/33/DC/ST) with 6M Extension
Double Circuit Tower Type ST2 (Tension, Dwg No.
F1.7 No 1
ESURP/AF/TOW/33/DC/ST) with 3M Extension
F1.8 Double Circuit Tower Type DE of basic height No 2
F1.9 Double Circuit Tower Type Specially designed for 90 deg Angle No 1
F2 Conductors and OPGW
F3.1 265mm2 Aluminium Alloy Conductor (AAC) km 46.8
F3.2 Vibration dampers for 265mm2 AAC No 732
Optical Ground Wire OPGW (32 fibers) complete (including
F3.3 km 7.2
joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w 35sq.mm
F3.4 Set 61
insulated Cu Conductor, Earth Rod & Clamp
Approach fiber optic cable to link the substation and the OPGW
F3.5 m 400
joint box on the terminal pole
F3.6 OPGW joint box c/w termination Set 4
F3 33kV Insulators & Fittings Designed for 265mm2 AAC
33kV Polymeric suspension insulator sets including fittings and
F3.1 Set 156
hardware
33kV Polymeric tension insulator set including fittings and
F3.2 Set 420
hardware
F4 Counterpoise Grounding
F4.1 Counterpoise grounding additional to the standard grounding No 12
F5 Cable Works
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 154
SCHEDULE No. 2: Plant, Equipment and Mandatory Spare Parts Supplied from Within the Employer’s Country
EXW EXW
Qty Unit Total
Item DESCRIPTION Unit Price1 Price1
[3] =
[1] [2]
[1]x[2]
3x(1x300mm2) 33kV, single core XLPE/SWA/PVC Cu Cable
F5.1 m 900
(route length)
F5.2 33kV Cable Termination kits (set of 1-phase, 300mm2), outdoor Set 24
F5.3 33kV Surge Arrestor (Set of 3No) c/w brackets and clamps Set 4
F6 Spares
33kV Polymeric suspension insulator sets including fittings and
F6.1 Set 31
hardware
33kV Polymeric tension insulator set including fittings and
F6.2 Set 84
hardware
F6.3 265sq.mm Aluminium Alloy Conductor (AAC) km 4.7
Sub-Total (Schedule F) carried to Summary
Schedule G: 33kV Transmission Line from Jui S/S to Waterloo S/S
G1 33kV, Double Circuit Lattice Towers (Narrow base, basic - height 19m) for 400sq.mm AAC
Double Circuit Tower Type SS (Suspension, Dwg No.
G1.1 No 45
ESURP/AF/TOW/33/DC/SS) of basic height
Double Circuit Tower Type SS (Suspension, Dwg No.
G1.2 No 21
ESURP/AF/TOW/33/DC/SS) with 3M extension
Double Circuit Tower Type SS (Suspension, Dwg No.
G1.3 No 3
ESURP/AF/TOW/33/DC/SS) with 6M extension
Double Circuit Tower Type ST1 (Tension, Dwg No.
G1.4 No 30
ESURP/AF/TOW/33/DC/ST) of basic height
Double Circuit Tower Type ST1 (Tension, Dwg No.
G1.5 No 10
ESURP/AF/TOW/33/DC/ST) with 3M Extension
Double Circuit Tower Type ST1 (Tension, Dwg No.
G1.6 No 3
ESURP/AF/TOW/33/DC/ST) with 6M Extension
G1.7 Double Circuit Tower Type DE of basic height No 4
G1.8 Double Circuit Tower Type Specially designed for 90 deg Angle No 1
G2 Conductors and OPGW
G2.1 265mm2 Aluminium Alloy Conductor (AAC) km 118.8
G2.2 Vibration dampers for 265mm2 AAC No 1,572
Optical Ground Wire OPGW (32 fibers) complete (including
G2.3 km 18.5
joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w 35sq.mm
G2.4 Set 131
insulated Cu Conductor, Earth Rod & Clamp
Approach fiber optic cable to link the substation and the OPGW
G2.5 m 400
joint box on the terminal pole
G2.6 OPGW joint box c/w termination Set 4
G3 33kV Insulators & Fittings Designed for 265mm2 AAC
33kV Polymeric suspension insulator sets including fittings and
G3.1 Set 450
hardware
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 155
SCHEDULE No. 2: Plant, Equipment and Mandatory Spare Parts Supplied from Within the Employer’s Country
EXW EXW
Qty Unit Total
Item DESCRIPTION Unit Price1 Price1
[3] =
[1] [2]
[1]x[2]
33kV Polymeric tension insulator set including fittings and
G3.2 Set 672
hardware
G4 Counterpoise Grounding
G4.1 Counterpoise grounding additional to the standard grounding No 26
G5 Cable Works
3x(1x300mm2) 33kV, single core XLPE/SWA/PVC Cu Cable
G5.1 m 900
(route length)
G5.2 33kV Cable Termination kits (set of 1-phase, 300mm2), outdoor Set 24
G5.3 33kV Surge Arrestor (Set of 3No) c/w brackets and clamps Set 4
G6 Spares
33kV Polymeric suspension insulator sets including fittings and
G6.1 Set 90
hardware
33kV Polymeric tension insulator set including fittings and
G6.2 Set 134
hardware
G6.3 265sq.mm Aluminium Alloy Conductor (AAC) km 11.9
Sub-Total (Schedule G) carried to Summary
Schedule H: 33kV Transmission Line from Blackhall Road S/S to Wellington S/S
H1 Conductors and OPGW
H1.1 265mm2 Aluminium Alloy Conductor (AAC) km 27.4
H1.2 Vibration dampers for 265mm2 AAC No 672
Optical Ground Wire OPGW (32 fibers) complete (including
H1.3 km 8.4
joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w 35sq.mm
H1.4 Set 56
insulated Cu Conductor, Earth Rod & Clamp
Approach fiber optic cable to link the substation and the OPGW
H1.5 m 200
joint box on the terminal pole
H1.6 OPGW joint box c/w termination Set 4
H2 33kV Insulators & Fittings Designed for 265mm2 AAC
33kV Polymeric suspension insulator sets including fittings and
H2.1 Set 98
hardware
33kV Polymeric tension insulator set including fittings and
H2.2 Set 148
hardware
H3 Counterpoise Grounding
H3.1 Counterpoise grounding additional to the standard grounding No 12
H4 Cable Works
3x(1x300mm2) 33kV, single core XLPE/SWA/PVC Cu Cable
H4.1 m 450
(route length)
H4.2 33kV Cable Termination kits (set of 1-phase, 300mm2), outdoor Set 24
H4.3 33kV Surge Arrestor (Set of 3No) c/w brackets and clamps Set 4
H5 Spares
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 156
SCHEDULE No. 2: Plant, Equipment and Mandatory Spare Parts Supplied from Within the Employer’s Country
EXW EXW
Qty Unit Total
Item DESCRIPTION Unit Price1 Price1
[3] =
[1] [2]
[1]x[2]
33kV Polymeric suspension insulator sets including fittings and
H5.1 Set 20
hardware
33kV Polymeric tension insulator set including fittings and
H5.2 Set 30
hardware
H5.3 265sq.mm Aluminium Alloy Conductor (AAC) km 2.7
Sub-Total (Schedule H) carried to Summary
Schedule I: Upgrade of 33kV Transmission Line Between Freetown 161 S/S, Blackhall Road S/S and Wilberforce S/S
(Provisional amount subject to analysis/adequacy assessment of existing towers and foundations)
I1 33kV, Double Circuit Lattice Towers
Reinforcement of existing Intermediate (IMP) (0 – 1 degree)
I1.1 No 15
Double Circuit lattice Tower Complete with all accessories
Reinforcement of existing Light Angle (1 – 15 degrees) Double
I1.2 No 15
Circuit Tower Complete with all accessories
Reinforcement of existing Intermediate (IMP) (0 – 1 degree)
I1.3 No 81
Double Circuit lattice Tower Complete with all accessories
Reinforcement of existing Heavy Angle (IMP) (16 – 90 degree)
I1.4 No 35
Double Circuit Tower Complete with all accessories
Reinforcement of existing Terminal Double Circuit Tower
I1.5 No 6
Complete with 33kV Lightening arrestors and all accessories
Reinforcement of existing Section Double Circuit Tower
I1.6 No 60
Complete with all accessories
I2 Conductors and OPGW
I2.1 265mm2 Aluminium Alloy Conductor (AAC) km 138.0
I2.2 Vibration dampers for 265mm2 AAC No 2,544
Optical Ground Wire OPGW (32 fibers) complete (including
I2.3 km 24.0
joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w 35sq.mm
I2.4 Set 212
insulated Cu Conductor, Earth Rod & Clamp
Approach fiber optic cable to link the substation and the OPGW
I2.5 m 400
joint box on the terminal pole
I2.6 OPGW joint box c/w termination Set 6
I3 33kV Insulators & Fittings Designed for 265mm2 AAC
33kV Polymeric suspension insulator sets including fittings and
I3.1 Set 90
hardware
33kV Polymeric tension insulator set including fittings and
I3.2 Set 2,364
hardware
I4 Counterpoise Grounding
I4.1 Counterpoise grounding additional to the standard grounding No 22
I5 Cable Works
3x(1x300mm2) 33kV, single core XLPE/SWA/PVC Cu Cable
I5.1 m 1,350
(route length)
I5.2 33kV Cable Termination kits (set of 1-phase, 300mm2), outdoor Set 36
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 157
SCHEDULE No. 2: Plant, Equipment and Mandatory Spare Parts Supplied from Within the Employer’s Country
EXW EXW
Qty Unit Total
Item DESCRIPTION Unit Price1 Price1
[3] =
[1] [2]
[1]x[2]
I5.3 33kV Surge Arrestor (Set of 3No) c/w brackets and clamps Set 6
I6 Spares
33kV Polymeric suspension insulator sets including fittings and
I6.1 Set 18
hardware
33kV Polymeric tension insulator set including fittings and
I6.2 Set 473
hardware
I6.3 265sq.mm Aluminium Alloy Conductor (AAC) km 13.8
Sub-Total (Schedule I) carried to Summary
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 158
1 Specify currency in accordance with specifications in Bid Data Sheet under ITB 18.1
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 159
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 160
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning, installation,
testing, commissioning, etc. and should include rates or prices for local transportation to named place of final destination,
insurance and other services incidental to delivery of the plant, all labor, contractor’s equipment, temporary works, materials,
consumables and all matters and things of whatsoever nature, including operations and maintenance services, the provision of
operations and maintenance manuals, training, etc. as necessary for the proper execution of the installation and other services,
including all taxes, duties, levies and charges payable in the Employer’s country
Total Total
Unit WHT
Qty Unit Price1
Price1 (10.5%)
Item DESCRIPTION Unit Price
[4] = [5] =
[1] [2] [3] [2]+[3] [1]x[4]
Schedule A: 33kV Transmission Line from Freetown 161 S/S to Aberdeen S/S
A1 Pole assembly and erection
Intermediate Pole Top Structure (0 - 5°), Dwg No.
A1.1 No 107
ESURP/AF/POLE/33/DC/INT)
Light Angle Pole Top Structure (5o - 20°), Dwg No.
A1.2 No 20
ESURP/AF/POLE/33/DC/TA)
Medium Angle Pole Top Structure (20o - 60°), Dwg No.
A1.3 No 25
ESURP/AF/POLE/33/DC/TA)
Large Angle/Dead end/Terminal Pole Top Structure (60o -
A1.4 No 5
90°), Dwg No. ESURP/AF/POLE/33/DC/TA)
A2 33kV Stay equipment
Stay Equipment complete with pole bracket, clamps, guy rod,
A2.1 bolts and nuts, etc. 33kV Stay Insulator and Stay Wire and Set 86
Stay Block
A2.2 Flying Stay Complete with pole & Accessories No 11
A3 Conductors and OPGW
265mm2 Aluminium Alloy Conductor (AAC) - Insulated
A3.1 km 18.5
(19.1kV)
265mm2 Aluminium Alloy Conductor (AAC) – bare
A3.2 km 6.7
conductor
Optical Ground Wire OPGW (32 fibers) complete (including
A3.3 km 7.7
joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w 35sq.mm
A3.4 Set 140
insulated Cu Conductor, Earth Rod & Clamp
Approach fiber optic cable to link the substation and the
A3.5 m 200
OPGW joint box on the terminal pole
A3.6 OPGW joint box c/w termination Set 4
A4 Cable Works
3x(1x300mm2) 33kV, single core XLPE/SWA/PVC Cu Cable
A4.1 m 450
(route length)
33kV Cable Termination kits (set of 1-phase, 300mm2),
A4.2 Set 12
outdoor
A4.3 33kV Surge Arrestor (Set of 3No) c/w brackets and clamps Set 2
A5 Survey and Bush Clearing
A5.1 Survey and Pegging km 7
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 161
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning, installation,
testing, commissioning, etc. and should include rates or prices for local transportation to named place of final destination,
insurance and other services incidental to delivery of the plant, all labor, contractor’s equipment, temporary works, materials,
consumables and all matters and things of whatsoever nature, including operations and maintenance services, the provision of
operations and maintenance manuals, training, etc. as necessary for the proper execution of the installation and other services,
including all taxes, duties, levies and charges payable in the Employer’s country
Total Total
Unit WHT
Qty Unit Price1
Price1 (10.5%)
Item DESCRIPTION Unit Price
[4] = [5] =
[1] [2] [3] [2]+[3] [1]x[4]
POLES FOUNDATIONS WORKS
Reinforced Concrete foundations, including all associated work such as excavations, soil investigation and foundation
A6
tests, formwork, sheeting, drainage, concrete and stubs including standard grounding, finishing of concrete surface,
Backfill, etc.
Intermediate Pole Top Structure (0 - 5°), Dwg No.
A6.1 No 107
ESURP/AF/POLE/33/INTFOUN)
Light Angle Pole Top Structure (5o - 20°), Dwg No.
A6.2 No 20
ESURP/AF/POLE/33/INTFOUN)
Medium Angle Pole Top Structure (20o - 60°), Dwg No.
A6.3 No 25
ESURP/AF/POLE/33/ASTFOUN)
Large Angle/Dead end/Terminal Pole Top Structure (60o -
A6.4 No 5
90°), Dwg No. ESURP/AF/POLE/33/ASTFOUN)
Sub-Total (Schedule A) carried to Summary
Schedule B: 33kV Transmission Line from Freetown 161 S/S to Falcon Bridge S/S
B1 Pole assembly and erection
Intermediate Pole Top Structure (0 - 5°), Dwg No.
B1.1 No 32
ESURP/AF/POLE/33/DC/INT)
Light Angle Pole Top Structure (5o - 20°), Dwg No.
B1.2 No 5
ESURP/AF/POLE/33/DC/TA)
Medium Angle Pole Top Structure (20o - 60°), Dwg No.
B1.3 No 10
ESURP/AF/POLE/33/DC/TA)
Large Angle/Dead end/Terminal Pole Top Structure (60o -
B1.4 No 5
90°), Dwg No. ESURP/AF/POLE/33/DC/TA)
B2 33kV Stay equipment
Stay Equipment complete with pole bracket, clamps, guy rod,
B2.1 bolts and nuts, etc. 33kV Stay Insulator and Stay Wire and Set 40
Stay Block
B2.2 Flying Stay Complete with pole & Accessories No 4
B3 Conductors and OPGW
265mm2 Aluminium Alloy Conductor (AAC) - Insulated
B3.1 km 12.2
(19.1kV)
265mm2 Aluminium Alloy Conductor (AAC) – bare
B3.2 km 4.3
conductor
Optical Ground Wire OPGW (32 fibers) complete (including
B3.3 km 2.8
joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w 35sq.mm
B3.4 Set 52
insulated Cu Conductor, Earth Rod & Clamp
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 162
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning, installation,
testing, commissioning, etc. and should include rates or prices for local transportation to named place of final destination,
insurance and other services incidental to delivery of the plant, all labor, contractor’s equipment, temporary works, materials,
consumables and all matters and things of whatsoever nature, including operations and maintenance services, the provision of
operations and maintenance manuals, training, etc. as necessary for the proper execution of the installation and other services,
including all taxes, duties, levies and charges payable in the Employer’s country
Total Total
Unit WHT
Qty Unit Price1
Price1 (10.5%)
Item DESCRIPTION Unit Price
[4] = [5] =
[1] [2] [3] [2]+[3] [1]x[4]
Approach fiber optic cable to link the substation and the
B3.5 m 200
OPGW joint box on the terminal pole
B3.6 OPGW joint box c/w termination Set 4
B4 Cable Works
3x(1x300mm2) 33kV, single core XLPE/SWA/PVC Cu Cable
B4.1 m 900
(route length)
33kV Cable Termination kits (set of 1-phase, 300mm2),
B4.2 Set 24
outdoor
B4.3 33kV Surge Arrestor (Set of 3No) c/w brackets and clamps Set 4
B5 Survey and Bush Clearing
B5.1 Survey and Pegging km 2.5
Schedule C: 33kV Transmission Line from Falcon Bridge S/S to Cline Town S/S
C1 Pole assembly and erection
Intermediate Pole Top Structure (0 - 5°), Dwg No.
C1.1 No 39
ESURP/AF/POLE/33/DC/INT)
Light Angle Pole Top Structure (5o - 20°), Dwg No.
C1.2 No 11
ESURP/AF/POLE/33/DC/TA)
Medium Angle Pole Top Structure (20o - 60°), Dwg No.
C1.3 No 6
ESURP/AF/POLE/33/DC/TA)
Large Angle/Dead end/Terminal Pole Top Structure (60o -
C1.4 No 3
90°), Dwg No. ESURP/AF/POLE/33/DC/TA)
C2 33kV Stay equipment
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 163
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning, installation,
testing, commissioning, etc. and should include rates or prices for local transportation to named place of final destination,
insurance and other services incidental to delivery of the plant, all labor, contractor’s equipment, temporary works, materials,
consumables and all matters and things of whatsoever nature, including operations and maintenance services, the provision of
operations and maintenance manuals, training, etc. as necessary for the proper execution of the installation and other services,
including all taxes, duties, levies and charges payable in the Employer’s country
Total Total
Unit WHT
Qty Unit Price1
Price1 (10.5%)
Item DESCRIPTION Unit Price
[4] = [5] =
[1] [2] [3] [2]+[3] [1]x[4]
Stay Equipment complete with pole bracket, clamps, guy rod,
C2.1 bolts and nuts, etc. 33kV Stay Insulator and Stay Wire and Set 40
Stay Block
C2.2 Flying Stay Complete with pole & Accessories No 5
C3 Conductors and OPGW
265mm2 Aluminium Alloy Conductor (AAC) - Insulated
C3.1 km 14
(19.1kV)
265mm2 Aluminium Alloy Conductor (AAC) – bare
C3.2 km 6
conductor
Optical Ground Wire OPGW (32 fibers) complete (including
C3.3 km 3.3
joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w 35sq.mm
C3.4 Set 59
insulated Cu Conductor, Earth Rod & Clamp
Approach fiber optic cable to link the substation and the
C3.5 m 200
OPGW joint box on the terminal pole
C3.6 OPGW joint box c/w termination Set 4
C4 Cable Works
3x(1x300mm2) 33kV, single core XLPE/SWA/PVC Cu Cable
C4.1 m 900
(route length)
33kV Cable Termination kits (set of 1-phase, 300mm2),
C4.2 Set 24
outdoor
C4.3 33kV Surge Arrestor (Set of 3No) c/w brackets and clamps Set 4
C5 Survey and Bush Clearing
C5.1 Survey and Pegging km 3
POLES FOUNDATIONS WORKS
Reinforced Concrete foundations, including all associated work such as excavations, soil investigation and foundation
C6
tests, formwork, sheeting, drainage, concrete and stubs including standard grounding, finishing of concrete surface,
Backfill, etc.
Intermediate Pole Top Structure (0 - 5°), Dwg No.
C6.1 No 39
ESURP/AF/POLE/33/INTFOUN)
Light Angle Pole Top Structure (5o - 20°), Dwg No.
C6.2 No 11
ESURP/AF/POLE/33/INTFOUN)
Medium Angle Pole Top Structure (20o - 60°), Dwg No.
C6.3 6
ESURP/AF/POLE/33/ASTFOUN)
Large Angle/Dead end/Terminal Pole Top Structure (60o -
C6.4 3
90°), Dwg No. ESURP/AF/POLE/33/ASTFOUN)
Sub-Total (Schedule C) carried to Summary
Schedule D: 33kV Transmission Line from Cline Town S/S to Blackhall Road S/S
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 164
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning, installation,
testing, commissioning, etc. and should include rates or prices for local transportation to named place of final destination,
insurance and other services incidental to delivery of the plant, all labor, contractor’s equipment, temporary works, materials,
consumables and all matters and things of whatsoever nature, including operations and maintenance services, the provision of
operations and maintenance manuals, training, etc. as necessary for the proper execution of the installation and other services,
including all taxes, duties, levies and charges payable in the Employer’s country
Total Total
Unit WHT
Qty Unit Price1
Price1 (10.5%)
Item DESCRIPTION Unit Price
[4] = [5] =
[1] [2] [3] [2]+[3] [1]x[4]
D1 Pole assembly and erection
Intermediate Pole Top Structure (0 - 5°), Dwg No.
D1.1 No 13
ESURP/AF/POLE/33/DC/INT)
Light Angle Pole Top Structure (5o - 20°), Dwg No.
D1.2 No 2
ESURP/AF/POLE/33/DC/TA)
Medium Angle Pole Top Structure (20o - 60°), Dwg No.
D1.3 No 4
ESURP/AF/POLE/33/DC/TA)
Large Angle/Dead end/Terminal Pole Top Structure (60o -
D1.4 No 3
90°), Dwg No. ESURP/AF/POLE/33/DC/TA)
D2 33kV Stay equipment
Stay Equipment complete with pole bracket, clamps, guy rod,
D2.1 bolts and nuts, etc. 33kV Stay Insulator and Stay Wire and Set 18
Stay Block
D2.2 Flying Stay Complete with pole & Accessories No 2
D3 Conductors and OPGW
265mm2 Aluminium Alloy Conductor (AAC) - Insulated
D3.1 km 2.4
(19.1kV)
265mm2 Aluminium Alloy Conductor (AAC) – bare
D3.2 Km 5.5
conductor
Optical Ground Wire OPGW (32 fibers) complete (including
D3.3 km 1.3
joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w 35sq.mm
D3.4 Set 24
insulated Cu Conductor, Earth Rod & Clamp
Approach fiber optic cable to link the substation and the
D3.5 m 200
OPGW joint box on the terminal pole
D3.6 OPGW joint box c/w termination Set 2
D4 Cable Works
3x(1x300mm2) 33kV, single core XLPE/SWA/PVC Cu Cable
D4.1 m 900
(route length)
33kV Cable Termination kits (set of 1-phase, 300mm2),
D4.2 Set 24
outdoor
D4.3 33kV Surge Arrestor (Set of 3No) c/w brackets and clamps Set 4
D5 Survey and Bush Clearing
D5.1 Survey and Pegging km 1.2
POLES FOUNDATIONS WORKS
Reinforced Concrete foundations, including all associated work such as excavations, soil investigation and foundation
D6
tests, formwork, sheeting, drainage, concrete and stubs including standard grounding, finishing of concrete surface,
Backfill, etc.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 165
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning, installation,
testing, commissioning, etc. and should include rates or prices for local transportation to named place of final destination,
insurance and other services incidental to delivery of the plant, all labor, contractor’s equipment, temporary works, materials,
consumables and all matters and things of whatsoever nature, including operations and maintenance services, the provision of
operations and maintenance manuals, training, etc. as necessary for the proper execution of the installation and other services,
including all taxes, duties, levies and charges payable in the Employer’s country
Total Total
Unit WHT
Qty Unit Price1
Price1 (10.5%)
Item DESCRIPTION Unit Price
[4] = [5] =
[1] [2] [3] [2]+[3] [1]x[4]
Intermediate Pole Top Structure (0 - 5°), Dwg No.
D6.1 No 13
ESURP/AF/POLE/33/INTFOUN)
Light Angle Pole Top Structure (5o - 20°), Dwg No.
D6.2 No 2
ESURP/AF/POLE/33/INTFOUN)
Medium Angle Pole Top Structure (20o - 60°), Dwg No.
D6.3 No 4
ESURP/AF/POLE/33/ASTFOUN)
Large Angle/Dead end/Terminal Pole Top Structure (60o -
D6.4 No 3
90°), Dwg No. ESURP/AF/POLE/33/ASTFOUN)
Sub-Total (Schedule D) carried to Summary
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 166
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning, installation,
testing, commissioning, etc. and should include rates or prices for local transportation to named place of final destination,
insurance and other services incidental to delivery of the plant, all labor, contractor’s equipment, temporary works, materials,
consumables and all matters and things of whatsoever nature, including operations and maintenance services, the provision of
operations and maintenance manuals, training, etc. as necessary for the proper execution of the installation and other services,
including all taxes, duties, levies and charges payable in the Employer’s country
Total Total
Unit WHT
Qty Unit Price1
Price1 (10.5%)
Item DESCRIPTION Unit Price
[4] = [5] =
[1] [2] [3] [2]+[3] [1]x[4]
E4 Cable Works
3x(1x300mm2) 33kV, single core XLPE/SWA/PVC Cu Cable
E4.1 m 450
(route length)
33kV Cable Termination kits (set of 1-phase, 300mm2),
E4.2 Set 12
outdoor
E4.3 33kV Surge Arrestor (Set of 3No) c/w brackets and clamps Set 2
E5 Survey and Bush Clearing
E5.1 Survey and Pegging km 13.5
POLES FOUNDATIONS WORKS
Reinforced Concrete foundations, including all associated work such as excavations, soil investigation and foundation
E6
tests, formwork, sheeting, drainage, concrete and stubs including standard grounding, finishing of concrete surface,
Backfill, etc.
Intermediate Pole Top Structure (0 - 5°), Dwg No.
E6.1 No 184
ESURP/AF/POLE/33/INTFOUN)
Light Angle Pole Top Structure (5o - 20°), Dwg No.
E6.2 No 24
ESURP/AF/POLE/33/INTFOUN)
Medium Angle Pole Top Structure (20o - 60°), Dwg No.
E6.3 32
ESURP/AF/POLE/33/ASTFOUN)
Large Angle/Dead end/Terminal Pole Top Structure (60o -
E6.4 6
90°), Dwg No. ESURP/AF/POLE/33/ASTFOUN)
Sub-Total (Schedule E) carried to Summary
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 167
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning, installation,
testing, commissioning, etc. and should include rates or prices for local transportation to named place of final destination,
insurance and other services incidental to delivery of the plant, all labor, contractor’s equipment, temporary works, materials,
consumables and all matters and things of whatsoever nature, including operations and maintenance services, the provision of
operations and maintenance manuals, training, etc. as necessary for the proper execution of the installation and other services,
including all taxes, duties, levies and charges payable in the Employer’s country
Total Total
Unit WHT
Qty Unit Price1
Price1 (10.5%)
Item DESCRIPTION Unit Price
[4] = [5] =
[1] [2] [3] [2]+[3] [1]x[4]
F1.8 Double Circuit Tower Type DE of basic height No 2
Double Circuit Tower Type Specially designed for 90 deg
F1.9 No 1
Angle
F2 Conductors and OPGW
F3.1 265mm2 Aluminium Alloy Conductor (AAC) km 46.8
F3.2 Vibration dampers for 265mm2 AAC 732
Optical Ground Wire OPGW (32 fibers) complete (including
F3.3 km 7.2
joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w 35sq.mm
F3.4 Set 61
insulated Cu Conductor, Earth Rod & Clamp
Approach fiber optic cable to link the substation and the
F3.5 m 400
OPGW joint box on the terminal pole
F3.6 OPGW joint box c/w termination Set 4
F3 33kV Insulators & Fittings Designed for 265mm2 AAC
33kV Polymeric suspension insulator sets including fittings
F3.1 Set 156
and hardware
33kV Polymeric tension insulator set including fittings and
F3.2 Set 420
hardware
F4 Counterpoise Grounding
F4.1 Counterpoise grounding additional to the standard grounding No 12
F5 Cable Works
3x(1x300mm2) 33kV, single core XLPE/SWA/PVC Cu Cable
F5.1 m 900
(route length)
33kV Cable Termination kits (set of 1-phase, 300mm2),
F5.2 Set 24
outdoor
F5.3 33kV Surge Arrestor (Set of 3No) c/w brackets and clamps Set 4
F6 Survey
F6.1 Tower spotting and Pegging km 6.5
TOWERS FOUNDATIONS WORKS
Reinforced Concrete foundations, including all associated work such as excavations, soil investigation and foundation
F7
tests, formwork, sheeting, drainage, concrete and stubs including standard grounding, finishing of concrete surface,
Backfill, etc.
Double Circuit Lattice Tower Type SS - Foundation in Normal
F7.1 No 21
Soil
Double Circuit Lattice Tower Type SS - Foundation in Wet
F7.2 No 3
Soil
Double Circuit Lattice Tower Type SS - Foundation in
F7.3 No 2
Unfractured Rock
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 168
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning, installation,
testing, commissioning, etc. and should include rates or prices for local transportation to named place of final destination,
insurance and other services incidental to delivery of the plant, all labor, contractor’s equipment, temporary works, materials,
consumables and all matters and things of whatsoever nature, including operations and maintenance services, the provision of
operations and maintenance manuals, training, etc. as necessary for the proper execution of the installation and other services,
including all taxes, duties, levies and charges payable in the Employer’s country
Total Total
Unit WHT
Qty Unit Price1
Price1 (10.5%)
Item DESCRIPTION Unit Price
[4] = [5] =
[1] [2] [3] [2]+[3] [1]x[4]
Double Circuit Lattice Tower Type ST1 - Foundation in
F7.4 No 23
Normal Soil
Double Circuit Lattice Tower Type ST1 - Foundation in Wet
F7.5 No 3
Soil
Double Circuit Lattice Tower Type ST1 - Foundation in
F7.6 No 6
Unfractured Rock
Double Circuit Lattice Tower Type DE - Foundation in
F7.7 No 1
Normal Soil
Double Circuit Lattice Tower Type DE - Foundation in Wet
F7.8 No 1
Soil
Double Circuit Lattice Tower Type DE - Foundation in
F7.9 No 1
Unfractured Rock
Sub-Total (Schedule F) carried to Summary
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 169
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning, installation,
testing, commissioning, etc. and should include rates or prices for local transportation to named place of final destination,
insurance and other services incidental to delivery of the plant, all labor, contractor’s equipment, temporary works, materials,
consumables and all matters and things of whatsoever nature, including operations and maintenance services, the provision of
operations and maintenance manuals, training, etc. as necessary for the proper execution of the installation and other services,
including all taxes, duties, levies and charges payable in the Employer’s country
Total Total
Unit WHT
Qty Unit Price1
Price1 (10.5%)
Item DESCRIPTION Unit Price
[4] = [5] =
[1] [2] [3] [2]+[3] [1]x[4]
Approach fiber optic cable to link the substation and the
G2.5 m 400
OPGW joint box on the terminal pole
G2.6 OPGW joint box c/w termination Set 4
G3 33kV Insulators & Fittings Designed for 265mm2 AAC
33kV Polymeric suspension insulator sets including fittings
G3.1 Set 450
and hardware
33kV Polymeric tension insulator set including fittings and
G3.2 Set 672
hardware
G4 Counterpoise Grounding
G4.1 Counterpoise grounding additional to the standard grounding No 26
G5 Cable Works
3x(1x300mm2) 33kV, single core XLPE/SWA/PVC Cu Cable
G5.1 m 900
(route length)
33kV Cable Termination kits (set of 1-phase, 300mm2),
G5.2 Set 24
outdoor
G5.3 33kV Surge Arrestor (Set of 3No) c/w brackets and clamps Set 4
G6 Survey
G6.1 Tower spotting and Pegging km 17
TOWERS FOUNDATIONS WORKS
Reinforced Concrete foundations, including all associated work such as excavations, soil investigation and foundation
G7
tests, formwork, sheeting, drainage, concrete and stubs including standard grounding, finishing of concrete surface,
Backfill, etc.
Double Circuit Lattice Tower Type SS - Foundation in Normal
G7.1 No 61
Soil
Double Circuit Lattice Tower Type SS - Foundation in Wet
G7.2 No 9
Soil
Double Circuit Lattice Tower Type SS - Foundation in
G7.3 No 5
Unfractured Rock
Double Circuit Lattice Tower Type ST1 - Foundation in
G7.4 No 37
Normal Soil
Double Circuit Lattice Tower Type ST1 - Foundation in Wet
G7.5 No 4
Soil
Double Circuit Lattice Tower Type ST1 - Foundation in
G7.6 No 10
Unfractured Rock
Double Circuit Lattice Tower Type DE - Foundation in
G7.7 No 3
Normal Soil
Double Circuit Lattice Tower Type DE - Foundation in Wet
G7.8 No 1
Soil
Double Circuit Lattice Tower Type DE - Foundation in
G7.9 No 1
Unfractured Rock
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 170
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning, installation,
testing, commissioning, etc. and should include rates or prices for local transportation to named place of final destination,
insurance and other services incidental to delivery of the plant, all labor, contractor’s equipment, temporary works, materials,
consumables and all matters and things of whatsoever nature, including operations and maintenance services, the provision of
operations and maintenance manuals, training, etc. as necessary for the proper execution of the installation and other services,
including all taxes, duties, levies and charges payable in the Employer’s country
Total Total
Unit WHT
Qty Unit Price1
Price1 (10.5%)
Item DESCRIPTION Unit Price
[4] = [5] =
[1] [2] [3] [2]+[3] [1]x[4]
Sub-Total (Schedule G) carried to Summary
Schedule H: 33kV Transmission Line from Blackhall Road S/S to Wellington S/S
H1 Conductors and OPGW
H1.1 265mm2 Aluminium Alloy Conductor (AAC) km 27.4
H1.2 Vibration dampers for 265mm2 AAC 672
Optical Ground Wire OPGW (32 fibers) complete (including
H1.3 km 8.4
joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w 35sq.mm
H1.4 Set 56
insulated Cu Conductor, Earth Rod & Clamp
Approach fiber optic cable to link the substation and the
H1.5 m 200
OPGW joint box on the terminal pole
H1.6 OPGW joint box c/w termination Set 4
H2 33kV Insulators & Fittings Designed for 265mm2 AAC
33kV Polymeric suspension insulator sets including fittings
H2.1 Set 98
and hardware
33kV Polymeric tension insulator set including fittings and
H2.2 Set 148
hardware
H3 Counterpoise Grounding
H3.1 Counterpoise grounding additional to the standard grounding No 12
H4 Cable Works
3x(1x300mm2) 33kV, single core XLPE/SWA/PVC Cu Cable
H4.1 m 450
(route length)
33kV Cable Termination kits (set of 1-phase, 300mm2),
H4.2 Set 24
outdoor
H4.3 33kV Surge Arrestor (Set of 3No) c/w brackets and clamps Set 4
Sub-Total (Schedule H) carried to Summary
Schedule I: Upgrade of 33kV Transmission Line Between Freetown 161 S/S, Blackhall Road S/S and Wilberforce S/S
(Provisional amount subject to analysis/adequacy assessment of existing towers and foundations)
I1 33kV, Double Circuit Lattice Towers
Reinforcement of existing Intermediate (IMP) (0 – 1 degree)
I1.1 No 15
Double Circuit lattice Tower Complete with all accessories
Reinforcement of existing Light Angle (1 – 15 degrees)
I1.2 No 15
Double Circuit Tower Complete with all accessories
Reinforcement of existing Intermediate (IMP) (0 – 1 degree)
I1.3 No 81
Double Circuit lattice Tower Complete with all accessories
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 171
SCHEDULE No. 4: Installation and Other Services including but not limited to: construction, decommissioning, installation,
testing, commissioning, etc. and should include rates or prices for local transportation to named place of final destination,
insurance and other services incidental to delivery of the plant, all labor, contractor’s equipment, temporary works, materials,
consumables and all matters and things of whatsoever nature, including operations and maintenance services, the provision of
operations and maintenance manuals, training, etc. as necessary for the proper execution of the installation and other services,
including all taxes, duties, levies and charges payable in the Employer’s country
Total Total
Unit WHT
Qty Unit Price1
Price1 (10.5%)
Item DESCRIPTION Unit Price
[4] = [5] =
[1] [2] [3] [2]+[3] [1]x[4]
Reinforcement of existing Heavy Angle (IMP) (16 – 90
I1.4 No 35
degree) Double Circuit Tower Complete with all accessories
Reinforcement of existing Terminal Double Circuit Tower
I1.5 No 6
Complete with 33kV Lightening arrestors and all accessories
Reinforcement of existing Section Double Circuit Tower
I1.6 No 60
Complete with all accessories
I2 Conductors and OPGW
I2.1 265mm2 Aluminium Alloy Conductor (AAC) km 138.0
I2.2 Vibration dampers for 265mm2 AAC 2,544
Optical Ground Wire OPGW (32 fibers) complete (including
I2.3 km 24.0
joints kit & fittings) as Earth wire
Grounding for Optical Ground Wire OPGW c/w 35sq.mm
I2.4 Set 212
insulated Cu Conductor, Earth Rod & Clamp
Approach fiber optic cable to link the substation and the
I2.5 m 400
OPGW joint box on the terminal pole
I2.6 OPGW joint box c/w termination Set 6
I3 33kV Insulators & Fittings Designed for 265mm2 AAC
33kV Polymeric suspension insulator sets including fittings
I3.1 Set 90
and hardware
33kV Polymeric tension insulator set including fittings and
I3.2 Set 2,364
hardware
I4 Counterpoise Grounding
I4.1 Counterpoise grounding additional to the standard grounding No 22
I5 Cable Works
3x(1x300mm2) 33kV, single core XLPE/SWA/PVC Cu Cable
I5.1 m 1,350
(route length)
33kV Cable Termination kits (set of 1-phase, 300mm2),
I5.2 Set 36
outdoor
I5.3 33kV Surge Arrestor (Set of 3No) c/w brackets and clamps Set 6
Sub-Total (Schedule I) carried to Summary
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 172
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 173
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 174
Name of Bidder
Signature of
Bidder
1
Specify currency in accordance with ITB 18. Create and use as many columns for Foreign Currency
requirement as there are foreign currencies
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 175
Name of Bidder
Signature of Bidder
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 176
Price Adjustment
Not Applicable
Technical Proposal
- Site Organization
- Method Statement
- Mobilization Schedule
- Construction Schedule
- Plant
- Contractor’s Equipment
- Personnel
- Proposed Subcontractors for Major Items of Plant and Installation Services
- Others
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 177
Site Organization
Bidders shall provide the hierarchical organization chart indicating head office and field
personnel that would be involved in the Management and Construction works.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 178
Method Statement
Provide adequate narrative detailing the sequence and methods to carry out the
works in strict adherence to the specifications and the Environmental and Social
Safeguard policies of the Bank including:
• Design, Supply & Installation: Substation, and equipment design procedure,
the procedure for procurement of major equipment and materials, procedure
for civil & installation work;
• Quality control measures: Adequate narration of specific quality control
measures at design, manufacture, erection, installation, testing and
commissioning stages of the project. The presentation shall include
recruitment/selection of the subcontractors/sub suppliers if any and how they
will be supervised;
• Environment, Social, Health and Safety (ESHS) Management Strategy and
Implementation Plans (C-ESMP): The preliminary Contractor’s
Environmental, Health and Social Management Plan should include an
identification of expected Environmental, Health and safety hazards, and
mitigation measures that will be adopted to ensure that the projects are
completed without accidents, and with minimum negative impact on the
environment. Bidders shall prepare their preliminary C-ESMP based on the
ESMP in the ESHIA report prepared by EDSA. The ESHIA report would be
made available to prospective bidders;
• Workers’ ESHS Code of Conduct: Adequacy of ESHS Code of Conduct that
will apply to the employees and sub-contractors of the contractor, and
details of how it will be enforced
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 179
Mobilization Schedule
Bidders shall provide the mobilization schedule in the form of bar chart showing the schedule
for undertaking the activities leading to contract effectiveness and the sequence of mobilizing
personnel and work items to site.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 180
Construction Schedule
Bidders shall provide the construction schedule in a bar chart form showing the sequence for
undertaking the key events from notification of award through construction up until
commissioning, handover and defect liability period. The activities should include but not
limited to the period for site testing, detailed designs, civil works, procurement of materials,
manufacturing, delivering, installation of equipment, testing, commissioning and hand over
(provision of as-built-documentation).
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 181
Plant
Bidders shall complete the Technical Data Sheet (Technical Schedules) for all plants as
requested in the Technical Specifications and provided below.
The Technical Schedules form an integral part of the corresponding Technical Specifications
in Volume II of this bidding document and shall be completed as follows:
The Bidder shall be bound to adhere strictly to the requirements, design data and criteria as
stated in these Technical Schedules or elsewhere in the Specifications.
Concerning the Technical Schedules only the "Offered" columns of the following pages must
be filled-in by the Bidder, without omission. The manner and breakdown of these pages must
not be changed, i.e. the Bidder must in no case add or change anything within the
requirements or the "Required" columns. The values stated by the Bidder shall be guaranteed
values. If a particular item is not applicable or not quoted, the letters NA (not applicable) or
NQ (not quoted) shall be typed in the space provided. For any data not duly inserted in the
data sheets, the most unfavorable data stated by any competitor may be used for evaluation
purposes. The Employer also reserves the right to reject all such bids.
If the Bidder's bid contains deviations from the "Specifications" ("Technical Characteristics"
and/or Technical Schedules), these and any further explanations must be stated on extra
sheets only, clearly declared as "List of Deviations".
All these points in which the "Specifications" ("Technical Characteristics" and/or Technical
Schedules) cannot be fulfilled shall be stated and explained separately. Whenever the Bidder
is able to bid better values than required, they are invited to state this. The expression like "or
equivalent" for the manufacturers' names is unacceptable and shall be disregarded
The schedules should be accompanied by the relevant equipment manuals/brochures)
Each Schedule shall be signed off by the bidder as indicated below:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 182
The column headed “Bidder’s Offer” shall be completed and each page of the Schedules signed and
stamped by the bidder. Bidders should also attach relevant equipment manuals/brochures.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 183
Table of Contents
Technical Schedule/Data Sheet for 161/33kV, 35/40MVA Power Transformer ................. 185
Technical Schedule/Data Sheet for 161kV Outdoor live Tank Circuit Breaker ................... 194
Technical Schedule/Data Sheet for 161kV Outdoor Disconnect Switch .............................. 199
Technical Schedule/Data Sheet for 161kV Outdoor Current Transformers ......................... 203
Technical Schedule/Data Sheet for 161kV Outdoor Post Insulators .................................... 204
Technical Schedule/Data Sheet for 161kV Outdoor Surge Arresters ................................... 205
Technical Schedule/Data Sheet for 33kV Outdoor Live Tank Circuit Breakers .................. 206
Technical Schedule/Data Sheet for 33kV Outdoor Disconnect Switches ............................ 208
Technical Schedule/Data Sheet for 33kV Outdoor Earthing Switches ................................ 210
Technical Schedule/Data Sheet for 33kV Outdoor Post Insulators ...................................... 212
Technical Schedule/Data Sheet for 33kV Outdoor Voltage Transformers .......................... 213
Technical Schedule/Data Sheet for 33kV Outdoor Current Transformers ........................... 215
Technical Schedule/Data Sheet for 33/11 KV, 20/26 MVA Power Transformers ............... 216
Technical Schedule/Data Sheet for 11/0.415 kV, 100kVA Auxiliary Services Transformer
............................................................................................................................................... 220
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Single
Busbar) .................................................................................................................................. 224
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Double
Busbar) .................................................................................................................................. 233
Technical Schedule/Data Sheet for 11 KV Metal Clad Air Insulated Switchgear ............... 243
Technical Schedule/Data Sheet for MV/LV Substation Protection Relays/Schemes .......... 251
Technical Schedule/Data Sheet for 1Cx300mm2 33 kV Cables and Terminations .............. 266
Technical Schedule/Data Sheet for 1Cx300mm2 11 kV Cables and Terminations .............. 270
Technical Schedule/Data Sheet for 3Cx240mm2 11 kV Cables and Terminations .............. 274
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 184
Technical Schedule/Data Sheet for 3Cx70mm2 11 kV Cables and Terminations ................ 278
Technical Schedule/Data Sheet for 4Cx70mm2 0.4 kV Cables and Terminations ............... 282
Technical Schedule/Data Sheet for Control and Signal Cables without Armoring (4, 7, 12, 19,
27x2.5mm2)........................................................................................................................... 286
Technical Schedule/Data Sheet for Control and Signal Cables with Steel Tape Armoring (4,
7, 12, 19, 27x2.5mm2)........................................................................................................... 289
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 185
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 186
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 187
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 188
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 189
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 190
- material Copper
- current density at rated power and voltage
(A/sq.mm):
- HV winding (40MVA) Bidder to provide
- Regulation winding Bidder to provide
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 191
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 192
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 193
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 194
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 195
Technical Schedule/Data Sheet for 161kV Outdoor live Tank Circuit Breaker
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 196
Technical Schedule/Data Sheet for 161kV Outdoor live Tank Circuit Breaker
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 197
Technical Schedule/Data Sheet for 161kV Outdoor live Tank Circuit Breaker
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 198
Technical Schedule/Data Sheet for 161kV Outdoor live Tank Circuit Breaker
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 199
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 200
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 201
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 202
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 203
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 204
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 205
Service Condition
- elevation above sea level m <1000
- ambient temperature
0
- maximum value C +40
0
- minimum value C +15
0
- average yearly value C +30
Type/Class Bidder to provide
Nominal Voltage kV 161
Rated Voltage kV 156
Nominal Discharge Current kA 10
IEC Discharge Class 3
Lightning Impulse Protection Level kV peak 406
Energy Discharge Capacity kJ/kV 7.5
Porcelain Housing:
- Lightning Impulse Test Value kV peak 750
-Power Frequency Voltage Test Value kV rms 325
Minimum creepage distance mm 5100
Steel Supporting Structure Yes
Minimum height of steel supporting mm 3000
Structure
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 206
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 207
Technical Schedule/Data Sheet for 33kV Outdoor Live Tank Circuit Breakers
Description Unit Required Bidder’s Offer
IEC60056)
Rated Short Line Fault Line Characteristic (Table V IEC
60056)
Rated Duration of Short Circuit 1sec.
Rated Out-Of-Phase Breaking Current kA kA (IEC 60056)
(with rate of rise 0.43kV/tts)
Rated Operating Sequence O-0.3S-CO-3 min-
CO
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 208
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 209
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 210
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 211
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 212
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 213
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 214
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 215
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 216
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 217
Technical Schedule/Data Sheet for 33/11 KV, 20/26 MVA Power Transformers
Description Unit Required Bidder’s Offer
- Secondary side kA 25
Short time duration s 3
Tap Changer On-load
Tapped winding HV
Principle tapping kV 33
Tapping range ±% ±10
Number of steps ± steps ± 8 x 1.25%
Vector group Dyn11
Insulation uniform
Type of cooling ONAN/ ONAF
No-load losses at rated frequency and kW 12
100% voltage - maximum value
Load losses at rated frequency and
100% voltage (75°C) – maximum
value
- ONAN kW 80
- ONAF kW 100
Material of winding copper
Temperature rise at rated power over
35°C maximum ambient [Performance
Guarantee]
- oil (upper level) °C 45
- winding °C 55
- hot spot winding °C 68
Rated power frequency withstand kV 70/28
voltage 33/11 kV (50Hz, 1min)
Rated lightning impulse withstand
voltage
- 33kV windings kV peak 170
- 11 kV windings kV peak 75
Short circuit impedance at nominal % 10
power
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 218
Technical Schedule/Data Sheet for 33/11 KV, 20/26 MVA Power Transformers
Description Unit Required Bidder’s Offer
operating), with rated voltage and
frequency at a measuring distance of
2m
Maximum no-load current % In 0.2
Painting Admiralty Grey shade
No. 632 as per BS 381C
Dimensions
- length mm Bidder to provide
- width mm Bidder to provide
- height mm Bidder to provide
- distance between wheels' centers mm Bidder to provide
Total weight kg Bidder to provide
Oil weight kg Bidder to provide
Applicable standard(s) IEC 60076
Transformer Bushings
- Maximum current carrying capacity
of bushings:
- HV A 120% of IN
- LV A 120% of IN
- Rated service voltage of bushings:
- 33 kV kV 36
- 11 kV, neutral kV 12
- 1 minute, 50 Hz dry withstand
voltage:
- HV bushing kV 70
- LV bushing kV 28
- Impulse withstand voltage:
- HV bushing kV 170
- LV bushing kV 75
Bushing Current transformer – 33 kV HV
- Number of metering cores per 1
bushing
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 219
Technical Schedule/Data Sheet for 33/11 KV, 20/26 MVA Power Transformers
Description Unit Required Bidder’s Offer
- Number of protection cores per 3
bushing
- Accuracy Class metering core 0.2 S FS 5
- Accuracy Class protection cores 5P20
- Burden metering core VA 10
- Burden protection cores VA 30
- Secondary Rated Current A 1
- Ratio (secondary tap) 600-400:1
Bushing Current transformer – Neutral
SEF = Sensitive Earth Fault SEF / REF
REF = Restricted Earth Fault
Number of protection cores 1/1
Accuracy Class protection cores * / 5P20
Burden protection cores VA * / 30
Secondary Rated Current A 1/1
Ratio (secondary tap) *:1 / 100-200:1
‘* to be specified according to
protection relay requirement
Primary terminal box
- Type Air filled cable box
- Termination type Bidder to provide
- Cables 3X(1X300mm2)
Secondary terminal box
- Type Air filled cable box
- Termination type Bidder to provide
- Cables 4x3x(1x300mm2) +
1x(1x300mm2)
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 220
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 221
Technical Schedule/Data Sheet for 11/0.415 kV, 100kVA Auxiliary Services Transformer
Description Unit Required Bidder’s Offer
Principal tapping at kV 11
Tapping range ±% ± 2 x 2.5
Number of steps ± ±2
Vector group Dyn11
Insulation uniform
Type of cooling ONAN
No-load losses at rated frequency and kW 0.145
100% voltage - maximum value
Load losses at rated frequency and 100% 1.75
voltage (75°C) - maximum value
Material of winding copper
Temperature rise at rated power over 35°C
maximum ambient [Performance
Guarantee]
- oil (upper level) °C 45
- winding °C 55
- hot spot winding °C 68
Rated power frequency withstand voltage
- 11kV bushings kV 28
- 11kV windings kV 28
Rated lightning impulse withstand voltage:
- 11kV bushings kV peak 75
- 11 kV windings kV peak 75
Short circuit impedance at nominal power % 4
Maximum noise level (LpA) at mean tap, dB (A) 70
with rated voltage and frequency at a
measuring distance of 2m
Maximum no-load current % In 0.2
Painting Admiralty Grey
shade No. 632 as per
BS 381C
Dimensions
- length mm Bidder to provide
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 222
Technical Schedule/Data Sheet for 11/0.415 kV, 100kVA Auxiliary Services Transformer
Description Unit Required Bidder’s Offer
- width mm Bidder to provide
- height mm Bidder to provide
- distance between wheels' centers mm Bidder to provide
Total weight kg Bidder to provide
Oil weight kg Bidder to provide
Applicable standard(s) IEC 60076
Transformer Bushings
- Maximum current carrying capacity of
bushings:
- HV A 120% of IN
- LV A 120% of IN
- Rated service voltage of bushings:
- HV kV 11
- LV kV 0.415
- LV neutral kV 0.415
Primary terminal box
- Type Air filled cable box
- Termination type Bidder to provide
- Cables 3Cx70mm2 11kV
XLPE/SWA/PVC Cu
Secondary terminal box
- Type Air filled cable box
- Termination type Bidder to provide
- Cables 4Cx70mm2 0.4kV
XLPE/SWA/PVC Cu
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 223
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 224
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 225
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Single Busbar)
Description Unit Required Bidder’s Offer
- LV compartments IP5X
SLD mimic diagram on the front of cubicles yes/no yes
CIRCUIT BREAKER
Manufacturer name Bidder to provide
Country of manufacturing Bidder to provide
Manufacturer’s type designation Bidder to provide
Type tested yes/no Yes
Standards IEC 62271-100
Class E2, M2, C2
Arc quenching medium type vacuum
Combined earthing and busbar yes/no Yes
disconnecting
Number of phases 3
Operating voltage kV 33
Rated voltage kV 36
Max. continuous system voltage kV 36
Impulse withstand voltage (peak) kV 170
Power frequency withstand voltage (1 kV 70
min.):
Rated frequency Hz 50
Rated short-time withstand current (3 s) kA 25
Rated peak short circuit current kA 63
Rated normal current:
- incoming/outgoing A 1250
- transformer A 1250
- bus section A 1250
Rated short circuit breaking current kA 25
Rated short circuit making current kA 63
Rated cable charging breaking current A Bidder to provide
Maximum capacitive breaking current A Bidder to provide
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 226
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Single Busbar)
Description Unit Required Bidder’s Offer
Rated operating sequence O-0.3Sec-CO- 3min
- CO
Closing time ms <60
Dead time ms 300
Break time ms <60
Make time ms <60
Arcing time ms <15
Live span of contacts (for no. of operations)
- at rated continuous current no. 10,000
- at rated breaking current no. 100
Auxiliary contacts:
- number of NO no. 10NO
- number of NC no. 10NC
- voltage rating Vdc 110
- current rating A 10A
No. of making coil No 1
No. of tripping coil No 2
Operating mechanism
- for closing Spring
- for opening Spring
Motor
- voltage Vdc 110
- maximum spring recharging time s 25
- power W Bidder to provide
Hand operating facilities yes/no Yes
MAINTENANCE BUSBAR EARTHING
SWITCH
Manufacturer name Bidder to provide
Country of manufacturing Bidder to provide
Manufacturer’s type designation Bidder to provide
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 227
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Single Busbar)
Description Unit Required Bidder’s Offer
Type tested yes/ Yes
no
Standards IEC
Operating voltage kV 33
Rated voltage kV 36
Max. continuous system voltage kV 36
Impulse withstand voltage (peak) kV 170
Power frequency withstand voltage (1 kV 70
min.):
Rated current A Bidder to provide
Rated short-time withstand current (3 s) kA 25
Rated peak short circuit current kA 63
Auxiliary contacts:
- number of NO no. 10NO
- number of NC no. 10NC
- voltage rating Vdc 110
- current rating A 10A
Operating mechanism Spring
Motor
- voltage Vdc 110
- maximum spring recharging time s 25
- power W Bidder to provide
Hand operating facilities yes/no Yes
MAINTENANCE EARTHING SWITCH
(FEEDERS AND POWER
TRANSFORMERS)
Manufacturer name Bidder to provide
Country of manufacturing Bidder to provide
Manufacturer’s type designation Bidder to provide
Type tested yes/no Yes
Standards IEC
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 228
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Single Busbar)
Description Unit Required Bidder’s Offer
Operating voltage kV 33
Rated voltage kV 36
Max. continuous system voltage kV 36
Impulse withstand voltage (peak) kV 170
Power frequency withstand voltage (1 kV 70
min.):
Rated current A Bidder to provide
Rated short-time withstand current (3 s) kA 25
Rated peak short circuit current kA 63
Auxiliary contacts:
- number of NO no. 10NO
- number of NC no. 10NC
- voltage rating Vdc 110
- current rating A 10A
Operating mechanism Manual
CURRENT TRANSFORMERS
Manufacturer name Bidder to provide
Country of manufacturing Bidder to provide
Manufacturer’s type designation Bidder to provide
Type tested yes/no Yes
Standards IEC
Operating voltage kV 33
Rated voltage kV 36
Max. continuous system voltage kV 36
Impulse withstand voltage (peak) kV 170
Power frequency withstand voltage (1 kV 70
min.):
Rated frequency Hz 50
Arrangement Cast resin, Indoor
Number of phases Single
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 229
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Single Busbar)
Description Unit Required Bidder’s Offer
Rated primary current for:
- incoming/outgoing A 800-400
- power transformer A 600-400
- bus sectionalizer A 1200-600
Rated secondary current for power
transformer
- Control measuring core 1 A 1
- Control & Protection core 2 A 1
- Protection core 3 A 1
Accuracy class
- core 1 0.2s
- core 2 5P20
- core 3 PX
Burden
- core 1 VA Bidder to indicate as
per requirement of
protection scheme
- core 2 VA Bidder to indicate as
per requirement of
protection scheme
- core 3 VA Bidder to indicate as
per requirement of
protection scheme
Rated secondary current for
incoming/outgoing feeders
- Control measuring core 1 A 1
- Control & Protection core 2 A 1
- Protection core 3 A 1
Accuracy class
- core 1 0.2s
- core 2 5P20
- core 3 PX
Burden
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 230
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Single Busbar)
Description Unit Required Bidder’s Offer
- core 1 VA Bidder to indicate as
per requirement of
protection scheme
- core 2 VA Bidder to indicate as
per requirement of
protection scheme
- core 3 VA Bidder to indicate as
per requirement of
protection scheme
Rated secondary current for bus
sectionalizer
- Control measuring core 1 A 1
- Control & Protection core 2 A 1
- Protection core 3 A 1
Accuracy class
- core 1 0.2s
- core 2 5P20
- core 3 PX
Burden
- core 1 VA Bidder to indicate as
per requirement of
protection scheme
- core 2 VA Bidder to indicate as
per requirement of
protection scheme
- core 3 VA Bidder to indicate as
per requirement of
protection scheme
VOLTAGE TRANSFORMERS
Manufacturer name Bidder to provide
Country of manufacturing Bidder to provide
Manufacturer’s type designation Bidder to provide
Type tested yes/no Yes
Standards IEC
Operating voltage kV 33
Rated voltage kV 36
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 231
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Single Busbar)
Description Unit Required Bidder’s Offer
Max. continuous system voltage kV 36
Impulse withstand voltage (peak) kV 170
Power frequency withstand voltage (1 kV 70
min.):
Rated frequency Hz 50
Insulation material Cast resin, Indoor
Number of phases No. 1
Rated primary voltage kV 33/ √3
Rated secondary voltage V 110 / √3/ 110 / √3
Voltage transformers for busbars
Accuracy class
- core 1 metering 0.2
- core 2 protection 3P
Burden
- core 1 metering VA Bidder to indicate as
per requirement of
protection scheme
- core 2 protection VA Bidder to indicate as
per requirement of
protection scheme
Voltage transformers for incoming/outgoing
feeders
Accuracy class
- core 1 metering 0.2
- core 2 protection 3P
Burden
- core 1 metering VA Bidder to indicate as
per requirement of
protection scheme
- core 2 protection VA Bidder to indicate as
per requirement of
protection scheme
SURGE ARRESTER
Manufacturer name Bidder to provide
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 232
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Single Busbar)
Description Unit Required Bidder’s Offer
Country of manufacturing Bidder to provide
Manufacturer’s type designation Bidder to provide
Type tested yes/no Yes
Standards IEC
Operating voltage kV 33
Rated voltage kV 36
Max. continuous system voltage kV 36
Impulse withstand voltage (peak) kV 170
Power frequency withstand voltage (1 kV 70
min.):
Rated frequency Hz 50
Normal Discharge Current kA 10
IEC Discharge Class 2
Lightning Impulse Protection kV 94
METERING DEVICES, INSTRUMENTS As per requirements
of Technical
Specifications for
33kV Indoor
Metalclad
Switchgear
PROTECTION As per requirements
of relevant
Technical
Specifications for
Protection
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 233
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 234
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Double Busbar)
Description Unit Required Bidder’s Offer
- LV compartments IP5X
SLD mimic diagram on the front of cubicles yes/no yes
MAIN BUSBAR DISCONNECTOR
Manufacturer name Bidder to provide
Country of manufacturing Bidder to provide
Manufacturer’s type designation Bidder to provide
Type tested yes/no Yes
Standards IEC 62271-102
Number of phases 3
Installation indoor
No load operation only yes Yes
Operating voltage kV 33
Rated voltage kV 36
Max. continuous system voltage kV 36
Impulse withstand voltage (peak) kV 170
Power frequency withstand voltage (1 kV 70
min.):
System frequency Hz 50
Rated current A 1250
Rated short-time withstand current (3 s) kA 25
Rated peak short circuit current kA 63
Operating mechanism Motor
- voltage Vdc 110
- power W Bidder to provide
Hand operating facilities yes/no Yes
Auxiliary contacts:
- number of NO no. 10NO
- number of NC no. 10NC
- voltage rating Vdc 110
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 235
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Double Busbar)
Description Unit Required Bidder’s Offer
- current rating A 10A
CIRCUIT BREAKER
Manufacturer name Bidder to provide
Country of manufacturing Bidder to provide
Manufacturer’s type designation Bidder to provide
Type tested yes/no Yes
Standards IEC 62271-100
Class E2, M2, C2
Arc quenching medium type vacuum
Combined earthing and busbar yes/no Yes
disconnecting
Number of phases 3
Operating voltage kV 33
Rated voltage kV 36
Max. continuous system voltage kV 36
Impulse withstand voltage (peak) kV 170
Power frequency withstand voltage (1 kV 70
min.):
Rated frequency Hz 50
Rated short-time withstand current (3 s) kA 25
Rated peak short circuit current kA 63
Rated normal current:
- incoming/outgoing A 1250
- transformer A 1250
- bus sectionalizer A 1250
- bus coupler A 1250
Rated short circuit breaking current kA 25
Rated short circuit making current kA 63
Rated cable charging breaking current A Bidder to provide
Maximum capacitive breaking current A Bidder to provide
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 236
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Double Busbar)
Description Unit Required Bidder’s Offer
Rated operating sequence O-0.3Sec-CO- 3min
- CO
Closing time ms <60
Dead time ms 300
Break time ms <60
Make time ms <60
Arcing time ms <15
Live span of contacts (for no. of operations)
- at rated continuous current no. 10,000
- at rated breaking current no. 100
Auxiliary contacts:
- number of NO no. 10NO
- number of NC no. 10NC
- voltage rating Vdc 110
- current rating A 10A
No. of making coil No 1
No. of tripping coil No 2
Operating mechanism
- for closing Spring
- for opening Spring
Motor
- voltage Vdc 110
- maximum spring recharging time s 25
- power W Bidder to provide
Hand operating facilities yes/no Yes
MAINTENANCE BUSBAR EARTHING
SWITCH
Manufacturer name Bidder to provide
Country of manufacturing Bidder to provide
Manufacturer’s type designation Bidder to provide
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 237
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Double Busbar)
Description Unit Required Bidder’s Offer
Type tested yes/ Yes
no
Standards IEC
Operating voltage kV 33
Rated voltage kV 36
Max. continuous system voltage kV 36
Impulse withstand voltage (peak) kV 170
Power frequency withstand voltage (1 kV 70
min.):
Rated current A Bidder to provide
Rated short-time withstand current (3 s) kA 25
Rated peak short circuit current kA 63
Auxiliary contacts:
- number of NO no. 10NO
- number of NC no. 10NC
- voltage rating Vdc 110
- current rating A 10A
Operating mechanism Spring
Motor
- voltage Vdc 110
- maximum spring recharging time s 25
- power W Bidder to provide
Hand operating facilities yes/no Yes
MAINTENANCE EARTHING SWITCH
(FEEDERS AND POWER
TRANSFORMERS)
Manufacturer name Bidder to provide
Country of manufacturing Bidder to provide
Manufacturer’s type designation Bidder to provide
Type tested yes/no Yes
Standards IEC
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 238
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Double Busbar)
Description Unit Required Bidder’s Offer
Operating voltage kV 33
Rated voltage kV 36
Max. continuous system voltage kV 36
Impulse withstand voltage (peak) kV 170
Power frequency withstand voltage (1 kV 70
min.):
Rated current A Bidder to provide
Rated short-time withstand current (3 s) kA 25
Rated peak short circuit current kA 63
Auxiliary contacts:
- number of NO no. 10NO
- number of NC no. 10NC
- voltage rating Vdc 110
- current rating A 10A
Operating mechanism Manual
CURRENT TRANSFORMERS
Manufacturer name Bidder to provide
Country of manufacturing Bidder to provide
Manufacturer’s type designation Bidder to provide
Type tested yes/no Yes
Standards IEC
Operating voltage kV 33
Rated voltage kV 36
Max. continuous system voltage kV 36
Impulse withstand voltage (peak) kV 170
Power frequency withstand voltage (1 kV 70
min.):
Rated frequency Hz 50
Arrangement Cast resin, Indoor
Number of phases Single
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 239
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Double Busbar)
Description Unit Required Bidder’s Offer
Rated primary current for:
- incoming/outgoing A 800-400
- power transformer A 600-400
- bus sectionalizer A 1200-600
Rated secondary current for power
transformer
- Control measuring core 1 A 1
- Control & Protection core 2 A 1
- Protection core 3 A 1
Accuracy class
- core 1 0.2s
- core 2 5P20
- core 3 PX
Burden
- core 1 VA Bidder to indicate as
per requirement of
protection scheme
- core 2 VA Bidder to indicate as
per requirement of
protection scheme
- core 3 VA Bidder to indicate as
per requirement of
protection scheme
Rated secondary current for
incoming/outgoing feeders
- Control measuring core 1 A 1
- Control & Protection core 2 A 1
- Protection core 3 A 1
Accuracy class
- core 1 0.2s
- core 2 5P20
- core 3 PX
Burden
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 240
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Double Busbar)
Description Unit Required Bidder’s Offer
- core 1 VA Bidder to indicate as
per requirement of
protection scheme
- core 2 VA Bidder to indicate as
per requirement of
protection scheme
- core 3 VA Bidder to indicate as
per requirement of
protection scheme
Rated secondary current for bus
sectionalizer
- Control measuring core 1 A 1
- Control & Protection core 2 A 1
- Protection core 3 A 1
Accuracy class
- core 1 0.2s
- core 2 5P20
- core 3 PX
Burden
- core 1 VA Bidder to indicate as
per requirement of
protection scheme
- core 2 VA Bidder to indicate as
per requirement of
protection scheme
- core 3 VA Bidder to indicate as
per requirement of
protection scheme
VOLTAGE TRANSFORMERS
Manufacturer name Bidder to provide
Country of manufacturing Bidder to provide
Manufacturer’s type designation Bidder to provide
Type tested yes/no Yes
Standards IEC
Operating voltage kV 33
Rated voltage kV 36
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 241
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Double Busbar)
Description Unit Required Bidder’s Offer
Max. continuous system voltage kV 36
Impulse withstand voltage (peak) kV 170
Power frequency withstand voltage (1 kV 70
min.):
Rated frequency Hz 50
Insulation material Cast resin, Indoor
Number of phases No. 1
Rated primary voltage kV 33/ √3
Rated secondary voltage V 110 / √3/ 110 / √3
Voltage transformers for busbars
Accuracy class
- core 1 metering 0.2
- core 2 protection 3P
Burden
- core 1 metering VA Bidder to indicate as
per requirement of
protection scheme
- core 2 protection VA Bidder to indicate as
per requirement of
protection scheme
Voltage transformers for incoming/outgoing
feeders
Accuracy class
- core 1 metering 0.2
- core 2 protection 3P
Burden
- core 1 metering VA Bidder to indicate as
per requirement of
protection scheme
- core 2 protection VA Bidder to indicate as
per requirement of
protection scheme
SURGE ARRESTER
Manufacturer name Bidder to provide
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 242
Technical Schedule/Data Sheet for 33 KV metal clad Air Insulated Switchgear (Double Busbar)
Description Unit Required Bidder’s Offer
Country of manufacturing Bidder to provide
Manufacturer’s type designation Bidder to provide
Type tested yes/no Yes
Standards IEC
Operating voltage kV 33
Rated voltage kV 36
Max. continuous system voltage kV 36
Impulse withstand voltage (peak) kV 170
Power frequency withstand voltage (1 kV 70
min.):
Rated frequency Hz 50
Normal Discharge Current kA 10
IEC Discharge Class 2
Lightning Impulse Protection kV 94
METERING DEVICES, INSTRUMENTS As per requirements
of Technical
Specifications for
33kV Indoor Metal
clad Switchgear
PROTECTION As per requirements
of relevant
Technical
Specifications for
Protection
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 243
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 244
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 245
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 246
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 247
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 248
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 249
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 250
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 251
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 252
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 253
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 254
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 255
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 256
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 257
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 258
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 259
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 260
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 261
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 262
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 263
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 264
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 265
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 266
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 267
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 268
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 269
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 270
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 271
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 272
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 273
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 274
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 275
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 276
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 277
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 278
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 279
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 280
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 281
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 282
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 283
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 284
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 285
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 286
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 287
Technical Schedule/Data Sheet for Control and Signal Cables without Armoring (4, 7, 12, 19,
27x2.5mm2)
Description Unit Required Bidder’s Offer
- number of cores No. 4, 7, 12, 19, 27
Core insulation:
- material XLPE
- minimum thickness mm 0.7
Binder/Bedding
- material PE tape
- minimum thickness mm Bidder to provide
Common screen/shield
- copper tape yes/no Yes
- number (50% overlapped) No. 1
- nominal thickness mm 0.1
- cross-sectional area mm2 Bidder to provide
Inner covering
- material LSZH compound
- number No. 1
- nominal thickness mm Bidder to provide
Outer sheath
- material LSZH compound
- applicable standard IEC 60332-1, BS 7655
- nominal thickness mm 1.8
- color Black
Exterior cable diameter mm Bidder to provide
Cable weight kg/km Bidder to provide
Minimum bending radius when m Bidder to provide
installed
ELECTRICAL AND THERMAL
CHARACTERISTICS
- maximum DC resistance at 20°C Ω/km 7.4
- maximum AC resistance at the Ω/km 9.45
admissible operational temperature
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 288
Technical Schedule/Data Sheet for Control and Signal Cables without Armoring (4, 7, 12, 19,
27x2.5mm2)
Description Unit Required Bidder’s Offer
(90°C)
- Insulation resistance at 20°C μΩ/km Bidder to provide
- Capacitive reactance μF/km ≤0.37
- Inductive reactance Ω/km ≤0.098
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 289
Technical Schedule/Data Sheet for Control and Signal Cables with Steel
Tape Armoring (4, 7, 12, 19, 27x2.5mm2)
Technical Schedule/Data Sheet for Control and Signal Cables with Steel Tape Armoring (4, 7, 12,
19, 27x2.5mm2)
Description Unit Required Bidder’s Offer
Manufacturer’s name Bidder to provide
Country of Manufacturing Bidder to provide
Manufacturer’s type designation Bidder to provide
Type tested yes/no Yes
Standards IEC 60332-1, 60502-1
First commercial operation of offered year Bidder to provide
type
The design life of the offered cable years Bidder to provide
type
Rated voltage kV 0.6/1
Highest system voltage kV 1.2
Rated frequency Hz 50
Power frequency withstand voltage kV 2.4
(core to grounded screen/armor) for 5
min. at 20°C
Minimum short circuit current of the kA 0.358
conductor (1s)
Minimum short circuit current of kA 0.44
copper screen (1s)
Maximum permissible continuous °C 90
conductor temperature
Laying environment Ducts/cables
trenches/air/ground
Laying depth m 0.75
Thermal resistance of the laying °C x cm 100
environment
W
CONSTRUCTIVE
CHARACTERISTICS
Conductor:
- material Annealed Cu wires
- nominal cross-section mm2 2.5
- shape round
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 290
Technical Schedule/Data Sheet for Control and Signal Cables with Steel Tape Armoring (4, 7, 12,
19, 27x2.5mm2)
Description Unit Required Bidder’s Offer
- number of cores No. 4, 7, 12, 19, 27
Core insulation:
- material XLPE
- minimum thickness mm 0.7
Binder/Bedding
- material PE tape
- minimum thickness mm Bidder to provide
Common screen/shield
- copper tape yes/no Yes
- number (50% overlapped) No. 1
- nominal thickness mm 0.1
- cross-sectional area mm2 Bidder to provide
Inner covering
- material LSZH compound
- number No. 1
- nominal thickness mm Bidder to provide
Armoring
- galvanized steel tapes yes/no Yes
- number No. 2
- nominal thickness mm Bidder to provide
Outer sheath
- material LSZH compound
- applicable standard IEC 60332-1, BS 7655
- nominal thickness mm 1.8
- color Black
Exterior cable diameter mm Bidder to provide
Cable weight kg/km Bidder to provide
Minimum bending radius when m Bidder to provide
installed
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 291
Technical Schedule/Data Sheet for Control and Signal Cables with Steel Tape Armoring (4, 7, 12,
19, 27x2.5mm2)
Description Unit Required Bidder’s Offer
ELECTRICAL AND THERMAL
CHARACTERISTICS
- maximum DC resistance at 20°C Ω/km 7.4
- maximum AC resistance at the Ω/km 9.45
admissible operational temperature
(90°C)
- Insulation resistance at 20°C μΩ/km Bidder to provide
- Capacitive reactance μF/km ≤0.37
- Inductive reactance Ω/km ≤0.098
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 292
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 293
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 294
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 295
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 296
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 297
The column headed “Bidder’s Offer” shall be completed and each page of the Schedules signed and
stamped by the bidder. Bidders should also attach relevant equipment manuals/brochures.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 298
Table of Contents
Technical Schedule/Data Sheet for Overhead Conductor 265mm² AAC ............................. 303
Technical Schedule/Data Sheet for Optical Ground Wires (OPGW) ................................... 305
Technical Schedule/Data Sheet for 1Cx300mm2 33 kV Cables and Terminations .............. 308
Technical Schedule/Data Sheet for 33kv Composite Post Insulators ................................... 313
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 299
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 300
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 301
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 302
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 303
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 304
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 305
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 306
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 307
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 308
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 309
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 310
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 311
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 312
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 313
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 314
Contractor’s Equipment
Form EQU
The Bidder shall provide adequate information to demonstrate clearly that it has the capability
to meet the requirements for the key Contractor’s equipment listed in Section III, Evaluation
and Qualification Criteria. A separate Form shall be prepared for each item of equipment listed,
or for alternative equipment proposed by the Bidder.
Item of equipment
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 315
Functional Guarantees
Form FUNC
The Bidder shall copy in the left column of the table below, the identification of each
functional guarantee required in the Specification and stated by the Employer in para. 1.2 (c) of
Section III, Evaluation and Qualification Criteria, and in the right column, provide the
corresponding value for each functional guarantee of the proposed plant and equipment.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 316
Personnel
Form PER -1
Proposed Personnel
Bidders should provide the names of suitably qualified personnel to meet the specified
requirements stated in Section III. The data on their experience should be supplied using the
Form below for each candidate.
1. Title of position*
Name
2. Title of position*
Name
3. Title of position*
Name
4. Title of position*
Name
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 317
Form PER-2
Position
Professional qualifications
Address of employer
Fax E-mail
Summarize professional experience over the last 20 years, in reverse chronological order.
Indicate particular technical and managerial experience relevant to the project.
From To Company / Project / Position / Relevant technical and management experience
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 318
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 319
LOT 2
Steel Lattice Towers
Steel Tubular Poles
33kV Composite Post Insulators
33kV Composite Suspension/Tension
Insulators
Aluminum Conductors
33kV XLPE Cables
33kV Termination/jointing Kits
Optical Ground Wire (OPGW)
OPGW Joint Box
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 320
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 321
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 322
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 323
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 324
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 325
Form CON – 2
Historical Contract Non-Performance
Bidder’s Legal Name: _______________________ Date: _____________________
JV Member Legal Name: _______________________ ___________________
RFB No.: __________________
Page _______ of _______ pages
Non-Performed Contracts in accordance with Section III, Evaluation and Qualification Criteria
Contract non-performance did not occur since 1st January [insert year] specified in Section III,
Evaluation and Qualification Criteria, Sub-Factor 2.1.
Contract(s) not performed since 1st January [insert year] specified in Section III, Evaluation and
Qualification Criteria, requirement 2.1
Year Non- Contract Identification Total Contract
performed Amount (current
portion of value, currency,
contract exchange rate
and US$
equivalent)
[insert [insert amount Contract Identification: [indicate complete contract [insert amount]
year] and percentage] name/ number, and any other identification]
Name of Employer: [insert full name]
Address of Employer: [insert street/city/country]
Reason(s) for nonperformance: [indicate main
reason(s)]
Pending Litigation, in accordance with Section III, Evaluation and Qualification Criteria
No pending litigation in accordance with Section III, Evaluation and Qualification Criteria,
Sub-Factor 2.3.
Pending litigation in accordance with Section III, Evaluation and Qualification Criteria, Sub-
Factor 2.3 as indicated below.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 326
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 327
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 328
Form CCC
2.
3.
4.
5.
etc.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 329
Financial Situation
Historical Financial Performance
Bidder’s Legal Name: _______________________ Date: _____________________
JV Member Legal Name: _______________________ RFB No.: __________________
Page _______ of _______ pages
To be completed by the Bidder and, if JV, by each member
Total Assets
(TA)
Total
Liabilities
(TL)
Net Worth
(NW)
Current
Assets (CA)
Current
Liabilities
(CL)
Total
Revenue
(TR)
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 330
Profits
Before Taxes
(PBT)
Attached are copies of financial statements (balance sheets, including all related notes, and
income statements) for the years required above complying with the following conditions:
(a) Must reflect the financial situation of the Bidder or member to a JV, and not sister
or parent companies
(b) Historic financial statements must be audited by a certified accountant
(c) Historic financial statements must be complete, including all notes to the financial
statements
(d) Historic financial statements must correspond to accounting periods already
completed and audited (no statements for partial periods shall be requested or
accepted)
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 331
_________________________________________ ____________________
_________________________________________ ____________________
_________________________________________ ____________________
_________________________________________ ____________________
_________________________________________ ____________________
*Average _________________________________________ ____________________
Annual
Turnover
*Average annual turnover calculated as total certified payments received for work in progress
or completed, divided by the number of years specified in Section III, Evaluation Criteria,
Sub-Factor 2.3.2.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 332
Form FIN3.3
Financial Resources
Specify proposed sources of financing, such as liquid assets, unencumbered real assets, lines of
credit, and other financial means, net of current commitments, available to meet the total cash
flow demands of the subject contract or contracts as indicated in Section III, Evaluation and
Qualification Criteria
Source of financing Amount (US$ equivalent)
1.
2.
3.
4.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 333
Experience
General Experience
Bidder’s Legal Name: ____________________________ Date: _____________________
JV Member Legal Name: ____________________________ RFB No.:
__________________
Page _______ of _______ pages
Starting Ending
Contract Identification Role of
Month / Month /
Year Year Years Bidder
*
Contract name:
______ ______ Brief Description of the Works performed by the _________
Bidder:
Name of Employer:
Address:
Contract name:
______ ______ Brief Description of the Works performed by the _________
Bidder:
Name of Employer:
Address:
Contract name:
______ ______ Brief Description of the Works performed by the _________
Bidder:
Name of Employer:
Address:
Contract name:
______ ______ Brief Description of the Works performed by the _________
Bidder:
Name of Employer:
Address:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 334
Starting Ending
Contract Identification Role of
Month / Month /
Year Year Years Bidder
*
Contract name:
______ ______ Brief Description of the Works performed by the _________
Bidder:
Name of Employer:
Address:
Contract name:
______ ______ Brief Description of the Works performed by the _________
Bidder:
Name of Employer:
Address:
*List calendar year for years with contracts with at least nine (9) months activity per year
starting with the earliest year
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 335
Specific Experience
Bidder’s Legal Name: ___________________________ Date: _____________________
JV Member Legal Name: _________________________ RFB No.: __________________
Page _______ of _______ pages
Role in Contract
Subcontract
Contractor Management or
Contractor
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 336
Amount _________________________________
Complexity _________________________________
Methods/Technology _________________________________
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 337
Information
Contract Identification _______________________________________
Award date _______________________________________
Completion date _______________________________________
Role in Contract
Subcontracto
Contractor Management r
Contractor
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 338
Information
Description of the key activities in
accordance with Sub-Factor 4.2b) of
Section III:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 339
[The bank shall fill in this Bank Guarantee Form in accordance with the instructions
indicated.]
RFB No.:[Employer to insert reference number for the Request for Bids]
Guarantor: [Insert name and address of place of issue, unless indicated in the letterhead]
We have been informed that ______ [insert name of the Bidder, which in the case of a joint
venture shall be the name of the joint venture (whether legally constituted or prospective) or
the names of all members thereof](hereinafter called "the Applicant") has submitted or will
submit to the Beneficiary its Bid (hereinafter called "the Bid") for the execution of
________________ under RFB No. ____________
At the request of the Applicant, we, as Guarantor, hereby irrevocably undertake to pay the
Beneficiary any sum or sums not exceeding in total an amount of ___________
(____________) upon receipt by us of the Beneficiary’s complying demand, supported by
the Beneficiary’s statement, whether in the demand itself or a separate signed document
accompanying or identifying the demand, stating that either the Bidder:
(a) has withdrawn its Bid during the period of Bid validity set forth in the Bidder’s Letter
of Bid (“the Bid Validity Period”), or any extension thereto provided by the Bidder; or
(b) having been notified of the acceptance of its Bid by the Beneficiary during the Bid
Validity Period or any extension thereto provided by the Applicant, (i) has failed to
execute the Contract Agreement, or (ii) has failed to furnish the Performance Security,
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 340
This guarantee will expire: (a) if the Applicant is the successful Bidder, upon our receipt of
copies of the contract agreement signed by the Applicant and the Performance Security
issued to the Beneficiary in relation to such contract agreement; or (b) if the Applicantis not
the successful Bidder, upon the earlier of (i) our receipt of a copy of the Beneficiary’s
notification to the Applicant of the results of the Bidding process; or (ii)twenty-eight days
after the end of the Bid Validity Period.
Consequently, any demand for payment under this guarantee must be received by us at the
office indicated above on or before that date.
This guarantee is subject to the Uniform Rules for Demand Guarantees (URDG) 2010
Revision, ICC Publication No. 758.
_____________________________
[Signature(s)]
Note: All italicized text is for use in preparing this form and shall be deleted from the final
product.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 341
11
The amount of the Bond shall be denominated in the currency of the Employer’s Country or the equivalent
amount in a freely convertible currency.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV – Bidding Forms 342
Signed: _________________________________
In the capacity of ______________________
Name: ______________________________________________________
Duly authorized to sign the Bid for and on behalf of: __________________
Dated on ____________ day of __________________, _______
________________________
Corporate Seal (where appropriate)
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section IV - Bidding Forms 343
Manufacturer’s Authorization
Date: __________________
RFB No.: _________________
To: ________________________
WHEREAS
We hereby extend our full guarantee and warranty in accordance with Clause 27 of the
General Conditions, with respect to the goods offered by the above firm.
Signed: _______________________________________
Name: ______________________________________
Title:______________________________________
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines
(Lot 1-2) – Volume 1 of 2
Section V – Eligible Countries 345
Eligibility for the Provision of Goods, Works and Non Consulting Services in
Bank-Financed Procurement
In reference to ITB 4.8 and 5.1, for the information of the Bidders, at the present time firms,
goods and services from the following countries are excluded from this Bidding process:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VI – Fraud and Corruption 347
b. Rejects a proposal for award if the Bank determines that the firm or individual
recommended for award, any of its personnel, or its agents, or its sub-consultants,
sub-contractors, service providers, suppliers and/ or their employees, has, directly or
indirectly, engaged in corrupt, fraudulent, collusive, coercive, or obstructive
practices in competing for the contract in question;
c. In addition to the legal remedies set out in the relevant Legal Agreement, may take
other appropriate actions, including declaring misprocurement, if the Bank
determines at any time that representatives of the Borrower or of a recipient of any
part of the proceeds of the loan engaged in corrupt, fraudulent, collusive, coercive,
or obstructive practices during the procurement process, selection and/or execution
of the contract in question, without the Borrower having taken timely and
appropriate action satisfactory to the Bank to address such practices when they
occur, including by failing to inform the Bank in a timely manner at the time they
knew of the practices;
d. Pursuant to the Bank’s Anti- Corruption Guidelines and in accordance with the
Bank’s prevailing sanctions policies and procedures, may sanction a firm or
individual, either indefinitely or for a stated period of time, including by publicly
declaring such firm or individual ineligible (i) to be awarded or otherwise benefit
from a Bank-financed contract, financially or in any other manner; 1 (ii) to be a
nominated2 sub-contractor, consultant, manufacturer or supplier, or service provider
of an otherwise eligible firm being awarded a Bank-financed contract; and (iii) to
receive the proceeds of any loan made by the Bank or otherwise to participate further
in the preparation or implementation of any Bank-financed project;
e. Requires that a clause be included in bidding/request for proposals documents and in
contracts financed by a Bank loan, requiring (i) bidders (applicants/proposers),
consultants, contractors, and suppliers, and their sub-contractors, sub-consultants,
service providers, suppliers, agents personnel, permit the Bank to inspect 3 all
1
For the avoidance of doubt, a sanctioned party’s ineligibility to be awarded a contract shall include, without limitation,
(i) applying for pre-qualification, expressing interest in a consultancy, and bidding, either directly or as a nominated
sub-contractor, nominated consultant, nominated manufacturer or supplier, or nominated service provider, in respect of
such contract, and (ii) entering into an addendum or amendment introducing a material modification to any existing
contract.
2 A nominated sub-contractor, nominated consultant, nominated manufacturer or supplier, or nominated service provider
(different names are used depending on the particular bidding document) is one which has been: (i) included by the
bidder in its pre-qualification application or bid because it brings specific and critical experience and know-how that
allow the bidder to meet the qualification requirements for the particular bid; or (ii) appointed by the Borrower.
3 Inspections in this context usually are investigative (i.e., forensic) in nature. They involve fact-finding activities
undertaken by the Bank or persons appointed by the Bank to address specific matters related to investigations/audits,
such as evaluating the veracity of an allegation of possible Fraud and Corruption, through the appropriate mechanisms.
Such activity includes but is not limited to: accessing and examining a firm's or individual's financial records and
information, and making copies thereof as relevant; accessing and examining any other documents, data and
information (whether in hard copy or electronic format) deemed relevant for the investigation/audit, and making copies
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VI – Fraud and Corruption 349
accounts, records and other documents relating to the procurement process, selection
and/or contract execution, and to have them audited by auditors appointed by the
Bank.
thereof as relevant; interviewing staff and other relevant individuals; performing physical inspections and site visits;
and obtaining third party verification of information.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Part 2 – Employer’s Requirements 351
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 353
Contents
Scope of Supply of Plant and Installation Services by the Contractor .......................... 354
Specification......................................................................................................................... 407
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 354
The Scope of works for which bids are invited is an EPC (Engineering, Procurement and
Construction) for:
- Lot1: Supply and Installation of 33/11kV Primary Substations and extension of Freetown
161 Substation in Freetown (Lot 1)
- Lot2: Supply and Installation of 33kV Sub transmission Lines in Freetown (Lot 2)
Detailed Scope of Works for both lots is given hereafter.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 355
- 1 set of 161kV, 630A, 31.5 kA, 3s, SF6 Circuit Breaker with remote and local control
(set of 3-phase) c/w operating platforms, grounding mats and supporting steel structures
- 1 set of 161kV, 1250A, 31.5kA, 3s disconnect switch (set of 3-phase), motorized and
manual operating mechanism, c/w operating platforms, grounding mats and supporting
structures
- 2 sets of 161kV, 1250A, 31.5kA, 3s Pantograph break disconnect (set of 3-phase),
motorized and manual operating mechanism, c/w operating platforms, grounding mats
and supporting structures
- 1 set of 161kV O/D Current Transformer (set of 3-phase) c/w steel supporting structures
- 1 set of 161kV Voltage Transformers (set of 3-phase) c/w steel supporting structures
connected to main bus
- 1 set of 161kV Surge Arrester (set of 3-phase) c/w steel supporting structures
The related control/metering panel shall be equipped with:
- 1 interlocking hardwired.
- 1 synch-check facility through dedicated synch-check relay
- 1 ammeter set with 3 ammeters.
- 1 voltmeter with a 7- position selector switch.
- 1 energy meter (kVA, kW, kVAr, PF, etc.)
- 1 Microprocessor-based bay control and protection unit (BCPU) incorporating all
control, protection, synchronizing, supervision, alarm, metering and interlocking features
as required.
- 1 key-lockable selector switch for control, positions: OFF-LOCAL(BCPU)-REMOTE
(future SCMS)
- 1 set of material such as wiring, terminals, test terminal blocks / switches, etc.
- Mimic diagram with equipment position indicators and control switches for equipment
remote control
A.2 33kV Outdoor switchgear
The complete sets of 33kV Outdoor (OD) Switchgear, fully type tested to latest applicable
IEC, vis-à-vis application requirements as indicated, consisting of extended aluminum
tubular main and transfer bus bars, current rating 1250A (IEC rating), short circuit current
25kA – 1s, as described / detailed below, shall be supplied and installed as conceptually
shown in the single line diagram (SLD) drawing ESURP/AF/FT161/01. All Factory
Acceptance Tests (FAT) for the OD switchgear (circuit breakers, isolators, etc.) shall be
conducted as per the latest applicable IEC standards.
The 33kV switchgear shall have provisions for testing CT, VT, HV-tests etc.
Equipment / System shall be tested & commissioned by Original Equipment Manufacturer
(OEM).
Bus Bar in 33kV Switchgear shall be arranged as aluminum tubular busbar.
The 33kV switchgear shall be equipped with the following equipment:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 356
A.2.1 One (1) Incomer Bay from 161/33kV, 35/40MVA Power Transformer
Equipped asp per SLD drawing ESURP/AF/FT161/01, in accordance with Specifications and
Technical Schedules/Data sheets with:
- 1 set of 33kV O/D 1250A, 25kA 1s SF6 Circuit Breaker with remote and local control
(set of 3-phase) c/w with support structures
- 1 set of 33kV O/D 1250A, 25kA 1s Motorized Line Isolator (set of 3-phase) with Earth
Switch c/w with support structures
- 1 set of 33kV O/D 1250A, 25kA 1s Motorized Bus Isolator (set of 3-phase) c/w with
support structures
- 1 set of 33kV O/D Current Transformer (set of 3-phase) c/w support structures
- 1 set of 33kV O/D Voltage Transformer (set of 3-phase) c/w support structures
connected to bus bar
- 2 sets of 33kV O/D Surge Arrester (set of 3-phase) c/w all accessories
The related control/metering panel shall be equipped with:
- 1 interlocking hardwired.
- 1 synch-check facility through dedicated synch-check relay
- 1 ammeter set with 3 ammeters.
- 1 voltmeter with a 7- position selector switch.
- 1 energy meter (kVA, kW, kVAr, PF, etc.)
- 1 Microprocessor-based bay control and protection unit (BCPU) incorporating all
control, protection, synchronizing, supervision, alarm, metering and interlocking features
as required.
- 1 key-lockable selector switch for control, positions: OFF-LOCAL(BCPU)-REMOTE
(future SCMS)
- 1 set of material such as wiring, terminals, test terminal blocks / switches, etc.
- Mimic diagram with equipment position indicators and control switches for equipment
remote control
A.2.2 One (1) Bus Section Bay
Equipped asp per SLD drawing ESURP/AF/FT161/01, in accordance with Specifications and
Technical Schedules/Data sheets with:
- 1 set of 33kV O/D 1250A, 25kA 1s SF6 Circuit Breaker with remote and local control
(set of 3-phase) c/w with support structures
- 2 sets of 33kV O/D 1250A, 25kA 1s Motorized Bus Isolator (set of 3-phase) with Earth
Switch c/w with support structures
- 1 set of 33kV O/D Current Transformer (set of 3-phase) (400-800/1/1/1A) c/w support
structures
The related control/metering panel shall be equipped with:
- 1 interlocking hardwired.
- 1 synch-check facility through dedicated synch-check relay
- 1 ammeter set with 3 ammeters.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 357
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 358
The design of these transformers shall comply with the following main design data:
- Rated power: 35/40MVA
- No-load voltage ratio: 161/33kV
- Vector group symbol: YNyn0
- Rated frequency: 50Hz
- Kind of cooling: ONAN/ONAF
- Installation: Outdoor
For other technical data, relevant sections of the Specifications and Technical Schedules/Data
Sheets shall be referred to. The transformers shall be designed and tendered in full
compliance with all applicable sections of the Specifications, Technical Schedules/Data
Sheets and drawings.
The Transformer shall be suitably designed, installed and connected to the 161kV & 33kV
systems for parallel operation with existing 161/33kV, 35/40MVA Power Transformer.
A.3.2 Voltage Regulation / Parallel Interlocking Panel
One (1) independent, comprehensive control and voltage regulation systems shall be
provided for group of two (2) 161/33kV, 35/40MVA Power Transformers. The scheme/
wiring shall be suitable for the parallel operation of two (2) transformers.
In normal configuration, group of two (2) transformers will be operated in continuous parallel
mode to feed the 33kV switchgear. In the event of the loss of one transformer in a group,
remaining transformer will continue to feed the associated 33kV switchgear.
Transformer Paralleling Interlock BCU Cubicle
Transformer Paralleling Interlock (TPI) BCU Cubicle shall consist of
- Common Transformer Paralleling Interlock logic; the BCU used for the parallel
interlock logic shall be the same type provided for the SWG bays and shall be ready to
be integrated to the future SCMS system complete with status indications / min. 16
window alarm unit.
- All inputs shall be independent and direct from mechanical auxiliary switches of
breakers & or isolators.
Transformer Voltage Regulation Cubicle
Transformer Voltage Regulation Cubicle shall be equipped with the following equipment, for
each transformer:
- 1 Automatic Voltage Regulator multi-function numerical type (serially and fully
prepared to be integrated into future SCMS) Relay
- 1 Interface to the future SCMS System.
- 1 control selector switch (positions: Local-Remote).
- 1 control selector switch (positions: Auto-Manual).
- 1 control selector switch (Master/Follower)
- 1 control selector-switch (Parallel interlock bypass / normal).
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 359
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 361
The communication protocol of existing substation event and data recording system is based
on IEC 60870-5-103.
A.6 Protection Equipment for 161kV & 33kV Switchgear
Dedicated numerical, multi-function protection relays bay controllers (BCPUs) with
embedded protection functions shall be provided as specified in Technical Schedules/Data
Sheets. The scope of work shall also include documentation, including software for settings,
parameterization, analysis of disturbance records, licenses, operation and maintenance
manuals, fault finding manuals, etc. as well and recommended protection relay settings for
each protection terminal. Dedicated approved type Test Switches / Sockets shall be provided
for BCPU and Protection Relay terminals.
All software licenses shall be registered under EDSA name. All protection setting
calculations should be carried out using the latest version of ETAP or CYMDIST software
subject to EDSA approval. Models should be submitted for EDSA use. Finalized settings
shall be loaded into respective protection relays and BCPUs.
As a minimum the following protection shall be provided:
A.6.1 161/33kV, 35/40MVA Power Transformer
Equipped with:
- Protection: 87T, 50/51, 50N/51N
- auxiliary relays and secondary injection test facilities
Protection equipment for 161/33kV Power Transformer may be installed in Power
Transformer control cubicle or in separate panel.
A.6.2 33kV OHL Feeders
Equipped with:
- Protection: 67/50/51, 67N/50N/51N, 79
- auxiliary relays and secondary injection test facilities
Protection equipment for 33kV OHL feeders may be installed in 33kV OHL feeders control
cubicle or in separate panel.
A.6.3 33kV Bus Sectionalizer
Equipped with:
- Protection: 87/67/50/51, 67N/50N/51N, 79
- auxiliary relays and secondary injection test facilities
Protection equipment for 33kV Bus Sectionalizer may be installed in 33kV Bus Sectionalizer
control cubicle or in separate panel.
A.6.4 33kV Busbar Protection
The 33kV High Impedance type bus bar protection (HIBBP) with integrated Breaker Fail
Protection, 3-phase OC and EF protection and under and over voltage protection relays
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 362
(Incomers, Bus Couplers, Bus Sections included) shall be provided in standalone panel
located in the control room for both bus bars. BBP shall be in service even if one bay unit
fails for Section Feeder. If more than one control unit (CU) is installed, the CU shall
communicate with each other in order to clear/identify all possibility of Bus Fault.
The Contractor shall be responsible for full integration of new protection with existing
protection system.
A.7 Settlement metering system for the new 33kV incomer from new
161/33kV Power Transformer
Supply, Installation, Commissioning and Setting to Work in full compliance with the
requirements the following:
Duplicate redundant electricity settlement meters (one Main and one Check) of accuracy
class, 0.2s for Active energy and 0.5s for Reactive energy, for Defined Metering Points
(DMP) which is the 33kV Incomer from new 161/33kV power transformer to the new 33kV
Switchgears. The meters listed above shall be installed in separate panel dedicated for meters,
such as a single row contains both main and check meters.
A.8 Cables and Interface
The following cables shall be supplied, installed and commissioned as required to complete
the subject work in every respect:
- 33kV single core Cu/XLPE cables between the 33kV SWG and the 33kV OHL Terminal
towers including terminations at both ends.
- 33kV single core Cu/XLPE cables between the 33kV SWG and the 161/33kV Power
Transformer including terminations at both ends
- 33kV single core Cu/XLPE cables for grounding the Power Transformer 33kV Neutral
- 161kV single core Cu/XLPE cables for grounding the Power Transformer 161kV
Neutral
- 1kV insulated LV XPLE power cables.
- LV multi-core control, fiber optic cables, coaxial cables and FOC patch cords, etc. as
applicable.
- All required cable racks, pipes, supporting structures, cable sealing ends/terminations,
ferrules and auxiliary equipment necessary for their proper installation, connection and
operation to the satisfaction of EDSA.
All LV power cables and multi core control, telephone cables, fiber optic cables and FOC
patch cords shall be connected to the relevant substation equipment, in an approved manner.
The Contractor shall provide all necessary racks, cable trays, cable cleats and any other
accessories required for the substation cables. Contractor shall supply the complete set of
supports in the 33kV cable trenches for the Power for all feeders as per approved cable
routing within substation.
Cable ducts / trenches shall be provided for all 33kV outgoing feeder cables. Layout and
arrangement of cable ducts shall be subject to separate approval of EDSA.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 363
The price shall include all necessary wiring between the FOC, telephone cable termination
boxes/cabinets, and the related relay panels or optic terminals/signaling equipment (as
applicable).
A.9 Miscellaneous works
A.9.1 Earthing
An underground earthing system shall be provided to make it suitable for the highest earth
fault levels of the 161/33kV substation, as per the relevant Specifications.
The design, supply, installation and commissioning of the complete underground earthing
system for the complete extension of 161/33kV Substation as well as connection to the
existing substation earthing system shall be undertaken by the Contractor. The scope under
this item shall also cover all above-ground earth connections of all equipment supplied and
installed by the Contractor for the entire substation extensions and stub-outs for receiving
grounding connections of the transmission line (Cable) works. The above-ground earthing
for system is deemed as covered under this clause.
A.9.2 Outdoor Lighting and Small Power Systems
Complete substation area lighting and small power systems, including emergency lighting
systems as per EDSA approval, generally divided as below:
- 161kV and 33kV outdoor switchgear
- Power Transformer
- Common areas including Cable trenches, Roofs, Compounds of Transformers, Substation
Roads and Boundary Wall, etc.
A.9.3 Substation Lightning Protection System
Design, supply and installation of lightning protection system for substation extension and
connection of the same to the underground earthing system for the 161/33kV Substation shall
be a part of Contractor’s Scope. Protection for complete substation equipment including the
outdoor area shall be fully ensured.
A.10 Civil Engineering and Building Works
This section of the Scope of works covers the requirements of the civil and building works
necessary for the Substation equipment being provided under the scope of this Contract and
includes the design, manufacture, testing, delivery, transport, storage at SITE, erection,
installation, commissioning, performance testing and handing over in satisfactory operating
condition of all civil works related to the substation(s).
The Scope of Works shall include all engineering (including design & drawing) and building
works necessary for the proper completion of the project in every respect. The civil
engineering and building works to be executed by the Contractor are to cover the collection
of site data, detailed design, and preparation of construction drawings for EDSA approval, all
required approvals and NOCs from regulatory authorities, obtaining building permit,
obtaining permanent services connections (if applicable) such as telephone, water, drainage,
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 364
etc. supply of materials, construction and subsequent maintenance of the works required as
outlined in the Specification documents.
Bidders shall note that complete civil design of the Substation must be finished and approved
by EDSA within three (3) months after the date of the letter of award. All civil design inputs
(loading and layouts) for all equipment must be taken into consideration before the start of
civil structural design.
The civil and building works shall be constructed in accordance with Civil Works
Specifications.
The civil works shall be handled in full compliance with the Specifications and shall include
but not be limited as follows:
- Detailed Site survey & Site Grading as required.
- Temporary access roads/ lay-down areas, etc. suitable for delivery of all civil and
electromechanical equipment. Include for removal at the end of the project. The
regulations for both access roads and lay-down areas assigned to the Contractor shall be
in accordance with EDSA approval.
- Relocation and / or protection of any existing underground/ above ground services
within the plot area that interfere with new construction, as required by the concerned
authorities/ EDSA including for future, if any.
- Site mobilization, including installation of site offices etc., for EDSA/ CONTRACTOR,
and other preparatory works as required.
- Installation and commissioning of temporary site services including, power, water, air
conditioning, Fire Fighting, foul water treatment/disposal system and communications to
site offices. Include for removal at the end of the project.
- Soil investigation, complete in all aspects.
- Geophysical / Geo-technical Study, complete in all aspects
- Continuous provision of dewatering and temporary protection of works as may be
required during construction of buildings and structures.
- Supply, place, water and compact in layers, approved backfill material to raise the plot to
a level as specified above adjoining road level, including edge protection required, if
any.
- All works necessary for laying of cables, ducts, pipe/cable trenches/troughs with covers,
etc.
- Construct all roads/pathways inside the plot, including surface drainage, kerbs,
interlocking tiles, asphalt, road markings, signage for proper completion of the works.
- Complete all landscaping inside the plot, including filling, embankments, gravel
surfacing to un-built areas and all other necessary works.
- Reinforced concrete foundations and substructure works as required for associated
equipment, including all necessary protection and waterproofing.
- All associated finishing and fitting out works including drainage, manholes, pits, etc.
- Construct reinforced concrete transformer bay complete, including waterproofing,
trenches, sumps, gratings, gravel, etc.
- Site clearance and making good upon completion of the works.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 365
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 366
The Contractor shall furnish reference points, benchmark and elevations as may be required
for the execution of the Work. The Contractor shall protect all benchmarks, survey pegs and
monuments from damage or movement. If any of these are moved or disturbed, they shall be
replaced and installed at the Contractor's expense.
The Contractor shall be responsible for the entire cost of repairing, modifying or moving
Work improperly installed due to such bench marks, survey pegs and monuments having
been moved without the authorization of the respective authorities, or due to the Contractor’s
failure to protect and maintain same.
161/33kV Substation extension and Associated Works
A suitable minimum clearance shall be provided for all equipment to suit installation and
operational requirements and in compliance with the relevant Technical Specifications.
All structures shall be designed to carry the loads imposed by the structure itself, together
with live loads in accordance with approved standards and codes of practice to be
incorporated into the Design Criteria Document. Type of foundation, shallow or deep, shall
be in accordance with the findings and recommendations of the soil investigation report.
External lighting, lightning and earthing systems shall be EDSA approved and fulfil the
requirements of the relevant Specifications.
Any areas of exposed concrete such as equipment foundations, apron slabs, pathways etc.
shall receive a protective coating of approved chemically resistant paint.
For the fire rating requirements, as applicable for civil works, reference is made to
recognized international standards.
The layout and switchgear arrangement in the transformer bay may be modified and adopted
to suit the actual equipment sizes in order to achieve an optimum workable layout of all
equipment to be located inside the substation building.
The Bidder shall submit a properly worked out proposal for recommended layout of
equipment in accordance with the actual equipment dimensions whilst satisfying the building
and security regulations. The proposal shall include elevation drawings for the substation
extension. In the absence of such submission, it will be considered that the Bidder has studied
the site conditions and has agreed to accommodate all equipment in the available area.
The Contractor is responsible for all necessary coordination to meet the requirements of
electrical, mechanical and civil works to achieve a homogeneous and uniform design.
In particular, the scope of civil works shall be inclusive of the following:
- As applicable, reinforced cable trenches with racks/ladders and/or cable ducts and pipes
shall be provided as required. Trenches shall be sufficient in sizes and ducts shall be
sufficient in numbers for exit and entry of all HV, MV, LV and fiber optic cables. A
20% spare capacity shall be provided on each side of the building where it is possible to
avoid excavation inside the substation plot at later stages for installation of additional
cables.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 367
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 368
The Contractor shall provide reinforced concrete duct banks, sufficient in size and numbers
to accommodate required cables, including spares. Duct bank and cable trench shall include
waterproofing and proper sealing. Ends of ducts and cable trench are to be extended one
meter beyond the plot boundary (as applicable) and to be provided with removable caps.
Location of duct banks, orientation, slopes for ducts, if any, shall be subject to EDSA
approval. Contractor shall provide steel access platforms in all service shafts.
Pull pits of suitable size, located at the ends of duct banks shall be provided as deemed
necessary, and shall be subject to EDSA approval.
Adequate sumps and means of drainage shall be incorporated into the trench system.
Trenches shall be subject to EDSA approval.
- Required cable trenches shall be of concrete and provided with proper trays, ladders,
cleats etc., suitable removable trench covers, as necessary.
- Cable shaft, gallery, cable riser, cable entry ducts etc. shall be provided as per the site
requirement with minimum 20% spare quantity.
Internal Roads & Pavements & Access Roads
Construction of pavements made of interlocking tiles around the structures.
Site leveling and installation of single sized layer of gravel for the internal area inside plot
boundary are included in Contractor’s Scope. Gravel layer shall be smoothly leveled to reach
the kerb stone level.
Substation plot area drainage shall include soak away ditches or discharge to network storm
water system etc. It also includes Construction of vehicular access to the main substation
equipment rooms and external access ramps.
Design and installation of cross carriageway duct banks/pipe crossings.
Dismantling & Demolition Works
Existing facilities within substation perimeter (if any) shall be dismantled and demolished by
the Contractor. Whenever dismantling of equipment is carried out, the materials, which
become excess / redundant, are not to be returned to EDSA. While returning the materials to
EDSA stores, these materials shall be neatly bundled /packed, and along with detailed
packing list, these materials are to be handed over to EDSA stores. In such cases the expenses
for handing over the materials to EDSA Stores is deemed to be included in various rates
included in the Contract Price. In any case mentioned above, the materials shall be cleared
from site as early as possible. The area shall be back-filled with general fill as applicable. The
site of demolished building shall be in clean condition.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 369
consisting of a single bus bar system, current rating 1250A (IEC rating), short circuit current
25kA – 3s, as described / detailed below, shall be supplied and installed as conceptually
shown in the single line diagram (SLD) and layout drawings; ESURP/AF/ABN/01,
ESURP/AF/ABN/02, ESURP/AF/CTN/01, ESURP/AF/CTN/02, ESURP/AF/FB/01,
ESURP/AF/FB/02 and ESURP/AF/FB/03. All Factory Acceptance Tests (FAT) for the AIS
(circuit breakers, isolators, etc.) shall be conducted as per the latest applicable IEC standards.
The feeders shall have provision to connect two runs (2 runs) of 1Cx300mm2 cable. The
contractor shall cater terminations at switchgear side as well at riser pole side with all
accessories for each. The 33kV switchgear shall have provisions for testing CT, VT, HV-tests
etc. All VT fuses shall have Auxiliary Switch to signal OPEN/CLOSE status to BCPU.
Equipment / System shall be tested & commissioned by Original Equipment Manufacturer
(OEM).
Bus Bar in 33kV Switchgear shall be arranged as solid bus bars BB-A and BB-B.
Space for two (2nos) future bays (one on each side) shall be provided for 33kV Switchgear.
The 33kV switchgear shall be equipped with the following equipment:
B.1.1 Two (2) Feeder Panels (Aberdeen Substation)
These panels, each, shall be equipped with:
- 1 three-pole withdrawable circuit breaker, 1250 A
- 1 set of three-phase current transformers, separate cores for different protection and
metering purposes as per Specifications and SLD drawings.
- 1 set of three-pole maintenance earth switch
- 1 set of three-phase voltage transformers with disconnecting means.
- 1 capacitive cable live indication (3 phases)
- 1 set of surge arresters
- 1 set of cable-end terminations and boxes
The related low voltage compartment shall be equipped with:
- 1 interlocking hardwired.
- 1 synch-check facility through dedicated synch-check relay
- 1 ammeter set with 3 ammeters.
- 1 voltmeter with a 7- position selector switch.
- 1 energy meter (kVA, kW, kVAr, PF, etc.)
- 1 Microprocessor-based bay control and protection unit (BCPU) incorporating all
control, protection, synchronizing, supervision, alarm, metering and interlocking features
as required.
- 1 key-lockable selector switch for control, positions: OFF-LOCAL(BCPU)-REMOTE
(future SCMS)
- 1 set of material such as panels, wiring, terminals, test terminal blocks / switches, etc.
B.1.2 Four (4) Feeder Panels (Clinetown and Falconbridge Substations)
These panels, each, shall be equipped with:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 370
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 371
B.1.4 Two (2) 33/11kV Transformer Feeder Bays (Aberdeen, Clinetown and
Falconbridge Substations)
Each equipped with:
- 1 three-pole withdrawable circuit breaker, 1250 A
- 1 set of three-phase current transformers, separate cores for different protection and
metering purposes as per Specifications and SLD drawings.
- 1 set of three-pole maintenance earth switch
- 1 capacitive cable live indication (3 phases)
- 1 set of surge arresters
- 1 set of cable-end terminations and boxes
The related low voltage compartment shall be equipped with:
- 1 interlocking hardwired.
- 1 synch-check facility through dedicated synch-check relay
- 1 ammeter set with 3 ammeters.
- 1 voltmeter with a 7- position selector switch.
- 1 energy meter (kVA, kW, kVAr, PF, etc.)
- 1 Microprocessor-based bay control and protection unit (BCPU) incorporating all
control, protection, synchronizing, supervision, alarm, metering and interlocking features
as required.
- 1 key-lockable selector switch for control, positions: OFF-LOCAL(BCPU)-REMOTE
(future SCMS)
- 1 set of material such as panels, wiring, terminals, test terminal blocks / switches, etc.
B.1.5 Two (2) Metering / Earthing Panels Bay(s) (Aberdeen, Clinetown and
Falconbridge Substations)
These bays shall be equipped with:
- 1 Set of three-pole high speed / maintenance earth switches dedicated for the bus
sections
- 1 Set of three-phase voltage transformers for protection, synchronization, measuring, etc.
The related local control cubicle for this metering bay(s) shall be equipped with:
- 1 voltmeter with 7-position selector switch, for bus bar voltage indication
- 1 Microprocessor-based bay unit incorporating all supervision, alarm, metering and
interlocking features as required
- 1 key-lockable selector switch for control, positions: OFF-LOCAL(BCPU)-REMOTE
(future SCMS)
- 1 Digital Annunciation Module for respective bay level alarms.
- 1 Set of material such as panels, wiring, terminals, test terminal blocks / switches, etc.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 372
B.2 33kV Metal Clad Air Insulated Switchgear (AIS) Double Bus Bar (Jui
and Waterloo Substations)
The complete sets of 33kV Air Insulated Switchgear(AIS) in draw-out type execution, fully
type tested to latest applicable IEC, vis-à-vis application requirements as indicated,
consisting of a double bus bar system, current rating 1250A (IEC rating), short circuit current
25kA – 3s, as described / detailed below, shall be supplied and installed as conceptually
shown in the single line diagram (SLD) and layout drawings; ESURP/AF/JUI/01,
ESURP/AF/JUI/02, ESURP/AF/WTL/01 and ESURP/AF/WTL/02. All Factory Acceptance
Tests (FAT) for the AIS (circuit breakers, isolators, etc.) shall be conducted as per the latest
applicable IEC standards.
The feeders shall have provision to connect two runs (2 runs) of 1Cx300mm2 cable. The
contractor shall cater terminations at switchgear side as well at riser pole side with all
accessories for each. The 33kV switchgear shall have provisions for testing CT, VT, HV-tests
etc. All VT fuses shall have Auxiliary Switch to signal OPEN/CLOSE status to BCPU.
Equipment / System shall be tested & commissioned by Original Equipment Manufacturer
(OEM).
Bus Bar in 33kV Switchgear shall be arranged as upper solid bus bars BB1, and BB2 with
two sections BB2-A and BB2-B.
Space for two (2nos) future bays (one on each side) shall be provided for 33kV Switchgear.
The 33kV switchgear shall be equipped with the following equipment:
B.2.1 Six (6) Feeder Panels
These panels, each, shall be equipped with:
- 2 three pole bus bar selection isolator switch, 1250 A
- 1 three-pole withdrawable circuit breaker, 1250 A
- 1 set of three-phase current transformers, separate cores for different protection and
metering purposes as per Specifications and SLD drawings.
- 1 set of three-pole maintenance earth switch
- 1 set of three-phase voltage transformers with disconnecting means.
- 1 capacitive cable live indication (3 phases)
- 1 set of surge arresters
- 1 set of cable-end terminations and boxes
The related low voltage compartment shall be equipped with:
- 1 interlocking hardwired.
- 1 synch-check facility through dedicated synch-check relay
- 1 ammeter set with 3 ammeters.
- 1 voltmeter with a 7- position selector switch.
- 1 energy meter (kVA, kW, kVAr, PF, etc.)
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 373
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 374
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 375
B.3 11kV Metal Clad Air Insulated Switchgear (AIS) Single Bus Bar
(Aberdeen Substation)
The complete sets of 11kV Air Insulated Switchgear(AIS) in draw-out type execution, fully
type tested to latest applicable IEC, vis-à-vis application requirements as indicated,
consisting of a single bus bar system, current rating 2500A (IEC rating), short circuit current
25kA – 3s, as described / detailed below, shall be supplied and installed as conceptually
shown in the single line diagram (SLD) and layout drawings; ESURP/AF/ABN/01,
ESURP/AF/ABN/02. All Factory Acceptance Tests (FAT) for the AIS (circuit breakers,
isolators, etc.) shall be conducted as per the latest applicable IEC standards.
The feeders shall have provision to connect two runs (2 runs) of 3Cx240mm2 cable. The
contractor shall cater terminations at switchgear side as well at riser pole side with all
accessories for each. The 11kV switchgear shall have provisions for testing CT, VT, HV-tests
etc. All VT fuses shall have Auxiliary Switch to signal OPEN/CLOSE status to BCPU.
Equipment / System shall be tested & commissioned by Original Equipment Manufacturer
(OEM). Space for two (2nos) future bays (one on each side) shall be provided for 33kV
Switchgear.
The 11kV switchgear shall be equipped with the following equipment:
B.3.1 Two (2) Incomer Panels from 33/11kV, 20/26MVA Power Transformers
These panels, each, shall be equipped with:
- 1 three-pole withdrawable circuit breaker, 2500 A
- 1 set of three-phase current transformers, separate cores for different protection and
metering purposes as per Specifications and SLD drawings.
- 1 set of three-pole maintenance earth switch
- 1 set of three-phase voltage transformers with disconnecting means.
- 1 capacitive cable live indication (3 phases)
- 1 set of surge arresters
- 1 set of cable-end terminations and boxes
The related low voltage compartment shall be equipped with:
- 1 interlocking hardwired.
- 1 synch-check facility through dedicated synch-check relay
- 1 ammeter set with 3 ammeters.
- 1 voltmeter with a 7- position selector switch.
- 1 energy meter (kVA, kW, kVAr, PF, etc.)
- 1 Microprocessor-based bay control and protection unit (BCPU) incorporating all
control, protection, synchronizing, supervision, alarm, metering and interlocking features
as required.
- 1 key-lockable selector switch for control, positions: OFF-LOCAL(BCPU)-REMOTE
(future SCMS)
- 1 set of material such as panels, wiring, terminals, test terminal blocks / switches, etc.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 376
B.3.2 One (1) Bus Section Bay and One (1) Bus Raiser
Equipped with:
- 1 three-pole withdrawable circuit breaker, 2500 A
- 2 set of three-phase current transformers, separate cores for different protection and
metering purposes as per Specifications and SLD drawings.
- 1 set of three-pole maintenance earth switch
The related low voltage compartment shall be equipped with:
- 1 interlocking hardwired.
- 1 synch-check facility through dedicated synch-check relay
- 1 ammeter set with 3 ammeters.
- 1 voltmeter with a 7- position selector switch.
- 1 energy meter (kVA, kW, kVAr, PF, etc.)
- 1 Microprocessor-based bay control and protection unit (BCPU) incorporating all
control, protection, synchronizing, supervision, alarm, metering and interlocking features
as required.
- 1 key-lockable selector switch for control, positions: OFF-LOCAL(BCPU)-REMOTE
(future SCMS)
- 1 set of material such as panels, wiring, terminals, test terminal blocks / switches, etc.
B.3.3 Six (6) Feeder Panels
These panels, each, shall be equipped with:
- 1 three-pole withdrawable circuit breaker, 630 A
- 1 set of three-phase current transformers, separate cores for different protection and
metering purposes as per Specifications and SLD drawings.
- 1 set of three-pole maintenance earth switch
- 1 capacitive cable live indication (3 phases)
- 1 set of surge arresters
- 1 set of cable-end terminations and boxes
The related low voltage compartment shall be equipped with:
- 1 interlocking hardwired.
- 1 ammeter set with 3 ammeters.
- 1 voltmeter with a 7- position selector switch.
- 1 energy meter (kVA, kW, kVAr, PF, etc.)
- 1 Microprocessor-based bay control and protection unit (BCPU) incorporating all
control, protection, synchronizing, supervision, alarm, metering and interlocking features
as required.
- 1 key-lockable selector switch for control, positions: OFF-LOCAL(BCPU)-REMOTE
(future SCMS)
- 1 set of material such as panels, wiring, terminals, test terminal blocks / switches, etc.
B.3.4 One (1) 11kV Auxiliary Transformer Feeder Panel
11 kV Aux Transformer feeder panels shall be equipped with:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 377
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 379
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 380
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 381
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 382
In case of failure of the AVR, manual tap changer control shall be possible from the AVR
cubicle with master/follower scheme and the future SCMS system.
AVRs shall function in Master/Follower/Independent (M/F/I) modes even for the failure of
TPI. Failure of any single AVR should not break Master/Follower (M/F) combination.
B.5.3 One (1) 11/0.415kV, 100kVA, ONAN Auxiliary Transformer (Aberdeen, Jui and
Waterloo Substations)
Auxiliary transformers, oil filled, suitable for outdoor installation, with off load tap changer,
rated at 100kVA each are to be supplied and installed as per Specification and technical
Schedules/Data Sheets.
The design of these transformers shall comply with the following main design data:
- Rated power: 100kVA
- No-load voltage ratio: 11/0.415kV
- Vector group symbol: Dyn11
- Rated frequency: 50Hz
- Kind of cooling: ONAN
- Installation: Outdoor
For other technical data, relevant sections of the Specifications and Technical Schedules/Data
Sheets shall be referred to. The transformer shall be designed and tendered in full compliance
with all applicable sections of the Specifications, Technical Schedules/Data Sheets and
drawings.
The Auxiliary transformer shall be suitably installed and connected to the 11kV system and
the Main LVAC Panel.
B.6 LVAC/DC Supply and Distribution (Aberdeen, Jui and Waterloo
Substations)
The Main LVAC Panel shall be supplied from the 11/0.415kV, 100kVA Auxiliary
Transformer. The number of outgoing feeders to be provided in the LVAC board shall be
suitable to meet the total requirements in the ultimate configuration of the new 33/11kV
substation (covering all current and final future needs of the station).
Dual Redundant 110V DC system shall be provided for the substation. The 110V DC system
set shall consist of 2 sets of batteries, 2 sets of chargers and DC distribution panel with two
incomers and a coupler, configured in a dual redundant configuration. The design/capacity
selection for the batteries, chargers and the distribution system shall be aimed to meet the full
substation requirements in the final / ultimate configuration, including the future needs and
with the required number of spares. Additionally, a 20% capacity margin shall be provided
for design margin and 25% capacity for the ageing of the batteries. The number of outgoing
feeders to be provided in the 110VDC board shall be suitable to meet the total requirements
of the station, with dual redundant feeders as and where specified.
The Contractor shall be responsible to connect all the equipment supplied under the Contract
to the station LVAC and DC systems as required. Sub-Main Distribution Boards, Sub-
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 383
Distribution Boards and dedicated Final MCB DB (if required) as per approval shall be
installed at the respective locations including all cabling, wiring, terminations, etc. from the
main and sub-distribution boards, and Final MCB DB to the load terminals / spare points.
All cable support systems shall be provided in the respective work areas to meet with the
cabling requirements of the Works. The Contractor shall provide all necessary cable support
and steel embedment as required. The Contractor shall also be responsible for the
design/layout of the cable tray/support systems in time to provide the required provision in
the civil works.
The AC and DC supply as well as the batteries, chargers, distribution switchboards, etc., shall
meet the requirements of the Technical Specifications, Technical Schedules/Data Sheets and
conceptual drawings ESURP/AF/LVAC and ESURP/AF/110/DC provided with the Bid
document. This shall include all panels, wiring, etc. necessary to achieve the complete
auxiliary supply system, such as:
B.6.1 Main AC Distribution Panel (400V AC)
Equipped with:
- Motor operated 4-wire incomer air circuit breaker without ‘built-in releases’ but with
dedicated numerical O/C + E/F protections.
- Voltmeters and Ammeters, each with a selector switch.
- kWh meter (tariff metering accuracy class) for each incomer with test block for CT and
VT circuits, to facilitate meter testing.
- Outgoing ACB/MCCB/MCB for supply of station loads, lighting, air conditioning, DC
chargers, oil treatment plant, AIS testing, etc. of ratings as suitable for the loads to be
connected for the complete substation.
- 20% spare feeders, at least one (1) MCCB/MCB of each type used.
- The LVAC system incomer status, alarm and metering signals, along with other alarms,
shall be ready to be interfaced to the future SCMS system using the Common Services
BCUs.
B.6.2 110V DC Distribution Panel
Equipped with:
- Motor operated incomer and bus coupler circuit breakers, complete with adjustable
thermal and magnetic protection.
- Automatic and manual change over facilities with interlocking
- Voltmeters and Ammeters.
- Voltage control units (dropping diode)
- MCB's for emergency lighting, etc.
- 20% spare feeders, at least one (1) MCB of each type used.
- The DC system incomer and bus section breaker status, alarm and metering signals,
along with other alarms, shall be ready to be interfaced to the future SCMS system using
the Common Services BCUs.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 384
The distribution arrangement shall meet with the requirement of supplying the complete
substation loads.
B.6.3 110V DC Batteries and Chargers
For 110V DC system, the following equipment shall be provided:
- Two (2) sets of 100% rated, Ni-Cad, batteries sized for the complete substation.
- Two (2) 100% rated chargers, each with a voltage control unit, rated for the complete
substation.
- Two (2) battery switched-fuse boxes.
The capacity of the equipment supplied shall be as calculated according to the emergency
load requirements as well as the load requirements of the load to be connected and the
relevant Specifications and as stated above.
The power supply for the telecommunication equipment at 48VDC level, if any, shall be
derived from 110VDC System. This shall be through DC-DC Converters and approved
Compact MCB DB, all in Dual redundant configuration. This DC-DC package shall be
installed in approved wall/floor mounted cubicle.
B.7 SCMS System for 33/11kV System (Aberdeen, Clinetown,
Falconbridge, Jui and Waterloo Substations)
Substation Control and Monitoring System (SCMS) is not part of the scope of this RFB.
However, all equipment and systems supplied under this RFB shall be ready for integration
into the future SCMS.
B.8 Protection Equipment for 33kV & 11kV Switchgear
Dedicated numerical, multi-function bay control and protection units (BCPUs) with
embedded protection functions shall be provided as specified in Technical Schedules/Data
Sheets and Typical Protection Drawings ESURP/AF/PROT/PTR,
ESURP/AF/PROT/33/OHL, ESURP/AF/PROT/33/BC, ESURP/AF/PROT/33/11/BS,
ESUPR/AF/PROT/11/FEEDER and ESURP/AF/PROT/AUX/TRAFO provided with Bid
document. The scope of work shall also include documentation, including software for
settings, parameterization, analysis of disturbance records, licenses, operation and
maintenance manuals, fault finding manuals, etc. as well and recommended protection relay
settings for each protection terminal. Dedicated approved type Test Switches / Sockets shall
be provided for BCPU and Protection Relay terminals.
All software licenses shall be registered under EDSA name. All protection setting
calculations should be carried out using the latest version of ETAP or CYMDIST software
subject to EDSA approval. Models should be submitted for EDSA use. Finalized settings
shall be loaded into respective protection relays and BCPUs.
According to the typical protection drawings, the protection equipment shall cover the
following functions:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 385
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 386
- 33kV single core Cu/XLPE cables between the 33kV SWG and the 33kV OHL Terminal
towers including terminations at both ends.
- 33kV single core Cu/XLPE cables between the 33kV SWG and the 33/11kV Power
Transformer including terminations at both ends
- 11kV single core Cu/XLPE cables between the 33/11kV Power Transformer and 11kV
SWG including terminations at both ends.
- 11kV three core Cu/XLPE cables between the 11kV SWG and the Auxiliary
Transformer including terminations at both ends.
- 11kV three core Cu/XLPE cables between the 11kV SWG and the OHL terminal poles
including terminations at both ends.
- 11kV single core Cu/XLPE cables for grounding the MV Power Transformer 11kV
Neutral
- 1kV insulated LV XPLE power cables.
- LV multi-core control, fiber optic cables, coaxial cables and FOC patch cords, etc. as
applicable.
- All required cable racks, pipes, supporting structures, cable sealing ends/terminations,
ferrules and auxiliary equipment necessary for their proper installation, connection and
operation to the satisfaction of EDSA.
All LV power cables and multi core control, telephone cables, fiber optic cables and FOC
patch cords shall be connected to the relevant substation equipment, in an approved manner.
The Contractor shall provide all necessary racks, cable trays, cable cleats and any other
accessories required for the substation cables. Contractor shall supply the complete set of
supports in the 33kV & 11kV cable trenches for the Power for all feeders as per approved
cable routing within substation.
Cable ducts / trenches shall be provided for all 33kV & 11kV outgoing feeder cables. Layout
and arrangement of cable ducts shall be subject to separate approval of EDSA.
The price shall include all necessary wiring between the FOC, telephone cable termination
boxes/cabinets, and the related relay panels or optic terminals/signaling equipment (as
applicable).
B.10 Miscellaneous works
B.10.1 Earthing
An underground earthing system shall be provided to make it suitable for the highest earth
fault levels of the 33/11kV substation, as per the relevant Specifications.
The design, supply, installation and commissioning of the complete underground earthing
system for the complete 33/11kV Substation shall be undertaken by the Contractor. The
scope under this item shall also cover all above-ground earth connections of all equipment
supplied and installed by the Contractor for the entire substation and stub-outs for receiving
grounding connections of the transmission line (Cable) works. The above-ground earthing
for system is deemed as covered under this clause.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 387
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 388
Any items of work not mentioned above but required to meet HVAC requirements in full
shall be provided.
B.12 Civil Engineering and Construction Works
This section of the Scope of works covers the requirements of the civil and building works
necessary to house the Substation equipment being provided under the scope of this Contract
and includes the design, manufacture, testing, delivery, transport, storage at SITE, erection,
installation, commissioning, performance testing and handing over in satisfactory operating
condition of all civil works related to the substation(s).
The Scope of Works shall include all engineering (including design & drawing) and building
works necessary for the proper completion of the project in every respect. The civil
engineering and building works to be executed by the Contractor are to cover the collection
of site data, detailed design, and preparation of construction drawings for EDSA approval, all
required approvals and NOCs from regulatory authorities, obtaining building permit,
obtaining permanent services connections (if applicable) such as telephone, water, drainage,
etc. supply of materials, construction and subsequent maintenance of the works required as
outlined in the Specification documents.
Bidders shall note that complete civil design of the Substation must be finished and approved
by EDSA within three (3) months after the date of the letter of award. All civil design inputs
(loading and layouts) for all equipment must be taken into consideration before the start of
civil structural design.
The civil and building works shall be constructed in accordance with Civil Works
Specifications. The External Architectural Finish shall be explicitly approved by EDSA.
Substation Layout Drawings are provided for guidance and bidders are invited to propose
their own alternative layouts for optimization purposes.
The civil works and Electro Mechanical (including HVAC, Fire Detection and Protection,
etc.) works shall be handled in full compliance with the conceptual Tender Drawings and
Specifications and shall include but not be limited as follows:
- Detailed Site survey & Site Grading as required.
- Temporary access roads/ lay-down areas, etc. suitable for delivery of all civil and
electromechanical equipment. Include for removal at the end of the project. The
regulations for both access roads and lay-down areas assigned to the Contractor shall be
in accordance with the Municipality requirements.
- Relocation and / or protection of any existing underground/ above ground services
within the plot area that interfere with new construction, as required by the concerned
authorities/ EDSA including for future, if any.
- Site mobilization, including installation of site offices etc., for EDSA/ CONTRACTOR,
and other preparatory works as required.
- Installation and commissioning of temporary site services including, power, water, air
conditioning, Fire Fighting, foul water treatment/disposal system and communications to
site offices noted in. Include for removal at the end of the project.
- Soil investigation, complete in all aspects.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 389
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 390
The scope of supply / scope of works for civil works shall cover not only building as
described, but generally also all civil work related to:
- Cable laying within the station area(s) as necessary for the subject work,
- Earthing grid laying within the plot(s) as necessary,
- Piping for water, sewage and surface water drainage,
- Out Door and Indoor Fire Protection works,
- Air Conditioning layout as required,
- Access roads with road connections, plot and road area filling, if any.
The following external Civil Works, shall be taken into consideration under this scope of
works, but shall not be limited to the following:
- relocation of any services within the area, if required.
- modification / extension of surrounding pavements/sidewalks, if required.
- modification / extension of sewer and drainage systems, as required.
Examination of the Site by the Contractor
The Contractor has to study the Contract Documents, the Site, the location and the adjoining
buildings, premises and areas prior to having agreed on the Contract Price and that it has
made its own evaluation of the facilities available and the difficulties associated the Work.
Subsurface Conditions
The Contractor shall carry out his own subsoil investigation, which shall include a soil
investigation report and a geophysical / geo-technical survey, and he shall not contest the
contents of any report provided in the bid document, which shall be considered “for
information only”. EDSA shall not be liable for any deductions, interpretations or
conclusions made thereof by the Contractor.
The Contractor shall have full responsibility for interpreting the geo-technical data. Even if,
during the performance of the Work, it appears that the state of the sub-foundations and the
subsoil of the Site differ substantially from what has been set forth in the Contract Document,
the additional cost of the Work, if any, shall be borne solely by the Contractor.
Any necessary soil improvement shall be included in the Bidder’s price.
Surveys, Lines and levels
The Contractor shall furnish reference points, benchmark and elevations as may be required
for the execution of the Work. The Contractor shall protect all benchmarks, survey pegs and
monuments from damage or movement. If any of these are moved or disturbed, they shall be
replaced and installed at the Contractor's expense.
The Contractor shall be responsible for the entire cost of repairing, modifying or moving
Work improperly installed due to such bench marks, survey pegs and monuments having
been moved without the authorization of the respective authorities, or due to the Contractor’s
failure to protect and maintain same.
33/11kV Substation and Associated Works
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 391
200mm solid. All external design, appearance, and color to be proposed by Contractor for the
approval of EDSA.
The floor, wall and ceiling finishes shall be subject to EDSA approval. All visible concrete
surfaces shall be fair faced and painted. No defective concrete works shall be accepted.
Suitable reinforced concrete stiffeners and ties shall be used as required for the stability of
the internal walls.
Doors, frames, fixings and thresholds shall be EDSA approved of quality steel construction,
painted, and shall satisfy the requirements of the related clauses of the Specification. Dust
proofing shall be achieved by the use of neoprene or similar approved seals.
All doors shall open outwards from the building and from electrical rooms and shall be
provided with panic latches or bolts. All escape door leafs shall be fitted with panic bars
which override any locking device, for escape in the event of fire. Door closers shall be fixed
to all doors and door stays fixed to all external doors. Doors of offices, toilets, stores etc.
shall open inwards.
Switchgear rooms, large transformer compounds /cells shall have double access.
A key cabinet shall be provided suitable for holding all keys/padlocks required for the proper
operation of the substation. The cabinet shall be fitted with a hasp and staple and shall be
locked with a padlock (opened by substation master key).
Lighting (internal and external), air-conditioning, electrical and earthing systems, and
firefighting shall be EDSA approved and fulfil the requirements of the relevant
Specifications.
Any areas of exposed concrete such as equipment foundations, apron slabs, pathways etc.
shall receive a protective coating of approved chemically resistant paint.
For the fire rating requirements, as applicable for civil works, reference is made to
recognized international standards.
The layout and switchgear arrangement in the transformer bays and equipment rooms may be
modified and adopted to suit the actual equipment sizes in order to achieve an optimum
workable layout of all equipment to be located inside the substation building.
The Bidder shall submit a properly worked out proposal for recommended layout of
equipment in accordance with the actual equipment dimensions whilst satisfying the building
and security regulations. The proposal shall include elevation drawings for the substation
indicating the building height requirements for the quoted equipment. In the absence of such
submission, it will be considered that the Bidder has studied the conceptual bidding
document drawing and has agreed to accommodate all equipment in the building as detailed.
The Contractor is responsible for all necessary coordination to meet the requirements of
electrical, mechanical and civil works to achieve a homogeneous and uniform design.
In particular, the scope of civil works shall be inclusive of the following:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 393
- Access road construction, pavements and footpaths, shall be provided in accordance with
conceptual general layout drawing.
- As applicable, reinforced cable trenches with racks/ladders and/or cable ducts and pipes
shall be provided up to one meter beyond the plot limit. Trenches shall be sufficient in
sizes and ducts shall be sufficient in numbers for exit and entry of all HV, MV, LV and
fiber optic cables. A 20% spare capacity shall be provided on each side of the building
where it is possible to avoid excavation inside the substation plot at later stages for
installation of additional cables.
- Excavated material, excess to requirement shall be properly disposed of at an approved
tipping area. Dewatering, if required, shall be included. Filling and compaction shall be
performed with approved material only.
- Provision of Plumbing, ducting, Sewage, Water and Drainage system from building roof,
roads and any other contained areas shall be connected to the external Municipal
drainage network.
- Provision shall be made for septic tank, neutralizing pit, soak-away, if there is no
connection to nearby municipality network.
- Embedded electrical conduits, sleeves, bolts and steel elements
- Supply and install cable tray and cable support for power and control cables for
complete Switchgear including future if required
- Staircase, loading platform, etc. shall be provided as applicable
- Waterproofing of the building structure, water storage tanks, sump and drain pits, wet
areas and roof area including leak test for roof and water tanks
- Manholes, trap doors, grille, fire cabinets, associated covers, chequered plates, gratings
and its supporting systems.
- Sealing of all openings, joints, sleeves including fire stop seal.
- Air-conditioning and ventilation system for the complete installation, as applicable shall
be provided.
- Indoor and outdoor lighting and small power system for the substation complex shall be
provided.
- Lightning protection, earthing for power and communication systems shall be provided
for substation complex
- Fire detection, alarm and firefighting system as required for the substation complex shall
be included.
Substation Building
General conceptual layout is shown on the proposed substation layout drawings for guidance
only. All internal dimensions as indicated on the drawing are for reference only. The
Contractor is responsible for the final design and arrangement according to the proposed
equipment and requirements of this specification.
The walls shall be provided with cable transition facilities of adequate quantity to suit the
number of feeders plus 20% spare.
Each switchgear room shall be provided with fireproof steel door as well as personnel
entrance steel doors.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 394
Steel plates embedded in concrete shall be used for fixing the equipment to the floor.
Any areas of exposed concrete such as equipment foundations, apron slabs, pathways etc.
shall receive a protective coating of U-V resistant paint. Miscellaneous structural/ steel works
as required.
Power Transformer Area
The Contractor shall make all necessary arrangements including, but not limited to, the
provision of civil works required for transportation, access, loading and unloading, installing
heavy equipment in all the bays.
General conceptual layout is shown on the proposed substation layout drawings for guidance.
The dimensions as indicated on the drawing are for reference only. The Contractor is
responsible to properly design the layout according to the proposed equipment and
requirements of this specification.
The oil collecting pits shall be of adequate capacity to hold 120% of oil for each unit.
The transformer bays shall be of the “open to sky” type with security chain link fence or GI
mesh supported on a structural steel frame with lockable gates for substation.
The Contractor shall make provision for the catchment of oil spillage from the equipment
resulting from mechanical or electrical failure. Precautions shall be provided to prevent
pollution of ground water, irrigation ditches and other watercourses by leaking or ejected oil.
Equipment foundations shall be surrounded by a low watertight reinforced concrete wall
enclosing an area or pit in which the entire oil content of the equipment can be retained in the
event of a major leak.
Control Room Area
General conceptual layout is shown on the proposed substation layout drawings for guidance.
The internal dimensions as indicated on the drawing are preliminary and for reference. The
Contractor shall propose the most suitable layout arrangement according to the proposed
equipment and requirements of this specification.
Allocation of size and number of rooms as indicated on the drawing is tentative. The
Contractor shall propose a suitable arrangement to accommodate the proposed.
Cable Trench, Cable Shaft, Cable Riser, Cable Entry Ducts
The Contractor shall provide sufficient reinforced concrete cable trenches together with cable
racks and/or cable ducts. These trenches and ducts shall be sufficient in size and numbers to
accommodate all cables, including spare capacity.
Covers shall be provided with protective galvanized steel angles/channels. They shall be
easily removed and designed to withstand the maximum loadings likely to occur relative to
their location.
The Contractor shall provide reinforced concrete duct banks, sufficient in size and numbers
to accommodate required cables, including spares. Duct bank and cable trench shall include
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 395
waterproofing and proper sealing. Ends of ducts and cable trench are to be extended one
meter beyond the plot boundary (as applicable) and to be provided with removable caps.
Location of duct banks, orientation, slopes for ducts, if any, shall be subject to EDSA
approval. Contractor shall provide steel access platforms in all service shafts.
Pull pits of suitable size, located at the ends of duct banks shall be provided as deemed
necessary, and shall be subject to EDSA approval.
Adequate sumps and means of drainage shall be incorporated into the trench system.
Trenches shall be subject to EDSA approval.
- Required cable trenches shall be of concrete and provided with proper trays, ladders,
cleats etc., suitable removable trench covers, as necessary.
- Cable shaft, gallery, cable riser, cable entry ducts etc. shall be provided as per the site
requirement with minimum 20% spare quantity.
HVAC System
Air conditioning equipment shall be provided as specified in Price Schedules. The position of
the equipment shall be proposed by Contractor subject to EDSA approval.
Internal Roads & Pavements & Access Roads
Construction of internal roads within the plot area made of heavy-duty interlocking tiles, as
shown on proposed substation layout drawings.
Construction of pavements made of interlocking tiles, around the buildings and structures.
Site leveling and installation of single sized layer of gravel for the internal area inside plot
boundary are included in Contractor’s Scope. Gravel layer shall be smoothly leveled to reach
the kerb stone level.
Road Surface and substation plot area drainage shall include soak away ditches or discharge
to network storm water system etc. It also includes Construction of vehicular access to the
main substation equipment rooms and external access ramps.
Design and installation of cross carriageway duct banks/pipe crossings.
Construction of external access roads required for connection of substation to the main road,
as indicated in Price Schedules. The width of the external access roads shall be 10m or more
as per needs of Transportation.
Perimeter Fencing
Substations perimeter fence shall be constructed as solid block wall with steel barbed or
blade wire as shown on proposed substation layout drawings. The dimensions indicated on
the drawing are preliminary and for reference only. The height of substation perimeter fence
shall be at list 3.5m from the finished ground level.
Security/Guard House
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 396
Security/Guard house shall be constructed as solid block wall building as shown on proposed
substation layout drawings. The dimensions indicated on the drawing are preliminary and for
reference only.
Dismantling & Demolition Works
Existing facilities within substation perimeter (if any) shall be dismantled and demolished by
the Contractor. Whenever dismantling of equipment is carried out, the materials, which
become excess / redundant, are not to be returned to EDSA. While returning the materials to
EDSA stores, these materials shall be neatly bundled /packed, and along with detailed
packing list, these materials are to be handed over to EDSA stores. In such cases the expenses
for handing over the materials to EDSA Stores is deemed to be included in various rates
included in the Contract Price. In any case mentioned above, the materials shall be cleared
from site as early as possible. The area shall be back-filled with general fill as applicable. The
site of demolished building shall be in clean condition.
B.13 Site Training of EDSA Personnel
During execution of the contract, the Contractor shall provide training to O&M personnel
appointed by EDSA for their plant, as may be necessary.
Operation and maintenance training shall be imparted at site to the staff as nominated by the
EDSA.
The training shall familiarize the staff of the EDSA in operation, maintenance, fault finding
and restoration techniques for all equipment to enable them to attend to the same after the
works have been handed over.
The Contractor shall provide all instruction materials required, such as manuals, booklets,
drawings, etc. which shall become property of EDSA.
Training, the content of which shall be subject to approval by the EDSA during the execution
stage, shall be provided for the following (for one-week duration for up to five engineers per
item):
- 161/33kV Outdoor switching equipment (CB, switches, etc.)
- 161/33kV Transformer
- 33/11kV Transformers
- Transformers Paralleling
- 33/11kV Indoor switchgear
- 33/11kV Cables/Terminations
- Protection
- Telecommunication
- DC System
- Fire Protection and Detection Systems
If the Contractor considers that the nature and/or quantity of equipment requires another
training duration than stated above, he shall propose a relevant time schedule including
breakdown of topics and points to be covered, each associated with the suggested duration.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 397
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 398
New 33kV line from 33/11kV Jui S/S to 33/11kV Waterloo S/S
The line shall be in general constructed as double circuit 265mm2 AAC conductor and 32
fiber OPGW (optical ground wire) on steel lattice towers. Partially where site conditions
dictate line will be constructed with 300mm2 33kV, single core XLPE/SWA/PVC Cu
underground cable and 32 fiber optic cable. The approximate route length is 16.5 km.
Second circuit of 33kV line from 33/11kV Blackhall Road S/S to 33/11kV Wellington
S/S
Stringing of second circuit of 33kV line with 265mm2 AAC conductor and 32 fiber OPGW
(optical ground wire) on existing slim steel lattice towers. The approximate route length is
8.5 km.
Upgrade of existing 33kV lines between Freetown 161, Blackhall Road and Wilberforce
Substations
The works involve the upgrade of an existing network of double circuit 2x (3(1x150mm 2
ACSR)) Lattice tower lines to Double Circuit 2x (3(1x265mm2 AAC)). The Contractor shall
be required to do analysis/assessment of the strength of the existing towers to carry the
double circuit 265 AAC. For this, the design and/or drawings of the existing towers will be
provided by EDSA to the successful Bidder. If it is determined that the strength is
inadequate, then a re-design of the tower would have to be carried out by Contractor to
determine which and how new members would be introduced to reinforce towers. The
Contractor shall be required to examine strength and adequacy of existing foundations. If it is
determined that existing foundations can withstand increased load the Contractor shall be
required to reinforce the existing towers to ensure their capability to carry the heavier
conductors. However, if it is determined that existing foundations cannot withstand increased
load, than it wouldn’t be possible to upgrade existing 33kV lines.
The scope of work shall include but not limited to the following:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 399
A. Preliminary Works
A.1 Site Establishment
Provision of site establishment and execution of all temporary works, such as: Contractor's
and Owner/Engineer's temporary facilities, temporary services, site access roads, temporary
site fencing, signboards, etc. as per Standard Specification.
A.1.1 Line Route Survey
The scope of work shall include final route survey, collection of information about the
existing services (cables, pipes, ducts, etc.), profile survey, tower spotting etc.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 400
The detailed route maps shall be prepared by the Contractor in the required quantity and are
to be submitted for EDSA approval prior to submission to the Town Planning department and
other relevant authorities for their approval.
Before the construction stage, route maps shall be amended to display line access provisions.
A.1.2 Soil Investigation
The Contractor shall investigate the soil conditions at site prior to collect the necessary
information for the design of the transmission line foundations. Soil investigations are to be
performed as per approved standards, and shall provide sufficient information on the subsoil
conditions including all necessary tests and reports.
All necessary trenches, trial pits, tests, reports, etc to confirm the underground services
clearances are deemed to be included in Scope of Work.
A.1.3 Access Roads
The Scope of Work includes the provision and maintenance of access road to the
transmission line routes and the tower locations as required for erection work and EDSA
supervision.
All access roads to be prepared by the contractor and submitted, prior to construction, for
EDSA approval.
Access roads should be well maintained for the whole duration of the Contract.
Access roads along the line route shall be routed at a maximum distance of 10 m between the
edge of road and the tower legs. Sufficient working area surrounding the tower and the access
road shall be cleared for installation purposes.
B. Foundations
Design and execution of civil works shall be in line with the requirements of relevant British
Standards.
Before any work is commenced, the Contractor shall submit to EDSA for approval, full
details of the foundation design with all relevant dimensions, lengths, design, ultimate loads,
method of construction, ground conditions, full details of the method of carrying out the work
which he intends to use.
Contractor shall prepare, submit and obtain approval on the Design Criteria to be followed
during the course of the design.
All necessary formwork, concrete, reinforcement, permanent casing, earthing, corrosion
protection, etc. are deemed included in Scope of Work.
C. Towers/Poles
The scope of work shall include, but not limited to manufacturing, supply, testing and
inspection at manufacturer's works, insurance, packing for export shipment, delivery to site,
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 401
unloading, survey and profile plotting of support positions, pegging out, clearing, provision,
complete erection, setting to work, finishing, testing and commissioning, etc.
The towers/poles shall contain all required accessories such as identification plates, earth
clamping bolts, basic grounding, site services, tests, corrosion protection of stub angles,
painting, anti-climbing device, step bolts, etc. as follows:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 402
- Light Angle/Section Pole Single Circuit Structure (5o – 20o, Dwg No. ESURP-AF-POLE-
33-SC-AS)
- Tension/Light Angle Pole Double Circuit Structure (5o - 20o, Dwg. No. ESURP-AF-
POLE-33-DC-TA)
- Medium Angle/Section Pole Single Circuit Structure (20o – 60o, Dwg No. ESURP-AF-
POLE-33-SC-AS)
- Tension/Medium Angle Pole Double Circuit Structure (20o - 60o, Dwg. No. ESURP-AF-
POLE-33-DC-TA)
- Large Angle/Section Pole Single Circuit Structure (60o – 90o, Dwg No. ESURP-AF-
POLE-33-SC-AS)
- Tension/Large Angle Pole Double Circuit Structure (60o - 60o, Dwg. No. ESURP-AF-
POLE-33-DC-TA)
- Terminal Pole Single Circuit Structure (Dwg. No. ESURP-AF-POLE-33-SC-TE)
C.1 Extension of Tower Height
According to the project requirement and upon EDSA approval, height extension per running
meter of the tower shall be performed as follows:
- 3m extension of Suspension Tower type SS,
- 3m extension of Angle Tension Tower type ST1,
- 3m extension of Angle Tension Tower type ST2,
- 3m extension of Dead-end (Terminal) Tower type DE
- 6m extension of Suspension Tower type SS,
- 6m extension of Angle Tension Tower type ST1,
- 6m extension of Angle Tension Tower type ST2,
- 6m extension of Dead-end (Terminal) Tower type DE
C.2 Full Scale Tower/Pole Tests
Full-scale tower/pole load tests of assembled galvanized towers/poles shall be carried out for
each type of towers as follows:
- Suspension Tower type SS,
- Angle Tension Tower type ST1,
- Angle Tension Tower type ST2,
- Dead-end (Terminal) Tower type DE
- Intermediate Pole Single Circuit
- Intermediate Pole Double Circuit Structure
- Angle/Section Pole Signe Circuit Structure
- Tension/Angle Pole Double Circuit Structure
- Terminal pole Single Circuit Structure
C、 2 个全尺寸塔/杆测试 对于每种类型的塔,应进行组装镀锌塔/杆的足尺塔/
杆荷载试验,如下所示: -SS 型悬挂塔, -ST1 型角张力塔, -
ST2 型角张力塔, -DE 型终端塔 -中间极单回路 -中间极双回路
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 403
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 404
F. Miscellaneous Works
F.1 Additional works
According to the project requirement and upon EDSA approval, additional works may be
performed, such as:
- Reinforced concrete as instructed by EDSA
- Painting of towers/poles for corrosion protection with topcoat executed in red and white
bands for aircraft warning purpose
- Additional deep bore earthing rods for selected towers/poles
- Additional earthing/grounding gridding rings around the tower legs/poles for selected
tower/pole locations.
- Aircraft warning spheres
、 1 附加工程 根据项目要求,经 EDSA 批准,可开展额外工作,例如:
-EDSA 指示的钢筋混凝土 -飞机警告用红白相间面漆涂防腐塔/杆 -选定
塔/杆的附加深孔接地棒 -选定塔/杆位置的塔腿/杆周围的附加接地/接地网格环。
F.2 Protection of tower/pole locations
Foundation Stabilization Layer
Upon EDSA instruction and at selected locations where earth moving (e.g. landslides,
erosion, etc.) is likely to occur; tower/pole foundations and leg structures shall be protected
by means of backfilling and layers of stabilizing material/soil to prevent erosion.
Stabilizing material (e.g. gatch or other approved material) has to be laid and compacted to a
thickness of not less than 150 mm. The protected area should reach at least 3.0 m beyond the
edge of the foundations and as per EDSA approval.
Foundation Platforms and Stone Pitching
In low lying areas, the construction of foundation platforms (fill) may become necessary to
raise the foundations sufficiently above the existing ground. Such platforms shall be
constructed entirely from approved materials compacted to min. 500 mm thickness.
Platforms shall at least extend 3.0 m beyond the foundation edge. Platform sides shall be
compacted to the min. slope of 1:2 and protected by stone pitching set in a cement/sand
mortar. The platform is to be provided with continuous toe beams of approved cross section
to support the stone pitching.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 405
使地基充分地高于现有地基。此类平台应完全由经批准的材料制成,并压实至最小
500 mm 厚。平台至少应延伸超过基础边缘 3 米。平台侧面应压实至 1:2 的最小坡度,
并用水泥/砂浆中的砌石护坡进行保护。平台应配备批准横截面的连续趾梁,以支撑砌
石护坡。
F.3 Signboards for Road Crossings
The scope of work shall include design, supply, delivery and erection of signboards for road
crossings according the instructions of EDSA.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 406
Supply and installation of all required cable racks, pipes, supporting structures, clamps,
cable’s sealing ends / terminations, ferrules and auxiliary equipment necessary for proper
installation, connection and operation of all cables, to the satisfaction of the EDDSA as
follows:
- Supply and installation of cable terminations for 3x(1Cx300mm2) 33kV,
XLPE/SWA/PVC Cu
- Supply and installation of termination boxes for fiber optic cables at 33/11kV Substations
and terminal towers/poles,
- Supply and installation of PVC pipes 106mm/ 100mm diameters, for fiber optic cables as
required
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 407
Specification
The technical specifications and drawings are available in the following Annexure and can be
found in Volume II of the bidding document. The lists of Technical specifications and
drawings in each Annexure are given in this section.
Annexure No Particulars
Annexure -1 Technical Specifications
Annexure -2 Drawings
Annexure -1: The List of Technical Specifications attached are listed below
Sl. No. SECTIONS PARTICULARS
1. SECTION-1 GENERAL TECHNICAL SPECIFICATIONS
2. SECTION-2 TECHNICAL SPECIFICATIONS FOR SUBSTATIONS
ELECTROMECHANICAL WORKS – LOT 1
3. SECTION-3 TECHNICAL SPECIFICATIONS FOR OVERHEAD LINES
WORKS – LOT 2
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 408
______________________________
To: _________________________________
However, you are required to complete the outstanding items listed in the attachment hereto
as soon as practicable.
This letter does not relieve you of your obligation to complete the execution of the Facilities
in accordance with the Contract nor of your obligations during the Defect Liability Period.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 409
Title
(Project Manager)
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 410
Date:
Loan/Credit No:
RFB No:
_________________________________________
To: ________________________________________
Pursuant to GCC Sub-Clause 25.3 (Operational Acceptance) of the General Conditions of the
Contract entered into between yourselves and the Employer dated _______________, relating to
the ___________________________________, we hereby notify you that the Functional
Guarantees of the following part(s) of the Facilities were satisfactorily attained on the date
specified below.
Title
(Project Manager)
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 411
CONTENTS
1. General
2. Change Order Log
3. References for Changes
ANNEXES
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 412
(b) The above number “nnn” is the same for Request for Change, Estimate for
Change Proposal, Acceptance of Estimate, Change Proposal and Change
Order.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 413
Attention: ______________________________________
With reference to the captioned Contract, you are requested to prepare and submit a Change
Proposal for the Change noted below in accordance with the following instructions within
_______________ days of the date of this letter____________________.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 414
(a) Please submit your estimate to us showing what effect the requested Change will
have on the Contract Price.
(b) Your estimate shall include your claim for the additional time, if any, for
completion of the requested Change.
(c) If you have any opinion negative to the adoption of the requested Change in
connection with the conformability to the other provisions of the Contract or the
safety of the Plant or Facilities, please inform us of your opinion in your proposal
of revised provisions.
(d) Any increase or decrease in the work of the Contractor relating to the services of
its personnel shall be calculated.
(e) You shall not proceed with the execution of the work for the requested Change
until we have accepted and confirmed the amount and nature in writing.
(Employer’s Name)
(Signature)
(Name of signatory)
(Title of signatory)
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 415
Attention: _______________________________
16
Costs shall be in the currencies of the Contract.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 416
(Contractor’s Name)
(Signature)
(Name of signatory)
(Title of signatory)
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 417
(Employer’s Letterhead)
Attention: ________________________________
We hereby accept your Estimate for Change Proposal and agree that you should proceed with
the preparation of the Change Proposal.
6. Other Terms and Conditions: In the event that we decide not to order the Change
accepted, you shall be entitled to compensation for the cost of preparation of Change
Proposal described in your Estimate for Change Proposal mentioned in para. 3 above in
accordance with GCC Clause 39 of the General Conditions.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 418
(Employer’s Name)
(Signature)
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 419
Attention: _______________________________
17
Costs shall be in the currencies of the Contract.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 420
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 421
(Contractor’s Name)
(Signature)
(Name of signatory)
(Title of signatory)
2
Specify where necessary.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 422
Attention: _______________________________
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 423
(Contractor)
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 424
Attention: _______________________________
We instruct you to carry out the work in the Change Order detailed below in accordance with
GCC Clause 39 of the General Conditions.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 425
(Employer’s Name)
(Signature)
(Name of signatory)
(Title of signatory)
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 426
Attention: _______________________________
We hereby propose that the below-mentioned work be treated as a Change in the Facilities.
8. Appendix:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 427
(Contractor’s Name)
(Signature)
(Name of signatory)
(Title of signatory)
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 428
Drawings
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 429
SL.
DESCRIPTION DRAWING NUMBER
No.
CONCEPTUAL DESIGN OF LVAC STATION
14 ESURP/AF/LVAC
SUPPLY PANEL
The 33kV Overhead Lines Design Drawings included in this Bidding Document are
listed below
SL.
DESCRIPTION DRAWING NUMBER
No.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII – Employer’s Requirements 430
SL.
DESCRIPTION DRAWING NUMBER
No.
TYPICAL FOUNDATION SKETCH FOR
8 ESURP/AF/POLE/33/INTFOUN
INTERMEDIATE POLES
TYPICAL FOUNDATION SKETCH FOR ANGLE,
9 ESURP/AF/POLE/33/ASTFOUN
SECTION, TERMINAL POLES
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VII - Employer’s Requirements 431
Supplementary Information
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Part 3 – Conditions of Contract and Contract Forms 433
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 435
Table of Clauses
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 436
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 437
1. Definitions 1.1 The following words and expressions shall have the meanings hereby
assigned to them:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 438
“Site” means the land and other places upon which the Facilities are to
be installed, and such other land or places as may be specified in the
Contract as forming part of the Site.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 440
3. Interpretation 3.1 In the Contract, except where the context requires otherwise:
(b) words indicating the singular also include the plural and words
indicating the plural also include the singular;
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 441
The marginal words and other headings shall not be taken into
consideration in the interpretation of these Conditions.
3.2 Incoterms
3.4 Amendment
3.6 Non-Waiver
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 442
3.7 Severability
“Origin” means the place where the plant and component parts thereof
are mined, grown, produced or manufactured, and from which the
services are provided. Plant components are produced when, through
manufacturing, processing, or substantial or major assembling of
components, a commercially recognized product results that is
substantially in its basic characteristics or in purpose or utility from its
components.
4. Communica- 4.1 Wherever these Conditions provide for the giving or issuing of
tions approvals, certificates, consents, determinations, notices, requests and
discharges, these communications shall be:
5. Law and 5.1 The Contract shall be governed by and interpreted in accordance with
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 443
5.2 The ruling language of the Contract shall be that stated in the PCC.
5.3 The language for communications shall be the ruling language unless
otherwise stated in the PCC.
6. Fraud and 6.1 The Bank requires compliance with the Bank’s Anti-Corruption
Corruption Guidelines and its prevailing sanctions policies and procedures as set
forth in the WBG’s Sanctions Framework, as set forth in Appendix B
to the GCC.
6.2 The Employer requires the Contractor to disclose any commissions or
fees that may have been paid or are to be paid to agents or any other
party with respect to the Bidding process or execution of the Contract.
The information disclosed must include at least the name and address
of the agent or other party, the amount and currency, and the purpose
of the commission, gratuity or fee.
8. Time for 8.1 The Contractor shall commence work on the Facilities within the
Commence- period specified in the PCC and without prejudice to GCC Sub-
ment and Clause 26.2 hereof, the Contractor shall thereafter proceed with the
Completion Facilities in accordance with the time schedule specified in the
Appendix to the Contract Agreement titled Time Schedule.
9.2 The Contractor confirms that it has entered into this Contract on the
basis of a proper examination of the data relating to the Facilities
including any data as to boring tests provided by the Employer, and
on the basis of information that the Contractor could have obtained
from a visual inspection of the Site if access thereto was available
and of other data readily available to it relating to the Facilities as of
the date twenty-eight (28) days prior to Bid submission. The
Contractor acknowledges that any failure to acquaint itself with all
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 445
such data and information shall not relieve its responsibility for
properly estimating the difficulty or cost of successfully performing
the Facilities.
9.3 The Contractor shall acquire and pay for all permits, approvals
and/or licenses from all local, state or national government
authorities or public service undertakings in the country where the
Site is located which such authorities or undertakings require the
Contractor to obtain in its name and which are necessary for the
performance of the Contract, including, without limitation, visas for
the Contractor’s and Subcontractor’s personnel and entry permits
for all imported Contractor’s Equipment. The Contractor shall
acquire all other permits, approvals and/or licenses that are not the
responsibility of the Employer under GCC Sub-Clause 10.3 hereof
and that are necessary for the performance of the Contract.
9.4 The Contractor shall comply with all laws in force in the country
where the Facilities are to be implemented. The laws will include
all local, state, national or other laws that affect the performance of
the Contract and bind upon the Contractor. The Contractor shall
indemnify and hold harmless the Employer from and against any
and all liabilities, damages, claims, fines, penalties and expenses of
whatever nature arising or resulting from the violation of such laws
by the Contractor or its personnel, including the Subcontractors and
their personnel, but without prejudice to GCC Sub-Clause 10.1
hereof.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 446
10. Employer’s 10.1 All information and/or data to be supplied by the Employer as
Responsibilities described in the Appendix to the Contract Agreement titled Scope of
Works and Supply by the Employer, shall be deemed to be accurate,
except when the Employer expressly states otherwise.
10.2 The Employer shall be responsible for acquiring and providing legal
and physical possession of the Site and access thereto, and for
providing possession of and access to all other areas reasonably
required for the proper execution of the Contract, including all
requisite rights of way, as specified in the Appendix to the Contract
Agreement titled Scope of Works and Supply by the Employer. The
Employer shall give full possession of and accord all rights of
access thereto on or before the date(s) specified in that Appendix.
10.3 The Employer shall acquire and pay for all permits, approvals
and/or licenses from all local, state or national government
authorities or public service undertakings in the country where the
Site is located which (a) such authorities or undertakings require the
Employer to obtain in the Employer’s name, (b) are necessary for
the execution of the Contract, including those required for the
performance by both the Contractor and the Employer of their
respective obligations under the Contract, and (c) are specified in
the Appendix (Scope of Works and Supply by the Employer).
10.4 If requested by the Contractor, the Employer shall use its best
endeavors to assist the Contractor in obtaining in a timely and
expeditious manner all permits, approvals and/or licenses necessary
for the execution of the Contract from all local, state or national
government authorities or public service undertakings that such
authorities or undertakings require the Contractor or Subcontractors
or the personnel of the Contractor or Subcontractors, as the case
may be, to obtain.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 447
10.6 The Employer shall be responsible for the continued operation of the
Facilities after Completion, in accordance with GCC Sub-Clause
24.8, and shall be responsible for facilitating the Guarantee Test(s)
for the Facilities, in accordance with GCC Sub-Clause 25.2.
10.8 In the event that the Employer shall be in breach of any of his
obligations under this Clause, the additional cost incurred by the
Contractor in consequence thereof shall be determined by the
Project Manager and added to the Contract Price.
C. Payment
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 448
11. Contract Price 11.1 The Contract Price shall be as specified in Article 2 (Contract Price
and Terms of Payment) of the Contract Agreement.
11.3 Subject to GCC Sub-Clauses 9.2, 10.1 and 35 hereof, the Contractor
shall be deemed to have satisfied itself as to the correctness and
sufficiency of the Contract Price, which shall, except as otherwise
provided for in the Contract, cover all its obligations under the
Contract.
12. Terms of 12.1 The Contract Price shall be paid as specified in Article 2 (Contract
Payment Price and Terms of Payment) of the Contract Agreement and in the
Appendix to the Contract Agreement titled Terms and Procedures
of Payment, which also outlines the procedures to be followed in
making application for and processing payments.
12.3 In the event that the Employer fails to make any payment by its
respective due date or within the period set forth in the Contract, the
Employer shall pay to the Contractor interest on the amount of such
delayed payment at the rate(s) shown in the Appendix to the
Contract Agreement titled Terms and Procedures of Payment, for
the period of delay until payment has been made in full, whether
before or after judgment or arbitrage award.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 449
specified below.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 450
14. Taxes and 14.1 Except as otherwise specifically provided in the Contract, the
Duties Contractor shall bear and pay all taxes, duties, levies and charges
assessed on the Contractor, its Subcontractors or their employees by
all municipal, state or national government authorities in connection
with the Facilities in and outside of the country where the Site is
located.
(a) all customs and import duties for the Plant specified in Price
Schedule No. 1; and
(b) other domestic taxes such as, sales tax and value added tax
(VAT) on the Plant specified in Price Schedules No. 1 and
No. 2 and that is to be incorporated into the Facilities, and on
the finished goods, imposed by the law of the country where
the Site is located.
14.4 For the purpose of the Contract, it is agreed that the Contract Price
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 451
D. Intellectual Property
15. License/Use of 15.1 For the operation and maintenance of the Plant, the Contractor
Technical hereby grants a non-exclusive and non-transferable license
Information (without the right to sub-license) to the Employer under the
patents, utility models or other industrial property rights owned by
the Contractor or by a third Party from whom the Contractor has
received the right to grant licenses thereunder, and shall also grant
to the Employer a non-exclusive and non-transferable right
(without the right to sub-license) to use the know-how and other
technical information disclosed to the Employer under the
Contract. Nothing contained herein shall be construed as
transferring ownership of any patent, utility model, trademark,
design, copyright, know-how or other intellectual property right
from the Contractor or any third Party to the Employer.
16. Confidential 16.1 The Employer and the Contractor shall keep confidential and shall
Information not, without the written consent of the other Party hereto, divulge
to any third Party any documents, data or other information
furnished directly or indirectly by the other Party hereto in
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 452
16.2 The Employer shall not use such documents, data and other
information received from the Contractor for any purpose other
than the operation and maintenance of the Facilities. Similarly, the
Contractor shall not use such documents, data and other
information received from the Employer for any purpose other than
the design, procurement of Plant, construction or such other work
and services as are required for the performance of the Contract.
16.3 The obligation of a Party under GCC Sub-Clauses 16.1 and 16.2
above, however, shall not apply to that information which
(b) can be proven to have been possessed by that Party at the time
of disclosure and which was not previously obtained, directly or
indirectly, from the other Party hereto
16.4 The above provisions of this GCC Clause 16 shall not in any way
modify any undertaking of confidentiality given by either of the
Parties hereto prior to the date of the Contract in respect of the
Facilities or any part thereof.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 453
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 454
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 455
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 456
40, and shall submit all such revisions to the Project Manager.
18.5 Procedures
19. Subcontracting 19.1 The Appendix to the Contract Agreement titled List of Major
Items of Plant and Installation Services and List of Approved
Subcontractors, specifies major items of supply or services
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 457
19.2 The Contractor shall select and employ its Subcontractors for
such major items from those listed in the lists referred to in
GCC Sub-Clause 19.1.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 460
21.2.1 The Employer shall, at its own risk and expense, transport
each item to the place on or near the Site as agreed upon by
the Parties and make such item available to the Contractor at
the time specified in the program furnished by the Contractor,
pursuant to GCC Sub-Clause 18.2, unless otherwise mutually
agreed.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 461
21.2.2 Upon receipt of such item, the Contractor shall inspect the
same visually and notify the Project Manager of any detected
shortage, defect or default. The Employer shall immediately
remedy any shortage, defect or default, or the Contractor
shall, if practicable and possible, at the request of the
Employer, remedy such shortage, defect or default at the
Employer’s cost and expense. After inspection, such item
shall fall under the care, custody and control of the
Contractor. The provision of this GCC Sub-Clause 21.2.2
shall apply to any item supplied to remedy any such shortage
or default or to substitute for any defective item, or shall
apply to defective items that have been repaired.
21.3 Transportation
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 462
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 463
22.2 Labor:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 464
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 465
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 466
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 467
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 468
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 469
Such Site regulations shall include, but shall not be limited to,
rules in respect of security, safety of the Facilities, gate
control, sanitation, medical care, and fire prevention.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 470
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 471
23. Test and 23.1 The Contractor shall at its own expense carry out at the place
Inspection of manufacture and/or on the Site all such tests and/or
inspections of the Plant and any part of the Facilities as are
specified in the Contract.
23.3 Whenever the Contractor is ready to carry out any such test
and/or inspection, the Contractor shall give a reasonable
advance notice of such test and/or inspection and of the place
and time thereof to the Project Manager. The Contractor shall
obtain from any relevant third Party or manufacturer any
necessary permission or consent to enable the Employer and
the Project Manager or their designated representatives to
attend the test and/or inspection.
23.5 The Project Manager may require the Contractor to carry out
any test and/or inspection not required by the Contract,
provided that the Contractor’s reasonable costs and expenses
incurred in the carrying out of such test and/or inspection
shall be added to the Contract Price. Further, if such test
and/or inspection impede the progress of work on the
Facilities and/or the Contractor’s performance of its other
obligations under the Contract, due allowance will be made in
respect of the Time for Completion and the other obligations
so affected.
23.6 If any Plant or any part of the Facilities fails to pass any test
and/or inspection, the Contractor shall either rectify or replace
such Plant or part of the Facilities and shall repeat the test
and/or inspection upon giving a notice under GCC Sub-
Clause 23.3.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 473
23.8 The Contractor shall afford the Employer and the Project
Manager, at the Employer’s expense, access at any reasonable
time to any place where the Plant are being manufactured or
the Facilities are being installed, in order to inspect the
progress and the manner of manufacture or installation,
provided that the Project Manager shall give the Contractor a
reasonable prior notice.
24. Completion of 24.1 As soon as the Facilities or any part thereof has, in the opinion
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 474
24.2 Within seven (7) days after receipt of the notice from the
Contractor under GCC Sub-Clause 24.1, the Employer shall
supply the operating and maintenance personnel specified in
the Appendix to the Contract Agreement titled Scope of
Works and Supply by the Employer for Precommissioning of
the Facilities or any part thereof.
24.5 The Project Manager shall, within fourteen (14) days after
receipt of the Contractor’s notice under GCC Sub-Clause
24.4, either issue a Completion Certificate in the form
specified in the Employer’s Requirements (Forms and
Procedures), stating that the Facilities or that part thereof have
reached Completion as of the date of the Contractor’s notice
under GCC Sub-Clause 24.4, or notify the Contractor in
writing of any defects and/or deficiencies.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 475
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 477
25.3.2 At any time after any of the events set out in GCC
Sub-Clause 25.3.1 have occurred, the Contractor may
give a notice to the Project Manager requesting the
issue of an Operational Acceptance Certificate in the
form provided in the Employer’s Requirements (Forms
and Procedures) in respect of the Facilities or the part
thereof specified in such notice as of the date of such
notice.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 479
26. Completion 26.1 The Contractor guarantees that it shall attain Completion of the
Time Facilities (or a part for which a separate time for completion is
Guarantee specified) within the Time for Completion specified in the PCC
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 480
27. Defect 27.1 The Contractor warrants that the Facilities or any part thereof
Liability shall be free from defects in the design, engineering, materials
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 481
27.2 The Defect Liability Period shall be five hundred and forty (540)
days from the date of Completion of the Facilities (or any part
thereof) or one year from the date of Operational Acceptance of
the Facilities (or any part thereof), whichever first occurs, unless
specified otherwise in the PCC pursuant to GCC Sub-Clause
27.10.
27.3 The Contractor’s obligations under this GCC Clause 27 shall not
apply to:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 482
27.4 The Employer shall give the Contractor a notice stating the
nature of any such defect together with all available evidence
thereof, promptly following the discovery thereof. The
Employer shall afford all reasonable opportunity for the
Contractor to inspect any such defect.
27.5 The Employer shall afford the Contractor all necessary access to
the Facilities and the Site to enable the Contractor to perform its
obligations under this GCC Clause 27.
If such part fails the tests, the Contractor shall carry out further
repair, replacement or making good, as the case may be, until
that part of the Facilities passes such tests. The tests shall be
agreed upon by the Employer and the Contractor.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 483
27.10 In addition, any such component of the Facilities, and during the
period of time as may be specified in the PCC, shall be subject
to an extended defect liability period. Such obligation of the
Contractor shall be in addition to the defect liability period
specified under GCC Sub-Clause 27.2.
28. Functional 28.1 The Contractor guarantees that during the Guarantee Test, the
Guarantees Facilities and all parts thereof shall attain the Functional
Guarantees specified in the Appendix to the Contract Agreement
titled Functional Guarantees, subject to and upon the conditions
therein specified.
28.2 If, for reasons attributable to the Contractor, the minimum level
of the Functional Guarantees specified in the Appendix to the
Contract Agreement titled Functional Guarantees, are not met
either in whole or in part, the Contractor shall at its cost and
expense make such changes, modifications and/or additions to
the Plant or any part thereof as may be necessary to meet at least
the minimum level of such Guarantees. The Contractor shall
notify the Employer upon completion of the necessary changes,
modifications and/or additions, and shall request the Employer
to repeat the Guarantee Test until the minimum level of the
Guarantees has been met. If the Contractor eventually fails to
meet the minimum level of Functional Guarantees, the Employer
may consider termination of the Contract, pursuant to GCC Sub-
Clause 42.2.2.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 484
29. Patent 29.1 The Contractor shall, subject to the Employer’s compliance with
Indemnity GCC Sub-Clause 29.2, indemnify and hold harmless the
Employer and its employees and officers from and against any
and all suits, actions or administrative proceedings, claims,
demands, losses, damages, costs, and expenses of whatsoever
nature, including attorney’s fees and expenses, which the
Employer may suffer as a result of any infringement or alleged
infringement of any patent, utility model, registered design,
trademark, copyright or other intellectual property right
registered or otherwise existing at the date of the Contract by
reason of: (a) the installation of the Facilities by the Contractor
or the use of the Facilities in the country where the Site is
located; and (b) the sale of the products produced by the
Facilities in any country.
Such indemnity shall not cover any use of the Facilities or any
part thereof other than for the purpose indicated by or to be
reasonably inferred from the Contract, any infringement
resulting from the use of the Facilities or any part thereof, or any
products produced thereby in association or combination with
any other equipment, plant or materials not supplied by the
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 485
29.2 If any proceedings are brought or any claim is made against the
Employer arising out of the matters referred to in GCC Sub-
Clause 29.1, the Employer shall promptly give the Contractor a
notice thereof, and the Contractor may at its own expense and in
the Employer’s name conduct such proceedings or claim and any
negotiations for the settlement of any such proceedings or claim.
29.3 The Employer shall indemnify and hold harmless the Contractor
and its employees, officers and Subcontractors from and against
any and all suits, actions or administrative proceedings, claims,
demands, losses, damages, costs, and expenses of whatsoever
nature, including attorney’s fees and expenses, which the
Contractor may suffer as a result of any infringement or alleged
infringement of any patent, utility model, registered design,
trademark, copyright or other intellectual property right
registered or otherwise existing at the date of the Contract
arising out of or in connection with any design, data, drawing,
specification, or other documents or materials provided or
designed by or on behalf of the Employer.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 486
G. Risk Distribution
31. Transfer of 31.1 Ownership of the Plant (including spare parts) to be imported
Ownership into the country where the Site is located shall be transferred to
the Employer upon loading on to the mode of transport to be
used to convey the Plant from the country of origin to that
country.
32. Care of 32.1 The Contractor shall be responsible for the care and custody of the
Facilities Facilities or any part thereof until the date of Completion of the
Facilities pursuant to GCC Clause 24 or, where the Contract
provides for Completion of the Facilities in parts, until the date of
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 487
Completion of the relevant part, and shall make good at its own
cost any loss or damage that may occur to the Facilities or the
relevant part thereof from any cause whatsoever during such
period. The Contractor shall also be responsible for any loss or
damage to the Facilities caused by the Contractor or its
Subcontractors in the course of any work carried out, pursuant to
GCC Clause 27. Notwithstanding the foregoing, the Contractor
shall not be liable for any loss or damage to the Facilities or that
part thereof caused by reason of any of the matters specified or
referred to in paragraphs (a), (b) and (c) of GCC Sub-Clauses 32.2
and 38.1.
32.2 If any loss or damage occurs to the Facilities or any part thereof
or to the Contractor’s temporary facilities by reason of
(a) insofar as they relate to the country where the Site is located,
nuclear reaction, nuclear radiation, radioactive
contamination, pressure wave caused by aircraft or other
aerial objects, or any other occurrences that an experienced
contractor could not reasonably foresee, or if reasonably
foreseeable could not reasonably make provision for or
insure against, insofar as such risks are not normally
insurable on the insurance market and are mentioned in the
general exclusions of the policy of insurance, including War
Risks and Political Risks, taken out under GCC Clause 34
hereof; or
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 488
32.3 The Contractor shall be liable for any loss of or damage to any
Contractor’s Equipment, or any other property of the Contractor
used or intended to be used for purposes of the Facilities, except
(i) as mentioned in GCC Sub-Clause 32.2 with respect to the
Contractor’s temporary facilities, and (ii) where such loss or
damage arises by reason of any of the matters specified in GCC
Sub-Clauses 32.2 (b) and (c) and 38.1.
33. Loss of or 33.1 Subject to GCC Sub-Clause 33.3, the Contractor shall indemnify
Damage to and hold harmless the Employer and its employees and officers
Property; from and against any and all suits, actions or administrative
Accident or proceedings, claims, demands, losses, damages, costs, and
Injury to expenses of whatsoever nature, including attorney’s fees and
Workers; expenses, in respect of the death or injury of any person or loss
Indemnifica- of or damage to any property other than the Facilities whether
tion accepted or not, arising in connection with the supply and
installation of the Facilities and by reason of the negligence of
the Contractor or its Subcontractors, or their employees, officers
or agents, except any injury, death or property damage caused by
the negligence of the Employer, its contractors, employees,
officers or agents.
33.2 If any proceedings are brought or any claim is made against the
Employer that might subject the Contractor to liability under
GCC Sub-Clause 33.1, the Employer shall promptly give the
Contractor a notice thereof and the Contractor may at its own
expense and in the Employer’s name conduct such proceedings
or claim and any negotiations for the settlement of any such
proceedings or claim.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 489
33.3 The Employer shall indemnify and hold harmless the Contractor
and its employees, officers and Subcontractors from any liability
for loss of or damage to property of the Employer, other than the
Facilities not yet taken over, that is caused by fire, explosion or
any other perils, in excess of the amount recoverable from
insurances procured under GCC Clause 34, provided that such
fire, explosion or other perils were not caused by any act or
failure of the Contractor.
33.4 The Party entitled to the benefit of an indemnity under this GCC
Clause 33 shall take all reasonable measures to mitigate any loss
or damage which has occurred. If the Party fails to take such
measures, the other Party’s liabilities shall be correspondingly
reduced.
34. Insurance 34.1 To the extent specified in the Appendix to the Contract
Agreement titled Insurance Requirements, the Contractor shall at
its expense take out and maintain in effect, or cause to be taken
out and maintained in effect, during the performance of the
Contract, the insurances set forth below in the sums and with the
deductibles and other conditions specified in the said Appendix.
The identity of the insurers and the form of the policies shall be
subject to the approval of the Employer, who should not
unreasonably withhold such approval.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 490
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 491
34.5 The Employer shall at its expense take out and maintain in effect
during the performance of the Contract those insurances
specified in the Appendix to the Contract Agreement titled
Insurance Requirements, in the sums and with the deductibles
and other conditions specified in the said Appendix. The
Contractor and the Contractor’s Subcontractors shall be named
as co-insureds under all such policies. All insurers’ rights of
subrogation against such co-insureds for losses or claims arising
out of the performance of the Contract shall be waived under
such policies. The Employer shall deliver to the Contractor
satisfactory evidence that the required insurances are in full
force and effect. The policies shall provide that not less than
twenty-one (21) days’ notice shall be given to the Contractor by
all insurers prior to any cancellation or material modification of
the policies. If so requested by the Contractor, the Employer
shall provide copies of the policies taken out by the Employer
under this GCC Sub-Clause 34.5.
34.6 If the Contractor fails to take out and/or maintain in effect the
insurances referred to in GCC Sub-Clause 34.1, the Employer
may take out and maintain in effect any such insurances and may
from time to time deduct from any amount due the Contractor
under the Contract any premium that the Employer shall have
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 492
35. Unforeseen 35.1 If, during the execution of the Contract, the Contractor shall
Conditions encounter on the Site any physical conditions other than climatic
conditions, or artificial obstructions that could not have been
reasonably foreseen prior to the date of the Contract Agreement
by an experienced contractor on the basis of reasonable
examination of the data relating to the Facilities including any
data as to boring tests, provided by the Employer, and on the
basis of information that it could have obtained from a visual
inspection of the Site if access thereto was available, or other
data readily available to it relating to the Facilities, and if the
Contractor determines that it will in consequence of such
conditions or obstructions incur additional cost and expense or
require additional time to perform its obligations under the
Contract that would not have been required if such physical
conditions or artificial obstructions had not been encountered,
the Contractor shall promptly, and before performing additional
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 493
(d) the additional cost and expense that the Contractor is likely
to incur.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 494
36. Change in 36.1 If, after the date twenty-eight (28) days prior to the date of Bid
Laws and submission, in the country where the Site is located, any law,
Regulations regulation, ordinance, order or by-law having the force of law is
enacted, promulgated, abrogated or changed which shall be
deemed to include any change in interpretation or application by
the competent authorities, that subsequently affects the costs and
expenses of the Contractor and/or the Time for Completion, the
Contract Price shall be correspondingly increased or decreased,
and/or the Time for Completion shall be reasonably adjusted to
the extent that the Contractor has thereby been affected in the
performance of any of its obligations under the Contract.
Notwithstanding the foregoing, such additional or reduced costs
shall not be separately paid or credited if the same has already
been accounted for in the price adjustment provisions where
applicable, in accordance with the PCC pursuant to GCC Sub-
Clause 11.2.
37. Force 37.1 “Force Majeure” shall mean any event beyond the reasonable
Majeure control of the Employer or of the Contractor, as the case may be,
and which is unavoidable notwithstanding the reasonable care of
the Party affected, and shall include, without limitation, the
following:
37.3 The Party who has given such notice shall be excused from the
performance or punctual performance of its obligations under
the Contract for so long as the relevant event of Force Majeure
continues and to the extent that such Party’s performance is
prevented, hindered or delayed. The Time for Completion shall
be extended in accordance with GCC Clause 40.
37.4 The Party or Parties affected by the event of Force Majeure shall
use reasonable efforts to mitigate the effect thereof upon its or
their performance of the Contract and to fulfill its or their
obligations under the Contract, but without prejudice to either
Party’s right to terminate the Contract under GCC Sub-Clauses
37.6 and 38.5.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 496
38. War Risks 38.1 “War Risks” shall mean any event specified in paragraphs (a)
and (b) of GCC Sub-Clause 37.1 and any explosion or impact of
any mine, bomb, shell, grenade or other projectile, missile,
munitions or explosive of war, occurring or existing in or near
the country (or countries) where the Site is located.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 497
38.5 If during the performance of the Contract any War Risks shall
occur that financially or otherwise materially affect the
execution of the Contract by the Contractor, the Contractor shall
use its reasonable efforts to execute the Contract with due and
proper consideration given to the safety of its and its
Subcontractors’ personnel engaged in the work on the Facilities,
provided, however, that if the execution of the work on the
Facilities becomes impossible or is substantially prevented for a
single period of more than sixty (60) days or an aggregate period
of more than one hundred and twenty (120) days on account of
any War Risks, the Parties will attempt to develop a mutually
satisfactory solution, failing which either Party may terminate
the Contract by giving a notice to the other.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 498
42.1.3.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 499
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 500
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 501
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 502
40. Extension of 40.1 The Time(s) for Completion specified in the PCC pursuant to
Time for GCC Sub-Clause 8.2 shall be extended if the Contractor is
Completion delayed or impeded in the performance of any of its obligations
under the Contract by reason of any of the following:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 503
40.3 The Contractor shall at all times use its reasonable efforts to
minimize any delay in the performance of its obligations under
the Contract.
40.4 In all cases where the Contractor has given a notice of a claim for
an extension of time under GCC 40.2, the Contractor shall
consult with the Project Manager in order to determine the steps
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 504
41. Suspension 41.1 The Employer may request the Project Manager, by notice to the
Contractor, to order the Contractor to suspend performance of
any or all of its obligations under the Contract. Such notice shall
specify the obligation of which performance is to be suspended,
the effective date of the suspension and the reasons therefor.
The Contractor shall thereupon suspend performance of such
obligation, except those obligations necessary for the care or
preservation of the Facilities, until ordered in writing to resume
such performance by the Project Manager.
41.2 If
(a) the Employer has failed to pay the Contractor any sum due
under the Contract within the specified period, has failed
to approve any invoice or supporting documents without
just cause pursuant to the Appendix to the Contract
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 505
41.4 During the period of suspension, the Contractor shall not remove
from the Site any Plant, any part of the Facilities or any
Contractor’s Equipment, without the prior written consent of the
Employer.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 506
42.1.1 The Employer may at any time terminate the Contract for
any reason by giving the Contractor a notice of
termination that refers to this GCC Sub-Clause 42.1.
(a) cease all further work, except for such work as the
Employer may specify in the notice of termination
for the sole purpose of protecting that part of the
Facilities already executed, or any work required to
leave the Site in a clean and safe condition
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 507
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 508
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 509
(a) cease all further work, except for such work as the
Employer may specify in the notice of termination
for the sole purpose of protecting that part of the
Facilities already executed, or any work required to
leave the Site in a clean and safe condition
42.2.4 The Employer may enter upon the Site, expel the
Contractor, and complete the Facilities itself or by
employing any third Party. The Employer may, to the
exclusion of any right of the Contractor over the same,
take over and use with the payment of a fair rental rate to
the Contractor, with all the maintenance costs to the
account of the Employer and with an indemnification by
the Employer for all liability including damage or injury to
persons arising out of the Employer’s use of such
equipment, any Contractor’s Equipment owned by the
Contractor and on the Site in connection with the Facilities
for such reasonable period as the Employer considers
expedient for the supply and installation of the Facilities.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 510
42.3.1 If
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 512
(a) cease all further work, except for such work as may
be necessary for the purpose of protecting that part
of the Facilities already executed, or any work
required to leave the Site in a clean and safe
condition
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 513
42.4 In this GCC Clause 42, the expression “Facilities executed” shall
include all work executed, Installation Services provided, and all
Plant acquired, or subject to a legally binding obligation to
purchase, by the Contractor and used or intended to be used for
the purpose of the Facilities, up to and including the date of
termination.
42.5 In this GCC Clause 42, in calculating any monies due from the
Employer to the Contractor, account shall be taken of any sum
previously paid by the Employer to the Contractor under the
Contract, including any advance payment paid pursuant to the
Appendix to the Contract Agreement titled Terms and Procedures
of Payment.
43. Assignment 43.1 Neither the Employer nor the Contractor shall, without the
express prior written consent of the other Party, which consent
shall not be unreasonably withheld, assign to any third Party the
Contract or any part thereof, or any right, benefit, obligation or
interest therein or thereunder, except that the Contractor shall be
entitled to assign either absolutely or by way of charge any
monies due and payable to it or that may become due and
payable to it under the Contract.
44. Export 44.1 Notwithstanding any obligation under the Contract to complete
Restrictions all export formalities, any export restrictions attributable to the
Employer, to the country of the Employer or to the use of the
Plant and Installation Services to be supplied which arise from
trade regulations from a country supplying those Plant and
Installation Services, and which substantially impede the
Contractor from meeting its obligations under the Contract, shall
release the Contractor from the obligation to provide deliveries
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 514
45. Contractor’s 45.1 If the Contractor considers himself to be entitled to any extension
Claims of the Time for Completion and/or any additional payment, under
any Clause of these Conditions or otherwise in connection with
the Contract, the Contractor shall submit a notice to the Project
Manager, describing the event or circumstance giving rise to the
claim. The notice shall be given as soon as practicable, and not
later than 28 days after the Contractor became aware, or should
have become aware, of the event or circumstance.
The Contractor shall also submit any other notices which are
required by the Contract, and supporting particulars for the claim,
all as relevant to such event or circumstance.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 515
(c) the Contractor shall send a final claim within 28 days after
the end of the effects resulting from the event or
circumstance, or within such other period as may be
proposed by the Contractor and approved by the Project
Manager.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 516
In the event that the Contractor and the Employer cannot agree on
any matter relating to a claim, either Party may refer the matter to
the Dispute Board pursuant to GCC 46 hereof.
The agreement between the Parties and either the sole member or
each of the three members shall incorporate by reference the
General Conditions of Dispute Board Agreement contained in the
Appendix to these General Conditions, with such amendments as
are agreed between them.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 517
(a) the Parties fail to agree upon the appointment of the sole
member of the DB by the date stated in the first paragraph
of GCC Sub-Clause 46.1,
(c) the Parties fail to agree upon the appointment of the third
member (to act as chairman) of the DB by such date, or
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 518
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 519
46.5 Arbitration
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 520
The arbitrator(s) shall have full power to open up, review and
revise any certificate, determination, instruction, opinion or
valuation of the Project Manager, and any decision of the DB,
relevant to the dispute. Nothing shall disqualify the Project
Manager from being called as a witness and giving evidence
before the arbitrator(s) on any matter whatsoever relevant to the
dispute.
(a) GCC Sub-Clauses 46.3 and 46.4 shall not apply, and
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 521
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 522
APPENDIX A
General Conditions of Dispute Board Agreement
1. Definitions
Each “Dispute Board Agreement” is a tripartite agreement by and between:
the “Employer”;
the “Contractor”; and
the “Member” who is defined in the Dispute Board Agreement as being:
(i) the sole member of the “DB” and, where this is the case, all references to the
“Other Members” do not apply, or
(ii) one of the three persons who are jointly called the “DB” (or “dispute board”) and,
where this is the case, the other two persons are called the “Other Members”.
The Employer and the Contractor have entered (or intend to enter) into a contract, which is
called the “Contract” and is defined in the Dispute Board Agreement, which incorporates this
Appendix. In the Dispute Board Agreement, words and expressions which are not otherwise
defined shall have the meanings assigned to them in the Contract.
2. General Provisions
Unless otherwise stated in the Dispute Board Agreement, it shall take effect on the latest of
the following dates:
(a) the Commencement Date defined in the Contract,
(b) when the Employer, the Contractor and the Member have each signed the
Dispute Board Agreement, or
(c) when the Employer, the Contractor and each of the Other Members (if any) have
respectively each signed a dispute board agreement.
This employment of the Member is a personal appointment. At any time, the Member may
give not less than 70 days’ notice of resignation to the Employer and to the Contractor, and
the Dispute Board Agreement shall terminate upon the expiry of this period.
3. Warranties
The Member warrants and agrees that he/she is and shall be impartial and independent of the
Employer, the Contractor and the Project Manager. The Member shall promptly disclose, to
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 523
each of them and to the Other Members (if any), any fact or circumstance which might
appear inconsistent with his/her warranty and agreement of impartiality and independence.
When appointing the Member, the Employer and the Contractor relied upon the Member’s
representations that he/she is:
(a) experienced in the work which the Contractor is to carry out under the Contract,
(b) experienced in the interpretation of contract documentation, and
(c) fluent in the language for communications defined in the Contract.
4. General Obligations of the Member
The Member shall:
(a) have no interest financial or otherwise in the Employer, the Contractor or the
Project Manager, nor any financial interest in the Contract except for payment
under the Dispute Board Agreement;
(b) not previously have been employed as a consultant or otherwise by the Employer,
the Contractor or the Project Manager, except in such circumstances as were
disclosed in writing to the Employer and the Contractor before they signed the
Dispute Board Agreement;
(c) have disclosed in writing to the Employer, the Contractor and the Other Members
(if any), before entering into the Dispute Board Agreement and to his/her best
knowledge and recollection, any professional or personal relationships with any
director, officer or employee of the Employer, the Contractor or the Project
Manager, and any previous involvement in the overall project of which the
Contract forms part;
(d) not, for the duration of the Dispute Board Agreement, be employed as a
consultant or otherwise by the Employer, the Contractor or the Project Manager,
except as may be agreed in writing by the Employer, the Contractor and the
Other Members (if any);
(e) comply with the annexed procedural rules and with GCC Sub-Clause 46.3;
(f) not give advice to the Employer, the Contractor, the Employer’s Personnel or the
Contractor’s Personnel concerning the conduct of the Contract, other than in
accordance with the annexed procedural rules;
(g) not while a Member enter into discussions or make any agreement with the
Employer, the Contractor or the Project Manager regarding employment by any
of them, whether as a consultant or otherwise, after ceasing to act under the
Dispute Board Agreement;
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 524
(h) ensure his/her availability for all site visits and hearings as are necessary;
(i) become conversant with the Contract and with the progress of the Facilities (and
of any other parts of the project of which the Contract forms part) by studying all
documents received which shall be maintained in a current working file;
(j) treat the details of the Contract and all the DB’s activities and hearings as private
and confidential, and not publish or disclose them without the prior written
consent of the Employer, the Contractor and the Other Members (if any); and
(k) be available to give advice and opinions, on any matter relevant to the Contract
when requested by both the Employer and the Contractor, subject to the
agreement of the Other Members (if any).
5. General Obligations of the Employer and the Contractor
The Employer, the Contractor, the Employer’s Personnel and the Contractor’s Personnel
shall not request advice from or consultation with the Member regarding the Contract,
otherwise than in the normal course of the DB’s activities under the Contract and the Dispute
Board Agreement. The Employer and the Contractor shall be responsible for compliance with
this provision, by the Employer’s Personnel and the Contractor’s Personnel respectively.
The Employer and the Contractor undertake to each other and to the Member that the
Member shall not, except as otherwise agreed in writing by the Employer, the Contractor, the
Member and the Other Members (if any):
(a) be appointed as an arbitrator in any arbitration under the Contract;
(b) be called as a witness to give evidence concerning any dispute before
arbitrator(s) appointed for any arbitration under the Contract; or
(c) be liable for any claims for anything done or omitted in the discharge or
purported discharge of the Member’s functions, unless the act or omission is
shown to have been in bad faith.
The Employer and the Contractor hereby jointly and severally indemnify and hold the
Member harmless against and from claims from which he is relieved from liability under the
preceding paragraph.
Whenever the Employer or the Contractor refers a dispute to the DB under GCC Sub-Clause
46.3, which will require the Member to make a site visit and attend a hearing, the Employer
or the Contractor shall provide appropriate security for a sum equivalent to the reasonable
expenses to be incurred by the Member. No account shall be taken of any other payments due
or paid to the Member.
6. Payment
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 525
The Member shall be paid as follows, in the currency named in the Dispute Board
Agreement:
(a) a retainer fee per calendar month, which shall be considered as payment in full
for:
(i) being available on 28 days’ notice for all site visits and hearings;
(ii) becoming and remaining conversant with all project developments and
maintaining relevant files;
(iii) all office and overhead expenses including secretarial services,
photocopying and office supplies incurred in connection with his duties;
and
(iv) all services performed hereunder except those referred to in sub-paragraphs
(b) and (c) of this Clause.
The retainer fee shall be paid with effect from the last day of the calendar month in which the
Dispute Board Agreement becomes effective; until the last day of the calendar month in
which the Taking-Over Certificate is issued for the whole of the Works.
With effect from the first day of the calendar month following the month in which Taking-
Over Certificate is issued for the whole of the Works, the retainer fee shall be reduced by one
third This reduced fee shall be paid until the first day of the calendar month in which the
Member resigns or the Dispute Board Agreement is otherwise terminated.
(b) a daily fee which shall be considered as payment in full for:
(i) each day or part of a day up to a maximum of two days’ travel time in each
direction for the journey between the Member’s home and the site, or
another location of a meeting with the Other Members (if any);
(ii) each working day on site visits, hearings or preparing decisions; and
(iii) each day spent reading submissions in preparation for a hearing.
(c) all reasonable expenses including necessary travel expenses (air fare in less than
first class, hotel and subsistence and other direct travel expenses) incurred in
connection with the Member’s duties, as well as the cost of telephone calls,
courier charges, faxes and telexes: a receipt shall be required for each item in
excess of five percent of the daily fee referred to in sub-paragraph (b) of this
Clause;
(d) any taxes properly levied in the Country on payments made to the Member
(unless a national or permanent resident of the Country) under this Clause 6.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 526
The retainer and daily fees shall be as specified in the Dispute Board Agreement. Unless it
specifies otherwise, these fees shall remain fixed for the first 24 calendar months, and shall
thereafter be adjusted by agreement between the Employer, the Contractor and the Member,
at each anniversary of the date on which the Dispute Board Agreement became effective.
If the Parties fail to agree on the retainer fee or the daily fee the appointing entity or official
named in the PCC shall determine the amount of the fees to be used.
The Member shall submit invoices for payment of the monthly retainer and air fares quarterly
in advance. Invoices for other expenses and for daily fees shall be submitted following the
conclusion of a site visit or hearing. All invoices shall be accompanied by a brief description
of activities performed during the relevant period and shall be addressed to the Contractor.
The Contractor shall pay each of the Member’s invoices in full within 56 calendar days after
receiving each invoice and shall apply to the Employer (in the Statements under the Contract)
for reimbursement of one-half of the amounts of these invoices. The Employer shall then pay
the Contractor in accordance with the Contract.
If the Contractor fails to pay to the Member the amount to which he/she is entitled under the
Dispute Board Agreement, the Employer shall pay the amount due to the Member and any
other amount which may be required to maintain the operation of the DB; and without
prejudice to the Employer’s rights or remedies. In addition to all other rights arising from this
default, the Employer shall be entitled to reimbursement of all sums paid in excess of one-
half of these payments, plus all costs of recovering these sums and financing charges
calculated at the rate specified in accordance with GCC Sub-Clause 12.3.
If the Member does not receive payment of the amount due within 70 days after submitting a
valid invoice, the Member may (i) suspend his/her services (without notice) until the payment
is received, and/or (ii) resign his/her appointment by giving notice under Clause 7.
7. Termination
At any time: (i) the Employer and the Contractor may jointly terminate the Dispute Board
Agreement by giving 42 days’ notice to the Member; or (ii) the Member may resign as
provided for in Clause 2.
If the Member fails to comply with the Dispute Board Agreement, the Employer and the
Contractor may, without prejudice to their other rights, terminate it by notice to the Member.
The notice shall take effect when received by the Member.
If the Employer or the Contractor fails to comply with the Dispute Board Agreement, the
Member may, without prejudice to his other rights, terminate it by notice to the Employer
and the Contractor. The notice shall take effect when received by them both.
Any such notice, resignation and termination shall be final and binding on the Employer, the
Contractor and the Member. However, a notice by the Employer or the Contractor, but not by
both, shall be of no effect.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 527
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 528
Appendix A
DISPUTE BOARD GUIDELINES
1. Unless otherwise agreed by the Employer and the Contractor, the DB shall visit the
site at intervals of not more than 140 days, including times of critical construction events, at
the request of either the Employer or the Contractor. Unless otherwise agreed by the
Employer, the Contractor and the DB, the period between consecutive visits shall not be less
than 70 days, except as required to convene a hearing as described below.
2. The timing of and agenda for each site visit shall be as agreed jointly by the DB, the
Employer and the Contractor, or in the absence of agreement, shall be decided by the DB.
The purpose of site visits is to enable the DB to become and remain acquainted with the
progress of the Works and of any actual or potential problems or claims, and, as far as
reasonable, to prevent potential problems or claims from becoming disputes.
3. Site visits shall be attended by the Employer, the Contractor and the Project Manager
and shall be coordinated by the Employer in co-operation with the Contractor. The Employer
shall ensure the provision of appropriate conference facilities and secretarial and copying
services. At the conclusion of each site visit and before leaving the site, the DB shall prepare
a report on its activities during the visit and shall send copies to the Employer and the
Contractor.
4. The Employer and the Contractor shall furnish to the DB one copy of all documents
which the DB may request, including Contract documents, progress reports, variation
instructions, certificates and other documents pertinent to the performance of the Contract.
All communications between the DB and the Employer or the Contractor shall be copied to
the other Party. If the DB comprises three persons, the Employer and the Contractor shall
send copies of these requested documents and these communications to each of these
persons.
5. If any dispute is referred to the DB in accordance with GCC Sub-Clause 46.3, the DB
shall proceed in accordance with GCC Sub-Clause 46.3 and these Guidelines. Subject to the
time allowed to give notice of a decision and other relevant factors, the DB shall:
(a) act fairly and impartially as between the Employer and the Contractor, giving
each of them a reasonable opportunity of putting his case and responding to
the other’s case, and
(b) adopt procedures suitable to the dispute, avoiding unnecessary delay or
expense.
6. The DB may conduct a hearing on the dispute, in which event it will decide on the
date and place for the hearing and may request that written documentation and arguments
from the Employer and the Contractor be presented to it prior to or at the hearing.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 529
7. Except as otherwise agreed in writing by the Employer and the Contractor, the DB
shall have power to adopt an inquisitorial procedure, to refuse admission to hearings or
audience at hearings to any persons other than representatives of the Employer, the
Contractor and the Project Manager, and to proceed in the absence of any Party who the DB
is satisfied received notice of the hearing; but shall have discretion to decide whether and to
what extent this power may be exercised.
8. The Employer and the Contractor empower the DB, among other things, to:
(a) establish the procedure to be applied in deciding a dispute,
(b) decide upon the DB’s own jurisdiction, and as to the scope of any dispute
referred to it,
(c) conduct any hearing as it thinks fit, not being bound by any rules or
procedures other than those contained in the Contract and these Guidelines,
(d) take the initiative in ascertaining the facts and matters required for a decision,
(e) make use of its own specialist knowledge, if any,
(f) decide upon the payment of financing charges in accordance with the
Contract,
(g) decide upon any provisional relief such as interim or conservatory measures,
(h) open up, review and revise any certificate, decision, determination,
instruction, opinion or valuation of the Project Manager, relevant to the
dispute, and
(i) appoint, should the DB so consider necessary and the Parties agree, a suitable
expert at the cost of the Parties to give advice on a specific matter relevant to
the dispute.
9. The DB shall not express any opinions during any hearing concerning the merits of
any arguments advanced by the Parties. Thereafter, the DB shall make and give its decision
in accordance with GCC Sub-Clause 46.3, or as otherwise agreed by the Employer and the
Contractor in writing. If the DB comprises three persons:
(a) it shall convene in private after a hearing, in order to have discussions and
prepare its decision;
(b) it shall endeavor to reach a unanimous decision: if this proves impossible the
applicable decision shall be made by a majority of the Members, who may
require the minority Member to prepare a written report for submission to the
Employer and the Contractor; and
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 530
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 531
APPENDIX B
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 532
(b) acts intended to materially impede the exercise of the Bank’s inspection
and audit rights provided for under paragraph 2.2 e. below.
b. Rejects a proposal for award if the Bank determines that the firm or individual
recommended for award, any of its personnel, or its agents, or its sub-consultants,
sub-contractors, service providers, suppliers and/ or their employees, has, directly or
indirectly, engaged in corrupt, fraudulent, collusive, coercive, or obstructive
practices in competing for the contract in question;
c. In addition to the legal remedies set out in the relevant Legal Agreement, may take
other appropriate actions, including declaring misprocurement, if the Bank
determines at any time that representatives of the Borrower or of a recipient of any
part of the proceeds of the loan engaged in corrupt, fraudulent, collusive, coercive,
or obstructive practices during the procurement process, selection and/or execution
of the contract in question, without the Borrower having taken timely and
appropriate action satisfactory to the Bank to address such practices when they
occur, including by failing to inform the Bank in a timely manner at the time they
knew of the practices;
d. Pursuant to the Bank’s Anti- Corruption Guidelines and in accordance with the
Bank’s prevailing sanctions policies and procedures, may sanction a firm or
individual, either indefinitely or for a stated period of time, including by publicly
declaring such firm or individual ineligible (i) to be awarded or otherwise benefit
from a Bank-financed contract, financially or in any other manner;1 (ii) to be a
nominated2 sub-contractor, consultant, manufacturer or supplier, or service provider
of an otherwise eligible firm being awarded a Bank-financed contract; and (iii) to
receive the proceeds of any loan made by the Bank or otherwise to participate further
in the preparation or implementation of any Bank-financed project;
e. Requires that a clause be included in bidding/request for proposals documents and in
contracts financed by a Bank loan, requiring (i) bidders (applicants/proposers),
consultants, contractors, and suppliers, and their sub-contractors, sub-consultants,
service providers, suppliers, agents personnel, permit the Bank to inspect 3 all
1
For the avoidance of doubt, a sanctioned party’s ineligibility to be awarded a contract shall include, without limitation,
(i) applying for pre-qualification, expressing interest in a consultancy, and bidding, either directly or as a nominated
sub-contractor, nominated consultant, nominated manufacturer or supplier, or nominated service provider, in respect of
such contract, and (ii) entering into an addendum or amendment introducing a material modification to any existing
contract.
2 A nominated sub-contractor, nominated consultant, nominated manufacturer or supplier, or nominated service provider
(different names are used depending on the particular bidding document) is one which has been: (i) included by the
bidder in its pre-qualification application or bid because it brings specific and critical experience and know-how that
allow the bidder to meet the qualification requirements for the particular bid; or (ii) appointed by the Borrower.
3 Inspections in this context usually are investigative (i.e., forensic) in nature. They involve fact-finding activities
undertaken by the Bank or persons appointed by the Bank to address specific matters related to investigations/audits,
such as evaluating the veracity of an allegation of possible Fraud and Corruption, through the appropriate mechanisms.
Such activity includes but is not limited to: accessing and examining a firm's or individual's financial records and
information, and making copies thereof as relevant; accessing and examining any other documents, data and
information (whether in hard copy or electronic format) deemed relevant for the investigation/audit, and making copies
thereof as relevant; interviewing staff and other relevant individuals; performing physical inspections and site visits;
and obtaining third party verification of information.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section VIII – General Conditions of Contract 533
accounts, records and other documents relating to the procurement process, selection
and/or contract execution, and to have them audited by auditors appointed by the
Bank.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section IX – Particular Conditions of Contract 535
The following Particular Conditions of Contract shall supplement the General Conditions
of Contract in Section VIII. Whenever there is a conflict, the provisions herein shall prevail
over those in the General Conditions.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section IX – Particular Conditions of Contract 536
PCC 1. The Employer is: Electricity Distribution and Supply Authority (EDSA)
Definitions The Project Manager is: This would be confirmed at pre contract
clarification meeting
The Bank is: International Development Association (IDA)
Country of Origin: all countries and territories as indicated in
Section V of the bidding document, Eligible Countries.
PCC 5.1 The Contract shall be interpreted in accordance with the
PCC 5. Law and
Language laws of: The Republic of Sierra Leone.
PCC 5.2 The ruling language is: English
PCC 5.3 The language for communications is: English
PCC 7.3 The Contractor agrees to supply spare parts for a period of
PCC 7. Scope of
years: Twenty Five
Facilities [Spare
Parts] (GCC Sample Addition to PCC 7.3
Clause 7) The Contractor shall carry sufficient inventories to ensure an ex-stock
supply of consumable spares for the Plant. Other spare parts and
components shall be supplied as promptly as possible, but at the most
within six (6) months of placing the order and opening the letter of
credit. In addition, in the event of termination of the production of
spare parts, advance notification will be made to the Employer of the
pending termination, with sufficient time to permit the Employer to
procure the needed requirement. Following such termination, the
Contractor will furnish to the extent possible and at no cost to the
Employer the blueprints, drawings and specifications of the spare
parts, if requested.
PCC 8.1 The Contractor shall commence work on the Facilities
PCC 8. Time for
within two weeks from the Effective Date for determining
Commencement
Time for Completion as specified in the Contract
and Completion
Agreement.
PCC 8.2 The Time for Completion of the whole of the Facilities shall
be 18 months from the Effective Date as described in the
Contract Agreement.
The following sustainable procurement contractual
PCC 9.
provisions apply: N/A
Contractor’s
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section IX – Particular Conditions of Contract 537
Responsibilities
PCC 26.2
PCC 26.
Completion Time Applicable rate for liquidated damages: 0.08% of Contract Price per
Guarantee day of delay for the Facilities or part thereof (as appropriate)
The above rate applies to the price of the part of the Facilities, as
quoted in the Price Schedule, for that part for which the Contractor
fails to achieve Completion within the particular Time for
Completion.
Maximum deduction for liquidated damages: 10% of the Contract
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section IX – Particular Conditions of Contract 538
Price
PCC 26.3 Applicable (amount or rate) for the bonus for early
Completion: N/A
Maximum bonus:
PCC 26.3 No bonus will be given for earlier Completion of the
Facilities or part thereof.
PCC 27.10 The critical components covered under the extended
PCC 27. Defect
defect liability are None, and the period shall be
Liability
_________________ (to be inserted only when an extended
defect liability is requested).
Sample Clause
PCC 30.
Limitation of PCC 30.1 (b) The multiplier of the Contract Price is: 1.1
Liability
PCC 46.1 The DB shall be appointed within [28 days] after the
PCC46. Disputes
Effective Date.
and Arbitration
PCC 46.1 The DB shall be: one sole member
PCC 46.2 Appointment (if not agreed) to be made by: International
Chamber of Commerce (ICC), Paris, France
PCC 46.5 Procedure to settle disputes in respect of DB’s
decisions: All disputes arising in connection with the present Contract
shall be finally settled under the Rules of Conciliation and Arbitration of
the International Chamber of Commerce by one or more arbitrators
appointed in accordance with said Rules (a) Appointed arbitration
institution
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 539
Table of Forms
Notification of Intention to Award .................................................................................... 540
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 540
[This Notification of Intention to Award shall be sent to each Bidder that submitted a Bid.]
[Send this Notification to the Bidder’s Authorized Representative named in the Bidder
Information Form]
For the attention of Bidder’s Authorized Representative
Name: [insert Authorized Representative’s name]
Address: [insert Authorized Representative’s Address]
Telephone/Fax numbers: [insert Authorized Representative’s telephone/fax numbers]
Email Address: [insert Authorized Representative’s email address]
[IMPORTANT: insert the date that this Notification is transmitted to Bidders. The
Notification must be sent to all Bidders simultaneously. This means on the same date and
as close to the same time as possible.]
DATE OF TRANSMISSION: This Notification is sent by: [email/fax] on [date] (local time)
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 541
2. Other Bidders [INSTRUCTIONS: insert names of all Bidders that submitted a Bid.
If the Bid’s price was evaluated include the evaluated price as well as the Bid price
as read out.]
Name of Bidder Bid price Evaluated Bid Cost
[insert name] [insert Bid price] [insert evaluated cost]
[insert name] [insert Bid price] [insert evaluated cost]
[insert name] [insert Bid price] [insert evaluated cost]
[insert name] [insert Bid price] [insert evaluated cost]
[insert name] [insert Bid price] [insert evaluated cost]
[INSTRUCTIONS: State the reason/s why this Bidder’s Bid was unsuccessful. Do
NOT include: (a) a point by point comparison with another Bidder’s Bid or (b)
information that is marked confidential by the Bidder in its Bid.]
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 542
provide the debriefing within five (5) Business Days of receipt of your request. If we are
unable to provide the debriefing within this period, the Standstill Period shall be extended
by five (5) Business Days after the date that the debriefing is provided. If this happens,
we will notify you and confirm the date that the extended Standstill Period will end.
The debriefing may be in writing, by phone, video conference call or in person. We shall
promptly advise you in writing how the debriefing will take place and confirm the date
and time.
If the deadline to request a debriefing has expired, you may still request a debriefing. In
this case, we will provide the debriefing as soon as practicable, and normally no later than
fifteen (15) Business Days from the date of publication of the Contract Award Notice.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 543
Award.
2. The complaint can only challenge the decision to award the contract.
3. You must submit the complaint within the period stated above.
4. You must include, in your complaint, all of the information required by the
Procurement Regulations (as described in Annex III).
6. Standstill Period
DEADLINE: The Standstill Period is due to end at midnight on [insert date] (local
time).
The Standstill Period lasts ten (10) Business Days after the date of transmission of this
Notification of Intention to Award.
The Standstill Period may be extended as stated in Section 4 above.
If you have any questions regarding this Notification please do not hesitate to contact us.
Signature: ______________________________________________
Name: ______________________________________________
Title/position: ______________________________________________
Telephone: ______________________________________________
Email: ______________________________________________
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 544
For the purposes of this Form, a Beneficial Owner of a Bidder is any natural person who
ultimately owns or controls the Bidder by meeting one or more of the following conditions:
• directly or indirectly holding 25% or more of the shares
• directly or indirectly holding 25% or more of the voting rights
• directly or indirectly having the right to appoint a majority of the board of
directors or equivalent governing body of the Bidder
In response to your request in the Letter of Acceptance dated [insert date of letter of
Acceptance] to furnish additional information on beneficial ownership: [select one option as
applicable and delete the options that are not applicable]
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 545
OR
(ii) We declare that there is no Beneficial Owner meeting one or more of the following
conditions:
• directly or indirectly holding 25% or more of the shares
• directly or indirectly holding 25% or more of the voting rights
• directly or indirectly having the right to appoint a majority of the board of directors or
equivalent governing body of the Bidder
OR
(iii) We declare that we are unable to identify any Beneficial Owner meeting one or more of
the following conditions. [If this option is selected, the Bidder shall provide explanation on
why it is unable to identify any Beneficial Owner]
• directly or indirectly holding 25% or more of the shares
• directly or indirectly holding 25% or more of the voting rights
• directly or indirectly having the right to appoint a majority of the board of directors or
equivalent governing body of the Bidder]”
Name of the person duly authorized to sign the Bid on behalf of the Bidder: **[insert
complete name of person duly authorized to sign the Bid]___________
Title of the person signing the Bid: [insert complete title of the person signing the
Bid]______
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 546
Signature of the person named above: [insert signature of person whose name and
capacity are shown above]_____
Date signed [insert date of signing] day of [insert month], [insert year]_____
*
In the case of the Bid submitted by a Joint Venture specify the name of the Joint Venture as Bidder. In the
event that the Bidder is a joint venture, each reference to “Bidder” in the Beneficial Ownership Disclosure Form
(including this Introduction thereto) shall be read to refer to the joint venture member.
**
Person signing the Bid shall have the power of attorney given by the Bidder. The power of attorney shall be
attached with the Bid Schedules.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 547
Letter of Acceptance
______________________
To: ____________________________
This is to notify you that your Bid dated ____________ for execution of the _________________
for the Contract Price in the aggregate of _____________________ ________________ , as corrected
and modified in accordance with the Instructions to Bidders is hereby accepted by our
Agency.
You are requested to furnish (i) the Performance Security within 28 days in accordance with
the Conditions of Contract, using for that purpose one of the Performance Security Forms
and (ii) the additional information on beneficial ownership in accordance with BDS ITB
46.1, within eight (8) Business days using the Beneficial Ownership Disclosure Form,
included in Section X, - Contract Forms, of the bidding document.
Authorized Signature:
Name and Title of Signatory:
Name of Agency:
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 548
Contract Agreement
THIS AGREEMENT is made the ________ day of ________________________, _____,
BETWEEN
WHEREAS the Employer desires to engage the Contractor to design, manufacture, test,
deliver, install, complete and commission certain Facilities, viz. _________________ (“the
Facilities”), and the Contractor has agreed to such engagement upon and subject to the terms
and conditions hereinafter appearing.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 549
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 550
IN WITNESS WHEREOF the Employer and the Contractor have caused this Agreement to
be duly executed by their duly authorized representatives the day and year first above written.
[Signature]
[Title]
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 551
in the presence of
[Signature]
[Title]
in the presence of
APPENDICES
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 552
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 553
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 554
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 555
The Project Manager would authorize the invoice for payment upon recommendation of the
Employer’s Engineer.
The mode of payment would be finalized during pre-contract meeting
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 556
All prices under this Contract shall remain firm and fixed for the duration
of the Contract
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 557
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 558
Covering use of all vehicles used by the Contractor or its Subcontractors (whether or
not owned by them) in connection with the supply and installation of the Facilities.
Comprehensive insurance in accordance with statutory requirements.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 559
The Employer shall at its expense take out and maintain in effect during the performance of
the Contract the following insurances.
NIL
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 560
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 561
Appendix 5. List of Major Items of Plant and Installation Services and List
of Approved Subcontractors
A list of major items of Plant and Installation Services is provided below.
The following Subcontractors and/or manufacturers are approved for carrying out the items
of the Facilities indicated below. Where more than one Subcontractor is listed, the
Contractor is free to choose between them, but it must notify the Employer of its choice in
good time prior to appointing any selected Subcontractor. In accordance with GCC Sub-
Clause 19.1, the Contractor is free to submit proposals for Subcontractors for additional items
from time to time. No Subcontracts shall be placed with any such Subcontractors for
additional items until the Subcontractors have been approved in writing by the Employer and
their names have been added to this list of Approved Subcontractors.
Major Items of Plant and Installation Approved Nationality
Services Subcontractors/Manufacturers
LOT 1
161kV O/D SF6 Live Tank Circuit Breakers
161kV O/D Disconnector with Earth Switch
161kV O/D Pantograph Switch
161kV O/D Current Transformers
161kV O/D Voltage transformers
161kV O/D Post insulators
161kV O/D Surge Arresters
33kV O/D SF6 Live Tank Circuit Breakers
33kV O/D Isolator with Earth Switch
33kV O/D Current Transformers
33kV O/D Voltage Transformers
33kV O/D Post Insulators
33kV O/D Surge Arresters
161/33kV Power Transformer
33/11kV Power Transformers
11/0.4kV Station Service Transformers
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 562
LOT 2
Steel Lattice Towers
Steel Tubular Poles
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 563
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 564
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 565
Pursuant to GCC Sub-Clause 20.3.1, the Contractor shall prepare, or cause its Subcontractor
to prepare, and present to the Project Manager in accordance with the requirements of GCC
Sub-Clause 18.2 (Program of Performance), the following documents for
A. Approval
1. All the design drawings
2. Supporting design calculations
3. Factory Acceptance Test (FAT) procedures
4. Factory Acceptance Test (FAT) reports
5. Method Statements for works and installation
6. Site Acceptance Test (SAT) procedures
7. Site Acceptance Test (SAT) reports
8. Project Schedule in .mpp file and .pdf file.
9. Upon approval of designs/drawings, contractor shall provide the editable soft copy of
the designs/drawings to Client.
B. Review
1. Fabrication drawings
2. Any other drawings/documents/standards required for review of documents
corresponding to ‘A’ above.
After the award of contract, the contractor will prepare an exhaustive list of documents, titled
Master Drawing List (MDL) covering every aspect of the project. The list will clearly
mention the category of the document i.e. whether for Approval or Reference and time frame
for submission of the same. The employer shall review the same and will approve after
necessary modifications. The documents shall be submitted strictly according to the approved
MDL.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 566
3. Functional Guarantees
Subject to compliance with the foregoing preconditions, the Contractor guarantees as
follows:
3.1 Production Capacity
_____________________________________________________________________________
and/or
3.2 Raw Materials and Utilities Consumption
____________________________________________________________________________
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 567
every complete one percent (1%) of the deficiency in the production capacity of
the Facilities, or at a proportionately reduced rate for any deficiency, or part
thereof, of less than a complete one percent (1%).
4.2 Raw Materials and Utilities Consumption in Excess of Guaranteed Level
__________________________________________________________________
If the actual measured figure of specified raw materials and utilities consumed per
unit (or their average total cost of consumption) exceeds the guaranteed figure
specified in para. 3.2 above (or their specified average total cost of consumption),
but the actual consumption attained in the guarantee test, pursuant to GCC Sub-
Clause 25.2, is not more than the maximum level specified in para. 4.3 below, and
the Contractor elects to pay liquidated damages to the Employer in lieu of making
changes, modifications and/or additions to the Facilities pursuant to GCC Sub-
Clause 28.3, then the Contractor shall pay liquidated damages at the rate of
[amount in the contract currency] for every complete one percent (1%) of the excess
consumption of the Facilities, or part thereof, of less than a complete one percent
(1%).
4.3 Minimum Levels
Notwithstanding the provisions of this paragraph, if as a result of the guarantee
test(s), the following minimum levels of performance guarantees (and
consumption guarantees) are not attained by the Contractor, the Contractor shall at
its own cost make good any deficiencies until the Facilities reach any of such
minimum performance levels, pursuant to GCC Sub-Clause 28.2:
(a) production capacity of the Facilities attained in the guarantee test: ninety-
five percent (95%) of the guaranteed production capacity (the values offered
by the Contractor in its Bid for functional guarantees represents 100%).
and/or
(b) average total cost of consumption of all the raw materials and utilities of the
Facilities: one hundred and five percent (105%) of the guaranteed figures
(the figures offered by the Contractor in its Bid for functional guarantees
represents 100%).
4.4 Limitation of Liability
Subject to para. 4.3 above, the Contractor’s aggregate liability to pay liquidated
damages for failure to attain the functional guarantees shall not exceed ______
percent ( ___ %) of the Contract price.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 568
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 569
Guarantor: [Insert name and address of place of issue, unless indicated in the letterhead]
We have been informed that ____________________ (hereinafter called “the Applicant”) has
entered into Contract No. ________________dated ____________ with the Beneficiary, for the
execution of ____________________________ (hereinafter called “the Contract”).
At the request of the Applicant, we as Guarantor, hereby irrevocably undertake to pay the
Beneficiary any sum or sums not exceeding in total an amount of
_________________(___)2,such sum being payable in the types and proportions of currencies in
which the Contract Price is payable, upon receipt by us of the Beneficiary’s complying
demand supported by the Beneficiary’s statement, whether in the demand itself or in a
separate signed document accompanying or identifying the demand, stating that the
Applicant is in breach of its obligation(s) under the Contract, without the Beneficiary needing
to prove or to show grounds for your demand or the sum specified therein.
1
The Employer should insert either the Bank Guarantee or the Conditional Guarantee.
2
The Guarantor shall insert an amount representing the percentage of the Contract Price specified in the
Contract and denominated either in the currency(ies) of the Contract or a freely convertible currency
acceptable to the Employer.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 570
required or provide in writing justifiable reasons why such Certificate has not
been issued, so that Operational Acceptance is deemed to have occurred.
Consequently, any demand for payment under this guarantee must be received by us at this
office on or before that date.
This guarantee is subject to the Uniform Rules for Demand Guarantees (URDG) 2010
Revision, ICC Publication No. 758, except that the supporting statement under Article 15(a)
is hereby excluded.
3
This text shall be revised as and where necessary to take into account (i) partial acceptance of the Facilities
in accordance with Sub-Clause 25.4 of the GCC; and (ii) extension of the Performance Security when the
Contractor is liable for an extended warranty obligation pursuant to Sub-Clause 27.10 of the GCC (although
in this latter case the Employer might want to consider an extended warranty security in lieu of the
extension of the Performance Security).
4
Insert the date twenty-eight days after the expected expiration date of the Defect Liability Period. The
Employer should note that in the event of an extension of the time for completion of the Contract, the
Employer would need to request an extension of this guarantee from the Guarantor. Such request must be in
writing and must be made prior to the expiration date established in the guarantee. In preparing this
guarantee, the Employer might consider adding the following text to the form, at the end of the penultimate
paragraph: “The Guarantor agrees to a one-time extension of this guarantee for a period not to exceed [six
months][one year], in response to the Employer’s written request for such extension, such request to be
presented to the Guarantor before the expiry of the guarantee.”
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 571
_____________________
[signature(s)]
Note: All italicized text (including footnotes) is for use in preparing this form and shall be
deleted from the final product.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 572
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 573
(c) a copy of your written notice to the Contractor stating your intent to claim under
this Letter of Guarantee because of the Contractor’s failure to remedy the default
in accordance with the request referred to in para. (a) above.
Our liability under this Letter of Guarantee shall be to pay to you whichever is the lesser of
the sum so requested or the amount then guaranteed hereunder in respect of any demand duly
made hereunder prior to expiry of this Letter of Guarantee, without being entitled to inquire
whether or not this payment is lawfully demanded.
This Letter of Guarantee shall be valid from the date of issue until the earlier of twelve (12)
months after the date of Operational Acceptance or eighteen (18) months after the date of
Completion of the Facilities or, where the Facilities are to be accepted in parts, twelve (12)
months after the date of Operational Acceptance or eighteen (18) months after the date of
Completion of the last part or [date], whichever comes first.
Except for the documents herein specified, no other documents or other action shall be
required, notwithstanding any applicable law or regulation.
If the Defect Liability Period is extended with respect to any part of the Facilities in
accordance with the Contract, you shall notify us, and the validity of this Letter of Guarantee
shall be extended with respect to the percentage of the Contract Price stipulated in the
notification until expiry of such extended Defect Liability Period.
Our liability under this Letter of Guarantee shall become null and void immediately upon its
expiry, whether it is returned or not, and no claim may be made hereunder after such expiry
or after the aggregate of the sums paid by us to you shall equal the sums guaranteed
hereunder, whichever is the earlier.
All notices to be given hereunder shall be given by registered (airmail) post to the addressee
at the address herein set out or as otherwise advised by and between the parties hereto.
We hereby agree that any part of the Contract may be amended, renewed, extended,
modified, compromised, released or discharged by mutual agreement between you and the
Contractor, and this security may be exchanged or surrendered without in any way impairing
or affecting our liabilities hereunder without notice to us and without the necessity for any
additional endorsement, consent or guarantee by us, provided, however, that the sum
guaranteed shall not be increased or decreased.
No action, event or condition which by any applicable law should operate to discharge us
from liability hereunder shall have any effect and we hereby waive any right we may have to
apply such law, so that in all respects our liability hereunder shall be irrevocable and, except
as stated herein, unconditional in all respects.
Yours truly,
Authorized Signature
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X – Contract Forms 574
Guarantor: [Insert name and address of place of issue, unless indicated in the letterhead]
...........................................................................................................................................................................................................................
A demand under this guarantee may be presented as from the presentation to the
Guarantor of a certificate from the Beneficiary’s bank stating that the advance payment
5
The Guarantor shall insert an amount representing the amount of the advance payment and denominated
either in the currency(ies) of the advance payment as specified in the Contract, or in a freely convertible
currency acceptable to the Employer.
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2
Section X - Contract Forms 575
referred to above has been credited to the Applicant on its account number ___________
at _________________..
The maximum amount of this guarantee shall be progressively reduced by the amount
of the advance payment repaid by the Applicant as indicated in copies of interim
statements or payment certificates which shall be presented to us. This guarantee shall
expire, at the latest, upon our receipt of documentation indicating full repayment by
the Applicant of the amount of the advance payment, or on the . . . day of . . . . . . . , . .
. . . 6 , whichever is earlier. Consequently, any demand for payment under this
guarantee must be received by us at this office on or before that date.
This guarantee is subject to the Uniform Rules for Demand Guarantees (URDG) 2010
Revision, ICC Publication No. 758, except that the supporting statement under Article 15(a)
is hereby excluded.
____________________ [signature(s)]
Note: All italicized text (including footnotes) is for use in preparing this form and shall be
deleted from the final product.
6
Insert the expected expiration date of the Time for Completion. The Employer should note that in the
event of an extension of the time for completion of the Contract, the Employer would need to request
an extension of this guarantee from the Guarantor. Such request must be in writing and must be
made prior to the expiration date established in the guarantee. In preparing this guarantee, the
Employer might consider adding the following text to the form, at the end of the penultimate
paragraph: “The Guarantor agrees to a one-time extension of this guarantee for a period not to
exceed [six months][one year], in response to the Beneficiary’s written request for such extension,
such request to be presented to the Guarantor before the expiry of the guarantee.”
Supply and Installation of 33/11kV Primary Substations and 33kV Sub Transmission Lines in
Freetown (Lot 1-2) – Volume 1 of 2