Professional Documents
Culture Documents
12.application of Capacitors
12.application of Capacitors
12.application of Capacitors
Distribution Systems
28-Mar-21 1
Introduction
Capacitors provide tremendous benefits to distribution
system performance. Most noticeably, capacitors
reduce losses, free up capacity, and reduce voltage
drop:
– Losses; Capacity: By providing the reactive power to motors and
other loads with low power factor, capacitors decrease the line
current. Reduced current frees up capacity; the same circuit can serve
more load. Reduced current also significantly lowers the I2R
line.
28-Mar-21 2
Introduction
If applied properly and controlled, capacitors can
significantly improve the performance of distribution
circuits.
28-Mar-21 3
Introduction
The problem faced by a distribution engineer is to decide for
a given feeder
– How much capacitance is necessary?
– Should the capacitance be fixed or switchable?
– Where should the capacitance be located?
This problem is complex and often, there is no method that
will provide a single solution. Identifying the most desirable
solution results from assessment of operational effects in
relation to investment levels.
What we will do in the remainder of these notes is to provide
certain evaluation strategies that give the distribution
engineer a means to assess the operational effects.
To be clear, we define operational effects in terms of
– Voltage regulation and
– Reduced power losses
28-Mar-21 4
Capacitor Construction
Capacitor elements have
sheets of polypropylene film,
less than one mil thick,
sandwiched between
aluminum foil sheets.
Capacitor dielectrics must
withstand on the order of 78
kV/mm. No other medium-
voltage equipment has such
high voltage stress.
28-Mar-21 5
Capacitor Construction
Capacitor units are supplied
with an internal discharge
resistor.
The purpose of the discharge
resistor is to provide a path
for current to flow in the
event that the capacitor is
disconnected from the source.
28-Mar-21 6
Capacitor Connection
28-Mar-21 7
Capacitor use in the Distribution
Network
The application of capacitors in the distribution systems
can be summarized as follows:
28-Mar-21 8
Capacitor use in the Distribution
Network
28-Mar-21 9
Capacitor Ratings
Capacitors should not be applied when any of the following
limits are exceeded:
• 135% of nameplate kvar.
• 110% of rated RMS voltage.
• 135% of nominal RMS current based on rated kvar and
rated voltage.
• Capacitors are designed to withstand over-voltages for
short periods of time.
28-Mar-21 10
Capacitor Losses
• Capacitor losses are typically on the order of 0.07
to 0.15 W/kvar at nominal frequency.
• Losses include resistive losses in the foil,
dielectric losses, and losses in the internal discharge
resistor.
• Capacitors must have an internal resistor that
discharges a capacitor to 50 V or less within 5 min
when the capacitor is charged to the peak of its
rated voltage . This resistor is the major component
of losses within a capacitor.
28-Mar-21 11
Capacitor Connection
a) Delta-connection
For delta connection, the single phase capacitor is a two
bushing capacitor unit.
28-Mar-21 13
a) Delta-connection
Example-1-solution
2400
kVAR / phase = = 800 kVAR / phase
3
28-Mar-21 14
Capacitor Connection
b) Y-connection
For Y connection, the single phase capacitor is a single
bushing capacitor unit.
28-Mar-21 16
b) Y-connection
Example-2
28-Mar-21 17
b) Y-connection
Example-2-solution
7200 2 7200 2
Z B = ZC = − j = − j32.4 ZA = − j = − j37.0
8 200,000 7 200,000
The source voltage references are selected as:
VAN = 72000, VBN = 7200 − 120, VCN = 7200120
7200120
IC = = 222.2210 A I N = −(I A + I B + I C ) = 27.690 A
32.4 − 90
28-Mar-21 18
a) Power Factor Correction
One of the main advantages of the application of
capacitors is the power factor correction.
28-Mar-21 19
Power Factor Correction Equations
28-Mar-21 20
Power factor corrections values
Correction factor = Qcap/Pload
28-Mar-21 21
Example-3
28-Mar-21 22
Power factor corrections values
Correction factor = Qcap/Pload
28-Mar-21 23
Solution:
28-Mar-21 24
From the capacitor rating Table the next
higher standard capacitor size is 400 kVAR,
therefore the resulting new correction factor
can be found to be
= 400/455 = 0.879
28-Mar-21 25
Power factor corrections values
Correction factor = Qcap/Pload
28-Mar-21 26
• From power correction Table by
linear interpolation, the resulting
corrected power factor, with an
original power factor of 0.65 and a
correction of 0.879 can be found as:
(0.879 − 0.878)
New corrected power factor = 0.96 + (.97 − .96) * = 0.96025 0.96
(0.918 − 0.878)
28-Mar-21 27
b) Voltage Support
As mentioned earlier, capacitors are used to
improve the voltage profile for the feeders.
28-Mar-21 28
b) Voltage Support
28-Mar-21 29
Voltage Rise From Capacitors
Let’s consider the simple circuit on shown below
VL
Z IL
IS
IC
ZL
28-Mar-21 30
Voltage Rise From Capacitors
Define the voltage rise obtained from switching in the
capacitor as ΔVL, given by:
VL = VL − VL
or,
VL = VS − I S Z − VS + I S Z
= ( I S − I S )Z
or,
VL = − I C Z
28-Mar-21 31
Voltage Rise From Capacitors
VL = VL − VL IC
Phasor rotation
VL = VL + VL
V L = V L + (− I C Z )
VL
ΔVL
VL = VL + (− I C R − jI C X ) -ICR
-jICX V’ L=VL+ΔVL
28-Mar-21 32
Voltage Rise From Capacitors
In terms of voltage magnitude,
V L = I C X
For a single phase systems
QC QC
IC = VL = X
VL VL
In terms of percentage voltage rise (%R), we have:
VL QC
% R = 100 = 100 2 X
VL VL
QC1
% R = 100 2 X (for single phase feeders)
VL , LN
QC 3 / 3 QC 3
% R = 100 X = 100 X (for 3-phase feeders)
(V L , LL / 3 )
2
VL2, LL
28-Mar-21 33
Fixed Shunt Capacitors
The main concept here is that since these
capacitors are on all of the time, they must apply to
all loading conditions.
The consequence of this is that in sizing fixed
capacitance for correcting voltage, we must do it
for the lightest-load conditions (highest voltage
level).
Otherwise, if we size for heavy load conditions,
the less loaded conditions will see overvoltages.
28-Mar-21 34
Approach for Sizing Fixed Capacitance
1. At the lightest load conditions (perhaps 25% of peak), identify the
load-end voltage with no capacitors. Call this Vlight.
2. Identify the maximum feeder voltage allowable (typically
corresponding to 126 volts on the residential service side). Call this
Vmax.
3. Compute the allowable percent rise:
Vmax − Vlight
%R = 100
Vlight
4. Compute reactive power required from capacitance:
(% R )Vlight
2
(% R )Vlight
2
QC = QC 3 =
100 X 100 X
28-Mar-21 35
Switched-Shunt Capacitors
At certain times of the day, the load will exceed the level
for which the fixed shunt caps were designed.
If we reach a load level where V<Vmin on any bus, it is
unacceptable.
Vmax
Voltage
of
minimum
voltage Vmin
bus
Loading as % of peak
28-Mar-21 37
Control Methods for Switching Shunt Capacitors
28-Mar-21 39
Control Methods for Switching Shunt Capacitors
28-Mar-21 40
Design Approach for Switched Capacitors
Vmax
Voltage
of
minimum
voltage Vmin
bus
Effects of
time-clock Effects of
switched voltage
capacitors switched
capacitors
Loading as % of peak
28-Mar-21 41
Approximate Calculation for Voltage
Rise
“K” Factor:
The Krise is similar to the Kdrop factor except that the
load now is a shunt capacitor. When a leading current
flows through an inductive reactance there will be a
voltage rise instead of voltage drop.
Vrise = ZI cap
Vrise = Z I cap = (.25 + j 0.6) 0.052590 = 0.034 V
0.0315
K rise = = 0.000537% rise / kVAR.mile
11000 / 3
7000
I load = − cos −1 (0.9) = 367 − 25.8
3 11
Vdrop = ( Z .I ) = 238.6 V
28-Mar-21 44
Example-4 Solution
238.6
%Vdrop = = 3.76%
11000 / 3
Vrise 2.26
kVAR = = 1403 kVAR
K rise mile 0.000537 3
28-Mar-21 45
c) Reducing Line Losses
One of the main benefits of applying capacitors is
that they can reduce distribution line losses.
Losses come from current through the resistance
of conductors.
Some of that current transmits real power, but
some flows to supply reactive power.
It is desirable to determine the size and location
of capacitors to maximize line loss reduction
28-Mar-21 46
c) Reducing Line Losses
where:
Ip = magnitude of in-phase component of line
current
Iq = magnitude of quadrature component of
line current
28-Mar-21 47
c) Reducing Line Losses
(
IL = I 2
p + (I q − I c ) )
2 1/ 2
where:
Ic = magnitude of the capacitor current
28-Mar-21 48
c) Reducing Line Losses
Example-5
If the load (700 kVA) in example 3 was
connected to the source via a feeder with the
following impedance: Z = 0.5+j1.3, find the line
losses before and after power factor correction.
Also, find the optimum location of the capacitor
for maximum line loss reduction.
28-Mar-21 49
c) Reducing Line Losses
Example-5-solution:
P = 700(.65) = 455 kW
Losses = 3 I 2 R
I L1 =
455
= 97 A Losses = 14.16 kW
3 4.16 .65
I L2 =
455
= 38.2 A Losses = 2.19 kW
3 4.16 .96
28-Mar-21 50
Capacitor Location
Consider the following feeder shown below.
The feeder length is l.
The feeder has a large number of loads uniformly distributed about its
length.
The feeder has a lumped reactive load at the end, drawing a current kI 1.
“I1” denotes the quadrature current component ( the reactive current) of
the load.
where Ii and Ri are the current and the resistance of each line segment
28-Mar-21 52
Losses Without Capacitor
In all of what follows, “I” denotes the quadrature current
component( the reactive current)
Let’s go back to the case of a uniformly distributed load
along the feeder
I1 I2 I3 I4 I5 I6 I7 I8 IM
IS
R1 R2 R3 R4 R5 R6 R7 R8
I ( x ) = I 1 − I ( x ) = I 1 − ( I 1 − I M ) x
Now what are the losses in a small length of the feeder at x
having resistance Rdx?
This will be:
dPL = 3 I ( x ) Rdx = 3I1 − (I1 − I M )x Rdx
2 2
28-Mar-21 54
Losses Without Capacitor
And now we can find the total losses in the feeder as:
1
PL = 3 I1 − ( I1 − I M ) x Rdx
2
PL = I12 + I1 I M + I M2 R
where
– PL is total 3-phase losses in feeder without cap.
– I1 is reactive current at beginning of feeder
– IM is reactive current at end of feeder
– R is total feeder resistance
28-Mar-21 55
Losses With Capacitor
Now let’s consider installation of one capacitor bank.
Assume it will be located at x=x1, which is just some
arbitrary point on the feeder, as illustrated below
I1 I2 I3 I4 I5 I6 I7 I8 IM
IS
R1 R2 R3 R4 R5 R6 R7 R8
x1 x
28-Mar-21 56
Losses With Capacitor
0 x x1
I ( x ) = I 1 − I ( x ) − I C
= I1 − (I1 − I M )x − I C
dPL = 3 I 2 ( x ) Rdx
= 3I1 − ( I1 − I M ) x − I C Rdx
2
28-Mar-21 57
Losses With Capacitor
x1 x 1.0
The downstream load will not be affected by the capacitor!
Therefore, for this case, the differential loss expression is the
same as the expression without the capacitor,
dPL = 3I1 − (I1 − I M )x Rdx
2
0
1
+ 3I1 − (I1 − I M )x Rdx
2
x1
PL = I 12 + I 1 I M + I M2 R
+ 3 x1 R ( x1 − 2 )I 1 I C − x1 I M I C + I C2
Therefore the loss reduction with the installation of the
capacitor is:
PL − PL = −3x1 R (x1 − 2)I1 I C − x1 I M I C + I C2
28-Mar-21 59
Losses With Capacitor
Now let’s normalize the above expression by PL.
PLR =
− 3 x1 R ( x1 − 2)I 1 I C − x1 I M I C + I C2
I 12 + I 1 I M + I M2 R
=
3 x1 (2 − x1 )I 1 I C + x1 I M I C − I C2
I 12 + I 1 I M + I M2
where,
PLR= the percentage loss reduction
Now let’s factor out an I12 from top and bottom, resulting in
28-Mar-21 60
Losses With Capacitor
2
3 x1 I 1 (2 − x1 ) + x1
I I I I
2 C M C
2
− 2
C
PLR = I1 I1 I1
I I 2
I 1 1 +
2 M
+ 2
M
I1 I1
There are two interesting ratios that appear in the above eq.
One is IC/I1 and the other is IM/I1. Let’s cancel the I12 out
IC IC
2
3 x1 (2 − x1 ) + x1
IC IM
−
I1 I1 I1 I1
PLR =
I IM
2
1 + M
+
I1 I1
28-Mar-21 61
Losses With Capacitor
Now define these ratios:
IC kVA of cap installed
c= =
I 1 kVA of total reactive load
28-Mar-21 62
Losses With Capacitor
The meaning of λ-ratio :
28-Mar-21 63
Losses With Capacitor
Replacing the corresponding ratios in the previous eq., we
have:
PLR =
3 x1 (2 − x1 )c + x1c − c 2
1 + + 2
Factoring out the c-parameter from the bracketed term in the
numerator, we have:
3 x1 c (2 − x1 ) + x1 − c
PLR =
1 + + 2
28-Mar-21 64
Losses With Capacitor
The above equation is a very useful equation. Since λ is
determined by the feeder (not a design characteristic), then
we can assume for a given situation that it is given. Then
our problem is to identify
– The optimal amount (by identifying c)
– The optimal location (by identifying x1).
The optimal amount or location can be obtained by taking
derivatives with respect to either c or x1, setting to zero,
and solving.
Note that we cannot optimize the amount and the location
simultaneously since the optimal amount depends on the
location, and the optimal location depends on the amount.
28-Mar-21 65
Losses With Capacitor
Procedure:
1. Fix λ.
2. Fix c at low number, e.g., c=k=0.1.
3. Find optimal value of x1.
4. Increment c by k, i.e., c→ c+k
5. If c>1, stop, otherwise, go to 3.
This approach is just finding optimal location (x1)
for various values of c, as c is incremented by 0.1
from 0.1 to 1.
28-Mar-21 66
Optimal Capacitor Location
Differentiation PLR eqn. with respect to x1 and equate that
to zero, we obtain:
6 x1,opt ( − 1) + (6 − 3c ) = 0
28-Mar-21 68
c) Reducing Line Losses
Example-6
For the reactive load shown below for a 4.16
feeder, determine the fixed and switched
capacitor to be added to correct the power
factor?
28-Mar-21 69
c) Reducing Line Losses
Example-6-solution
28-Mar-21 72
c) Reducing Line Losses
Optimum capacitor size and location:
kI − I
i ( x) = 1 1 .x + I1 − I C for 0 x x '
L
kI − I
i ( x) = 1 1 .x + I1 for x ' x L
L
2
kI − I
x'
PLoss = 1 1 .x + I1 − I C .R.dx
0
So: L
2
kI − I
L
+ 1 1 .x + I1 .R.dx
x' L
28-Mar-21 73
c) Reducing Line Losses
Optimum capacitor size and location:
x '2
L
PLoss = ( I1 I C (1 − K ) + x' ( I C2 − 2 I1 I C ) + I12 ( K 2 + K + 1) .R
L 3
• For a given load profile, line length,
and resistance, the quantities K, I1, R and
L are constant.
• The only two variables are IC and x’.
• To determine the optimum capacitor
size and location to minimize losses, the
partial derivatives are taken for these
two variables, IC and x’.
PLoss
=0=
2 x'
I1I C (1 − K ) + ( I C2 − 2I1I C ) (1)
x' L
PLoss
= 0 = I1 (1 − K ) + 2 I C − 2 I1
x'
(2)
I
28-Mar-21C
L 74
c) Reducing Line Losses
Optimum capacitor size and location:
Solving equation no.1 will result in:
− ( I C2 − 2 I1 I C ) L
x' =
I1 I C (1 − K ) 2
It is convenient to express the capacitor
current IC as a function of the reactive
current I1
L 2 −
I C = I1 x ' = (3)
2 1 − K
Substituting equations (3) in (2) will
results in:
3 2
0 = −1 =
28-Mar-21
2 3 75
c) Reducing Line Losses
Optimum capacitor size and location:
So the size of the capacitor is 2/3 of the total reactive current
entering the feeder. If this value is substituted in equation 3, then:
2 1
x' = L
3 1 − K
28-Mar-21 77
c) Reducing Line Losses
Capacitor size and placement:
• A generalization of the 2/3 rule for applying n
capacitors to a circuit is to size each one to 2/(2n+1)
of the circuit var requirements.
• Apply them equally spaced, starting at a distance of
2/(2n+1) of the total line length from the substation
and adding the rest of the units at intervals of
2/(2n+1) of the total line length.
28-Mar-21 78
c) Reducing Line Losses
Capacitor size and placement:
• The total vars supplied by the capacitors is
2n/(2n+1) of the circuit’s var requirements.
• So to apply three capacitors, size each to 2/7 of the
total vars needed, and locate them at per unit
distances of 2/7, 4/7, and 6/7 of the line length from
the substation.
28-Mar-21 79
Example 7:
28-Mar-21 80
Example 7-solution:
The ratio of reactive power at the end of the line section to the
reactive power at the beginning of the line is:
600
K= = 0.3
2000
Since K is less than 1/3, the optimum capacitor rating is two-
thirds time the reactive loading at the beginning of the line
section, i.e. kVARCAP = (2/3)*2000=1333.3 kVAR
2 1
x' = (3) = 2.86 miles
3 1 − 0 .3
28-Mar-21 81
d) Released Capacity
• In addition to reducing losses and improving voltage,
capacitors release capacity.
• Improving the power factor increases the amount of real-
power load the circuit can supply.
28-Mar-21 82
d) Released Capacity
28-Mar-21 83
Example 8:
In the following Figure a primary line with uniformly distributed load.
The voltage at the distribution substation low-voltage bus is held at 1.03
pu V with bus voltage regulation. When there is no capacitor bank
installed on the feeder, the per unit voltage at the end of the line at annual
peak load is 0.97. Use the nominal operating voltage of 13.8 KV of the
three-phase as the base voltage. Assume that the off peak load of the
system is about 25% of the on peak load. Also, assume that the line
reactance is 0.80 Ω /(phase.mi) but the line resistance is neglected and
determine the following:
a- When the shunt capacitor bank is not used, find the Vx, voltages at the
times of peak load and off-peak load.
b- Apply an un-switched capacitor bank and locate it at the point of X = 4
mi on the line, and size the capacitor bank to yield a voltage of 1.05 per
unit at point X=0 at the time of zero load. Find the size of the capacitor in
three phase kilovars.
28-Mar-21 84
Example 8, solution
The current flowing through any segment along a feeder with
uniformly distributed load can be calculated from the
following equation (no installed capacitors exist):
x
I x = I S 1 −
l
The voltage drop across this segment can be calculated from
the following equation:
dVD x = I x z dx
28-Mar-21 85
Example 8, solution
The total voltage drop from the source point to point x along
the feeder is given by:
x x
VD x = dVD x = I x z dx
0 0
x
x
VD x = I S 1 − z dx
0 l
x2 x
VD x = I S z x − = I S z x 1 −
2l 2l
28-Mar-21 86
Example 8, solution
The total voltage drop from the source point to the feeder
end-point is given by:
l2 l
VD l = I S z l − = I S z
2l 2
x
x 1 −
VD x % VD x 2l x x
= = = 2 −
VDl % VDl l l l
2
28-Mar-21 87
Example 8, solution
The total voltage drop from the source point to the feeder
end-point (no installed capacitors exist) at the peak load is
given by:
VDl , pu = 1.03 − 0.97 = 0.06 pu = 6 %
VD x x x 2 2 8
= 2 − = 2 − = = 0.888
VD l l l 3 3 9
VD x = 0.888 x 0.06 = 0.0533 pu
28-Mar-21 90
Capacitor banks switching control
28-Mar-21 91
Capacitor banks
28-Mar-21 92
Capacitor banks
– Vars:
• The capacitor uses var measurements to
determine switching.
• This is the most accurate method of ensuring
that the capacitor is on at the appropriate times
for maximum reduction of losses.
• Like the voltage control technique, there is a
bandwidth for switching of each capacitor bank
to prevent excessive switching operations in
most cases.
28-Mar-21 93
Control Methods used for Switched Capacitors
28-Mar-21 94
Capacitor Switching Consideration
28-Mar-21 96
Switching Single Capacitor Bank
Vo / s
I ( s) =
sLs + (1 / sC )
28-Mar-21 98
Switching Single Capacitor Bank
Vo / Ls
I ( s) = 2
s + (1 / Ls C )
Re-arranging the equation:
o
1/ 2
C
I ( s ) = Vo s2 + 2
L o
Where:
1
o =
Ls C
1/ 2 1/ 2
C C
i (t ) = Vo sin( o t ) I max = Vo
L L
28-Mar-21 99
Example 9:
28-Mar-21 100
Example 9-solution:
X = 0.07.
(4.16kV )
2
= 0.242
5MVA
0.242
The transformer inductance is: L= = 6.43 10 −4 H
2 .60
2 .4160
The peak source voltage is: Vo = = 3396V
3
1/ 2
1.84 10 −4
I max = 3396
−4
= 1817 A
6.43 10
28-Mar-21 101
Example 9-solution:
28-Mar-21 102