‘SIEMENS Example fain ince oven SIMATIC PCS 7 a iS Procese description (using the equipment in Group 1, Unit Af as an example): ‘Component X The reactor must first be empty and cold. Valve 1U101 is used to fill this component upto the L1=20% Lmax level. Mixer ‘The mixer motor 1£101 is tured on. ‘Component ¥ Valve 1U102 is used to mix this second component until the L2=80% Lmax level Is reached. Heating ‘The mixture is heated up to 90°C. The temperature controller 1T101 must maintain this temperature for at least two minutes, Draining After the heating is turned off, product Z must be drained completely, and the mixor 1£101 must be tured off In adaition ‘The fil eve! is monitored (1L7101 and 11102). The inlet valves 1101 and 1U102 must be closed when the upper level mit (Lmax) is reached. The drain valve must be closed when the reactor is empty. There must be a signall when the level ‘monitor responds. Both the temperature controller and the mixer must be ‘operated and monitored in the contol room. Training Contor “SIMATIC PCS 7 System Training orate and Dives Page 2 Configuration