Investigation On The Heating Performance of The Heat Pump Withwaste Heat Recovery For The Electric Bus

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

Renewable Energy 152 (2020) 835e848

Contents lists available at ScienceDirect

Renewable Energy
journal homepage: www.elsevier.com/locate/renene

Investigation on the heating performance of the heat pump with


waste heat recovery for the electric bus
Xinxin Han a, b, c, Huiming Zou a, *, Jiang Wu a, Changqing Tian a, c, Mingsheng Tang a,
Guangyan Huang a, c
a
Beijing Key Laboratory of Thermal Science and Technology, Key Laboratory of Cryogenics, Technical Institute of Physics and Chemistry, CAS, Beijing, 100190,
China
b
Henan Polytechnic University, Jiaozuo, 454000, Henan, China
c
University of Chinese Academy of Sciences, Beijing, 100049, China

a r t i c l e i n f o a b s t r a c t

Article history: Efficient heating system is critical for electric vehicles to extend the driving range. In this paper, an air
Received 17 June 2019 source heat pump system with waste heat recovery (WHR) for the electric bus was proposed to improve
Received in revised form the heating performance. According to the experimental results of the prototype, it’s found that the
17 December 2019
pressure drop of waste heat exchanger (WHX) has great effects on the heating performance and the heat
Accepted 17 January 2020
exchanger is required to be optimized. The simulation model of this series system was developed and
Available online 20 January 2020
validated to study the heating performance of the series waste heat recovery system with low pressure
drop WHX. The simulation results showed that heat recovery can improve the heating performance at
Keywords:
Heat pump
the ambient temperature of 5  C. Compared with the vapor injection heat pump without WHR, the
Waste heat recovery heating capacity and COP of the heat pump at 2 kW waste heat were increased by 1.61% and 1.38%,
Vapor injection respectively. The improvements of heating capacity and COP at 6 kW waste heat were 5.12% and 2.56%,
Electric bus respectively. As the ambient temperature is lower than 0  C, the heating performance of heat pump
system with 2 kW waste heat is better than that of system without WHR. However, as the ambient
temperature rises, the heating performance of heat pump with WHR becomes worse.
© 2020 Published by Elsevier Ltd.

1. Introduction heat pump can significantly reduce the power consumption


compared with PTC heaters. Heat pumps using some other re-
Under the background of global warming and energy shortage, frigerants were also studied. Wang [6] tested the heating perfor-
electric vehicles (EVs) have attracted lots of attention. The cabin mance of a single-stage CO2 heat pump system with internal heat
heating is a big challenge for EVs because no waste heat from in- exchanger for EVs. Wang’s experimental results suggested that the
ternal combustion engine can be used. Although electric heaters, coefficient of performance (COP) and heating capacity achieved
such as Positive Temperature Coefficient (PTC) heater, can be were 3.1 and 3.6 kW at 20  C indoor and outdoor temperatures,
applied for heating supply, its low efficiency dramatically reduces respectively. The COP was 1.7 at 20  C outdoor temperature and
the driving mileage in winter. Although Positive Temperature Co- 20  C indoor temperature. Yu [7] proposed a CO2propane auto
efficient (PTC) heater can be applied for cabin heating, its low ef- cascade heat pump system for EVs, and his theoretical calculation
ficiency reduces the driving mileage by 20%e60% in winter [ [1,2]]. showed that the COP of transcritical auto cascade heat pump sys-
Therefore, the efficient cabin heating solution is critical for tem at 0.8 CO2 mass fraction was 2.7 and 12.3% higher than that of
extending driving mileage. CO2 singlestage heat pump at the ambient temperature of 20  C.
Heat pumps used in EVs have become a hot research topic due to Liu [8] investigated the heating performance of an automobile heat
their high efficiency. The studies on R134a heat pump for EVs were pump using low-GWP refrigerant R290, and the heating perfor-
conducted extensively [ [3e5]], and these studies indicated that a mance of heat pump systems with different refrigerant were also
compared, including R290, R134a, R1234yf and CO2. Liu’s experi-
ments showed that R290 system had the best performance when
* Corresponding author. the ambient temperature was above 10  C, while the CO2 system
E-mail address: zouhuiming@mail.ipc.ac.cn (H. Zou).

https://doi.org/10.1016/j.renene.2020.01.075
0960-1481/© 2020 Published by Elsevier Ltd.
836 X. Han et al. / Renewable Energy 152 (2020) 835e848

Nomenclature Subscripts
suc suction of compressor
inj injection of compressor
Symbols dis discharge of compressor
p pressure, pa eva evaporator
h enthalpy, kJ/kg c condenser
t temperature,  C v volume
m mass flow rate, g/s mec mechanical
Q heat transfer rate, kW mot motor
COP coefficient of performance i indicated power
v specific volume, m3/kg c input power
k polytropic exponent sec section
r refrigerant
Greek symbols a air
h efficiency
a convective heat transfer coefficient, W/(m2,K) Abbreviations
d thickness, m VI vapor injection
l thermal conductivity, W/(m,K) WHR waste heat recovery
D difference WHX waste heat exchanger
r density, kg/m3 EEV electronic expansion valve
g specific heat, kJ/(kg,K) IHX internal heat exchanger
TS thermal storage

had a little advantage when the ambient temperature was 20  C. non-injection system at the ambient temperature of 10  C,
Zou [9] experimentally studied a heat pump with secondary fluid respectively. Qin et al. [17] experimentally studied the VI heat
circle using R1234yf as the refrigerant. It was found that the heating pump for EVs at outdoor temperature of 20  C. The heating ca-
performance of R1234yf system was very close to that of R134a pacity of VI heat pump was increased by 28.6%, compared with the
system and the heating capacity of the test system was decreased traditional single-stage compression heat pump. Han [18] devel-
by around 37.2% as ambient temperature dropped from 0  C oped a VI heat pump using R410a refrigerant for an electric bus and
to 10  C. experimentally investigated the heating performance under
Applying waste heat recovery (WHR) is a good method to different working conditions. When the working temperature
improve the heating performance for heat pumps in EVs. Ahn [10] conditions were 20  C/20  C and compressor speed was set to
experimentally investigated the heating performance of a dual 85 Hz, the results showed that using a VI heat pump increased COP
source heat pump for electric vehicles at three different operation to 1.6, which was a 14.5% increase compared to the no VI system.
modes: air source-only, waste heat-only and dual heat source. The In this paper, a heat pump combining waste heat recovery and
results showed that heat pumps in dual source mode had higher vapor injection for electric bus was proposed. The heating perfor-
heating performance than that of single source mode at the mance of this system at different ambient temperatures and
ambient temperature of 0  C. An alternating single source mode different waste heat was investigated experimentally and
was proposed for low ambient temperature condition because little numerically.
heat was absorbed from air source in the dual source heat mode.
Tian [11] proposed an integrated thermal management system for 2. System description and experimentation
EVs, considering cabin thermal comfort, battery pack cooling and
electric motor cooling simultaneously. The heat exchanger of bat- 2.1. System description
tery pack/electric motor circuit was connected to the evaporator of
heat pump in parallel. The cooling and heating performance of this The heat pump system for waste heat recovery normally in-
parallel system was investigated experimentally and numerically. cludes two types: series system and parallel system. The two sys-
The heating COP of heat pump system was improved by 25.55% tems can both increase the suction pressure and improve the
with the increase in waste heat from 0 W to 1000 W and the driving heating capacity, however, they have different characteristics.
range was extended up to 31.71% compared with PTC heaters. Ahn Table 1 lists the comparison of the two systems. The series system
[12] proposed a dual source dehumidifying heat pump for EVs with has only one evaporation branch and one EEV, and thus its control
a waste heat exchanger connected to outdoor heat exchanger in is very simple. The parallel system has two evaporation branches
parallel. The experimental results indicated that the heating ca- and two EEVs, and therefore the system and its control is relatively
pacity and COP of dual source dehumidifying heat pump were complex. Moreover, energy loss occurs in the mixing process of the
increased by 15.8% and 5.2%, respectively, compared with those of two evaporation branches for the parallel system. The main
air source dehumidifying heat pump. advantage of parallel system is that the WHX branch can be
Vapor injection (VI) is considered as a promising solution to adjusted independently and it can be closed if no waste heat can be
improve the heating performance of heat pump at low ambient used. The WHX branch in series system can’t be closed unless there
temperature [ [13e15]]. The studies on VI application for EVs were is a bypass branch. From the point of view of pressure drop, the
carried out by some researchers. Jongho Jung et al. [16] developed a parallel system exhibits better performance. The refrigerant flows
simulation model of VI heat pump for EVs and the heating per- through two heat exchangers in series in the evaporation process,
formance was investigated. The COP of VI heat pump with single- which leads to the series system has a greater pressure drop. In the
and dual-injection ports were 7.5% and 9.8% higher than that of low ambient temperature, the VI is normally used to enhance the
X. Han et al. / Renewable Energy 152 (2020) 835e848 837

Table 1
The comparison between series and parallel system.

4-6 evaporation in evaporator


4-5 evaporation in evaporator
5-7 evaporation in WHX
5-1 evaporation in WHX
Series system Parallel system

It has one EEV (3e4) It has two EEVs (3e4, 3e5)


Simple system and control relatively complex system and control
No mixing process and no energy loss Energy loss occurs in the mixing process
The refrigerant side branch of WHX can’t be closed The refrigerant side branch of WHX (4e6) can be completely closed,
unless there is a bypass branch. if no waste heat can be used
The pressure drop in the evaporation process is relatively large The pressure drop in the evaporation process is relatively small
The inlet quality of WHX is high The inlet quality of WHX is low
The system is compatible with the VI system The system becomes very complex as combined with the VI system

heating performance. The series system is easy to combine with the tested by two Coriolis flow meters with accuracy of ±0.2%.
VI system, whereas integration with the parallel system would be The prototype was tested under the ambient temperatures of
more complex. Therefore, series system is more applicable for 7  C, 0  C, 5  C and 10  C, whereas the indoor temperature was
heating in low temperatures and it is chosen in this paper. set at 20  C. The frequency of compressor was set as 60 Hz at the
ambient temperatures of 7  C, 0  C, 5  C and 10  C. The indoor
and outdoor air flow rate were set as 4000 m3/h and 7000 m3/h,
2.2. Experimental set up
respectively. The waste heat was set as 2 kW, 4 kW and 6 kW. The
total waste heat from electric motor, motor controller, battery and
Fig. 1(a) shows the flowchart of the heat pump system with
inverters for a 10e12 m electric bus at high velocity is about 6 kW.
WHR for electric bus proposed in this study. The system can operate
Thus, the range of waste heat in our paper is set as 0e6 kW. The
in cooling mode or heating mode by switching four-way reversing
opening of EEV1 and EEV2 were adjusted according to the super-
valve. In cooling mode, the refrigerant in WHR absorbed the heat
heat of suction refrigerant and injection refrigerant, respectively.
from the battery pack to maintain an appropriate temperature
The suction superheat was set as 3  C and the injection superheat
range, whereas in heating mode, the refrigerant absorbed the heat
was 1  C.
from the battery pack or the electric motor (EM) to improve cabin
The heating capacity of heat pump was evaluated from air side
heating. In this system, the WHX was connected to the evaporator
as given in Eq. (1). The COP of heat pump was calculated by Eq. (2),
in series. The adjustment and control of the series system was
in which the electricity power refers to compressor input power.
simpler than the parallel system.
The uncertainties of heating capacity and COP were calculated as
The main components of this system include indoor and out-
±5.09% and ±5.11%, respectively, according to Moffat’s equations
door heat exchanger (Indoor HX, Outdoor HX), scroll compressor
[19].
with injection port, electronic expansion valve (EEV) in the main
branch and the VI branch (EEV1, EEV2), internal heat exchanger  
Qh ¼ ma;c ,cp , ta; out  ta;in (1)
(IHX), gas-liquid separator, four-way reversing valve and waste
heat exchanger (WHX). The WHX was downstream of the evapo-
rator either in the cooling mode or the heating mode, because it’s Qh
COP ¼ (2)
placed between four-way reversing valve and gas-liquid separator. Pcomp
The WHX can be bypassed by switching V1, V2 and V3; the VI
branch can be turned on/off by controlling EEV2. Thus, four
different heating modes of the system can be realized: VI/WHR, VI/ 2.3. Experimental results
no WHR, no VI/WHR, no VI/no WHR. Table 2 details the flow paths
of the four modes. Fig. 2 shows the heating performance of heat pump with VI and
Based on the series system, an experimental unit for an electric without VI. The heating capacity of heat pump with VI is higher
bus was developed and Table 3 listed the detail and parameters of than that without VI at different ambient temperatures. This is
the main components. The heating performance of this prototype mainly because the discharge mass flow rate is increased greatly
was measured in the psychrometric test room, as shown Fig. 1(b). due to injecting refrigerant into the compressor during the
The detail test points can be seen in Fig. 1(a). The temperature and compression process. However, the COP doesn’t always have
pressure were measured by T-type thermocouples and pressure advantage. Compared to heat pump without VI, the COP of heat
transducers respectively, with accuracy of ±0.5  C and ±0.5% pump with VI is increased at low ambient temperature such
respectively. The mass flow rate of main branch and VI branch were as 10  C and 5  C, while it’s decreased at 0  C and 7  C.
838 X. Han et al. / Renewable Energy 152 (2020) 835e848

(a) The flowchart

(b) The experimental prototype

Fig. 1. The flowchart and experimental prototype of the heat pump system with WHX.

Table 2
The flow path of four different operation modes in heating.

Operation mode Valves switching Flow path

VI/WHR EEV2 on, V1 off, V2 and V3 on CompressorFour-way valveIndoor HX: (1)


IHXEEV1Outdoor HX Four-way valveWHXGas-liquid separatorCompressor;(2)
EEV2IHXCompressor
VI/no WHR EEV2 on, V1 on, V2 and V3 off CompressorFour-way valveIndoor HX: (1)
IHXEEV1Outdoor HX Four-way valveGas-liquid separatorCompressor;
(2)
EEV2IHXCompressor
no VI/WHR EEV2 off, V1 off, V2 and V3 on CompressorFour-way valveIndoor HXIHXEEV1Outdoor HX Four-way
valveWHXGas-liquid separatorCompressor
no VI/no WHR EEV2 off, V1 on, V2 and V3 off CompressorFour-way valveIndoor HXIHXEEV1Outdoor HX Four-way valveGas-liquid
separatorCompressor

Fig. 3 shows the experimental results of the series WHR heat capacity is mainly related to the decrease of suction pressure
pump with VI. Fig. 3(a) shows the heating capacity and suction caused by the high pressure drop of WHX. Fig. 3(b) shows that the
pressure. The heating capacity of system with WHX was less than pressure drop across the outdoor HX was not sensitive to the mass
that of system without WHX as waste heat varied from 2 kW to flow rate, however, the pressure drop across the WHX significantly
6 kW at the ambient temperature of 5  C. Ahn’s experimental varied with the mass flow rate. Moreover, the pressure drop of the
results [10] showed the heating capacity and COP of heat pump WHX was obviously higher than that of outdoor HX at the same
using waste heat can be improved. Here the decrease of heating mass flow rate. That’s because the WHX was placed downstream of
X. Han et al. / Renewable Energy 152 (2020) 835e848 839

Table 3
Specifications for major components of the prototype.

Components Specifications

Compressor Type: horizontal DC inverter scroll compressor


Displacement: 80 CC
Frequency controllability: 30e120 Hz
Refrigerant: R410a
Indoor HX Tube/fin material: copper/aluminum
Outer diameter of tube: 9.52 mm
Rows and columns: 7 rows, 8 columns, and 2 groups
Dimension: 1300 mm (width), 180 mm (height), 179 mm (thickness)
Outdoor HX Tube/fin material: copper/aluminum
Outer diameter of tube: 7 mm
Rows and columns: 6 rows and 40 columns
Dimension: 1400 mm (width), 109 mm (height), 840 mm (thickness)
IHX Type: plate heat exchanger
Material: copper
Plate number: 2 groups and each group 40 pieces
Dimension: 77 mm (width), 207 mm (height), 100 mm (thickness)
WHX Type: plate heat exchanger
Material: copper
Plate number: 40 pieces
Dimension: 77 mm (width), 153 mm (height), 75 mm (thickness)
EEV1 (main branch) Type: electronic expansion valve
Control steps: from 0 to 500
Tube diameter: 3.2 mm
EEV2 (VI branch) Type: electronic expansion valve
Control steps: from 0 to 500
Tube diameter: 2.2 mm

25 4.0
Heating capacity (kW)

non-inj non-inj
inj 3.5 inj
20
COP

3.0
15
2.5

10 2.0
-15 -10 -5 0 5 10 -15 -10 -5 0 5 10
Ambient temperature ( ) Ambient temperature ( )

(a) Heating capacity (b) COP

Fig. 2. The heating performance of heat pump with VI and without VI.

1.6 20 5.0
Pressure drop p (bar)

WHX Qh psuc 5 C 4.8


Suction pressure (bar)
Heating capacity (kW)

1.2 Outdoor HX 15 4.6


0.8 4.4
10
4.2
0.4
5 4.0
0 3.8
0.02 0.03 0.04 0.05 0.06 0.07
0 3.6
Mass flow rate of main branch (kg/s) no WHX WHX2kW WHX4kW WHX6kW

(a) Pressure drop (b) Heating capacity

Fig. 3. Experimental results of the series heat pump system with WHX.

the outdoor HX and the refrigerant quality defined as the mass pressure and the deterioration of heating performance. In order to
percentage of dry steam per kilogram of wet steam in WHX was investigate the heating performance of this series WHR heat pump
higher. Compared with the system without WHX, the great drop of system with low WHX pressure drop, the simulation model of this
WHX pressure resulted in the decrease of compressor suction system was developed.
840 X. Han et al. / Renewable Energy 152 (2020) 835e848

6 specific volume and enthalpy at point 3 can be calculated as


follows:
5 4 v3 ¼ v2 msuc

msuc þ minj

(6)
Pressure (MPa)

4   
h3 ¼ msuc h2 þ minj h5 msuc þ minj (7)
5
3 where, msuc and minj are suction mass flow rate and injection mass
3
flow rate, respectively.
2 2 Based on mass conservation law, the discharge mass flow rate
mdis can be calculated as:
1
1 mdis ¼ msuc þ minj (8)
0 The suction mass flow rate can be calculated as follows:
200 300 400 500 600
n,V
Enthalpy (kJ/kg) msuc ¼ hv (9)
60,vsuc
Fig. 4. Pressure-enthalpy diagram of the compressor model.
where, V is the compressor displacement, n is compressor speed,
vsuc is the specific volume at suction point, hv is volumetric effi-
3. Numerical modeling and validation ciency, which can be calculated by the following fitting formula:

3.1. Modeling of compressor hv ¼0:81490:006502rp þ2:42e5 n0:003103r2p þ1:231e5 nrp 

In this study, a theory-based simplified compressor model was 1:487e8 n2 þ0:0001031r 3p 2:287e7 r 2p n3:11e10 rp n2
developed, which assumed vapor injection as an instantaneous
þ7:27e13 n3
process. Fig. 4 illustrates the simplified lumped model, which
comprised of three stages. The first stage from point 1 to point 2 (10)
was a compression process and the second stage was an injection In the author’s previous study [20], the injection ratio r defined
and mixing process. The refrigerant from point 2 was mixed with as the ratio of injection mass flow rate to the discharge mass flow
the injection refrigerant from point 5 in an instant. In the third rate has been obtained:
stage, the mixed refrigerant at point 3 was compressed to the
discharge pressure.
 1k
V2 T1 xp5 V2 T1
The first and third stages were both compression processes, r¼  (11)
V1 kT5 p1 V1 kT5
which could be considered as a polytropic process and the
following equations can be obtained: The indicated power (Pi) and input power (Pc) of compressor
could be calculated by Eq. (12) and Eq. (13):
 k
p2 v
¼ 1 (3) Pi ¼ msuc ðh2  hsuc Þ þ mdis ðhdis  h3 Þ (12)
p1 v2

 k Pc ¼ Pi =hmec =hmot (13)


pdis v3
¼ (4)
p3 vdis where hmec is mechanical efficiency, and hmot is motor efficiency.

where p is the pressure, v is the specific volume, and k is the pol- 3.2. Modeling of heat exchangers
ytropic exponent. v1/v2 is determined by the injection port position.
The polytropic exponent is calculated by the following fitting The heat exchangers in the heat pump system with series WHX
formula based on the experimental dates: includes condenser, evaporator, IHX and WHX. The distributed-
parameter method was used to simulate the finned tube heat ex-
k ¼ 1:117 þ 0:003623rp  1:29e5 n þ 5:58e5 r 2p  3:91e6 rp nþ changers such as condenser and evaporator, and the plate heat
8:08e9 n2 þ 1:01e7 r 2p n þ 2:23e11 rp n2  3:73e13 n3 exchangers such as IHX and WHX. The heat exchanger was divided
into n segments and each segment was simulated as a control
(5)
volume. For each segment the heat transfer rate can be calculated
In the simplified model, the injection and mixing process is by Eq. (14) and Eq. (15). The total heat transfer coefficient can be
assumed as an adiabatic and isovolumetric process. Therefore, the calculated by Eq. (16) as follows:

Table 4
The heat transfer correlations in the model.

Working medium Content and region Correlations

refrigerant Heat transfer singlephase DittusBoelter correlation


Heat transfer twophase in evaporating process Gungor and Winterton correlation
Heat transfer twophase in condensing process Thome correlation
air Heat transfer DittusBoelter correlation
50% ethylene glycol solution Heat transfer DittusBoelter correlation
X. Han et al. / Renewable Energy 152 (2020) 835e848 841

pin  pout
X¼ (18)
pin

X
Y ¼1  (19)
3Fg XT

g
Fg ¼ (20)
1:4

where Cd is the flow coefficient, Y is the expansion factor, XT is


pressure differential ratio factor, and g is the refrigerant specific
heat at EEV inlet. In this model, the expansion factor was added to
the Bernoulli equation to describe the two-phase flow character-
istics of the refrigerant.

3.4. Modeling of the system

Fig. 5 shows the flowchart of the VI heat pump simulation


model. Firstly, the initial value of evaporator superheat SHeva,
evaporating pressure pe, condensing pressure pc, and injection
pressure pinj were assumed. Then, the EEV2 model was invocated
and the injection mass flow rate was calculated. Subsequently, the
IHX model and compressor model were calculated and another
injection mass flow rate was obtained. Then, pinj was adjusted by
comparing the injection mass flow rate calculated from EEV2
m2_EEV and that from compressor m2_comp. As this cycle was over,
the main branch mass flow rate will be balanced. It can be calcu-
lated from the EEV1 model and the compressor model. The
condensing pressure pc can be adjusted according to the difference
between m1_EEV and m1_comp. Next, the evaporator model was
invoked and the superheat was obtained. The evaporating pressure
pe was adjusted by comparing the calculated superheat and the
assumed value. Finally, the superheat SHeva was adjusted according
Fig. 5. Simulation flowchart of the heat pump system. to the refrigerant charging balance.

3.5. Model validation


qsec ¼ mr ,Dhr ¼ ma ,Dha (14)
The simulation model of heat pump in VI/no WHR model is
validated by the experimental data collected at the ambient tem-
DTmax  DTmin peratures of 0  C, 5  C, 10  C, and 15  C. Fig. 6 shows the
qsec ¼ U,Aout , (15)
lnðDTmax =DTmin Þ predicted heating capacity and input power using the simulation
model are consistent with the measured data within deviations of
 1 ±7%, ±6%, respectively, and the predicted accuracy of COP and
Aout d,Aout 1
U¼ þ þ (16) suction mass flow rate are ±7%, ±5%, respectively.
ain ,Ain l,Ain aout
The heat transfer correlations in the model are listed in Table 4. 4. Results and discussions
The heat transfer coefficient of different working medium in single-
phase can be calculated by Dittus-Boelter correlation [21]. The heat 4.1. The pressure drop of WHX
transfer coefficient for refrigerant in evaporation process and
condensation process can be predicted by Gungor and Winterton The Friedel correlation [24] was used to study the refrigerant
correlation [22] and Shah correlation [23], respectively. The pres- side pressure drop characteristics of WHX in this section. Fig. 7
sure drop of refrigerant in single-phase is predicted by Friedel shows the pressure drop ratio of WHX according to the heat
correlation [24], and that in two-phase is predicted by Moddy exchanger area at the outlet pressure of 5.4 bar and heat transfer
correlation [21]. rate of 3 kW. The pressure drop ratio is defined as the ratio of
pressure drop under some condition to that under the condition of
0.07 kg/s mass flow rate and 0.7 inlet quality. It can be seen in
3.3. Modeling of EEV
Fig. 7(a) that the pressure drop of WHX at the refrigerant mass flow
rate of 0.07 kg/s reduced quickly with the increase in effective heat
The main branch EEV1 and VI branch EEV2 were simulated by
exchanger area from 0.29 to 1.17 m2 and it changed slowly when
the following equations according to the previous studies [
the area was greater than 1.17 m2. This reduction trend was mainly
[25e27]]:
caused by the decrease of refrigerant channel velocity. The inlet
pffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi quality of refrigerant also has great effects on the pressure drop.
m ¼ Cd ,A,Y 2rin pin X (17)
The pressure drop increased with the increase of inlet quality and
the increasement was greater at smaller heat exchanger area. This
842 X. Han et al. / Renewable Energy 152 (2020) 835e848

25 8
Heating capacity (non inj) Input power (non inj)
7
20 Heating capacity (inj) Input power (inj)
6
Predicted data (kW)

Predicted data (kW)


+7% 5 +6%
15
4 -6%
-7%
10 3

2
5
1

0 0
0 5 10 15 20 25 0 2 4 6 8
Measured data (kW) Measured data (kW)

(a) Heating capacity (b) Input power

4 0.12
COP (no inj) suction mass flow rate (no inj)
COP (inj) 0.10 suction mass flow rate (inj)
3
Predicted data (kg/s)

0.08
Predicted data

+7% +5%
2 0.06
-7% -5%
0.04
1
0.02

0 0.00
0 1 2 3 4 0.00 0.02 0.04 0.06 0.08 0.10 0.12
Measured data Measured data (kg/s)

(c) COP (d) Suction mass flow rate

Fig. 6. Comparison between the measured data and predicted data.

means the effect of inlet quality on pressure drop can be ignored as pressure of the heat pump cycle in VI/WHR mode were all
the heat exchanger area is large enough. Fig. 7(b) shows the increased. The increase of suction pressure was caused by the
refrigerant mass flow rate has significant effects on the pressure higher temperature of waste heat source, compared with outdoor
drop. As the mass flow rate increased from 0.06 kg/s to 0.08 kg/s, air temperature. In order to maintain the same injection superheat
the pressure drop at inlet quality of 0.7 increased by 68.28% as the VI/no WHR cycle, the injection pressure of VI/WHR cycle was
(0.29 m2) and 86.29% (2.35 m2), respectively. It also showed the increased due to the increase of suction pressure. The optimum
increase of area can reduce the pressure drop and the absolute injection superheat and suction superheat of each cycle were set as
value of pressure drop increase caused by the increase of flow rate 3  C in this study. The slight increase of discharge pressure was
can be ignored as the area was large enough. In the system model, caused by the increase in suction pressure and injection pressure.
the effective heat exchanger area was set as 1.17 m2 to obtain Because the outlet temperature of IHX main branch was limited by
smaller pressure drop. the inlet temperature of IHX injection branch, as shown in Eq. (21),
the outlet enthalpy of IHX main branch (point 6) in VI/WHR cycle
was greater than that in VI/no WHR cycle. This resulted in the in-
4.2. Heating performance under different waste heat crease in inlet enthalpy of evaporator and the decrease in heat
transfer rate of evaporator.
4.2.1. Heat pump with VI
Fig. 8 shows the pressure-enthalpy diagrams of VI heat pump Tmain;out > TVI;in (21)
cycles with and without waste heat at the ambient temperature
of 5  C. The red solid line represents the heat pump cycle with Fig. 9 shows the heating performance of heat pump with VI
6 kW waste heat and the black dotted line represents the cycle according to waste heat at the ambient temperature of 5  C.
without waste heat. Compared with the heat pump cycle in VI/no Fig. 9(a) shows that the compressor suction pressure gradually
WHR mode, the suction pressure, injection pressure, and discharge increases and the evaporation temperature increases from 12.9  C
X. Han et al. / Renewable Energy 152 (2020) 835e848 843

1.4 1.4

The pressure drop ratio

The pressure drop ratio


1.2 Inlet quality 0.5 1.2 0.06 kg/s
1.0 Inlet quality 0.7 1.0 0.07kg/s
0.8 Inlet quality 0.9 0.8 0.08 kg/s
0.6 0.6
0.4 0.4
0.2 0.2
0.0 0.0
0.0 0.5 1.0 1.5 2.0 0.0 0.5 1.0 1.5 2.0
The area of WHX (m2) The area of WHX (m2)

(a) Inlet quality (b) Mass flow rate

Fig. 7. The pressure drop characteristics of the WHX.

> (21) to 10.6  C with the increasing of waste heat from 0 to 6 kW.
Fig. 9(b) shows the suction mass flow rate is increased according to
2.8 black line_VI/no WHR red line_VI/WHR the waste heat, which is mainly related to the increase in
2.4 6 4 2 compressor suction density caused by higher suction pressure.
2.0 Compared with the heat pump without waste heat, the suction
Pressure (MPa)

mass flow rate of VI heat pump at 6 kW waste heat is increased by


1.6
6.98%. The injection mass flow rate also increases due to the in-
1.2 3 crease of injection pressure. It is increased by 17.3% at 6 kW waste
0.8 5 heat and becomes one of the major reasons for the increase of
discharge mass flow rate. Fig. 9(c) shows the heat absorption from
0.4 9 1
7 evaporator gradually decreases with the increase of waste heat,
0.0 whereas the total heat absorption from waste heat and ambient air
-50 50 150 250 350
increases due to the greater heat absorption from the waste heat.
Enthalpy (kJ/kg)
Fig. 9(d) shows the heating capacity of VI heat pump at 2 kW and
Fig. 8. Pressure-enthalpy diagrams of the VI heat pump cycles with and without waste 6 kW waste heat is increased by 1.61% and 5.12%, respectively,
heat. compared with that of heat pump without waste heat. The COP at

0.57 -10.0 75 13

Mass flow rate m inj (g/s)


Mass flow rate m suc (g/s)
Suction pressure (MPa)

Psuc t e va msuc minj


0.56 -10.5
Evaporation temp. (

0.55 -11.0 73 12
0.54 -11.5
71 11
0.53 -12.0
0.52 5 C, -12.5 69 5 C, 10
0.51 VI -13.0 VI
0.50 -13.5 67 9
0 2 4 6 8 0 2 4 6 8
Waste heat (kW) Waste heat (kW)

(a) suction pressure (b) mass flow rate

16 14.8 19.0 2.98


Heat absorption Qeva (kW)

Heat absorbtion Qtotal (kW)

Heating capacity (kW)

Qe va Qtotal Qh COP
14.6 2.96
14 18.5
14.4 2.94
COP

12 5 C, 14.2 18.0 2.92


VI 14.0 2.90
10 17.5 5 C,
13.8 VI 2.88
8 13.6 17.0 2.86
0 2 4 6 8 0 2 4 6 8
Waste heat (kW) Waste heat (kW)

(c) heat absorption (d) heating capacity and COP

Fig. 9. Heating performance of heat pump with VI according to waste heat.


844 X. Han et al. / Renewable Energy 152 (2020) 835e848

2.8 black line_no VI/no WHR red line_no VI/WHR ambient air and waste heat is much less than the increasement of
waste heat.
2.4
3 2
2.0
Pressure (MPa)

4.2.2. Heat pump without VI


1.6 Fig. 10 shows the pressure-enthalpy diagrams of single stage
heat pump cycles with and without waste heat at the ambient
1.2 temperature of 5  C. The red solid line represents the cycle in no
VI/WHR mode with 6 kW waste heat and the black dotted line
0.8 represents the cycle without waste heat. Compared with the heat
pump cycle in no VI/no WHR mode, the suction pressure of the
0.4 4 5 1
cycle in no VI/WHR mode was increased, which resulted in the
0.0 increase of refrigerant mass flow rate. The discharge pressure was
-50 50 150 250 350 also increased due to the increase of mass flow rate.
Enthalpy (kJ/kg) Fig. 11 shows the heating performance of heat pump without VI
according to waste heat at the ambient temperature of 5  C.
Fig. 10. Pressure-enthalpy diagrams of the single stage heat pump cycles with and
Fig. 11(a) shows with the increase in waste heat from 0 to 6 kW, the
without waste heat.
compressor suction pressure gradually increases and the evapora-
tion temperature increases from 11.9  C to 9.8  C. Fig. 11(b)
shows the heating capacity of heat pump without VI is increased by
2 kW and 6 kW waste heat is increased by 1.38% and 2.56%, 3.84% at 2 kW waste heat and 9.45% at 6 kW waste heat. The COP is
respectively. Although the improvements of heating capacity and increased by 2.65% and 5.07%, respectively. Fig. 11(c) shows the
COP are comparable to the predicted accuracy, the results can be heating capacity of heat pump with VI is higher than that of the
referenced for the performance analysis. That’s because the heating system without VI as the waste heat increases from 0 to 6 kW. The
capacity increase varying with waste heat input is calculated based maximum improvement was 18.28% at 0 kW waste heat and the
on the simulation model with the same parameter setting. With the improvement gradually diminished with the increase of waste
increasing of waste heat, the improvement of heat capacity is very heat. Fig. 11(d) shows the COP of the heat pump with VI is higher
slight. The main reason is that the heat absorption from ambient air than that of the heat pump without VI at 0 kW waste heat, and
is decreased and the increasement of total heat absorption from similar under the condition of 2 kW and 4 kW waste heat, while

0.59 17 3.1
Suction pressure (MPa)

Heating capacity (kW)

Psuc t e va -8.5 Qh COP


0.58
Evaporation temp. (

0.57 -9.5 16 3.0


0.56

COP
0.55 -10.5
0.54 15 2.9
5 C, 5 C,
-11.5
0.53 no VI no VI
0.52 -12.5 14 2.8
0 2 4 6 8 0 2 4 6 8
Waste heat (kW) Waste heat (kW)

(a) suction pressure (b) heating capacity and COP

20 3.2
Heating caapcity (kW)

5 C 3.0 5 C
18
2.8
COP

16 2.6
VI VI
2.4
14 no VI no VI
2.2
12 2.0
0 2 4 6 0 2 4 6
Waste heat (kW) Waste heat (kW)

(c) heating capacity compared with VI system (d) COP compared with VI system

Fig. 11. Heating performance of heat pump without VI according to waste heat.
X. Han et al. / Renewable Energy 152 (2020) 835e848 845

0.80 95
VI/no WHR VI/no WHR

Suction pressure (MPa)


0.75 90

Mass flow rate msuc (g/s)


0.70 VI/WHR 85 VI/WHR
0.65 80
0.60 75
0.55 70
0.50 65
0.45 60
0.40 55
-15 -10 -5 0 5 10 -15 -10 -5 0 5 10
Ambient temperature ( C) Ambient temperature ( C)

(a) suction pressure (b) mass flow rate

23 3.3
22 VI/no WHR 3.2 VI/no WHR
Heating capacity (kW)

21 VI/WHR 3.1 VI/WHR


20
3.0

COP
19
2.9
18
17 2.8
16 2.7
15 2.6
-15 -10 -5 0 5 10 -15 -10 -5 0 5 10
Ambient temperature ( C) Ambient temperature ( C)

(c) heating capacity (d) COP

Fig. 12. Heating performance of heat pump with VI according to ambient temperature.

lower than that of the condition of 6 kW waste heat. 4.3.2. Heating performance of heat pump without VI
Fig. 13 shows the heating performance of single stage heat pump
with 2 kW waste heat and without waste heat at different ambient
4.3. Heating performance under different ambient temperature temperature. Fig. 13(a and b) shows that the suction pressure and
suction mass flow rate of heat pump in no VI/WHR mode and no VI/
4.3.1. Heating performance of heat pump with VI no WHR mode decrease with the decreasing of ambient tempera-
Fig. 12 displays the heating performance of VI heat pump with ture. At the same ambient temperature, suction pressure and suc-
2 kW waste heat and without waste heat at different ambient tion mass flow rate in no VI/WHR mode are a little higher than
temperatures. Fig. 12(a) shows that the suction pressure of heat those in no VI/no WHR mode. Fig. 13(c) indicates that the heating
pump in VI/WHR mode and VI/no WHR mode is both decreased capacity of heat pump in no VI/WHR and no VI/no WHR modes is
with decreasing ambient temperatures. As the ambient tempera- decreased by 30.97% and 32.25%, respectively, as ambient temper-
ture is lower than 0  C, suction pressure in VI/WHR mode is a little ature decreases from 7  C to 10  C. The heating capacity of heat
higher than that in VI/no WHR mode because the waste heat source pump with 2 kW waste heat is higher than that of the system
had higher temperature than ambient air. Fig. 12(b) shows that the without waste heat at the same ambient temperature and the
suction mass flow rate is strongly dependent on the ambient improvement rate gradually decreases with the increasing of
temperature and it decreases sharply with the dropping of ambient ambient temperature. Fig. 13(d) shows that the COP of heat pump
temperature due to the decrease in suction pressure. The suction with waste heat has an advantage over that without waste heat as
mass flow rate in VI/WHR mode is a little higher than that of VI/no the ambient temperature is lower than 4  C. However, as ambient
WHR mode due to the increase in suction pressure. Fig. 12(c and d) temperature rises above 4  C, waste heat recovery has no advan-
shows that the heating capacity of heat pump in VI/WHR and VI/no tage. This is because the heating capacity improvement decreases
WHR modes decreases by 37.65% and 29.27%, and the COP de- at high ambient temperatures due to the increase of WHX pressure
creases by 14.45% and 15.75%, as the ambient temperature drops drop.
from 7  C to 10  C. As the ambient temperature is lower than 0  C,
waste heat recovery is beneficial to improve the heating perfor- 5. Further discussions
mance. The heating capacity and COP of heat pump in VI/WHR
mode are higher than those in VI/no WHR mode. However, the 5.1. The operation strategy of mode switching
heating capacity and COP of heat pump in VI/WHR mode are both
decreased at 7  C ambient temperature due to the increase of WHX The heat pump system with WHR proposed in this study can
pressure drop. operate in four different heating modes: VI/WHR, VI/no WHR, no
846 X. Han et al. / Renewable Energy 152 (2020) 835e848

0.80 95
0.75 no VI/no WHR 90 no VI/no WHR

Mass flow rate msuc (g/s)


Suction pressure (MPa)
0.70 no VI/WHR 85 no VI/WHR
0.65 80
0.60 75
0.55 70
0.50 65
0.45 60
0.40 55
-15 -10 -5 0 5 10 -15 -10 -5 0 5 10
Ambient temperature ( C) Ambient temperature ( C)

(a) suction pressure (b) mass flow rate

21 3.3
20 no VI/no WHR no VI/no WHR
3.2
Heating capacity (kW)

19 no VI/WHR no VI/WHR
3.1
18
17 3.0
16 COP 2.9
15
2.8
14
13 2.7
12 2.6
-15 -10 -5 0 5 10 -15 -10 -5 0 5 10
Ambient temperature ( C) Ambient temperature ( C)

(c) heating capacity (d) COP

Fig. 13. Heating performance of heat pump without VI according to ambient temperature.

VI/WHR, no VI/no WHR. It can be converted into different operation system in VI/no WHR mode is 11.86%e16.05% higher than that of no
modes according to actual operation conditions. As the previous VI/WHR mode as ambient temperature rises from 10  C to 7  C,
section shows, the waste heat recovery exhibits advantage for both however, the COP is lower. Therefore, if the heating capacity of
VI system (ambient temperature lower than 0  C) and no VI system system in no VI/WHR mode can satisfy the heating load, no VI/WHR
(ambient temperature lower than 4  C). Therefore, the heat pump mode should be chosen as ambient temperature remains between
system can operate in VI/WHR mode as ambient temperature stays 0  C and 4  C. if not, VI/no WHR mode should be chosen.
lower than 0  C, and operate in no VI/no WHR mode when the
ambient temperature is more than 4  C. When the ambient tem- 5.2. The dynamic variation of waste heat
perature is between 0 and 4  C, two operating modes are available:
VI/no WHR and no VI/WHR. Fig. 14 shows the heating capacity of The waste heat of EVs mainly comes from the electric motor, the

24 24
no VI/WHR no VI/WHR
Heating capacity (kW)
Heating capacity (kW)

22 22
VI/no WHR VI/no WHR
20 20

18 18

16 16

14 14

12 12
-15 -10 -5 0 5 10 -15 -10 -5 0 5 10
Ambient temperature ( C) Ambient temperature ( C)

(a) heating capacity (b) COP

Fig. 14. Heating performance comparison between VI/no WHR and no VI/WHR.
X. Han et al. / Renewable Energy 152 (2020) 835e848 847

Indoor HX

Outdoor HX
EEV2

Compressor
IHX

P1
P2

V1 V2

Thermal
Storage

Battery
WHX

or EM
Gas-liquid
separator V3

EEV1 IHX
cooling
heating
Indoor HX

Fig. 15. The system flowchart of the heat pump with thermal storage.

battery, the inverter and other electric device. Thus, the value of recovery was better than that of system without waste heat
waste heat varies greatly in the actual driving conditions. In order recovery. However, as the ambient temperature rises, the
to obtain the relatively stable waste heat, the Thermal storage (TS) heating performance of waste heat recovery system becomes
could be integrated into the waste heat recovery system. Phase worse than that of the system without waste heat recovery due
change energy storage is very suitable for waste heat recovery to the increase of pressure drop of the waste heat exchanger.
system for EVs due to the large latent heat of phase change material
and the small volume of the energy storage device, which can also
be combined with the battery thermal management. Some re- Author contributions section
searches [ [28e30]] proposed the heat pump with TS for EVs, in
which the electric battery was used as TS device and was predicted Xinxin Han: Conceptualization, Methodology, Software, Writing
by the electric heater before the heat pump was started. The TS - Original Draft. Huiming Zou: Conceptualization, Methodology,
could be used to preheat the cabin supply air or as a heat source of Writing - Review & Editing. Jiang Wu: Visualization, Supervision.
the heat pump. Here the TS is combined with the waste heat re- Changqing Tian: Conceptualization, Writing - Review & Editing.
covery heat pump with VI, as shown in Fig. 15. Compared to Fig. 1, Mingsheng Tang: Software, Supervision. Guangyan Huang:
the increasement part is circled in the red rectangle. The heat of TS Validation.
is completely from the waste heat rather than the electric heater. As
the EV starts, the pump P2 is turned on and the waste heat is stored Declaration of competing interest
into the TS. As the heat pump starts, the pump P1 is turned on and
the heat is extracted from the TS. The heat storage and heat removal The authors declare that they have no known competing
may be processed simultaneously in the TS. financial interests or personal relationships that could have
appeared to influence the work reported in this paper.

6. Conclusions
Acknowledgements
In this paper, a heat pump with heat recovery for electric bus is
We would like to thank the support by the National Key
investigated experimentally and numerically. The following con-
Research and Development Program of China (No.
clusions can be obtained:
2018YFB0105900).
1) The pressure drop of waste heat exchanger has great effects on
References
the heating performance of the heat pump with waste heat
exchanger connected to evaporator in series. The waste heat [1] Norm Meyer, Ian Whittal, Martha Christenson, Aaron Loiselle-Lapointe, The
exchanger should be optimized to reduce the pressure drop impact of driving cycle and climate on electrical consumption & range of fully
because it’s in the high-quality evaporating region. electric passenger vehicles, in: EVS26 International Battery, Hybrid and Fuel
Cell Electric Vehicle Symposium, 2012. Los Angeles, USA.
2) Waste heat recovery can improve the heating capacity of heat [2] J. Lee, S. Kwon, Y. Lim, M. Chon, Effect of airconditioning on driving range of
pump. As ambient temperature was at 5  C, the heating ca- electric vehicle for various driving modes (No. 2013-01-0040), SAE Technical
pacity and COP of injection heat pump with 2 kW waste heat Paper, 2013, https://doi.org/10.4271/2013010040.
[3] M. Hoso, M. Dire, Performance evaluation of an integrated automotive air
recovery were 1.61% and 1.38% higher than those of heat pump
conditioning and heat pump system, Energy Convers. Manag. 47 (2006)
without waste heat recovery. The improvements of heat pump 545e559, https://doi.org/10.1016/j.enconman.2005.05.004.
with 6 kW waste heat recovery were 5.12% and 2.56%, , Parametric analysis of the defrosting process of a reversible
[4] S. Alois, R. Rene
respectively. heat pump system for electric vehicles, Appl. Therm. Eng. 61 (2013) 393e400,
https://doi.org/10.1016/j.applthermaleng.2013.07.044.
3) As the ambient temperature was lower than 0  C, the heating [5] H.S. Lee, M.Y. Lee, Steady state and startup performance characteristics of air
performance of heat pump system with 2 kW waste heat source heat pump for cabin heating in an electric passenger vehicle, Int. J.
848 X. Han et al. / Renewable Energy 152 (2020) 835e848

Refrig. 69 (2016) 232e242, https://doi.org/10.1016/j.ijrefrig.2016.06.021. portholes compressors for electric vehicles, Appl. Energy 185 (2017)
[6] D. Wang, B. Yu, J. Hu, L. Chen, J. Shi, J. Chen, Heating performance charac- 2085e2093, https://doi.org/10.1016/j.apenergy.2015.12.032.
teristics of CO2 heat pump system for electrical vehicle in a cold climate, Int. J. [18] X. Han, H. Zou, H. Xu, C. Tian, W. Kang, Experimental study on vapor injection
Refrig. 85 (2018) 27e41, https://doi.org/10.1016/j.ijrefrig.2017.09.009. air source heat pump with internal heat exchanger for electric bus, Energy
[7] B. Yu, J. Yang, D. Wang, J. Shi, J. Chen, Modeling and theoretical analysis of a Procedia 158 (2019) 4147e4153, https://doi.org/10.1016/
CO2propane autocascade heat pump for electrical vehicle heating, Int. J. j.egypro.2019.01.817.
Refrig. 95 (2018) 146e155, https://doi.org/10.1016/j.ijrefrig.2018.07.030. [19] R.J. Moffat, Describing the uncertainties in experimental results, Exp. Therm.
[8] C. Liu, Y. Zhang, T. Gao, J. Shi, J. Chen, T. Wang, L. Pan, Performance evaluation Fluid Sci. 1 (1) (1988) 3e17, https://doi.org/10.1016/0894-1777(88)90043-X.
of propane heat pump system for electric vehicle in cold climate, Int. J. Refrig. [20] X. Han, H. Zou, W. Kang, H. Xu, Y. Chen, C. Tian, Experimental investigation on
95 (2018) 51e60, https://doi.org/10.1016/j.ijrefrig.2018.08.020. vapor injection ASHP for electric rail vehicles in cold region, Appl. Therm. Eng.
[9] H. Zou, G. Huang, S. Shao, X. Zhang, C. Tian, X. Zhang, Experimental study on 153 (2019) 473e482, https://doi.org/10.1016/j.applthermaleng.2019.03.037.
heating performance of a R1234yf heat pump system for electric cars, Energy [21] S.M. Yang, W.Q. Tao, Heat Transfer, Higher Education Press, Beijing, 2006 [In
Procedia 142 (2017) 1015e1021, https://doi.org/10.1016/ Chinese].
j.egypro.2017.12.348. [22] K. Gungor, R. Winterton, A general correlation for flow boiling in tubes and
[10] J.H. Ahn, H. Kang, H.S. Lee, H.W. Jung, C. Baek, Y. Kim, Heating performance annuli, Int. J. Heat Mass Tran. 29 (1986) 351e358, https://doi.org/10.1016/
characteristics of a dual source heat pump using air and waste heat in electric 0017-9310(86)90205-X.
vehicles, Appl. Energy 119 (2014) 1e9, https://doi.org/10.1016/ [23] M.M. Shah, A general correlation for heat transfer during film condensation
j.apenergy.2013.12.065. inside pipes, Int. J. Heat Mass Tran. 22 (1979) 547e556, https://doi.org/
[11] Z. Tian, W. Gan, X. Zhang, B. Gu, L. Yang, Investigation on an integrated 10.1016/0017-9310(79)90058-9.
thermal management system with battery cooling and motor waste heat [24] L. Friedel L, Improved friction drop correlations for horizontal and vertical
recovery for electric vehicle, Appl. Therm. Eng. 136 (2018) 16e27, https:// two-phase pipe flow, in: European Two-phase Flow Group Meeting, 1979,
doi.org/10.1016/j.applthermaleng.2018.02.093. https://doi.org/10.1016/0894-1777(88)90043-X. Ispra, Italy.
[12] J.H. Ahn, J.S. Lee, C. Baek, Y. Kim, Performance improvement of a dehumidi- [25] T. Chen, D.A. Cha, O.K. Kwon, Experimental investigation on mass flow
fying heat pump using an additional waste heat source in electric vehicles characteristics of R245fa through electronic expansion valve, Appl. Therm.
with low occupancy, Energy 115 (2016) 67e75, https://doi.org/10.1016/ Eng. 125 (2017) 111e117, https://doi.org/10.1016/
j.energy.2016.08.104. j.applthermaleng.2017.06.127.
[13] X. Wang, Y. Hwang, R. Radermacher, Twostage heat pump system with [26] W. Li, Simplified modeling analysis of mass flow characteristics in electronic
vaporinjected scroll compressor using R410A as a refrigerant, Int. J. Refrig. expansion valve, Appl. Therm. Eng. 53 (2013) 8e12, https://doi.org/10.1016/
32 (2009) 1442e1451, https://doi.org/10.1016/j.ijrefrig.2009.03.004. j.applthermaleng.2012.12.035.
[14] A. Redo n, E. Navarro-Peris, M. Pitarch, Gonza lvez-Macia, J.M. Corbera n, [27] X. Cao, Z.Y. Li, L.L. Shao, C.L. Zhang, Refrigerant flow through electronic
Analysis and optimization of subcritical twostage vapor injection heat pump expansion valve: experiment and neural network modeling, Appl. Therm. Eng.
systems, Appl. Energy 124 (2014) 231e240, https://doi.org/10.1016/ 92 (2016) 210e218, https://doi.org/10.1016/j.applthermaleng.2015.09.062.
j.apenergy.2014.02.066. [28] A. Steiner, A. Mladek, April. Reducing the energy consumption for comfort and
[15] I.Y. Cho, H.J. Seo, D. Kim, Y. Kim, Performance comparison between R410A and thermal conditioning in EVs, in: 2017 Twelfth International Conference on
R32 multiheat pumps with a subcooler vapor injection in the heating and Ecological Vehicles and Renewable Energies (EVER), IEEE, 2017, pp. 1e4.
cooling modes, Energy 112 (2016) 179e187, https://doi.org/10.1016/ [29] J. Jeffs, A. McGordon, W.D. Widanage, S. Robinson, A. Picarelli, December. Use
j.energy.2016.06.069. of a thermal battery with a heat pump for low temperature electric vehicle
[16] J. Jung, Y. Jeon, H. Lee, Y. Kim, Numerical study of the effects of injectionport operation, in: 2017 IEEE Vehicle Power and Propulsion Conference (VPPC),
design on the heating performance of an R134a heat pump with vapor in- IEEE, 2017, pp. 1e5.
jection used in electric vehicles, Appl. Therm. Eng. 127 (2017) 800e811, [30] J.J. Meyer, J. Lustbader, N. Agathocleous, A. Vespa, J. Rugh, G. Titov, Range
https://doi.org/10.1016/j.applthermaleng.2017.08.098. Extension Opportunities while Heating a Battery Electric Vehicle (No. 2018-
[17] F. Qin, G. Zhang, Q. Xue, H. Zou, C. Tian, Experimental investigation and 01-0066), SAE Technical Paper, 2018.
theoretical analysis of heat pump systems with two different injection

You might also like