PCS-985B - AW Generator-Transformer Unit Relay - NR Electric

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Contact 

us  Login  Sitemap  Worldwide  Online Order  ( 0)

Home About Us News Center Products Solutions Service &Support Careers

Home > Protection, Automation & Control > Protection & Control > Generator Protection

PCS-985B/AW Generator-Transformer Unit Relay

Generator Protection
PCS­985 generator­transformer unit relay can be applied for turbo­
dynamo, gas­turbine, hydro, pumped storage and nuclear power
generator with different connection modes. It supports conventional
CT/VT and ECT/EVT, and provides interfaces for power plant
automation.
Categories
For medium to large generator, two sets of PCS­985 protections can be Protection, Automation & Control
used to achieve duplicated protection configuration. Two PCS­985
protections use different CT groups, and main and backup protection in
- Protection & Control
one PCS­985 share one group of CTs.
· Transmission Line Protection
· Busbar Protection
PCS­985B provides complete electric quantity protection of a turbo­
dynamo or nuclear power generator­transformer unit which usually · Transformer Protection

comprises generator, main transformer, step­ down transformer and · Reactor Protection


Send Inquiry Now exciter or excitation transformer. · Circuit Breaker Protection
PCS­985AW can be applied for a large­scale hydro or pumped storage
· Generator Protection
generator­transformer unit with different connection modes. 
· Feeder Protection

· Motor Protection
Functions Features Download
· Capacitor Protection

· Arc Protection
Generator protection Main Transformer Protection
· Transfer & Synchronization
Unrestraint current differential protection. (87UG) Unrestraint current differential protection for - Automation
87UG provides high speed clearing of stator generator­ transformer unit. (87U) - Digital Substation
phase­to­phase faults, especially for serious fault. Unrestraint current differential protection is used to
- Energy Management
accelerate the trip speed for generator­transformer
Percentage restraint current differential protection. - Power Stability Control
unit inner serious fault. It does not need any block
(87PG)
element, but the setting should be greater than - Measurement
87PG is variable slope differential protection.
maximum inrush current. - Recording
Advanced “asynchronous method” CT saturation
detection algorithms can prevent 87PG from mal Percentage restraint current differential protection - Accessories

operation caused by CT saturation during eternal for generator­transformer unit. (87P) - Software Kit


fault. The fast detection of differential CT circuit­ 87P can protect the generator, main transformer,
break can avoid malfunction due to the abnormal auxiliary transformer, and exciter or excitation HVDC & FACTS
CT circuit. transformer. It is based on a variable slope
Renewable & BESS
percentage differential restraint characteristic with
DPFC differential protection. (87DG)
inrush and overexcitation inhibits. It includes two
87DG reflects only deviation components of
different inrush current detection principles: Related Links
differential current and restraint current, it will not
second harmonic restraint principle and waveform
be affected by load current. It can detect slight fault Thermal Power Plant
distortion discrimination principle. CT saturation
within the generator.
detection element can prevent maloperation due Hydro Power Plant
Split phase transverse differential protection. to CT saturation during external fault.
(87SG) Nuclear Power Plant
Unrestraint current differential protection. (87UT)
87SG is mostly utilized for inter­turn faults of hydro
Unrestraint current differential protection is used to Pumped Storage Power Plant
generators.
accelerate the trip speed for transformer’s inner
PCS-985BT/TW/TS/T Transformer
Incomplete differential protection 1. (87IG) serious fault. It does not need any block element,
Relay
87IG is mostly utilized for hydro generators, and it but the setting should be greater than maximum
adopts currents of the terminal and one of the inrush current. RCS-985U Voltage Injector
branches at neutral point to detect stator inter­turn
Percentage restraint current differential protection. PCS-985RE Rotor Earth-Fault Relay
fault and phase­to­phase fault.
(87PT)
PCS-985G/GW/BG/RS Generator
Incomplete differential protection 2. (87IG) Percentage restraint current differential protection
Relay
87IG is mostly utilized for hydro generators, and it is based on a variable slope percentage
adopts currents of the terminal and one of the differential restraint characteristic with inrush and PCS-985GI Generator Relay
branches at neutral point to detect stator inter­turn overexcitation inhibits. It includes two different
fault and phase­to­phase fault. inrush current detection principles: second PCS-985TI Transformer Relay
harmonic restraint principle and waveform
High sensitive transverse differential protection.
distortion discrimination principle. CT saturation
(87S) detection element can prevent maloperation due
87S adopts frequency tracking, digital filter and full to CT saturation during external fault.
cycle Fourier transformation, the filtration ratio of
DPFC differential protection. (87DT)
third harmonic component is able to exceed 100. It
87DT reflects only deviation components of
is installed on a connection between two neutral
differential current and restraint current, it is not
points of a generator, and mainly used for inter­
affected by the load current. It can detect slight
turn faults of generator’s stator winding, open
fault within transformer.
circuit fault of branches and short circuit fault
between phases. Restricted earth­fault protection. (REF) REF
extends protection coverage to the neutral point of
Longitudinal zero­sequence overvoltage
wye­ connected windings where fault currents may
protection for inter­ turn fault. (59N)
be below the pickup of the main transformer
59N uses the zero­sequence voltage from the
differential elements.
open­ delta winding of dedicated VT at the
generator terminal. It adopts frequency tracking, Voltage controlled overcurrent protection at HV
digital filter and full cycle Fourier transformation, side. (50P/51P)
the filtration ratio of third harmonic component is 2 stages of voltage controlled overcurrent
able to exceed 100. Within the frequency tracking protection at HV side are used for phase­to­phase
range the protection can only respond to the backup protection of the main transformer. Of
fundamental wave component. which, voltage controlled element can be enabled
or disabled by logic setting.
DPFC directional protection for inter­turn fault.
(7/67) Phase­to­phase impedance protection at HV side.
DPFC directional protection for inter­turn fault has (21P)
default settings, and the sensitivity is about 3V of Three kinds of impedance characteristics can be
longitudinal zero­ sequence voltage. selected, i.e. full impedance, directional
impedance and shifted impedance.
Calculated longitudinal residual overvoltage
protection for inter­turn fault. (59N) Ground overcurrent protection at HV side.
Dedicated VT is not needed for this protection. (50G/51G)
Calculated longitudinal zero­sequence voltage Ground overcurrent protection at HV side has two
used by this protection is composed of zero­ stages, with separate time delay of each stage.
sequence voltages of generator terminal and
Directional zero­sequence overcurrent protection
neutral point.
at HV side. (67G)
Phase­to­phase impedance protection. (21P) The directional element uses calculated zero­
Two stages impedance protection is equipped at sequence current and calculated zero­sequence
the generator terminal as phase­to­phase backup voltage. The direction points to the system side,
protection. Full impedance, directional impedance definitely with the reach angle of 75。.
or shifted impedance characteristics can be
Inverse­time zero­sequence overcurrent protection
selected for these two stages.
at HV side. (51G)
Voltage controlled overcurrent protection. Four IEC inverse­time operating characteristics are
(50P/51P) provided, and users can select according to their
There are two stages with two separate time needs.
delays. Stage 1 is used to trip bus coupler breaker
Gap zero­sequence overvoltage/overcurrent
or other breakers, and stage 2 is to shut down the
protection at HV side.
generator. Composite voltage element consists of
Gap zero­sequence protection at HV side is used
phase­to­phase undervoltage element and
for the transformer with neutral point grounded
negative overvoltage element.
through a gap or small reactance.
Fundamental zero­sequence voltage protection for
Definite­time over­excitation protection. (24)
stator earth fault. (59G)
Definite­time over­excitation protection consists of
59G reacts to the magnitude of zero­sequence
two stages, one is for alarm and the other is for
voltage from the generator neutral point. It adopts
tripping. Both of these time delays can be set
frequency tracking, digital filter and full cycle
independently.
Fourier transformation, the filtration ratio of third
harmonic component is able to exceed 100. Within Inverse­time over­excitation protection. (24)
the frequency tracking range the protection can Inverse­time over­excitation protection realizes
only respond to the basic wave component. This inverse­time characteristic by linear processing on
protection consists of two stages: sensitive stage given inverse time operation characteristic,
and insensitive stage (high setting stage). obtaining multiple of over excitation by
calculations, and calculates corresponding
Zero­sequence overcurrent protection for stator
operation time delay by sectional linear insertion. It
earth fault. (51G)
reflects heat accumulation and radiation.
51G detects the zero­sequence current from the
neutral point of the generator, and operates when Pole discrepancy protection at HV side. (62PD)
the current is over the setting. It is very sensitive for Pole discrepancy protection at HV side adopts
stator earth fault. phase current, negative­sequence current, and
zero­sequence current as criteria to detect the
Third harmonic overvoltage ratio protection for
abnormal situation of Pole discrepancy.
stator earth fault. (27/59TN)
27/59TN covers about 20~25% of the stator Breaker flashover protection.
winding near the neutral point of the generator. Before the generator­transformer unit connecting
with the system, when the difference of phase
Third harmonic overvoltage differential protection
angle between bus voltage and generator voltage
for stator earth fault. (87TN)
is around 1800, breaker flashover is possible.
87TN is enabled automatically when the generator
Breaker flashover protection is used in case of this
is connected with the system and if the load current
situation, and one phase and two phase flashover
exceeds 0.2Ie (generator rated current) it will only
are considered.
issue an alarm. It will protect 100% of the stator
winding. Zero­sequence voltage alarm at LV side. (59G)
Zero­sequence voltage alarm at LV side can be
100% stator earth­fault protection with voltage
provide for the main transformer as the supervision
injection. (64S, with RCS­985U)
of earthing fau when GCB is not closed.
Using the 100% stator earth­fault protection based
on sub­harmonic injection, a 20Hz voltage from Overload alarm. (49)
RCS­985U is injected to detect earth faults at any
Initiating cooling. (49)
point across the winding. 64S provides a 100%
stator earth­fault protection during generator start­
up, running and stopped conditions. The solution
includes: earthing resistance criterion, earthing
Auxiliary Transformer
current criterion and external voltage circuit Unrestraint current differential protection. (87UT)
monitoring.
Percentage restraint current differential protection.
Rotor one­point earth­fault protection with ping­
(87PT)
pong principle. (64R1)
64R1 adopts the switch­over sampling principle, Voltage controlled overcurrent protection at HV
and detects any insulation resistance between side. (50P/51P)
rotor winding and the axis. It includes two stages:
Voltage controlled overcurrent protection of branch
sensitive stage and regular stage.
1 at LV side. (50P/51P)
Rotor two­point earth­fault protection with ping­ Voltage controlled overcurrent protection of branch
pong principle. (64R2) 2 at LV side. (50P/51P)
If 64R1 is used for alarm only, when the earth
resistance is less than the regular stage setting, it Zero­sequence overcurrent protection of branch 1

will automatically switch into 64R2 with a time at LV side. (50N/51N)
delay.
Zero­sequence overcurrent protection of branch 2
Rotor earth­fault protection with voltage injection. at LV side. (50N/51N)

(64R) Overload alarm. (49)
Based on the leading­out mode of the rotor
windings, 64R has two injection styles: double­ Initiating cooling. (49)
ends injection and single­end injection. The
switching cycle of the injected power supply can
be adjusted in accordance with the capacitor Miscellaneous
between rotor winding and ground. 64R can reflect
Mechanical protection. (MR)
the decline of insulation resistance between
generator rotor and shaft by real­time calculating Fault detector. (FR)
one­point earth resistance of rotor, with or without
Voltage and current drift auto adjustment.
excitation voltage.
VT circuit supervision. (VTS)
Definite­time stator overload protection. (49S)
Definite­time stator overload protection has two CT circuit supervision. (CTS)
stages: one for alarm and the other for tripping.
CT saturation detection. (CTS)
Inverse­time stator overload prot ection. (49S)
Inrush current detection. (VTS)
Inverse­time stator overload protection consists of
three parts: low­setting initiator, inverse­time part Self diagnostic.
and upper­limit definite­time part.
GPS clock synchronization.
Definite­time negative­sequence overload
Fault Recorder.
protection. (46)
Definite­time negative­sequence overload IEC61850 MMS & GOOSE for station bus
protection has two stages: one for alarm and the
IEC60870­5­103 protocol
other for tripping.
MODBUS protocol
Inverse­time negative­sequence overload
protection. (46) DNP 3.0 LAN0
Inverse­time negative­sequence overload
protection consists of three parts: low­setting
initiator, inverse­time part and upper­limit definite­
time part.

Loss­of­excitation protection. (40)
Loss­of­excitation protection represents abnormal
operation of the generator due to excitation failure.
It includes 3 criteria: undervoltage criterion, stator­
side impedance criterion and rotor­side criterion.
The voltage at the generator terminal and neutral
point can be selected as undervoltage criterion.
Static stability impedance circle and asynchronous
impedance circle can be selected as stator­side
impedance criterion.

Out­of­step protection. (78)
Out­of­step protection calculates impedance
element by positive­sequence voltage and current,
the operation characteristic of out­of­step
protection comprises three parts: lens part,
boundary part and reactance line part.

Overvoltage protection. (59)
Two stages of overvoltage protection can be used
for tripping or alarming.

Undervoltage protection. (27)
Undervoltage protection reflects the reduction of
three phase­to­phase voltages, and it is locked by
the binary input of synchronous condenser
operation.

Definite­time over­excitation protection. (24)
Definite­time over­excitation protection consists of
two stages: one is for alarm, the other is for
tripping. Both of these time delays can be set
independently.

Inverse­time over­excitation protection. (24)
Inverse­time over­excitation protection realizes
inverse­time characteristic by linear processing on
given inverse time operation characteristic,
obtaining multiple of over excitation by calculation,
and calculating corresponding operation time
delay by sectional linear insertion. It reflects heat
accumulation and radiation.

Reverse­power protection. (32R)
Reverse power protection is provided to detect
generator motoring in order to protect the prime
mover from damage.

Low forward power protection. (32F)
Low forward power protection responds to low
forward power flow. it can be released by the
binary input for non­ emergency shutoff or the
binary input indicating that the valve of the steam
turbine is in the closed position.

Sequential tripping reverse­power protection.
(32R)
Sequential tripping reverse­power protection is
used when the steam valve of the turbine has been
closed first before tripping.

Underfrequency protection. (81U)
Underfrequency protection will issue an alarm or
trip if the accumulated time delay or once duration
time delay exceeds its setting.

Overfrequency protection. (81O)
Overfrequency protection will issue an alarm or trip
when it operates.

Inadvertent energization protection. (50/27)
Considering security of the protection, both
currents from the generator terminal and neutral
point are used as criteria.
Startup/shutdown protection of differential current.
(SS)
Startup/shutdown protection of differential current
is used for phase­to­phase fault of the generator.

Startup/shutdown protection of zero­sequence
voltage. (SS)
Zero­sequence overvoltage is utilized for stator
earth fault of the generator during
Startup/shutdown.

Breaker failure protection. (50BF)
When there is an internal fault of the generator, the
protection operates to trip but the breaker at the
generator terminal fails, it needs to initiate breaker
failure protection and trip adjacent breakers in
time.

Low­frequency overcurrent protection. (50LF)
Low­freuquency overcurrent protection is used for
phase­to­ phase fault of the generator during
Startup/shutdown.

Excitation Transformer/Excitor
Protection

Differential protection. (87E)
Differential protection consists of unrestraint
differential protection and variable slop differential
protection. It adopts 2nd, 3rd, 5th harmonic current
detection and blocking method.

Overcurrent protection. (50P/51P)
Overcurrent protection includes two stages used
as backup protection.

Overload protection. (49)
Overload protection consists of definite­time and
inverse­ time excitation winding overload
protection.

 
 
 

Who Are We What Are We Doing Whom Do We Serve Follow Us


·Our News ·Protection, Automation & Control ·Power Grids
·Our Culture ·FACTS & HVDC ·Power Plants    
·Contact Us ·Renewable Energy Generation ·Industrials
·Quality Control

Copyright NR Electric Co., Ltd. 2001­2016. All Rights Reserved.

You might also like