SPECIALISTS GROUP INC.

LIMITED
TEST REPORT
Client: Tribal Area Electric Supply Company Limited (TESCO) Date:
Purchase Order No: 483-89 CEO/TESCO, Dated: 10-02-2021
Sr.
Desciption Quantity
No.
1 ZM-1 Type Tower w/o Stubs & Cleats 50
2 Stubs & Cleats for ZM-1 200
3 3M Leg Extension for ZM-1 5
SAMPLING PLAN FOR 132KV TOWER TYPE ZM-1 WITH STUBS, CLEATS & LEG EXTENSIONS

Galvanizing Test
Angle Size Total Weight Tensile Bend Chemical Impact
Sr.# Embrittlement
Inches (kg) Test Test Test Test Wt of Uniformit
Coating y Test

1 L 4-1/2 X 4-1/2 X 3/8 49,641 8 8 8 1 - 8 8


2 L 4-1/2 X 4-1/2 X 5/16 9,508 1 1 1 - - 1 1
3 L 4 X 4 X 5/16 15,918 2 2 2 1 - 2 2
4 L 4 X 4 X 1/4 8,907 1 1 1 - - 1 1
5 L 3-1/2 X 3-1/2 X 5/16 13,752 2 2 2 1 - 2 2
6 L 3 X 3 X 1/4 15,189 2 2 2 1 - 2 2
7 L 3 X 3 X 3/16 25,945 4 4 4 1 - 4 4
8 L 2-1/2 X 2-1/2 X 1/4 4,681 1 1 1 - - 1 1
9 L 2-1/2 X 2-1/2 X 3/16 23,529 4 4 4 1 - 4 4
10 L 2 X 2 X 1/4 3,605 1 1 1 - - 1 1
11 L 2 X 2 X 3/16 45,981 8 8 8 2 - 8 8
12 L 1-3/4 X 1-3/4 X 3/16 14,909 2 2 2 - - 2 2
Grand Total 231,564 36 36 36 8 - 36 36
SPECIALISTS GROUP INC. LIMITED
TEST REPORT
Client: Tribal Area Electric Supply Company Limited (TESCO) Date:
Purchase Order No: 483-89 CEO/TESCO, Dated: 10-02-2021
Sr.
Description Quantity
No.
1 ZM-1 Type Tower w/o Stubs & Cleats 50
2 Stubs & Cleats for ZM-1 200
3 3M Leg Extension for ZM-1 5

VERIFICATION WEIGHT AND DIMENSION FOR 132KV TOWER TYPE ZM-01 WITH STUBS, CLEATS & LEG EXTENSIONS
Observed
Sr. Component Specified Size Specified Size Observed Size Specified Observed Specified
Weight Remarks
# No. Inches (mm) mm Length (mm) Length (mm) Weight (Kgs)
(Kgs)
1 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 L114.3 x 114.3 x 9.525 L114.5 x 114.6 x 9.53 3100 3101 50.80 50.85 OK
2 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 L114.3 x 114.3 x 9.525 L114.4 x 114.5 x 9.54 3100 3102 50.80 50.95 OK
3 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 L114.3 x 114.3 x 9.525 L114.6 x 114.7 x 9.53 3100 3100 50.80 51.00 OK
4 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 L114.3 x 114.3 x 9.525 L114.7 x 114.6 x 9.52 3100 3101 50.80 50.90 OK
5 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 L114.3 x 114.3 x 9.525 L114.7 x 114.6 x 9.53 3100 3102 50.80 50.95 OK
6 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 L114.3 x 114.3 x 9.525 L114.4 x 114.5 x 9.52 3100 3101 50.80 51.00 OK
7 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 L114.3 x 114.3 x 9.525 L114.7 x 114.7 x 9.55 3100 3101 50.80 50.86 OK
8 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 L114.3 x 114.3 x 9.525 L114.6 x 114.6 x 9.53 3100 3102 50.80 50.87 OK
9 ZM1-2A L-4-1/2 X 4-1/2 X 5/16 L114.3 x 114.3 x 7.94 L114.5 x 114.4 x 7.95 3196 3196 43.95 44.08 OK
10 ZM1-7A L 4 X 4 X 5/16 L101.6 x 101.6 x 7.94 L101.7 x 101.8 x 7.95 6540 6541 79.59 79.91 OK
11 ZM1-7BL L 4 X 4 X 5/16 L101.6 x 101.6 x 7.94 L101.6 x 101.7 x 7.96 6540 6541 79.59 79.75 OK
12 ZM1-21A L 4 X 4 X 1/4 L101.6 x 101.6 x 6.35 L101.7 x 101.7 x 6.36 4540 4542 44.54 44.67 OK
13 ZM1-17A L 3-1/2 X 3-1/2 X 5/16 L88.9 x 88.9 x 7.94 L88.91 x 88.92 x 7.95 6493 6494 68.76 69.04 OK
14 ZM1-17BL L 3-1/2 X 3-1/2 X 5/16 L88.9 x 88.9 x 7.94 L88.92 x 88.93 x 7.95 6493 6495 68.76 68.90 OK
15 ZM1-43K L 3 X 3 X 1/4 L76.2 x 76.2 x 6.35 L76.3 x 76.4 x 6.36 2855 2855 20.78 20.83 OK
16 ZM1-57L L 3 X 3 X 1/4 L76.2 x 76.2 x 6.35 L76.3 x 76.3 x 6.36 4119 4119 29.99 30.08 OK
17 ZM1-3 L 3 X 3 X 3/16 L76.2 x 76.2 x 4.76 L76.3 x 76.4 x 4.77 3629 3630 20.03 20.11 OK
18 ZM1-8 L 3 X 3 X 3/16 L76.2 x 76.2 x 4.76 L76.4 x 76.3 x 4.77 4736 4737 26.14 26.20 OK
19 ZM1-9 L 3 X 3 X 3/16 L76.2 x 76.2 x 4.76 L76.3 x 76.3 x 4.77 4283 4283 23.64 23.71 OK
20 ZM1-63 L 3 X 3 X 3/16 L76.2 x 76.2 x 4.76 L76.4 x 76.4 x 7.76 4074 4076 22.49 22.58 OK
VERIFICATION WEIGHT AND DIMENSION FOR 132KV TOWER TYPE ZM-01 WITH STUBS, CLEATS & LEG EXTENSIONS
Observed
Sr. Component Specified Size Specified Size Observed Size Specified Observed Specified
Weight Remarks
# No. Inches (mm) mm Length (mm) Length (mm) Weight (Kgs)
(Kgs)
21 ZM1-22A L 2-1/2 X 2-1/2 X 1/4 L63.5 x 63.5 x 6.35 L63.6 x 63.7 x 6.36 3894 3896 23.40 23.45 OK
22 ZM1-6 L 2-1/2 X 2-1/2 X 3/16 L63.5 x 63.5 x 4.76 L63.7 x 63.6 x 4.77 4589 4591 20.97 21.01 OK
23 ZM1-10 L 2-1/2 X 2-1/2 X 3/16 L63.5 x 63.5 x 4.76 L63.6 x 63.6 x 4.76 3861 3863 17.64 17.70 OK
24 ZM1-11 L 2-1/2 X 2-1/2 X 3/16 L63.5 x 63.5 x 4.76 L63.7 x 63.7 x 4.77 3461 3462 15.82 15.88 OK
25 ZM1-31 L 2-1/2 X 2-1/2 X 3/16 L63.5 x 63.5 x 4.76 L63.6 x 63.7 x 4.77 4589 4588 20.97 21.01 OK
26 ZM1-27A L 2 X 2 X 1/4 L50.8 x 50.8 x 6.35 L50.9 x 50.8 x 6.36 3796 3792 18.02 18.08 OK
27 ZM1-12 L 2 X 2 X 3/16 L50.8 x 50.8 x 4.76 L50.9 x 50.8 x 4.77 3091 3093 11.19 11.23 OK
28 ZM1-13 L 2 X 2 X 3/16 L50.8 x 50.8 x 4.76 L50.8 x 50.9 x 4.77 2745 2746 9.94 9.96 OK
29 ZM1-14 L 2 X 2 X 3/16 L50.8 x 50.8 x 4.76 L50.9 x 51 x 4.76 2396 2398 8.67 8.69 OK
30 ZM1-15 L 2 X 2 X 3/16 L50.8 x 50.8 x 4.76 L50.9 x 50.8 x 4.76 2104 2105 7.62 7.64 OK
31 ZM1-16 L 2 X 2 X 3/16 L50.8 x 50.8 x 4.76 L50.9 x 50.9 x 4.76 1818 1819 6.58 6.61 OK
32 ZM1-18 L 2 X 2 X 3/16 L50.8 x 50.8 x 4.76 L51 x 51.1 x 4.78 1549 1549 5.61 5.62 OK
33 ZM1-19 L 2 X 2 X 3/16 L50.8 x 50.8 x 4.76 L51.1 x 50.7 x 4.76 1610 1611 5.83 5.85 OK
34 ZM1-20 L 2 X 2 X 3/16 L50.8 x 50.8 x 4.76 L50.9 x 51.1 x 4.77 1548 1549 5.60 5.63 OK
35 ZM1-4 L 1-3/4 X 1-3/4 X 3/16 L44.45 x 44.45 x 4.76 L44.5 x 44.47 x 4.78 1186 1187 3.74 3.74 OK
36 ZM1-5 L 1-3/4 X 1-3/4 X 3/16 L44.45 x 44.45 x 4.76 L44.47 x 44.46 x 4.77 1634 1635 5.15 5.16 OK
Note :- As per Wapda Specification # P-139:80
Tolerance in Weight:- Variation of 2.5% from the theoretical and specified amount.
Tolerance in Size: ASTM A6

Engr. Farhan Engr. Imtiaz-Ur-Rehman


Mechanical Engineer SGI Director (MM) TESCO, Peshawar
SPECIALISTS GROUP INC. LIMITED
TEST REPORT
Client: Tribal Area Electric Supply Company Limited (TESCO) Date:
Purchase Order No: 483-89 CEO/TESCO, Dated: 10-02-2021
Sr.
Desciption Quantity
No.
1 ZM-1 Type Tower w/o Stubs & Cleats 50
2 Stubs & Cleats for ZM-1 200
3 3M Leg Extension for ZM-1 5

MECHANICAL TEST REPORT FOR 132KV TOWER TYPE ZM-01 WITH STUBS, CLEATS & LEG EXTENSIONS

Size Yield Strength Tensile Strength % Elongation G.L Embrittlement


Sr.# Component No. Bend Test Remarks
Inches Kg/mm2 Kg/mm2 =200mm %age

1 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 29.1 51.1 20 5.9 OK OK


2 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 30.7 48.8 21 6.4 OK OK
3 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 33.3 48.7 22 7.3 OK OK
4 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 31.4 52.5 20 6.3 OK OK
5 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 32.9 50.2 20 6.6 OK OK
6 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 30.0 51.0 21 7.3 OK OK
7 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 31.0 51.6 20 6.1 OK OK
8 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 32.0 47.5 21 7.3 OK OK
9 ZM1-2A L-4-1/2 X 4-1/2 X 5/16 28.6 52.1 19 6.3 OK OK
10 ZM1-7A L 4 X 4 X 5/16 28.3 52.7 19 6.5 OK OK
11 ZM1-7BL L 4 X 4 X 5/16 29.6 49.6 21 7.3 OK OK
12 ZM1-21A L 4 X 4 X 1/4 34.4 50.1 19 6.1 OK OK
13 ZM1-17A L 3-1/2 X 3-1/2 X 5/16 31.0 47.6 21 6.5 OK OK
14 ZM1-17BL L 3-1/2 X 3-1/2 X 5/16 33.3 48.7 22 7.3 OK OK
15 ZM1-43K L 3 X 3 X 1/4 31.4 52.5 20 6.3 OK OK
16 ZM1-57L L 3 X 3 X 1/4 32.9 50.2 20 6.6 OK OK
MECHANICAL TEST REPORT FOR 132KV TOWER TYPE ZM-01 WITH STUBS, CLEATS & LEG EXTENSIONS

Size Yield Strength Tensile Strength % Elongation G.L Embrittlement


Sr.# Component No. Bend Test Remarks
Inches Kg/mm2 Kg/mm2 =200mm %age

17 ZM1-3 L 3 X 3 X 3/16 30.0 51.0 21 7.3 OK OK


18 ZM1-8 L 3 X 3 X 3/16 31.0 51.6 20 6.1 OK OK
19 ZM1-9 L 3 X 3 X 3/16 32.0 47.5 21 7.3 OK OK
20 ZM1-63 L 3 X 3 X 3/16 28.6 52.1 19 6.3 OK OK
21 ZM1-22A L 2-1/2 X 2-1/2 X 1/4 33.3 48.7 22 7.3 OK OK
22 ZM1-6 L 2-1/2 X 2-1/2 X 3/16 31.4 52.5 20 6.3 OK OK
23 ZM1-10 L 2-1/2 X 2-1/2 X 3/16 32.9 50.2 20 6.6 OK OK
24 ZM1-11 L 2-1/2 X 2-1/2 X 3/16 30.0 51.0 21 7.3 OK OK
25 ZM1-31 L 2-1/2 X 2-1/2 X 3/16 31.0 51.6 20 6.1 OK OK
26 ZM1-27A L 2 X 2 X 1/4 32.0 47.5 21 7.3 OK OK
27 ZM1-12 L 2 X 2 X 3/16 28.6 52.1 19 6.3 OK OK
28 ZM1-13 L 2 X 2 X 3/16 28.3 52.7 19 6.5 OK OK
29 ZM1-14 L 2 X 2 X 3/16 29.6 49.6 21 7.3 OK OK
30 ZM1-15 L 2 X 2 X 3/16 34.4 50.1 19 6.1 OK OK
31 ZM1-16 L 2 X 2 X 3/16 31.0 47.6 21 6.5 OK OK
32 ZM1-18 L 2 X 2 X 3/16 33.3 48.7 22 7.3 OK OK
33 ZM1-19 L 2 X 2 X 3/16 31.4 52.5 20 6.3 OK OK
34 ZM1-20 L 2 X 2 X 3/16 32.9 50.2 20 6.6 OK OK
35 ZM1-4 L 1-3/4 X 1-3/4 X 3/16 30.0 51.0 21 7.3 OK OK
36 ZM1-5 L 1-3/4 X 1-3/4 X 3/16 31.0 51.6 20 6.1 OK OK
Specified Values: P-139:80 & P-182:91 As per Wapda Specification, for Fabrication of Steel Structures.52.7
Yield Strength :-Mild Steel: 26.0 Kg/mm2
Tensile Strength :-Mild Steel: 40-56 Kg/mm2
Elongation :Mild Steel :16-20 %
Bend Test : No Crack, Minimum Embrittlement : 5.0 %
MECHANICAL TEST REPORT FOR 132KV TOWER TYPE ZM-01 WITH STUBS, CLEATS & LEG EXTENSIONS

Size Yield Strength Tensile Strength % Elongation G.L Embrittlement


Sr.# Component No. Bend Test Remarks
Inches Kg/mm2 Kg/mm2 =200mm %age

Engr. Farhan Engr. Imtiaz-Ur-Rehman


Mechanical Engineer SGI Director (MM) TESCO, Peshawar
SPECIALISTS GROUP INC. LIMITED
TEST REPORT
Client: Tribal Area Electric Supply Company Limited (TESCO) Date:
Purchase Order No: 483-89 CEO/TESCO, Dated: 10-02-2021
Sr.
Desciption Quantity
No.
1 ZM-1 Type Tower w/o Stubs & Cleats 50
2 Stubs & Cleats for ZM-1 200
3 3M Leg Extension for ZM-1 5

GALVANIZING TEST REPORT FOR 132KV TOWER TYPE ZM-01 WITH STUBS, CLEATS & LEG EXTENSIONS

Component Size Weight of Zinc Coating


Sr.# Uniformity of Coating Adherance of Coating
No. (inches) (g/m2)
1 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 895 OK No Copper Deposit
2 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 895 OK No Copper Deposit
3 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 917 OK No Copper Deposit
4 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 915 OK No Copper Deposit
5 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 886 OK No Copper Deposit
6 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 818 OK No Copper Deposit
7 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 966 OK No Copper Deposit
8 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 919 OK No Copper Deposit
9 ZM1-2A L-4-1/2 X 4-1/2 X 5/16 966 OK No Copper Deposit
10 ZM1-7A L 4 X 4 X 5/16 786 OK No Copper Deposit
11 ZM1-7BL L 4 X 4 X 5/16 829 OK No Copper Deposit
12 ZM1-21A L 4 X 4 X 1/4 854 OK No Copper Deposit
13 ZM1-17A L 3-1/2 X 3-1/2 X 5/16 915 OK No Copper Deposit
14 ZM1-17BL L 3-1/2 X 3-1/2 X 5/16 886 OK No Copper Deposit
15 ZM1-43K L 3 X 3 X 1/4 818 OK No Copper Deposit
16 ZM1-57L L 3 X 3 X 1/4 966 OK No Copper Deposit
GALVANIZING TEST REPORT FOR 132KV TOWER TYPE ZM-01 WITH STUBS, CLEATS & LEG EXTENSIONS

Component Size Weight of Zinc Coating


Sr.# Uniformity of Coating Adherance of Coating
No. (inches) (g/m2)
17 ZM1-3 L 3 X 3 X 3/16 919 OK No Copper Deposit
18 ZM1-8 L 3 X 3 X 3/16 966 OK No Copper Deposit
19 ZM1-9 L 3 X 3 X 3/16 786 OK No Copper Deposit
20 ZM1-63 L 3 X 3 X 3/16 829 OK No Copper Deposit
21 ZM1-22A L 2-1/2 X 2-1/2 X 1/4 849 OK No Copper Deposit
22 ZM1-6 L 2-1/2 X 2-1/2 X 3/16 895 OK No Copper Deposit
23 ZM1-10 L 2-1/2 X 2-1/2 X 3/16 917 OK No Copper Deposit
24 ZM1-11 L 2-1/2 X 2-1/2 X 3/16 915 OK No Copper Deposit
25 ZM1-31 L 2-1/2 X 2-1/2 X 3/16 886 OK No Copper Deposit
26 ZM1-27A L 2 X 2 X 1/4 818 OK No Copper Deposit
27 ZM1-12 L 2 X 2 X 3/16 966 OK No Copper Deposit
28 ZM1-13 L 2 X 2 X 3/16 919 OK No Copper Deposit
29 ZM1-14 L 2 X 2 X 3/16 966 OK No Copper Deposit
30 ZM1-15 L 2 X 2 X 3/16 786 OK No Copper Deposit
31 ZM1-16 L 2 X 2 X 3/16 829 OK No Copper Deposit
32 ZM1-18 L 2 X 2 X 3/16 849 OK No Copper Deposit
33 ZM1-19 L 2 X 2 X 3/16 895 OK No Copper Deposit
34 ZM1-20 L 2 X 2 X 3/16 917 OK No Copper Deposit
35 ZM1-4 L 1-3/4 X 1-3/4 X 3/16 915 OK No Copper Deposit
36 ZM1-5 L 1-3/4 X 1-3/4 X 3/16 886 OK No Copper Deposit
Note :- As per Wapda Specification # P-182 : 91 & P-82 : 81
Specified Value of Coating Minimum 610 g/m2 for 3mm to 6mm and Minimum 700 g/m2 for greater than 6mm.
GALVANIZING TEST REPORT FOR 132KV TOWER TYPE ZM-01 WITH STUBS, CLEATS & LEG EXTENSIONS

Component Size Weight of Zinc Coating


Sr.# Uniformity of Coating Adherance of Coating
No. (inches) (g/m2)

Engr. Farhan Engr. Imtiaz-Ur-Rehman


Mechanical Engineer SGI Director (MM) TESCO, Peshawar
SPECIALISTS GROUP INC. LIMITED
TEST REPORT
Client: Tribal Area Electric Supply Company Limited (TESCO) Date:
Purchase Order No: 483-89 CEO/TESCO, Dated: 10-02-2021
Sr.
Desciption Quantity
No.
1 ZM-1 Type Tower w/o Stubs & Cleats 50
2 Stubs & Cleats for ZM-1 200
3 3M Leg Extension for ZM-1 5

CHEMICAL ANALYSIS FOR 132KV TOWER TYPE ZM-01 WITH STUBS, CLEATS & LEG EXTENSIONS

Manganese
Sr.# Component No. Size Carbon % Specified Value Remarks
%

1 ZM1-1 L-4-1/2 X 4-1/2 X 3/8 0.25 0.88 OK


2 ZM1-7A L 4 X 4 X 5/16 0.24 0.89 OK
3 ZM1-17BL L 3-1/2 X 3-1/2 X 5/16 0.29 0.92 OK
For Mild Steel
4 ZM1-43K L 3 X 3 X 1/4 0.28 0.86 Carbon = 0.23-0.3% OK
5 ZM1-3 L 3 X 3 X 3/16 0.26 0.88 OK
Manganses = 0.79-0.93%
6 ZM1-6 L 2-1/2 X 2-1/2 X 3/16 0.24 0.82 OK
7 ZM1-12 L 2 X 2 X 3/16 0.27 0.91 OK
8 ZM1-13 L 2 X 2 X 3/16 0.26 0.88 OK
Note :- As per Wapda Specification # P-139:80 & P-182:91
Engr. Farhan Engr. Imtiaz-Ur-Rehman
Mechanical Engineer SGI Director (MM) TESCO, Peshawar
SPECIALISTS GROUP INC. LIMITED
TEST REPORT
Client: Tribal Area Electric Supply Company Limited (TESCO) Date:
Purchase
Sr. Order No: 483-89 CEO/TESCO, Dated: 10-02-2021

Desciption Quantity
No
1. ZM-1 Type Tower w/o Stubs & Cleats 50
2 Stubs & Cleats for ZM-1 200
3 3M Leg Extension for ZM-1 5

VERIFICATION WEIGHT OF HARDWARE AND DIMENSION AS PER NTDC SPECIFICATION


Manufactures Length of Un- Length of Thickness of Thickness of Thickness of
Sr. Drawing Size Length/ Dia of Thickness of Remark
ID & threaded portion threaded Washer Main Nut Lock Nut
# (mm) Bolts (mm) Head (mm) s
Grade (mm) portion (mm) (mm) (mm) (mm)
1 SGI 5.8 M 16 X 45 16 X 47 13 34 10.4 5.2 14.5 7.5 OK
2 SGI 5.8 M 16 X 45 16 X 46 12 34 10.2 5.1 13.5 7.6 OK
3 SGI 5.8 M 16 X 45 16 X 46 15 31 10.0 4.8 15.1 7.9 OK
4 SGI 5.8 M 16 X 50 16 X 51 20 30 10.3 5.1 14.8 7.5 OK
5 SGI 5.8 M 16 X 50 16 X 50 20 31 10.2 5.2 14.7 7.8 OK
6 SGI 5.8 M 16 X 50 16 X 52 20 32 10.4 5.1 14.6 7.4 OK
7 SGI 5.8 M 16 X 55 16 X 55 21 34 10.7 5.2 14.8 7.6 OK
8 SGI 5.8 M 16 X 55 16 X 56 23 33 10.1 5.3 15.1 7.4 OK
9 SGI 5.8 M 16 X 55 16 X 57 22 35 10.6 4.9 15.6 7.1 OK
10 SGI 5.8 M 16 X 60 16 X 61 24 37 10.3 5.0 14.6 6.9 OK
11 SGI 5.8 M 16 X 60 16 X 63 23 40 10.0 5.2 14.9 7.0 OK
12 SGI 5.8 M 16 X 75 16 X 77 26 51 10.4 5.1 15.0 7.2 OK
13 SGI 5.8 M 16 X 185 16 X 187 119 68 10.6 4.9 14.4 7.4 OK
14 SGI 5.8 M 16 X 185 16 X 189 122 67 10.4 5.3 14.6 7.0 OK
15 SGI 5.8 M 16 X 185 16 X 186 125 61 10.1 5.0 15.1 7.5 OK
16 SGI 5.8 M 16 X 185 16 X 188 120 68 10.7 4.9 14.5 7.8 OK
Note :- As per Wapda Specification # P-139:80, P-182:91 & P-19:83

Engr. Farhan Engr. Imtiaz-Ur-Rehman


Mechanical Engineer SGI Director (MM) TESCO, Peshawar
SPECIALISTS GROUP INC. LIMITED
TEST REPORT
Client: Tribal Area Electric Supply Company Limited (TESCO) Date:
Purchase Order No: 483-89 CEO/TESCO, Dated: 10-02-2021
Sr.
Desciption Quantity
No.
1 ZM-1 Type Tower w/o Stubs & Cleats 50
2 Stubs & Cleats for ZM-1 200
2 3M Leg Extension for ZM-1 5

HARDWARE GALVINIZING TESTS REPORT AS PER NTDC SPECIFICATION


Proof Load
Bolt Tensile
Sr. Sizes Zinc Coating Thickness (in micron)
Strength Specified Value Remarks
No. (mm) Strength
Bolt Nut Lock Nut Washer kg kg
1 M 16 X 45 65 93 102 82 8097 9431 OK
2 M 16 X 45 70 83 87 82 8260 9621 Zinc Coating OK
Min = 43
3 M 16 X 50 87 67 89 86 8111 9447 OK
microns
4 M 16 X 50 93 97 107 73 8296 9662 Avg = 53 micron OK
5 M 16 X 55 93 84 83 89 8473 9869 OK
Tensile Test
6 M 16 X 55 87 85 83 88 8393 9775 OK
9600 kgs
7 M 16 X 60 84 88 102 74 8327 9699 OK
8 M 16 X 75 93 97 96 84 8042 9367 Proof Load Test OK
9 M 16 X 185 99 102 95 89 8091 9424 OK
10 M 16 X 185 103 110 97 97 8159 9503 OK
7046 kgs
Note :- As per Wapda Specification # P-139:80, P-182:91 & P-19:83

Engr. Farhan Engr. Imtiaz-Ur-Rehman


Mechanical Engineer SGI Director (MM) TESCO, Peshawar
SPECIALISTS GROUP INC. LIMITED
TEST REPORT
Client: Tribal Area Electric Supply Company Limited (TESCO) Date:
Purchase Order No: 483-89 CEO/TESCO, Dated: 10-02-2021

Sr.
Desciption Quantity
No.
1 ZM-1 Type Tower w/o Stubs & Cleats 50
2 Stubs & Cleats for ZM-1 200
2 3M Leg Extension for ZM-1 5

U-BOLT REPORT FOR 132KV TOWER TYPE ZM-01 WITH STUBS, CLEATS & LEG EXTENSIONS

Tensile Strength of Bolt


Sr. No. Description Specified Value Remarks
(Kg)

1 U-Bolt 9985 OK
Tensile Test
V-Shackle = 8,000
2 U-Bolt 10150 OK

Note :- As per Wapda Specification # P-139:80 & P-182:91

Engr. Farhan Engr. Imtiaz-Ur-Rehman


Mechanical Engineer SGI Director (MM) TESCO, Peshawar