GREEN ENERGY

GEEU ECOLOGY UNITS

A Powerful,
Efficient
Air Purification
System
GREEN ENERGY
GEEU ECOLOGY UNITS
Green Energy Ecology Units offer an
excellent solution for architects and ▪▪ Eliminate up to 98% of smoke, oil and grease
particles
builders who need high-performance,
cost effective odor and smoke control. ▪▪ Filters particles down to sub-micron levels

Green Energy Ecology units are comprised of high-quality ▪▪ Carbon filters eliminate malodors
components sourced from leading European and U.S.
▪▪ Modular design
manufacturers, engineered into custom-built systems
designed to meet the requirements of your application.
▪▪ Specifically designed for commercial kitchen
applications
Each unit is comprised of a multi-stage filtration system that
removes 98% of smoke, grease and odors from exhaust air. ▪▪ Energy efficient – uses no more than 50W

Green Energy’s unique, modular architecture allows units to ▪▪ Greatly reduces grease build-up
be easily fitted to any application. Units are skid-mounted, within the duct run
ready to install and can be enclosed in weather-proof,
securely-locked, galvanized steel cabinets.

AIR TREATMENT
Kitchen exhaust systems provide a means to remove heat
and contaminants (smoke, grease aerosols, and water vapor)
generated during cooking operations. While exhausting these
items provides a better indoor environment, it can cause
problems outdoors to neighboring facilities due to the associated
odors and particulates emitted.

The amount and type of contaminants generated from a kitchen


exhaust application will depend on the cooking operations taking
place inside. The contaminants include gases, vapors, aerosols,
and particulates. Therefore, kitchen exhaust filtration must
incorporate a wide range of filtration types and be versatile to
provide an adequate solution.

Commercial kitchens typically include grease and moisture


capture devices at the cooking locations. These may be in the
form of hoods with baffles or other equipment to remove the
initial amount of grease aerosols and particulate. The exhaust air
stream will have carryover of contaminants that are not removed
by these devices, or from cooking operations that do not use
removal devices at the cooking location.

3
GREEN ENERGY GEEU ECOLOGY UNITS

THE O.N. 100 ODOR NEUTRALIZER ODOR NEUTRALIZATION


How it works and its use in the control of odors
from commercial kitchen extract systems
The O.N. 100 has been developed by Purified Air Limited using
patented technology which combines physics and chemistry
to encapsulate and treat cooking odors being emitted from
restaurants and other commercial cooking applications. There
is high demand world wide for the O.N. 100 and associated
products which are easy to install and maintain. When applied
correctly, the O.N. can reduce the odors emanating from cooking
premises by as much as 90%

Major Advantages of the O.N. 100 Fan Control


Damper Control
• Instant control of odors
High
• Efficiency up to 90% How it works Quick Release Locks Voltage
• Visual awareness of neutralizing agent The air stream must first be cleaned of the majority of particulate
• Fully adjustable contaminants made up of hydrocarbons and grease vapors leaving
• Easy and economical to maintain the gaseous phase (odor) the be treated by the O.N. 100. Ambient
• Installed easily into new and existing systems air is drawn into the unit and mixed with a specially-blended
• No resistance to airflow The O.N. 100 installed on a flat roof with ESP 3000 E neutralizing chemical. A vapor is formed which is then ionized to a
prefiltration unit. negative potential of 15,000 volts. The ionized vapor passes along a
non-conductive tube and is discharged into the center of the duct
O.N. 100 Technical Data O.N. 100 Dimensions via a venturi spigot. The metal duct is grounded through the same
high-tension circuit which makes the contaminant at an opposite
Electrical supply 220/240V 50 Hz*
potential to the negatively-charged vapor. The electrostatic Top Up Level Indicator
Power consumption 40 watts difference between the contaminant and the neutralizing vapor
causes the two to combine electrically after which a chemical
A = 500 mm
Weight 12.25 Kg B = 400 mm reaction takes place to treat the malodor.
C = 200 mm
Capacity Up to 15,000 m3/h exhaust air Maintenance
The O.N. 100 needs to be topped off with a chemically-formulated
Ionization voltage 15 Kv negative neutralizing agent on a regular basis. In an average situation we
advise two to six weekly servicing, dependent on usage.

ELIMINODOR
This unique product has been blended solely for use in Purified Air Product to counteract Electrostatic Precipitators.
cooking odors from the exhaust of restaurants and commercial cooking operations.
Electrostatic precipitators are used to clean the air stream of
ELIMINODOR has been developed using space-age technology and is a finely-balanced blend
grease and hydrocarbons (smoke). These highly-efficient units can
of oils and other chemicals which neutralize cooking odors. This blend must not become
remove particles as small as 0.01 microns at an efficiency in excess
unbalanced by mixing with any other products as this will render ELIMINODOR ineffective
of 90%. This equipment would be used before the O.N. 100 in our
and result in damage to the equipment. The design of this unique system provides that
systems with a high carry over of grease or smoke. The units come
only minimal quantities are required for optimal results. Approximate dosage: One liter per
in modular form, shown is the ESP 3000E, which is suitable for
three weeks under normal conditions. ELIMINODOR combined with Purified Air Systems can
airflows of up to 5,000 cubic meters per hour (3,000 CFM).
eliminate nuisance caused by cooking odors by up to 90%

4 5
GREEN ENERGY GEEU ECOLOGY UNITS

HOUSING DETAILS SECTIONS


Initial Filter Stage: Second & Third Fourth Filtration Stage: Fifth Filtration Stage: Last Stage:
Grease, Oil & Moisture Filtration Stage: Final filter Section Odor Removal Fan Section
Separation High-Efficiency Removal – High-Efficiency
of Grease, Oil & Moisture Particulate Filtration
• Washable prefilters
followed by bag filters • Electrostatic precipitator • High-efficiency filters,
cells (2 passes, high 2 passes (lower MERV
efficiency) followed by MERV 16)

Green Energy Ecology Units are designed to withstand the most intense kitchen environments. Green
Energy’s technical experts will design your housing around the filter elements that are best suited to the
specifications for your job. CHOOSING SYSTEM COMPONENTS
All housings are a self-supporting, modular design, on an integrated base frame, featuring a double skin Grease and Smoke (Particulates)
panel for maximum acoustic and thermal insulation.
The air stream must first be cleaned of the majority of particulate contaminants made up of
hydrocarbons and grease Green Energy Ecology Units remove the particulate contaminants
Features (grease aerosols, moisture, other particulate) that are carried over into the exhaust air stream
• Double wall construction, duly insulated using electrostatic precipitators in combination with the appropriate stages of particulate filters.
• Hinged door with handle These include metal washable filters, high capacity bag filters, and high efficiency (MERV 16)
• Spring isolators for fan motor assembly pleated filters. In applications with lighter loading of particulates, solutions may solely use stages
• 4-inch galvanized base frame of particulate filters. In both cases, it is critical to performance and safety that proper maintenance,
• Design provides for a wide range of customization cleaning, and replacement are performed as required for the application.

Odors (Gases)
Dimensions Odors result from the release of volatile organic compounds during cooking operations. These
Model No. CFM Width (mm) Height (mm) Depth (mm) volatile organic compounds are in the gas -phase; they are not removed by the particulate
contaminant solutions mentioned above. The most widespread solution to remove these
ECU4500 4500 1200 600 800 compounds is activated carbon applied in filtration cells such as metal cassettes or canisters. In
some instances, applications have used a blend of activated carbon and other media. The filtration
ECU9000 9000 1200 1200 800
cells are commonly designed to achieve at least 0.1 seconds of residence time, however, the
ECU12000 12000 1800 1200 800 actual configuration and associated residence time will depend on the cooking operations taking
place inside the kitchen.
ECU18000 18000 1800 1800 800

6 7
GREEN ENERGY GEEU ECOLOGY UNITS

GREASE AND PARTICULATE FILTERS VENTILATION FANS


Passive filtration is a major component in any air purification system. Passive filters can capture a large amount of Green Energy is proud to be your single source for commercial and industrial ventilation product solutions. We have
grease and particulate before it reaches the electrostatic precipitator (ESP). Certain passive filters can be used after evolved with the industry to provide full-service ventilation products to commercial and light-industrial customers
the ESP stage when the system requires additional cleaning. Green Energy offers a complete line of passive filters worldwide. Building on best practices established at our predecessor companies over six decades, we are developing
designed to work with the other components in your system to provide optimal results. new products, exploring new technology, improving our manufacturing process, streamlining our distribution channels
and enhancing our competitive stance to ensure your satisfaction for decades to come.

Pleated Panels Dynamo


Our new generation pleated panel filters are constructed using Aqua-Kote card Centrifugal fans are SWSI, Class 1, Arrangement 9 and
frames making them highly-resistant to tear, puncture and corner crush. Using the 10 general purpose air moving devices. They are used to
revolutionary electrostatically-treated and hydrophobic intrepid filter media from supply or exhaust applications in commercial, institutional
Kimberley Clark, our range of pleated panel filters have excellent bi-directional and industrial HVAC systems. At the heart of the Dynamo
strength and high dirt-holding capacities is a computer-designed, backward inclined, centrifugal
Panel Filter Nominal Size Height Width Depth Rated Airflow
wheel. This heavy-duty, non-overloading, aluminum wheel
Part Number (in.) (mm) (mm) (mm) (m3/2) assures low noise and high efficiency performance.
Filter 023 24 x 24 x 2 597 594 45 0.705
Filter 024 24 x 24 x 2 597 594 45 0.945 Features
• Class I Heavy-Gauge Galvanized Steel, Roof/Floor/
Inline Mount Utility Blower
Bag Filters • Belt Drive, Backward Inclined Wheel
• U.L. 762 Rated for Grease laden Exhaust Air
Our general-purpose bag filters are manufactured using a galvanized steel • Capacity: From 500 - 29,150 CFM; 0 - 5.0” w.g.
header and are 100% thermally bonded. The pleated polyester filter media is
flame retardant to CP413 (BS5588) and can be applied as a pre filter to carbon
cells in malodor extraction, taking out oil and grease particles ahead of the
carbon filter stage. These bag filters will remove up to 95% of particles down to Centrex Inliner
5 microns in optimum conditions. Direct-drive and belt-drive centrifugal, inline fans are widely
Panel Filter used in square ducts as clean air boosters in both supply
Header Dimensions Pocket Details
Part Number Capacity and exhaust systems where the installation of conventional
Height Width Thickness Depth Number of (m3/2) blowers is impractical. Their compact design gives designers
Filter 023
(mm) (mm) (mm) (mm) Pockets an excellent alternative to conventional blowers. Centrex
Filter 026 597 594 20 300 4 0.583 Inliner fans can be installed either horizontally, vertically
or at any angle determined by the duct work. Full-size
removable panels enable easy access to the fan interior
Absolute HEPA Filters
Features
We supply a range of HEPA filters to suit your needs. To qualify to be called a
• Square Inline Duct-Mount
High-Efficiency Particulate Air (HEPA) filter, the filter must be able to remove, from
• Direct or Belt Drive
the air that passes through it, 99.97% of particles down to a sub-micron level of
• Application: Supply, Return or Exhaust Air for General
0.3 microns. Our main use of HEPA filtration is the removal of smoke particles.
HVAC Systems
HEPA Filter Nominal Size Height Width Depth Rated Airflow • Capacity: From 103 - 27,502 CFM; 0 - 3.5 w.g.
Part Number (in.) (mm) (mm) (mm) (m3/2)
Filter 027 24 x 24 x 11.5 597 594 292 0.778

8 9
GREEN ENERGY GEEU ECOLOGY UNITS

SPECIFICATIONS
ECOLOGY UNIT panel filter with a reusable aluminum or steel frame and
synthetic fiber media, Class MERV-7 , and have a large dust
tion time, rinse and wash cycle. The controller to be in
weather proof box with necessary push button to start
4. BLOWER SECTION

1. GENERAL holding capacity. It can be cleaned with a solution of water / off the unit. 4.1 The Fan shall be industrial quality, heavy-duty fan, with one
1.1 The ecology units shall be sized and selected at a face veloc- and detergent on a limited basis. 3. Five gallon liquid wash detergent should be supplied duty and one standby motor. The fan impeller shall be with
ity as following table in according to duty time of cooking; to a along with each unit. backward curved vanes, DIDW, Type.
higher velocity is not acceptable. 3.4 ELECTROSTATIC PRECIPITATOR 4.2 The fan assembly shall be belt driven with fixed motor
Duty Time Maximum Face Velocity 3.4.1 Industrial grade Electronic Cell meant for kitchen smoke 3.5 Bag Filter sheave. Fan shall be sized for the designed airflow, including
Heavy Duty (12-18 H/Day) : < 350 FPM control, skid base, modular design having electrostatic pre- This shall be a UL Listed, 21” Deep, Type Fine Filter, with total internal static pressure and external static pressure
Medium Duty (6-12 H/Day) : < 400 FPM cipitator housed inside double wall weatherproof Ecology Glass Fiber Media Construction, Confirming to MERV-14 , drop, as stated in the equipment schedule.
Light Duty (3-6 H/Day) : < 450 FP unit. 90-95% efficiency. 4.3 Fan assemblies are easy to service provided with Adjustable
Very Light Duty ( < 3 H/Day ) : < 500 FPM 3.4.2 Electrostatic precipitator shall have two sections, a motor bases to allow for proper tensioning of the belts at all
charging section and a collection section. Thecharging 3.6 High Efficiency Filter times.
1.2 The complete unit casing and the filtration elements section using ionizer wires to impart a positive charge to This shall be a UL Listed, 12” Deep, Compact Rigid Box 4.4 25mm deflection spring isolators to be used under fan.
shall be supplied by a specialized and reputed filter manufactur- the incoming smoke fume and dust particles. The charged (Galvanized, Metallic Cell sides) Type Fine Filter, with Glass
er. particles are then drawn into a secondary electric field Fiber Media, Mini Pleated Construction and Confirming to 5. DIFFERENTIAL PRESSURE GAGES / SWITCHES:
1.3 The unit construction shall meet or exceed the follow- where they need to collect on a series of metal plates. Ac- Efficiency 95% @ 0.03 microns), Each Filter shall be factory
ing specifications: cess door shall be provided with safety disconnect switch, tested, and test certificate provided for each filter. The 5.1 Dwyer Make, Industrial Type, rugged Differential Pressure
shall meet or exceed the following points: media shall have a non-boron outgassing characteristic. Gages/Switches, selected for purpose of sensing kitchen
2. HOUSING extract, shall the installed for each of the following sections,
2.1 The housing construction shall be qualified and tested in 1. The Pre-Filter Permanent Metal Filters or AmWash 3.7 Activated Carbon /chemical filter (Canisters with media) and shall be used to monitor the operation of the unit :
accordance with the requirements of DW/143 and certified shall be installed upstream of Electrostatic Precipitator 1) Pre-Filters -1 ( 0-250 Pa)
to have a minimum rating of Class B at -1,000 Pa (4.02” Section. 3.7.1 The Canister to be in galvanized steel finish having 2) Pre Filter 3 ( 0-250 Pa)
w.g.) negative pressures. Certifications shall be available on refillable cylindrical design, initial chemical media tobe 3) Fine Filter 1 ( 0-500Pa)
request without exception. 2. The Electrostatic system shall be requiring minimum pre-filled by factory. The individual canister seals and 4) Super Fine Filter – 1 ( 0-750 Pa)
2.2 Housing: SAH shall have a corrosion resistant casing con- and easy maintenance. The unit shall have control panel holds in the frame with fully secure bayonetclamp 5) Fan Section ( 0 - 500 Pa )
sisting of a rigid coated steel and structural frame and 42 mounted on the unit or remote. sealing with cap gasket.
mm thick, insulated, double wall panels (for airflows below 6. CONTROL PANEL:
20000 CFM) All units with higher flow, shall be with 62 mm 3. The units are all fitted with a drip tray and an oil drain 3.7.2 The Canisters and the Media should be supplied by a 6.1 A Remotely installed, Starter/Control/Monitoring Panel shall
thick, insulated, double wall panels. point to allow collected waste grease and oil to be single source supply i.e. from same manufacturerwho is be constructed for remote mounting with front locking
2.3 Outer wall shall be 0.8 mm Pre-Coated External & Inter- drained away providing the Housing and All other filter stages. screws, shall be provide dalong with the unit.
nal Finish (Standard Whitish Grey Color) having PUF filled 6.2 The panel shall be supplied with an Alarm Silence Button.
insulation. 4. Neoprene seals shall be provided all around. 3.7.3 The unit shall house a media odor control section 6.3 Control circuits to operate of 24 VAC.
2.4 The filter enclosure shall include side-access extruded alu- consisting of 24”x24”x18” and/or 12”x24”x18”refillable 6.4 The Starter cum Control panel shall allow for Remote Start /
minum tracks to support the filters & odor control sections. 5. This section shall be installed upstream of (prior to) to GI canisters delivery system. Stop from the BMS.
2.5 Access doors shall be provided on the filter sections to the Bag Filter (DRIPAK 2000), and shall be designed and 6.5 Following Monitoring points shall also be available :
allow ease of access to, and installation and removal of, all selected to have a minimum 95% efficiency. 3.7.4 Each canister will be loaded with at least 2.10 kg of 1) The panel shall be complete with lamps for system
the filter stages. media. running status and alarm condition of :
2.6 Weather Proof Roof Top, shall be provided in case the units 6. Face Velocity to be selected to meet the efficiency re- a. Power On,
are installed outdoors. quired, for this section. 3.7.5 The sizing/selection of the canister delivery system b. Fan On / Off / Trip,
shall be done to ensure a minimum dwell time of0.12 c. Dirty Pre-Filter-1,
3. FILTER SECTIONS 7. Unit shall comply with UL 867 Standard for Electrostatic seconds. d. Dirty Pre-Filter-3,
3.1 The Ecology Unit, shall consist of the following filtration Air Cleaners and UL 710 Standard for Exhaust Hoods for e. Dirty Fine Filter 1,
stages/sections : Commercial Cooking Equipment or equivalent stan- 3.7.6 The selected media shall be UL Listed as following f. Dirty Super Fine Filter 1,
a) Electro Static Precipitator Section dards. The units shall be in complete accordance with Media to be used for effectively removing food odors 2) The panel shall be able to give the following trip sig-
b) Pre-Filtration Section ASHRAE Standard 52.2-2007 Method of Testing General carried down to the air stream prior to discharge. nals separately.
c) Fine Filtration Section Ventilation Air-Cleaning Devices for Removal Efficiency Media Shall be opened wide range of VOC Odors a. ELR Fault Status
d) Odor Removal Section by Particle Size Included but not only following typical gases b. MCB Trip Status
e) Super Fine / HEPA Filtration Section Media Capacity (minimum value of media capacity for c. OLR Trip Status.
3.4.3 Option: Auto Wash option following typical gases) :
3.2 PRE-FILTER Meat ( VOC eg. Toluene ) : 3 Kg Gas / 1 Ft3 Media
Shall be 2’’ Thick, Heavy Duty Industrial Grade, Suitable for 1. High cleaning efficiency is using multi-jet wash mani-
Grease Filtration in Kitchen Extract, fold covering the entire span of ESP. The wash system Media to be used for effectively removing food odors
Class MERV-3 , Washable Type, Stainless steel media; multi- should be complete with wash detergent pump, sole- carried down to the air stream prior to discharge.
ple layers in SS frames. The unit shall have a noid valve, spray nozzles in brass and SS drain pan. The Media Shall be opened wide range of Sulfur com-
stainless steel drain tray with appropriate drain size, below wash detergent liquid container to be included within pounds and amine Odors Included but not only
this section, to drain the collected grease , It shall be able to the ESP section. following typical gases
withstand operating temperatures to 930 F. Media Capacity (minimum value of media capacity for
2. Sequence Controller: The ESP along with the Ecology following typical gases) :
3.3 Pre- Filters unit should be provided with timer based sequence Garlic (diallyl sulfide ) : 0.48 Kg Gas / 1 Ft3 Media
Shall be 2’’ Thick , Class MERV-3 , ChevroNet is a lightweight controller allowing to program the shutdown, opera- Fishy, egg (Dimethylamine ) : 1.8 Kg Gas / 1 Ft3 Media

10 11