Visit Report No.01
Visit Report No.01
Visit Report No.01
NACC-JW-01
Mr.Hatem
Work in progress
Work Progress
and Site
Conditions
work continue on demolish.
Site Conditions
Remove all loose material or dust before using bonding agent (photo 2).
As per our conversation a full sample will be finished on next Saturday (photo 4).
Photoes
Total (SR)
THANK YOU FOR YOUR BUSINESS
Photo (1)
Photo (3)
Photo (5)
Photo (7)
Photo (9)
Monday, April 12, 2021
QUT-RU-AHC-2256
10,000
APPROVED BY
NAME :
SIGNATURE :
Photo (2)
Photo (4)
Photo (6)
Photo (8)
Photo (10)
CHECK DESIGN AND CALCULATIONS REPORT FOR
EXISTING ARGON TANK FOUNDATION DUE TO NEW
LOAD APPLIED ,REV.01
Perpared by:
Eng'r / Hany Mohammed
Senior structural engineer
17.02.2021
STRUCTURAL DESIGN ANALYSIS REFERANCE
A. DESIGN CRITERIA
1.0 INTRODUCTION
This specifications list the design criteria used while performing calculations for the design
check of ARGON Tank Foundation.
Briefly described herein are the design approach adopted, various codes used,
materials properties, loads and soil properties. This criterion complies with all relevant
Intenational Code and Standards.
Check if the new applied load (New tank = 85 ton) due to increase tank capacity could be
suppored safely with existing raft foundation.
1.3 MATERIALS
1.3.1 Concrete:
Concrete cylinder compressive strength at 28 days shall be, f'c = 28 Mpa.
for concrete pavement and f'c = 17 Mpa for blinding concrete.
1.3.2 Cement:
Portland cement shall conform to ASTM C150. Sulphate resistant cement Type V shall
be used for concrete pavement.
1.3.3 Reinforcing Steel Bars:
All reinforcing steel bars shall conform to ASTM A615M grade 60 deformed bars
with fy = 414 Mpa.
Plan
STRUCTURAL DESIGN ANALYSIS REFERANCE
C. Calculate Wind Load:
LOAD DIAGRAM
Therefore, qz= 0.613 x 1.04 x 1.00 x 0.95 x 432 / 1000 = 1.12 KN/M2
H / D = 3.15
D√qz = 103.92
Cf = 0.90 Figure 29.5-1 Figure 29.5-1
Af = 9.00*3.00 = 27 M2
R.M. - O.M.
X= = 1.21 m
ΣP
L
e= -X = 0.34 m
2
e < L / 6, Therefore the Resultant Force is within the middle third
R.M. - O.M.
X= = 1.43 m
ΣP
L
e= - X = 0.12 m
2
e < L / 6, Therefore the Resultant Force is within the middle third
p(max.)/p(min.) = ΣP / AF ± Mc / I
Where:
AF = Area of Footing = L x B = 9.61 M2
M = O.M. = 118.00 KN-M
c = L / 2 = 1.55 M
I = B x L3 / 12 = 7.70 M4
p(max.) is greater than the allowable and even, as per code: If the Vertical Load is
combined with Wind Load, the Allowable Soil Bearing Capacity could be increased by
33 %, Therefore 60 x 1.33 = 79.80 KN/M2 < p(max.). Unsafe
F. 1. Summary Report
2. Conclusion
1. The existing tank foundation is not capable of carrying extra loads due
to Unsafe soil pressure that could lead to differtial settlement and structure failure.
2.To accept extra load , Soil bearing capacity must be improved by replacing the poor soil
with A-1-a Material and apply compaction Test or increase foundation dimensions .
INVOICE.
Project L 150 UPGRADE PROJECT DAMMAM Date: Monday, April 12, 2021
1 DESIGN CHECK & REPORT FOR TANK FOUNDATION 2000 NO VAT. REGISTERATION
NOTES:
1.ADDITIONAL SUPERVISION VISIT CHARGES 1000 SR/VISIT .
2.FIRST INVOICE TO BE SUBMITTED AFTER ITEM NO.01 COMPLETION.
2.SECOND INVOICE TO BE SUBMITTED AFTER ITEM NO.02 COMPLETION.
3 ANALYSIS AND DESIGN FOR PUMP FOUNDATION. 2,000 SITE ALREADY INSPECTED
4 ANALYSIS AND DESIGN FOR COOLING TOWER SUPPORT 2,000 SITE ALREADY INSPECTED
FOUNDATION.
5 ANALYSIS AND DESIGN FOR WATER PIPELINES SUPPORT. 2,000 SITE ALREADY INSPECTED
NOTES:
1.ADDITIONAL SUPERVISION VISIT CHARGES 1000 SR/VISIT .
2.SINGLE INVOICE TO BE SUBMITTED AFTER EACH JOB COMPLETION.