Download as pdf or txt
Download as pdf or txt
You are on page 1of 46

Learn more about RM6 24

and its new applications


Energy Business Training

● Understand the RM6 offer and its new applications


● Know the technical solutions provided

Speaker: Lowell Estrella


MV Marketing
Situate the 24 kV Ring Main Unit
In HV/MV, MV/LV substations

RM6 IDI RM6 II RM6 IQI

RM6 IIDI

RM6 DI
RM6 IQI RM6 IBI

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 2
1 - Explanation of the RM6 offer and its new
applications
Contents
Explanation of the RM6 offer and its new
applications
Transformer and line protection
RM6 offer strong points
Selling points / markets
Network connections
Accessories and options
What to remember

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 3
4 basic functions to choose from: I, B, D, Q
Network Line feeder 630A Transformer feeder Transformer feeder
switch circuit breaker 200A circuit breaker combined
fuse-switch

I function B function D function Q function


400 or 630A Line protection Transformer 200A transformer
protection only protection

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 4
4 additional functions
Network coupling Network coupling Cable MV
switch 630A circuit breaker connection metering

IC function BC function O function Mt function

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 5
Representation of devices
Types of tanks:
NE: non extensible
RE: right extensible
LE: left extensible
(O function)
DE: double extensible I I Q I

NE-IIQI Substation
Function configurations:
Multifunction configurations Unit configurations

Examples of designations:
RM6 NE-IIQI RM6 NE-D
RM6 RE-DIDI RM6 DE-Mt

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 6
Extensibility options: RE, DE

RE: Right Extensible DE: Double Extensible


(1 function)

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 7
Double extensibility on 3 and 4 functions
RE IIDI DE IC DE IIDI

● DE-III, DE-IIII, DE-IDI, DE-IIDI


● DE-IBI, DE-IIBI, DE-IQI, DE-IIQI

RE IIDI DE IC DE I DE I DE D DE I

DE-I+ DE-I+ DE-D+ DE-I = 2.100 mm 100 (base Euro)


RE IIDI DE IC DE IIDI

DE-IIDI = 1.600 mm 50 (base Euro)

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 8
Medium Voltage metering

● Air insulation, with conventional VTs


and CTs
● Insensitivity to the environment:
● Fully closed
● Connected directly to the adjacent
busbars
● Internal arc withstand
● Optional LV cabinet

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 9
ATS: Automatic Transfer System

● The ATS includes:


● an Easergy T200I
● motorised switch functions
● Voltage presence indicator (VPIS with
voltage output)
● VD23 voltage detector
● Fault indicator (included in Easergy T200I)
● Possibility of communication with the
SCADA
● Automatic control
● Supervision of power sources

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 10
2 - Transformer and line protection

Contents
Explanation of the RM6 offer and its new
applications
Transformer and line protection
RM6 offer strong points
Selling points / markets
Network connections
Accessories and options
What to remember

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 11
Circuit breaker protection
Transformer protection Line protection
D function: 0 to 200A B function: 0 to 630A

● Simple threshold setting: 0 to 200A 0 to 630A


just one button to turn

● Adaptable: same CTs from 0 to 200A same CTs from 0 to 630A

● setting of different
thresholds if the installation
is modified
VIP 30: phase faults VIP 300: phase and earth
VIP 35: phase and earth faults faults
● The most suitable Sepam Series 10: phase and Sepam Series 10: phase
protection earth faults and earth faults

● More sensitive detection Transformer overload protection


from 20% of setting current
than with fuses

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 12
VIP relays
For transformer feeders: For line feeders:

- VIP 30 phase/ - VIP 35 phase/phase - VIP 300 phase/phase and earth


phase protection and earth protection protection (top discrimination with
multiple curves)

Vip 30 and 35 phase Vip 35 earth Phase and earth


protection protection protection

● Operating tests with or without tripping

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 13
Sepam Series 10 relay

● Very sensitive earth fault


● Possibility of remote communication
● Overload protection with thermal image
● Logic discrimination
● Recording of the last fault or last 5 events

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 14
MV/LV transformer feeder: which kind of
protection ?
● Circuit breaker protection is the only solution for large transformers

RM6 Circuit breaker range (D function) Fuse switch range (Q function)

Switchgear

Standard IEC 62271-100 IEC 62271-105

MV/LV transformer 100 - 3000 kVA 100 - 1250 kVA


rating

Protection unit VIP 30/35 relays + sensors DIN fuses


t

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 15
Field of
Application
The RM6 is a compact unit combining
all MV functional units
to enable connection, supply and
protection of transformers
on an open ring or radial network:

1. by a fuse-switch combination for


100 - 1250 kVA

2. by a circuit breaker with


protection unit for 100 - 3000 kVA

Schneider Electric - Infrastructure -2012 May 16


Field of
Application
Operating a distribution network sometimes
requires switching points in addition
to the HV/MV substations, in order to limit
the effect of a fault on the network.

The RM6 offers a choice of solutions to


make 2, 3 or 4 directional connections:

1) with line protection by 630 A circuit


breakers
2) with network switching by switch-
disconnectors
3) with integrated power supply
telecontrol devices.

Schneider Electric - Infrastructure -2012 May 17


D or Q function: selling point strategy

Logistic costs for fuses &


1 set of fuses for
replacement

1 set of fuses Negotiation margin

RM6 IQI RM6 IDI


(switchgear)

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 18
D or Q functions - What is our strategy ?
The circuit breaker gives us a competitor advantage

Manufacturer =S= ABB F&G Siemens Ormazabal

switchgear type RMU RMU mod. RMU mod. RMU

product name RM6² CTC.V RGC GA24 8DH10 CGC

In (A) 200 / 200 630 200 630 630


630

insulation SF6 SF6 SF6 SF6 SF6 SF6

breaking SF6 vacuum vacuum SF6 vacuum SF6

costs ☺☺ ☺ ☺

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 19
D or B function: consider the price
Market price

Transformer protection
VIP30 At the MV / LV substation level

I D I
= 100

Network point
VIP300 Upstream of the MV / LV substation

I B I
> 120 to 160

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 20
- advantages of fuses

● Current-limiting capacity
● capability to limit short-circuit current

● Fast interruption
● for high short-circuit values

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 21
- drawbacks of fuses

● Only work once


● Fragile
● Dissipate a lot of energy as heat
(cost of Joule losses)
● Sensitive to aging (approximate service life: 10 years)
● Have a danger zone (In < I < I3)
● Possible single-pole breaking
● Application limited to small transformers
● One rating per application (large stock of spare parts)

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 22
- advantages of circuit breaker protection
● 10 to 100 times less dissipated power than with fuses

● Simple choice of equipment

● Variety of relays available:


● phase-to-phase fault protection
● earth fault protection
● overload protection
● etc...

● Possibility of adjusting protection relays (upgrading


capability)

● Possibility of testing operating capability (with or without


tripping)
Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 23
- cost comparison over time
Costs

1 spare set of fuses +


logistics and labor
Switch / fuse solution
100 € / 10 years

Joule losses
Joule losses 0.22 € / year
110 € / year

2 sets of fuses
Circuit breaker solution
Circuit breaker
Combination unit

1 year 10 years 20 years 30 years Time


Acquisition Operation

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 24
Summary - MV/LV Transformer : Which kind of protection?

Switch-fuse Circuit breaker


combination unit
● For very high I (rare) ● For very high I (rare)
● current-limiting effect ● no current-limiting effect
● fast breaking ● but reaction time: 70 to 100 ms

● For lower I ● For lower I


● danger zone: Irf - I 3 ● no use limitations
● no overload protection ● discrimination easily ensured
● slow with low current close to I 3
● choice of fuse difficult or impossible in
combination unit
● discrimination problems

● More generally speaking ● More generally speaking


● Joule losses (environment, losses of ● very low Joule losses
110 €/year with combination unit) ● possibility of remote reclosing
● need to change fuses, need for spare (telecontrol)
stock (with many different ratings) ● 30-year service life, no maintenance
● risk of thermal aging (service life: about ● flexibility: upgrading capability (change
10 years) of settings), earth fault protection, etc..
● fragility

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 25
3 - RM6 offer strong points

Contents
Explanation of the RM6 offer and its new
applications
Transformer and line protection
RM6 offer strong points
Selling points / markets
Network connections
Accessories and options
What to remember

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 26
Insensitivity to the environment

● GIS technology: switch and busbars in SF6, in a gas-tight compartment


● Sealed-for-life stainless steel tank

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 27
Extensibility = reduction of costs

● Compact size: space savings

● Flexibility to adapt to changes in MV networks

● Possible on-site installation by customers within 2 hours

● No handling of SF6 (direct connection to busbars)

● No specific tools required

● Investments postponed

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 28
Visible earthing

Closed Open Earthed

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 29
RM6 for Marine application
● Safety for personnel
● Resistance to vibrations
● Resistance to harsh environments

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 30
4 - Selling points / markets

Contents
Explanation of the RM6 offer and its new
applications
Transformer and line protection
RM6 offer strong points
Selling points / markets
Network connections
Accessories and options
What to remember

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 31
Situate the 3 markets

● Schneider Electric International MV market (RM6 + SM6):


> 5 billion Euros
Leading sector
60% Margin for progress

50%
10% Not the leading sector
for RM6, but specific
40%
applications
RM6 for simple, basic
applications
30%
43% 12% 0%
20%

10% 18% 17%

0%
Energy Building Industry

MV/LV distribution Transmission MV/MV substations


Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 32
Energy segment: RMU
RM6 (GIS) SM6 (AIS)

Switchgear RMU RMU Modular


Differentiating type non extensible extensible air insulated
customer key values

Insensitive to environment ☺☺ ☺☺
Easy installation ☺☺☺ ☺ ☺
(Including
Optimization of investments ☺☺ screened
connectors)
☺ ☺ ☺☺
Network upgrading ☺☺ ☺☺☺

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 33
Building/industry segments: SM6

Switchgear
RMU RMU SM6 modular
Differentiating type
non extensible extensible system
customer key values

Flexibility, width of offer ☺ ☺☺☺


Upgrading capability ☺ ☺☺☺
Optimization of investments ☺☺ ☺ ☺☺ ☺
Insensitivity to environment ☺ ☺☺ ☺ ☺☺

RM6 if the environment factor counts the most

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 34
Location: MCset, SM6, RM6
power
station

HV transmission

public industrial
distribution distribution
MV
MCset
primary MV primary primary process
distribution substation substation control

secondary MV pole-mounted secondary secondary


distribution switchgear substation substation

SM6 LV

RM6

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 35
5 - Network connections

Contents
Explanation of the RM6 offer and its new
applications
Transformer and line protection
RM6 offer strong points
Selling points / markets
Network connections
Accessories and options
What to remember

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 36
Connection interface

EN50181 standard

Type A Type B Type C


In (A) 200 400 630
Ith (kA/1s) 12.5 16 25
Insert ∅8 ∅ 14 M 16

Plug type plug-in plug-in bolted

Types of connection interface

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 37
Type of cables

● Controlled field, plug-in or disconnectable connectors


In (A) Ith (kA/1s) type of cables

Type A plug-in type 200 12.5 plastic insulated,


Type B plug-in type 400 16 single-core,
Type C bolted type M 16 630 25 (XPLE)

● Non controlled field, heat shrinkable elements or simplified


disconnectable connectors

plastic or oil
insulation, single or
Type C bolted type M 16 630 25
three core, (XPLE
or MIND)

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 38
Example of connection to C type bushing

● Directed field disconnectable connector


● C type bushing - 630A

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 39
6 - Accessories and options

Contents
Explanation of the RM6 offer and its new
applications
Transformer and line protection
RM6 offer strong points
Selling points / markets
Network connections
Accessories and options
What to remember

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 40
RM6 switches & fuse-switch combination
accessories ● Undervoltage release

● Opening release

● Voltage indicator
● VDS
● VPIS

● Motor mechanism

● Auxiliary contacts

● Fuse protection

Motor mechanism ● Cable connections


for fuse function

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 41
Fault passage indicator / Load current indicator
/ Voltage detector
● Amp 21D ammeter (new generation)

● Easergy Flair 21D, Flair 22D, Flair 23DV


● self-powered fault passage indicators
● detection of phase-to-phase faults and earth faults
● automatic setting on site

● Alpha type short-circuit indicator (Hortsmann)

● Voltage detector
● compatible with all types of earthing system

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 42
RM6 circuit breaker accessories

● VIP relay
or Sepam
Series 10

● Motor mechanism

● Auxiliary contacts

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 43
7 – What To Remember

Contents
Explanation of the RM6 offer and its new
applications
Transformer and line protection
RM6 offer strong points
Selling points / markets
Network connections
Accessories and options
What to remember

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 44
What to remember

● I function: networks from 400 to 630A

● Q and D functions: 200A network supply

● B function: 630A only

● BC, IC, O functions: 630A

● Mt function: 630A metering

● Short-circuit current: 16, 20, 21, 25 kA

● Network voltage: 12, 17.5, 24 kV

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 45
Energy Business training

Thanks !
Make the most of your energy

Schneider Electric - Power Business training - Learn more RM6-24 New Applications 02/2010 46

You might also like