Professional Documents
Culture Documents
10.feeder Analysis & Modeling
10.feeder Analysis & Modeling
10.feeder Analysis & Modeling
1
Part I
Feeder Modeling
INTRODUCTION
3
Why Model Distribution Feeders?
4
What Should a Model Be Able to Tell Us?
Whether:
System voltages, currents, and harmonics
are within established limits
Adequate system resources and
infrastructure are available to meet peak
demand and/or generation
The system is safe, secure, and reliable
5
Transmission Lines Vs. Distribution Lines
6
Transmission Lines
Phase balance
– Lines has mutual influence over each others.
– Three phase lines will have mutual impedances between each phase.
– The mutual coupling between phases is different because the spacing
between phases are different
– For longer power lines without branches, wires are transposed
according to a transposing scheme as shown in the figure.
– Loads are balanced.
– Accordingly, Transmission studies can assume a balanced system
R/X ratio
Transmission lines have small R/X ratio which leads to normally neglecting
the line resistance for power flow studies
7
Distribution Feeders
Phase balance
– Distribution lines are not transposed
– Distribution lines may be three-phase, two-phase
and single-phase
– Loading is not balanced
– Distribution system modelling must be done by
phase as distribution system are normally
unbalanced
R/X ratios
Distribution feeders have a relatively higher R/X ratio
compared to transmission lines. Therefore, wire
resistance are not neglected for distribution feeder
modelling
8
Why phase unbalance is studied?
Confirm that voltage unbalance is within
specifications.
Determine how to better balance the
loads, so no phase is heavily loaded
more than the others.
Reduce losses due to neutral currents.
9
Overhead vs. Underground
Cost: Overhead’s number one Safety: Underground’s number
advantage. Significantly less cost, one advantage. Much less
especially initial cost. chance for public contact.
10
Underground Cables
11
Overhead vs. Underground
12
UNBALANCED DISTRIBUTION
FEEDER MODELLING
Inductance of unequal phase spacing,
transposed lines
The phase inductance of un-equal phase spacing and transposed lines is:
−7
Deq
L = 2 10 ln H/m
GMR
where : D eq = 3 D12 D23 D31
Deq
x = L = 2 (60) 2 10 ln−7
/m
GMR
Hence the phase
Deq
reactance will be: = 753.6 10 −7 ln /m
GMR
Deq Deq
x = 1609.3 753.6 10 −7 ln = 0.12134 ln /mile
GMR GMR
^ Deq
And the impedance: z = r + j 0.12134 ln /mile
GMR
Modeling of Distribution Feeders
The loading of a distribution feeder is inherently
unbalanced because of the large number of
unequal single-phase loads that must be served.
An additional unbalance is introduced by the
unequal conductor spacing of the three-phase
overhead and underground line segments.
If a distribution engineer is to be able to perform
accurate power-flow and short-circuit studies, it is
imperative that the distribution feeder be modeled
as accurately as possible.
This means that three-phase models of the major
components must be utilized.
Inductance of unequal phase spacing,
un-transposed lines
The un-equal phase spacing and un-transposed lines will result in self and
mutual inductances between the line which can be written as
1
Ẑii = ri + j 0.12134 ln / mile
GMR
1
Zˆ ij = j 0.12134 ln / mile
Dij
Zii is the self inductance of conductor i due to its current and Zij is the
mutual inductance of conductor i due to the current in conductor j.
Inductance of unequal phase spacing,
un-transposed lines
Using KVL:
Vag V ' ag z aa z ab z ac z an
I a
'
Vbg V bg zba zbb zbc zbn I b
V = V ' + . I
cg cg zca zcb zcc zcn c
Vng V ' ng I n
z na z nb z nc z nn
Vabc
=V '
abc
+ zij .I abc + zin .I n
0 = 0 + znj .I abc + znn .I n
For a grounded neutral, the voltages Vng and V’ng are equal to zero.
Phase Impedance Matrix for Overhead
Lines
Solving for In:
−1
Vabc = V abc
'
+ zabc .I abc
where
Zˆ
abc
−1
= zij − zin . znn . znj
Phase Impedance Matrix for Overhead
Lines
zaa zab zac
Z abc = zba zbb zbc
zca zcb zcc
For a distribution line that is not transposed, both the diagonal terms
of above equation will not be equal and the off-diagonal elements
will not be equal too. However, the matrix will be symmetric.
The phase impedance matrix for a open delta connections with
phase a and c only available will be:
zaa 0 zac
Z abc = 0 0 0
zca 0 zcc
Phase Impedance Matrix for Overhead
Lines
For The diagram of a three phase system without a neutral wire is as
shown in the following figure:
Sequence Voltages
Unbalance Voltages Balance
Systems
zero sequence
Vag Zero
Sequence positive sequence
Vcg
Symmetrical Three
Positive
components Sequence balanced
Systems
Vbg
Negative
Sequence
negative sequence
Phase Impedance Matrix for Overhead
Lines
Sequence Impedance:
Vag 1 1 1 VLG 0
2
bg
V = 1 a a VLG1
V 1 a a2 VLG 2
n
cg
In condensed form this equation can be written as:
VLG abc = A. VLG 012
The phase line currents are defined in the same manner:
1 1 1
where: A−1 = 1 1 a a2
3
1 a 2 a
Phase Impedance Matrix for Overhead
Lines
Sequence Impedance:
Since: I abc = A. I 012 and VLG abc n = VLG abc m + Z abc I abc
VLG012 = A−1.VLGabc
Then:
VLG012 n = A−1.VLG abc m + A−1.Z abc . A. I 012
Z 012
Where:
Z 00 Z01 Z02 Z00 = zero sequence impedance
Z 012 = Z10 Z11 Z12 Z11 = positive sequence impedance
Z 20 Z21 Z22
Z22 = negative sequence impedance
Example 1
An overhead three-phase distribution line is constructed as
shown in the following figure. Determine the phase impedance
matrix and the positive and zero sequence impedances of the
line. The phase conductors are 336,400 26/7 ACSR and the
neutral conductor is 4/0 6/1 ACSR.
Example 1, solution
V Y YZ
Vs = VR + Z I R + R = 1 + VR + ZI R
2 2
VRY VsY
Is = IR + + , subsitute the value of Vs
2 2
YZ YZ YZ
I s = Y 1 + V +
R 1 + I R A = D = 1+
4 2 2
B=Z
YZ
C = Y 1 +
4
Exact Feeder Model
Exact Feeder Model (Cont.)
VLG
abc m a b VLG abc n
−1
I =
abc m c d abc n
I
12470
VLG = = 7199.56
3
7538.71.57
VLG abc n = [a].VLG abc m + [b].I abc m = 7451.25 − 118.3
7485121.93
Example 2, solution
Calculation of the voltage unbalance:
Vs VR
Z
Vs = VR + ZI R A = D =1
Is = IR B=Z
C =0
Modified Feeder Model
Modified Feeder Model (Cont.)
7199.560
VLG abc n = 7199.56 − 120
7199.56120
The unbalanced currents measured at the source end are given by:
I a 249.97 − 24.5
I = 277.56 − 145.8
b
I c n 305.5495.2
Determine the line-ground and line-line voltages at the load using the
modified line model. Also, find the complex power of the load.
Example 3, solution
The line-ground voltages at the load end are:
VLG abc m = AVLG abc n − [ B]I abc m
Since the source currents are equal to the load currents (why):
Example 3, solution
V .I
*
1735.4223.03
S a
ag a
S = 1 V .I * = 1920.2624.25 kVA
b 1000 bg b
S c Vcg .I c 2104.4722.11
*
Cable structure
where,
GMRS is the geometric mean radius of the solid concentric neutral strands,
k the number of the concentric neutral strands,
R the radius of the circle passing through the center of the concentric neutral Strands,
dod the outside diameter over the concentric neutral strands in inch,
dS the diameter of the concentric neutral strand in inch,
rcn equivalent resistance of the concentric neutral
rs resistance of single neutral strand
Concentric Neutral Underground Cables
Dij = k Dnm
k
− Rk
Where: Dnm is the center to center distance between the phases conductors.
If the distance Dnm is much larger than R, then Dij can be assumed to be Dnm
Then we use the modified Carson’s equations:
^
1
zii = ri + 0.0953 + j 0.12134 ln + 7.93402 /mile
GMR
^ 1
zij = 0.0953 + j 0.12134 ln + 7.93402 /mile
D
ij
Example 4
Three concentric neutral cables are buried in a trench
with spacing as shown in the following figure. The
cables are 15 kV, 250,000 CM stranded AA with 13
strands of #14 annealed, copper wire neutral. The
outside diameter of the cable over the neutral strands
is 1.29 inches. Determine the phase impedance matrix
and the sequence impedance matrix.
Example 4, Solution
4 5 6
R R R
1 2 3
d od − d S 1.29 − 0.0641
R= = = 0.0511 ft.
24 24
rS 14.8722
rcn = = = 1.144 /mile.
k 13
Example 4, Solution
The phase conductors are numbered 1, 2 and 3. The concentric
neutrals are numbered 4, 5 and 6. The conductor-conductor and
concentric neutral-concentric neutral spacing are:
D12 = D21 = D45 = D54 = 0.5 ft D23 = D32 = D56 = D65 = 0.5 ft
R R R
1 2 3
R R R
^
1
zii = ri + 0.0953 + j 0.12134 ln + 7.93402 /mile
GMR
^
1
z11 = 0.41 + 0.0953 + j 0.12134 ln + 7.93402 = 0.505 + j1.456 /mile
0.0171
Example 4, Solution
The self impedance of the concentric neutral
^
1
z 44 = 1.144 + 0.0953 + j 0.12134 ln + 7.93402 = 1.2393 + j1.3296 /mile
0.0486
Zˆ nj nn
[Znj] = [Zin]T
Example 4, Solution
Tape Shielded Underground Cables
The geometric mean radius of the tape shielded underground
cable can be expressed by
T
ds −
GMRshield = 1000 ft.
24
rshield = 7.9385 108 /mile
d s .T
Where:
dc the outside diameter of phase conductor in inch,
dS the outside diameter of the tape shield in inch,
T Thickness of copper tape shield in mils
rsheild resistance of tape shielded
Example 5
A single phase circuit consists of a 1/0 AA, 220 mil
insulation tape shielded cable and a 1/0 Cu neutral
conductor as shown below. The single phase line is
connected to phase b. Determine the phase impedance
matrix. Assume = 2.3715 X 10-8 -meter
Example 5, solution
Cable data: Outside of the tape shield = 0.88 inches,
R = 0.97 /mile, GMRp = 0.0111 ft., Tape shield
thickness = 5 mils.
Neutral data: Resistance = 0.67 /mile and GMRn =
0.01113 ft.,
rshield = 7.9385 10 8
/mile
d s .T
−8
2.3715 10
rshield = 7.9385 108 = 4.2785 /mile
0.88.5
T 5
ds − 0.88 -
GMRshield = 1000 = 1000 = 0.0365 ft.
24 24
Example 5, solution
The conductors are numbered such that:
– #1 = 1/0 AA conductor
– # 2 = tape shield
– # 3 = 1/0 copper ground
1
z11 = 0.0953 + 0.97 + j 0.12134 ln + 7.93402 = 1.065 + j1.509 / mile
0.0111
D22 = GMRShield = 0.0365
1
z 22 = 0.0953 + 4.2786 + j 0.12134 ln + 7.93402 = 4.374 + j1.365 / mile
0.0365
Example 5, solution
1
z12 = 0.0953 + j 0.12134 ln + 7.93402 = 0.0953 + j1.365 / mile
0.0365
Cable Ampacity
The national electric code NEC has also defined
ampacity as “the current in amperes a conductor can
carry continuously under the conditions of use
without exceeding its temperature rating”.
= W T
where: is the temperature difference across the material (like potential),
W is the flow of heat (like current) and T is the thermal resistance (like
electrical resistance)
20-Mar-21 73
Introduction
By analyzing a three phase feeder supplying a load,
we will be able to compute the voltages at the
receiving end (the customer) given the voltage at the
sending end (the substation) and given the loads.
The sending end voltage at the substation is normally
controllable (and therefore known) through the tap
setting of the transformer or through the voltage
regulator.
The receiving end voltage at the customer is normally
not controllable, although it is important since the
customer appliances require that the voltage
magnitude lie within a certain range in order to
properly operate.
Voltage Drop Calculation for Primary
Circuit for Radial System
20-Mar-21 75
Example 6
76
Example 6, solution
Current in section AD is the vector sum of the three
load currents:
I AD = 50 + 100(0.8 − j 0.6) + 50(0.6 − j 0.8) = 160 − j100 A
Current in section DC is :
I DC = 160 − j100 − 50 = 110 − j100 A
77
Example 6, solution
The impedance of section DC is:
100
Z DC = (0.02 + j0.4) = 0.004 + j0.008
500
Current in section CB is :
I CB = 50(0.6 − j 0.8) = 30 − j 40 A
79
Voltage Drop Calculation for a Ring
System
20-Mar-21 80
Example 7
A
1+j1
1+j3
B C
1+j2
20 A, 0.8 15 A, 0.6
p.f. p.f.
20-Mar-21 81
Example 7, solution
20-Mar-21 82
Voltage Drop Calculation for Primary
Circuit Using K-factor
Example 8
A primary feeder system is composed of a primary feeder and two
laterals as shown below. Each lateral is connected to a uniformly
distributed load with total kVA of 518 kVA. The maximum allowed
voltage drop is 4%. The voltage level of the main and laterals are
2400/4160 V. The distance between phases is 37 inches. Use ampacity
sized conductors but in no case smaller than AWG # 6 for reasons of
mechanical strength. Determine:
The %VD at the end of laterals and main
If 4% max VD criterion is exceeded, find a reasonable combination of
larger conductors for both the main and the laterals that will meet the
VD criterion
Example 8, solution
The current in the lateral is: I 518
lateral = = 72 A
3 4.16
From table A1, AWG # 6 copper conductor with 130 A
ampacity is selected for the lateral.
1036
I main = = 144 A
The current in the main is: 3 4.16
20-Mar-21 84
Example 8, solution
1
%VDlateral = K kVA L =
2
1 5760
0.015 518 = 4.24%
2 5280
%VDmain = K kVA L =
3300
0.01 1036 = 6.48%
5280
85
Example 8, solution
And hence the voltage drop is more than the required value.
Determine:
– The total load on the transformer in kVA and in pu.
– The total steady-state voltage drop in pu at the most remote and severe
customer’s meter for the given annual maximum system load.
20-Mar-21 87
Example (Cont’d)
20-Mar-21 88
Table A: Single-phase 7200-120/240 V distribution
transformer data at 65C
Rated Core Loss Copper Loss R X Excitation
kVA kW kW pu pu Current
A
20-Mar-21 89
Table B: Twin concentric Al/Cu XLPE 600 V cable
data
~
K*
R(/1000 ft) per conductor X(/1000 Per unit voltage
Direct-burial drop per 104 A.ft
ft)
Size Ampacity
Phase Neutral per phase
A 90 % 50 %
conductor Conductor conductor
PF PF
90C 80C
2 AWG 0.334 0.561 0.0299 180 0.02613 0.01608
1 AWG 0.265 0.419 0.305 205 0.02098 0.01324
1/0 AWG 0.21 0.337 0.0297 230 0.01683 0.01089
2/0 AWG 0.167 0.259 0.029 265 0.0136 0.00905
3/0 AWG 0.132 0.211 0.028 300 0.01092 0.00752
4/0 AWG 0.105 0.168 0.0275 340 0.00888 0.00636
250 kcmil 0.089 0.133 0.028 370 0.00769 0.00573
350 kcmil 0.063 0.085 0.027 445 0.00571 0.00458
500 kcmil 0.044 0.066 0.026 540 0.00424 0.00371
20-Mar-21 90
Solution
Assume perfectly balanced loading in all three-wires single-phase circuits,
and nominal operating voltage of 240 V when computing currents from kVA
loads.
To calculate the total steady-state voltage drop in pu at the most remote and
service customer’s meter. We have to calculate the per unit voltage drops in
the transformer, the service line, and that of the most remote and severe
customer. This is carried out as follows:
For the transformer:
VDTr = ZI = (0.0101+j0.0143)*0.96 angle(-25.8)
= 0.0168 angle(28.9o)
20-Mar-21 91
Solution (Cont’d)
– For the service lines:
ISL = SSL, max / Voperating = (6+7+8+10)kVA / 240 V =31 / 240 = 129.17 A.
20-Mar-21 92
Solution (Cont’d)
20-Mar-21 93
Solution (Cont’d)
V = 1 – 0.0168 = 0.9832
– For the service lines:
ISL = SSL, max / Voperating = (6+7+8+10)kVA / (0.9832*240) V = 131.3 A.
3000
Z12 = (0.3 + j 0.6) = 0.1705 + j 0.3409
5280
4000
Z 23 = (0.3 + j 0.6) = 0.2273 + j 0.4545
5280
A single phase example-Solution
Step 1:
Assume node 3 voltage is V3=7200/0◦ .V
Step 2: (Forward sweep)
From node 3 voltage & node 3 power, we get node 3 load
current from S=VI*.
* *
S3 (900 + j500) 10
3
I 3 = = = 143 − 29.0 A
V3 7200
The node 2-3 current is equal to the node 3 current.
I 23 = I 3 = 143 − 29.0 A
A single phase example-Solution
The node 2 voltage is:
V2 = V3 + I 23 Z 23
= 72000 + 143 − 29.0(0.2273 + j 0.4545)
= 7260.10.32
Node 2 load current is
* *
S2 (1500 + j 750) 103
I 2 = = = 231.0 − 26.3
V2 7260.10.32
Node 1-2 current is
I12 = I 2 + I 23
= 231.0 − 26.3 + 143.0 − 29.0
= 373.9 − 27.3
A single phase example-Solution
The node 1 voltage is:
V1 = V2 + I12 Z12
= 7260.10.32 + 373.9 − 27.3(0.1705 + j 0.3409)
= 7376.20.97
8 4 10 11
12
9 7 5
13
20-Mar-21 116
References
[5] C. Morrison, "A linear approach to the problem of planning new feeder points
into a distribution system," AIEE Trans., pt. III (PAS), Dec. 1963, pp. 819-832.