Inspection and Tests Plan: OPGW 60mm, 24cores

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Inquiry No. :- Ref. No.

: ITP1904-103
User / Customer : INDONESIA Page No. : 1 of 3
Project Title :-
Document Title :

Inspection and Tests Plan


For
OPGW 60mm2, 24Cores

A Apr. 26, 2019 Issued for Approval D. G. Shin W. H. Kim


Rev. No. Date Descriptions Prepared By Approved By
Ref. No. : ITP1904-103
Rev. No. : A
Page No. : 2 of 3

Type Designation : OPGW 60mm2, 24Cores


Test Items Reference Standard Requirements Sampling

[Aluminum clad steel wire after stranding]

1. Appearance IEC 61232 Shall be good 10% of wires on sampling drums

2. Diameter IEC 61232 2.52±1.5% 10% of wires on sampling drums

3. Tensile strength IEC 61232 Min. 1346.15N/mm2 10% of wires on sampling drums
* Note) The tensile strength of individual wire after stranding shall be not less than 95% of the min. Tensile strength specified for before stranding (1417N/mm2)
according to LSGS-18-PO0135 (The 5% reduction accounts for handling and twisting of wires during stranding process)
4. Elongation at fracture IEC 61232 Min. 1.5% 10% of wires on sampling drums

5. Conductivity at 20℃ IEC 61232 Min. 20.3%IACS 10% of wires on sampling drums

6. Torsion test IEC 61232 Min. 20No. 10% of wires on sampling drums

7. Thickness of aluminum IEC 61232 Min. 0.126mm 10% of wires on sampling drums

[Aluminum alloy wire after stranding]

1. Appearance IEC 60104 Shall be good 10% of wires on sampling drums

2. Diameter IEC 60104 2.52±1.5% 10% of wires on sampling drums

3. Tensile strength IEC 60104 Min. 308.75N/mm2 10% of wires on sampling drums
* Note) The tensile strength of individual wire after stranding shall be not less than 95% of the min. Tensile strength specified for before stranding (325N/mm2)
according to LSGS-18-PO0135 (The 5% reduction accounts for handling and twisting of wires during stranding process)
4. Elongation at fracture IEC 60104 Min. 3.0% 10% of wires on sampling drums

5. Conductivity at 20℃ IEC 60104 Min. 52.5%IACS 10% of wires on sampling drums

6. Wrapping test IEC 60104 Not break 10% of wires on sampling drums
Ref. No. : ITP1904-103
Rev. No. : A
Page No. : 3 of 3

Test Items Reference Standard Requirements Sampling

[Complete OPGW]

1. Appearance IEC 60794-4 Shall be good 10% of drums on shipments


Center: Aluminum-clad steel wire : 1ea
1st Layer: Aluminum-clad steel wire : 5ea
2. Construction IEC 60794-4 10% of drums on shipments
Stainless steel loose tube : 1ea
2nd Layer: Aluminum alloy wire : 12ea
3. Overall diameter IEC 60794-4 Approx. 12.6mm 10% of drums on shipments

4. Lay ratio IEC 60794-4 10 ~ 16times 10% of drums on shipments

5. Outer stranding direction IEC 60794-4 Right-hand (Z) 10% of drums on shipments

6. Weight IEC 60794-4 Nom. 379kg/km 10% of drums on shipments

7. D.C resistance at 20℃ IEC 60794-4 Max. 0.5Ω/km 10% of drums on shipments
8. Attenuation coefficient
[ITU-T G.652D]
10% of drums on shipments
- at 1310 ㎚ ITU-T G.652D Max. 0.34dB/km(Avg.) / 0.35dB/km(Indiv.)
(* 100% of fibers on sampling drums)
- at 1383 ㎚ Max. 0.31dB/km(Avg.) / 0.33dB/km(Indiv.)
- at 1550 ㎚ Max. 0.21dB/km(Avg.) / 0.23dB/km(Indiv.)