Space Engineering Co.,ltd.

46/38 Nguyen Cuu Van


Binh Thanh, HCM

Calculation sheet Fire Sprinkler & Hydrant calculation summary Project: First solar Phase 2
Prepared by: Hieu.Thach
Checked by: Hoan.Le Date: 17-Apr-18

1 Logicstic zone
1.1 To NFPA 13 2016

Input data: Product: Solar panel, storaged height up to 6.1m

Class II: noncombustible product that is in slatted wooden crates, solid wood boxes, multiple-
Class of commodity: layered corrugated cartons, or equivalent combustible packaging material, with or without
pallets.
As figure 14.2.4.1

Design area 200 m2


Density 9.5 mm/min = 0.158 l/s.m2
Total flowrate for current design area 32 l/s
Minimum operating pressure 50 Kpa
Number of sprinklers in calculation 17 nos
Number of sprinklers in calculation 1.86 l/s = 112 l/min
Sprinkler's K factor 11.2 (gpm & psi) = 14 (l/min & kPa)

Total inside and outside hose stream allowance flowrate 250 gpm = 16 l/s
Inside hose stream allowance 100 gpm = 5 l/s
Outside hose stream allowance 150 gpm = 11 l/s

Water supply duration 90 min


Water storage tank volume 260 m3

1.2 Hyena Calculation Result & Analysis

Maximum demand flowrate: (zone 9) 4,556 l/min = 75.9 l/s


Plus outside hose stream allowance demand 11 l/s
Total flowrate 87 l/s
Require pressure 625 Kpa

Area Flowrate(l/min) Pressure(kPa)


Zone 1 3339 625
Zone 2 3753 541
Zone 3 3997 564
Zone 4 4029 540
Zone 5 4151 545
Zone 6 3706 516
Zone 7 3673 514
Zone 8 3733 539
Zone 9 4556 625

Summary all.xls
2 Factory Zone
2.1 To NFPA 13 2016
Classification of occurpancy OH2
As figure 11.2.3.1.1

Design area 139 m2


Density 8.1 mm/min = 0.135 l/s.m2
Total flowrate for current design area 19 l/s
Minimum operating pressure 50 Kpa
Number of sprinklers in calculation 13 nos
Flowrate per 1 sprinkler 1.44 l/s = 87 l/min
Sprinkler's K factor 5.6 (gpm & psi) = 8 (l/min & kPa)

Total inside and outside hose stream allowance flowrate 250 gpm = 16 l/s
Inside hose stream allowance 100 gpm = 5 l/s
Outside hose stream allowance 150 gpm = 11 l/s

2.2 Hyena Calculation Result & Analysis

Maximum demand flowrate: (zone 25) 2,661 l/min = 44.4 l/s


Plus outside hose stream allowance demand 11 l/s
Total flowrate 55 l/s
Require pressure 711 Kpa

Area Flowrate (l/min) Pressure( kPa)


Zone 10 2,223 563
Zone 11 2,661 639
Zone 12 2,438 686
Zone 13 2,353 666
Zone 14 2,363 638
Zone 15 2,445 701
Zone 16 2,377 676
Zone 17 2,437 681
Zone 18 2,389 666
Zone 19 2,259 568
Zone 20 2,331 620
Zone 21 2,447 623
Zone 22 2,438 702
Zone 23 2,419 683
Zone 24 2,354 653
Zone 25 2,464 711
Zone 26 2,445 691
Zone 27 2,448 674
Zone 28 2,378 589
Zone 29 2,372 620
Zone 30 2,302 601
Zone 31 2,283 600
Zone 32 2,266 583
Zone 33 2,333 601
Zone 34 2,255 580
Zone 35 2,270 588
Zone 36 2,230 573

Summary all.xls
3 Office Zone
3.1 To NFPA 13 2016
Classification of occurpancy OH2
As figure 11.2.3.1.1

Design area 139 m2


Density 4.1 mm/min = 0.068 l/s.m2
Total flowrate for current design area 9 l/s
Minimum operating pressure 50 Kpa
Number of sprinklers in calculation 13 nos
Flowrate per 1 sprinkler 0.73 l/s = 44 l/min
Sprinkler's K factor 5.6 (gpm & psi) = 8 (l/min & kPa)

Total inside and outside hose stream allowance flowrate 100 gpm = 5 l/s
Inside hose stream allowance 100 gpm = 5 l/s

3.2 Hyena Calculation Result & Analysis

Demand flowrate: 1,686 l/min = 28.1 l/s


Require pressure 552 Kpa

4 Technical data (as NFPA calculation)


Pump capacity
Flowrate 87 l/s
Head 750 kPa
Logicstic
Sprinkler's branch lines DN65
Sprinkler's K factor: 11.2 (gpm & psi)
Factory
Sprinkler's branch lines DN40
Sprinkler's K factor: 5.6 (gpm & psi)
Office
Sprinkler's K factor: 5.6 (gpm & psi)