Professional Documents
Culture Documents
Maintenance IPASO
Maintenance IPASO
iPASOLINK 1000
SECTION III MAINTENANCE
CONTENTS
1. General..........................................................................................................................1-1
2. Precaution ....................................................................................................................2-1
2.1 Maintenance and Operation Manual....................................................................................... 2-4
2.1.1 Wrist Strap Connection.................................................................................................... 2-4
2.1.2 Maintenance Mode Setting (for the LCT Operation) ........................................................ 2-5
2.1.3 Manual Switch Operation ................................................................................................ 2-9
3. Test Sets and Accessories .........................................................................................3-1
4. Current Status ..............................................................................................................4-1
4.1 Current Status......................................................................................................................... 4-1
5. Routine Maintenance...................................................................................................5-1
5.1 Meter Reading ........................................................................................................................ 5-1
5.2 Performance Monitoring ......................................................................................................... 5-3
5.2.1 PM Parameters ............................................................................................................... 5-3
5.2.1.1 PM Status Monitor Types....................................................................................... 5-3
6. Corrective Maintenance ..............................................................................................6-1
6.1 Alarm/Status ........................................................................................................................... 6-2
6.1.1 Alarm Management ......................................................................................................... 6-6
6.1.1.1 Alarm Class............................................................................................................ 6-6
6.1.2 Alarm and Status............................................................................................................. 6-7
6.1.2.1 ODU Alarms & Status ............................................................................................ 6-7
6.1.2.2 MODEM Alarms & Status ...................................................................................... 6-8
6.1.2.3 STM-1 Option Card Alarms & Status ..................................................................... 6-9
6.1.2.4 16E1 Option Card Alarms & Status...................................................................... 6-10
6.1.2.5 AUX-A Option Card Alarms & Status ................................................................... 6-11
6.1.2.6 GBE-A Option Card Alarms & Status................................................................... 6-11
6.1.2.7 EQUIPMENT COMMON Alarms & Status ........................................................... 6-12
7. Control Items................................................................................................................7-1
7.1 Loopback ................................................................................................................................ 7-2
7.1.1 IF Loopback..................................................................................................................... 7-2
7.1.1.1 IF Loopback (for 1+1 TP) ....................................................................................... 7-3
7.1.1.2 IF Loopback (for 1+1 HS)....................................................................................... 7-9
7.1.2 TDM Loopback Control.................................................................................................. 7-15
7.1.2.1 TDM Loopback Control (E1 Loopback1).............................................................. 7-15
7.1.2.2 TDM Loopback Control (E1 Loopback2).............................................................. 7-19
7.1.2.3 TDM Loopback Control (STM-1 Loopback1)........................................................ 7-23
7.1.2.4 TDM Loopback Control (STM-1 Loopback2)........................................................ 7-26
7.2 Equipment Maintenance ....................................................................................................... 7-29
7.2.1 Equipment Utility ........................................................................................................... 7-29
7.2.1.1 Database Upload (Export (NE-> Storage) Utility)................................................. 7-29
Maintenance NWD-118791-01E
March, 2011
Submission Prohibited
NEC Internal Use Only
-2-
7.2.1.2 Download Database (Update (Storage -> NE) Utility) .......................................... 7-32
7.2.1.3 Switch (Swap) Program ROM .............................................................................. 7-57
7.2.1.4 Check USB Memory Utility................................................................................... 7-61
7.2.1.5 Clear Provisioning Data ..................................................................................... 7-62
7.2.1.6 Adjust Current Date and Time.............................................................................. 7-64
7.2.2 Equipment Reset........................................................................................................... 7-66
7.2.2.1 Reset H/W............................................................................................................ 7-67
7.2.2.2 Reset F/W ............................................................................................................ 7-70
7.2.3 Radio Control ................................................................................................................ 7-75
7.2.3.1 ATPC Manual Control .......................................................................................... 7-77
7.2.3.2 TX Mute Control................................................................................................... 7-79
7.2.3.3 CW Control .......................................................................................................... 7-84
7.2.3.4 TX Modulation Manual Control (for AMR Mode only)........................................... 7-86
7.2.4 Laser Management ....................................................................................................... 7-89
7.2.4.1 Laser Shutdown Control ...................................................................................... 7-89
7.2.4.2 ALS Manual Switch Control ................................................................................. 7-92
7.2.5 Cluster Alarm Setting .................................................................................................... 7-94
7.2.6 Inventory........................................................................................................................ 7-98
7.2.6.1 Equipment Inventory Information ......................................................................... 7-98
7.2.7 Software License Key Information............................................................................... 7-105
7.3 Performance Monitor .......................................................................................................... 7-112
7.3.1 Link Performance Monitor ........................................................................................... 7-112
7.3.2 Monitor Report............................................................................................................. 7-112
7.3.2.1 MODEM PMON Report...................................................................................... 7-113
7.3.2.2 E1 PMON Report ............................................................................................... 7-117
7.3.2.3 STM-1 PMON Report......................................................................................... 7-121
7.3.2.4 ETH RMON Report ............................................................................................ 7-127
7.3.2.5 VLAN Counter Report ........................................................................................ 7-132
7.3.2.6 PMON/RMON/FDB Clear .................................................................................. 7-133
7.4 Offline Maintenance............................................................................................................ 7-137
7.4.1 DADE Adjustment ....................................................................................................... 7-137
7.4.2 RF Sub Band Selection ............................................................................................... 7-139
7.5 Maintenance Test ............................................................................................................... 7-142
8. Abbreviations ...............................................................................................................8-1
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
General 1-1
1. GENERAL
This section provides information regarding the routine and corrective maintenance
for the iPASOLINK of the 6 to 38 GHz PDH/SDH digital radio system.
The information includes the following with their instructions and procedures:
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
1-2 General
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Precaution 2-1
2. PRECAUTION
The maintenance personnel should report his/her arrival and departure from a station
to the relevant station. Following precautions must be carefully observed during
maintenance.
Warning
1. The –48V DC power is superimposed on the center conductor of the coaxial
cable between the IDU and the ODU. Connecting test equipment directly to
this terminal may damage it and touching the coaxial cable core may cause
electrical shock.
2. Persons performing maintenance must take necessary steps to avoid
Electrostatic Discharge (ESD) which may damage the cards on the IDU or
cause error. Wear a conductive wrist strap connected to the grounded (G)
jack on the front of the equipment shelf. This will minimize static build-up
during maintenance.
3. Turn off the "ODU PWR" switch on the IDU before connecting/disconnecting
the IF cable to avoid the equipment damaged.
4. After turning ON the equipment, wait at least 1 minute before turning it OFF
again. Repeatedly turning the power ON and OFF within a short interval may
cause the equipment damaged.
5. Do not allow open or short circuit ODU TX output with the TX power on
conditions. Perform the TX Mute control in the Maintenance mode or turn the
“ODU PWR” switch off at the IDU before disconnecting cable or feeder from
the ODU TX output.
6. Contact NEC before program download on the LCT is performed. Equipment
may not function correctly with improper operation.
Caution
1. In a system using the optical STM-1 INTFC, do not stare at the laser beam
or look at it directly with optical instruments. Otherwise, it may hurt your eyes
(Class 1 laser product).
2. The top surface of the IDU above MODEM is hot in operation.
3. When replacing the IDU, turn off the “ODU PWR” switch and disconnected
all cables.
4. During maintenance, the IDU should be set to maintenance On by the LCT.
5. To prevent traffic interruption, under the maintenance, perform TX/RX SW
manual switching in 1+1 system.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
2-2 Precaution
6. While the CPU is initialized by the CPU RESET switch, alarm(s) status is
reset to normal. After initialized, the alarm information is properly provided
through relay contacts.
7. Information on the maintenance and the control such as Mute, CW, LB, etc.
is released if the power is turned off.
8. If each setup item of NE SETUP or SYSTEM OPERATION is changed
during operation, traffic will be momentarily interrupted.
9. When the TX SW is activated, momentary traffic interruption may occur.
10. After completing maintenance, restore all connections, manual control
settings to normal and confirm that all alarm LEDs are unlit.
11. After equipment start-up, allow the equipment to warm up at least 30
minutes.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Precaution 2-3
Straight Type
Tighten the TNC-male connector of IF cable to the IDU with engage connector nut
only using fingers and holding the cable with another hand.
L-angle Type
Tighten the engage connector nut only for the L-angle connector also.
(Tightening Torque: 0.3 to 0.5 N-m (3 to 5 kg-cm))
If you rotate other parts of the L-angle connector as illustrated left, it may cause
connector damage.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
2-4 Precaution
Procedure 2-1
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Precaution 2-5
Procedure 2-2
2. Confirm that the MAINT on the top of the LCT window turns amber.
Maintenance Button
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
2-6 Precaution
3. Confirm that the MAINT LED on the front of MC-M Card turns amber.
(1) MC-M
(2 Slots)
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Precaution 2-7
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
2-8 Precaution
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Precaution 2-9
• RSTP Control
Note: This item is supported when the configuration is set to 1+1 HS mode
only.
Ex: MODEM No.1 and No.2 constructed as 1+1 HS mode and MODEM
No.1 act as working side. MODEM No.2 is act as standby side.
Procedure 2-3
1. Click the Maintenance button on the top of the LCT window to turn on the
maintenance mode.
4. Select MODEM TX/RX Switch Control from the Protection Control sub
menu.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
2-10 Precaution
5. The MODEM TX/RX Switch Control window appears. Click SW GRP No. in
the TX SW Manual Control field.
7. Click OK button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Precaution 2-11
10. The MODEM TX/RX Switch Control window appears again. Confirm the
parameters displayed.
11. Click the Maintenance button on the top of the LCT window to exit the
maintenance mode.
12. Confirm that the MAINT color turns from amber to white.
Note: This item is supported when the configuration is set to 1+1 TP/HS mode
only.
For example, MODEM No.1 and No.2 constructed as 1+1 TP mode and
MODEM No.1 acts as working side. MODEM No.2 acts as standby side.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
2-12 Precaution
Procedure 2-4
1. Click the Maintenance button on the top of the LCT window to turn on
maintenance mode.
4. Select MODEM TX/RX Switch Control from the Protection Control sub
menu.
5. The MODEM TX/RX Switch Control window appears. Click SW GRP No. in
the RX SW Manual Control field.
7. Click OK button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Precaution 2-13
10. The MODEM TX/RX Switch Control window appears again. Confirm the
parameters displayed.
11. Click the Maintenance button on the top of the LCT window to exit
maintenance mode.
12. Confirm that the MAINT color turns from amber to white.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
2-14 Precaution
Procedure 2-5
1. Click the Maintenance button on the top of the LCT window to turn on
maintenance mode.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Precaution 2-15
8. The RSTP Control window appears again. Confirm the parameters displayed.
9. After finishing RSTP Control, click the Maintenance button on the top of the
LCT window to exit maintenance mode.
10. Confirm that the MAINT color turns from amber to white.
Procedure 2-6
1. Click the Maintenance button on the top of the LCT window to turn on
maintenance mode.
4. Select SNCP Switch Control from the Protection Control sub menu.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
2-16 Precaution
5. The SNCP Switch Control window appears. Click the desired number to
configure.
7. Click OK button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Precaution 2-17
10. The SNCP Switch Control window appears again. Confirm the parameters
displayed.
11. Click Maintenance button on the top of the LCT window to exit maintenance
mode.
12. Confirm that the MAINT color turns from amber to white.
Procedure 2-7
1. Click the Maintenance button on the top of the LCT window to turn on
maintenance mode.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
2-18 Precaution
4. Select APS Switch Group Control from the Protection Control sub menu.
5. The APS Switch Group Control window appears. Click the desired number
to configure.
6. The APS Switch Group Control option window appears. Select Manual SW
to Protection or Forced SW to Protection from the APS Manual SW
Control drop-down list.
7. Click OK button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Precaution 2-19
10. The SNCP Switch Control window appears again. Confirm the parameters
displayed.
11. Click the Maintenance button on the top of the LCT window to exit
maintenance mode.
12. Confirm that the MAINT color turns from amber to white.
(6) Timing Source Switch Control (This mode available when the Lock
Out is Off only)
In case that Lock Out Status is set to On, follow the Procedure 2-7 to change the
setting to Off and then follow the Procedure 2-8 to configure Timing Source
Switching.
Procedure 2-8
1. Click the Maintenance button on the top of the LCT window to turn on
maintenance mode.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
2-20 Precaution
4. Select Timing Source Switch Control from the Protection Control sub
menu.
5. The Timing Source Switch Control window appears. Click desired Lock
Out to configure.
6. The Timing Source Switch Control option window appears. Click Off radio
button from Lock Out.
7. Click OK button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Precaution 2-21
10. The Timing Source Switch Control window appears again. Confirm the
displayed parameters.
11. After finishing Lock Out Setting, click the Maintenance button on the top of
the LCT window to exit maintenance mode.
12. Confirm that the MAINT color turns from amber to white.
Procedure 2-9
1. Click the Maintenance button on the top of the LCT window to turn on
maintenance mode.
4. Select Timing Source Switch Control from the Protection Control sub
menu.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
2-22 Precaution
5. The Timing Source Switch Control window appears. Click the desired
Timing Source Switch Control to configure.
7. Click OK button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Precaution 2-23
10. The Timing Source Switch Control window appears again. Confirm the
displayed parameters.
11. Click the Maintenance button on the top of the LCT window to exit
maintenance mode.
12. Confirm that the MAINT color turns from amber to white.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
2-24 Precaution
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Test Sets and Accessories 3-1
The test sets and special accessories listed in Table 3-1 are required for maintenance.
If recommended test sets and accessories are not available, equivalents may be used.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
3-2 Test Sets and Accessories
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Current Status 4-1
4. CURRENT STATUS
The Active Alarm tab displays all current alarms detected at the equipment
side.
The current alarm list can be downloaded to LCT PC by clicking the Save
button on the top left of the Active Alarm tab.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
4-2 Current Status
The Event Log tab displays all detected alarms and status, which includes
any changes made on the line card and equipment configuration.
The Event Status list can be downloaded to the LCT PC by clicking the
Save button on the top left of the Event Log tab.
1. Click the Save button of the Active Alarm tab or the Event Log tab.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Current Status 4-3
3. The Save As window appears. Select the appropriate folder from the Local
PC, and then click Save button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
4-4 Current Status
5. Confirm that the log file was saved in the selected folder.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Current Status 4-5
The MODEM/ODU tab displays all alarm and status detected on MODEM
Card(s) and ODU.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
4-6 Current Status
The IDU tab displays all alarms and status detected on IDU.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Current Status 4-7
(5) E1 Tab
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
4-8 Current Status
The STM-1 tab displays all alarms and status detected on STM1-A.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Current Status 4-9
The GbE tab displays all alarms and status detected on GbE-A .
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
4-10 Current Status
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Routine Maintenance 5-1
5. ROUTINE MAINTENANCE
This section provides procedures for the routine (annually) maintenance to ensure the
equipment operating properly, or to prevent the equipment from being damaged.
Before proceeding with the routine maintenance, carefully observe the precautions
given in Section 2.
Procedure 5-1
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
5-2 Routine Maintenance
Notes
1. If an abnormal indication appears, check Alarm/Status, performance monitor
and perform loopback test to distinguish sections of normal and alarmed.
2. RX LEVEL varies depending on received RF signal level.
3. Power Supply voltage at ODU varies depending on IF cable length between
the IDU and ODU.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Routine Maintenance 5-3
5.2.1 PM Parameters
Performance Monitor Parameters can be measured from iPASOLINK.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
5-4 Routine Maintenance
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Routine Maintenance 5-5
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
5-6 Routine Maintenance
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Routine Maintenance 5-7
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
5-8 Routine Maintenance
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Routine Maintenance 5-9
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
5-10 Routine Maintenance
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Routine Maintenance 5-11
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
5-12 Routine Maintenance
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Corrective Maintenance 6-1
6. CORRECTIVE MAINTENANCE
Faults can be classified in to those that cause deterioration of the transmission quality
and those that interrupt the traffic due to a malfunction of the equipment. This
chapter explains the troubleshooting procedures for equipment faults and the
corresponding remedial methods. The purpose of troubleshooting malfunctioning
equipment is to restart the service by locating the faulty part and replacing it with a
spare.
The faults that cause deterioration quality are primarily originated by changes
occurred in the state of propagation. Therefore, if a decline in the transmission
quality or similar fakes place frequently, the link design will have to be reviewed.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
6-2 Corrective Maintenance
6.1 Alarm/Status
When an alarm event has occurred, at first, check alarm indication on the front of the
IDU. Continuously, connect the PC to the LOCAL jack on the LCT port mounted on
the IDU and check alarm/status indication.
A faulty part can be located by checking the alarm LED indications and LCT
Alarm indications.
Alarm Report
When an alarm is detected, alarm notification is made to the user by lighting
up the LEDs on the rack, and reporting the alarm to user interface. The alarm
notification is also made to the user by an Office alarm, such as the station
alarm bell and lamps.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Corrective Maintenance 6-3
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
6-4 Corrective Maintenance
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Corrective Maintenance 6-5
Web-LCT indication
The alarm LED indications and PNMT indication faulty part can be located
by checking the ALM LED indicators and Web-LCT Alarm indications.
(g) Loopback
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
6-6 Corrective Maintenance
Cleared (CL):
The Cleared severity level indicates the clearing of one or more previously reported
alarms. This alarm clears all alarms for this managed object that have the same
Alarm type, Probable cause and Specific problems (if given). Multiple associated
notifications may be cleared by using the Correlated notifications parameter (defined
below).
Indeterminate (ID):
The Indeterminate severity level indicates that the severity level cannot be
determined.
Critical (CR) :
The Critical severity level indicates that a service affecting condition has occurred
and an immediate corrective action is required. Such a severity can be reported, for
example, when a managed object becomes totally out of service and its capability
must be restored.
Major (MJ):
The Major severity level indicates that a service affecting condition has developed
and an urgent corrective action is required. Such a severity can be reported, for
example, when there is a severe degradation in the capability of the managed object
and its full capability must be restored.
Minor (MN):
The Minor severity level indicates the existence of a non-service affecting fault
condition and that corrective action should be taken in order to prevent a more
serious (for example, service affecting) fault. Such a severity can be reported, for
example, when the detected alarm condition is not currently degrading the capacity
of the managed object.
Warning (WR):
The Warning severity level indicates the detection of a potential or impending
service affecting fault, before any significant effects have been felt. Action should be
taken to further diagnose (if necessary) and correct the problem in order to prevent it
from becoming a more serious service affecting fault.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Corrective Maintenance 6-7
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
6-8 Corrective Maintenance
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Corrective Maintenance 6-9
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
6-10 Corrective Maintenance
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Corrective Maintenance 6-11
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
6-12 Corrective Maintenance
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Corrective Maintenance 6-13
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
6-14 Corrective Maintenance
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-1
7. CONTROL ITEMS
Operations listed below are available only on the maintenance mode. Note that these
control items may cause a traffic interruption if operated while in service.
z Loopback Control
- IF Loopback Control
- TDM Loopback Control (E1 Loopback1/ Loopback2)
- TDM Loopback Control (STM-1 Loopback1/ Loopback2)
z Database Upload/Download
- HW Reset Control
- FW Reset Control
z Radio Control
z License Management
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-2 Control Items
z Inventory Information
z Performance Monitor
z Offline Maintenance
- Data Adjust
- RF Sub Band Select
7.1 Loopback
When there is an interruption of signals, use the SDH/SONET/PDH analyzers and
isolate the faulty section by checking the traffic signal using loopback. Setup the test
equipment according to the following diagrams for PDH or SDH configuration.
In the facility loopback, a signal is looped back is toward the baseband interface
direction and, in the terminal loopback, a signal is looped back is toward the CS card
direction. They are performed at the STM-1/4 (SDH) or E1 (PDH) interfaces. (Notes
1, 2)
When executing the loopback control, set Maintenance Mode to ON and do not
release Maintenance Mode while controlling loopback.
7.1.1 IF Loopback
Execute the MODEM Loopback control for checking the incoming of traffic signal
inside MODEM interface (The traffic signal from E1 interfaces to wireless
direction).
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-3
Notes
Turn ON the TX Mute Control before executing IF Loopback. While IF Loopback
is being executed, the TX INPUT ALM of ODU will occur because the MOD
output is determinate. So, the MOD ALM and TX INPUT ALM will be masked
while IF Loopback is executed.
The MOD ALM and TX INPUT ALM will be un-masked as soon as the IF
Loopback is released.
If the remote control connected at opposite side, the remote control will be
disconnected while the IF Loopback is executed and does not restore in
default. So, it is necessary to set the IF Loopback Release Time to release
IF Loopback automatically before executing the IF Loopback.
Important:
1. Turn ON the TX Mute control before executing IF Loopback.
When executing the Loopback control, set Maintenance Mode to ON and do not
release Maintenance Mode during controlling loopback.
Procedure 7-1
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-4 Control Items
4. Select the MODEM Loopback Control from the Loopback Control sub
menu.
5. The MODEM Loopback Control window appears. Click Off at the specified
MODEM No. (or SW GRP) of IF Loopback field.
7. Click OK button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-5
10. The MODEM Loopback Control window appears again. Confirm that the
status of IF Loopback of specified MODEM indicates On.
11. When the loopback test ends, click Maintenance button on the top of the LCT
window to exit maintenance mode.
12. Confirm that the MAINT color turns from amber to white.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-6 Control Items
Procedure 7-2
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
4. Select the MODEM Loopback Control from the Loopback Control sub
menu.
5. The MODEM Loopback Control window appears. Click Off at the specified
MODEM No. (or SW GRP) of IF Loopback field.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-7
7. Click OK button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-8 Control Items
11. The MODEM Loopback Control window appears again. Confirm that the
status of IF Loopback of specified MODEM indicates On.
12. When the loopback test ends, click Maintenance button on the top of the LCT
window to exit maintenance mode.
13. Confirm that the MAINT color turns from amber to white.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-9
Important:
1. Turn ON the TX Mute control before executing IF Loopback.
When executing the Loopback control, set Maintenance Mode to ON and do not
release Maintenance Mode during controlling loopback.
Procedure 7-3
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
4. Select the MODEM Loopback Control from the Loopback Control sub
menu.
5. The MODEM Loopback Control window appears. Click Off at the specified
MODEM (No.1/No.2) of IF Loopback field.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-10 Control Items
7. Click OK button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-11
10. The MODEM Loopback Control window appears again. Confirm that the
status of IF Loopback of specified MODEM indicates On.
11. When the loopback test ends, click Maintenance button on the top of the LCT
window to exit maintenance mode.
12. Confirm that the MAINT color turns from amber to white.
Procedure 7-4
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
4. Select the MODEM Loopback Control from the Loopback Control sub
menu.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-12 Control Items
5. The MODEM Loopback Control window appears. Click Off at the specified
MODEM No. (or SW GRP) of IF Loopback field.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-13
7. Click OK button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-14 Control Items
11. The MODEM Loopback Control window appears again. Confirm that the
status of IF Loopback of specified MODEM indicates On.
12. When the loopback test ends, click Maintenance button on the top of the LCT
window to exit maintenance mode.
13. Confirm that the MAINT color turns from amber to white.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-15
Execute the TDM Loopback Control (E1 Loopback1) for checking the incoming of
E1 traffic signal inside E1 interfaces (The traffic signal from outside to E1 interfaces
direction).
Note: During executing Loopback, the AIS will be detected at down stream of
the specified channel (Loopback channel).
Important:
1. When executing the Loopback control, set Maintenance Mode to ON and do
not release Maintenance Mode while controlling loopback.
Procedure 7-5
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
4. Select the TDM Loopback Control (E1 Loopback1) from the Loopback
Control sub menu.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-16 Control Items
5. The TDM Loopback Control (E1 Loopback1) window appears. Click Off
at the specified E1 Loopback1 channel from the 16E1-A(Slot**) field.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-17
6. The TDM Loopback Control (E1 Loopback) option window appears. Click
On radio button of the specified E1 Loopback CH**.
Parameter Description
7. Click OK button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-18 Control Items
10. The TDM Loopback Control window appears again. Confirm that the status
of the specified CH indicates On.
11. When the loopback test ends, click Maintenance button on the top of the LCT
window to exit maintenance mode.
12. Confirm that the MAINT color turns from amber to white.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-19
Execute the TDM Loopback Control (E1 Loopback2) for checking the incoming of
E1 traffic signal through MODEM IF (The traffic signal from wireless to E1
interfaces direction).
Remote login to the opposite site NE and execute Loopback2 at opposite site NE.
Note: During executing Loopback, the AIS alarm will be detected at down
stream of the specified channel (Loopback channel).
Important:
1. When executing the Loopback control, set Maintenance Mode to ON and do
not release Maintenance Mode during controlling loopback.
Procedure 7-6
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
4. Select the TDM Loopback Control (E1 Loopback2) from the Loopback
Control sub menu.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-20 Control Items
5. The TDM Loopback Control (E1 Loopback2) window appears. Click Off
at the specified E1 Loopback2 Channel from the 16E1-A(Slot**) field.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-21
7. Click OK button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-22 Control Items
10. The TDM Loopback Control window appears again. Confirm that the status
of the specified CH indicates On.
11. When the loopback test ends, click Maintenance button on the top of the LCT
window to exit maintenance mode.
12. Confirm that the MAINT color turns from amber to white.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-23
Execute the TDM Loopback Control (STM-1 Loopback1) for checking the incoming
of TDM traffic signal inside STM-1 interfaces (The traffic signal from outside to
STM-1 interfaces direction).
Note: During executing Loopback, the AIS will be detected at down stream of
the specified channel (Loopback channel).
Important:
1. When executing the Loopback control, set Maintenance Mode to ON and do
not release Maintenance Mode while controlling loopback.
Procedure 7-7
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-24 Control Items
7. Click OK button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-25
10. The TDM Loopback Control window appears again. Confirm that the status
of STM-1 Loopback1 Port** indicates On.
11. When the loopback test ends, click Maintenance button on the top of the LCT
window to exit maintenance mode.
12. Confirm that the MAINT color turns from amber to white.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-26 Control Items
Execute the TDM Loopback Control (STM-1 Loopback2) for checking the incoming
of TDM traffic signal through MODEM IF (The traffic signal from wireless to
STM-1 interfaces direction).
Remote login to the opposite site NE and execute STM-1 Loopback2 at opposite site
NE.
Note: During executing Loopback, the AIS will be detected at down stream of
the specified channel (Loopback channel).
Important:
1. When executing the Loopback control, set Maintenance Mode to ON and do
not release Maintenance Mode during controlling loopback.
Procedure 7-8
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-27
7. Click OK button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-28 Control Items
10. The TDM Loopback Control window appears again. Confirm that the status
of STM-1 Loopback2 Port** indicates On.
11. When the loopback test ends, click Maintenance button on the top of the LCT
window to exit maintenance mode.
12. Confirm that the MAINT color turns from amber to white.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-29
• Shipment
This function clears the user defined Provisioning data, which restores the
factory default (except for the Network Configurations if registered).
• Date/Time Setting
This function adjusts the date and time on an NE.
Procedure 7-9
2. Select the Export (NE-> Storage) Utility from the Equipment Utility sub
menu.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-30 Control Items
3. The Export (NE-> Storage) Utility window appears. Select the specified
Config Data and storage (local PC or USB memory), then click Execute button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-31
5. The Save As window appears. Select the specified directory on the specified
device (local PC/USB memory) and then click Save button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-32 Control Items
7. After the upload process is finished, open the export destination (folder) on
specified device (local PC or USB memory) to confirm whether the data has
been upload correctly or not.
NOTE: Connect USB memory to the USB port at the front of iPASOLINK and the
operation is on LCT.
Following is the items list that is available on Update (Storage -> NE) Utility.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-33
This function updates the MODEM parameter file on the MODEM module.
Important:
1. Confirm that you have the IDU Main Card Program File that is supplied by
NEC.
2. Confirm the current version of IDU Main Card Program File from the IDU tab
of Equipment Inventory Information window.
3. Turn ON the Maintenance Mode before downloading IDU Main Card
Program File. Do not release Maintenance Mode while downloading.
Procedure 7-10
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Update (Storage -> NE) Utility from the Equipment Utility sub
menu.
4. The Update (Storage -> NE) Utility window appears. Select the Program
File radio button and then click Execute button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-34 Control Items
5. The Update (Storage -> NE) Utility option window appears. Select the Main
Card from drop-down list and then click Next button.
7. The file selection window appears. Select the Main Card firmware file and then
click Open (or OK) button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-35
• Local PC
• USB Memory
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-36 Control Items
11. After the download is completed, the Update Complete! window appears.
Check the Program ROM Switching check dialog box and then click OK
button.
12. The Warning message dialog dialog box appears. Click OK button.
iPASOLINK will be restarted automatically.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-37
13. The Information dialog dialog box appears. Click OK button. The WebLCT
will shut down automatically.
15. Select Inventory (Equipment Inventory Information) from the LCT menu.
16. The Equipment Inventory Information (IDU) window appears. Verify the
Current version (new program running version) of Main Card.
17. When completed, click Maintenance button on the top of the LCT window to
exit maintenance mode.
18. Confirm that the MAINT color turns from amber to white.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-38 Control Items
(b) ODU
Important:
1. Confirm that you have ODU Program File that is provided from NEC.
2. Confirm the current version of ODU Program File from the ODU tab of the
Equipment Inventory Information window.
Procedure 7-11
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Update (Storage -> NE) Utility from the Equipment Utility sub
menu.
4. The Update (Storage -> NE) Utility window appears. Select the Program
File radio button and then click Execute button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-39
5. The Update (Storage -> NE) Utility option window (1/2) appears. Select the
ODU from drop-down list and then click Next button.
6. The Update (Storage -> NE) Utility option window (2/2) appears. Select the
MODEM from drop-down list and then click Next button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-40 Control Items
8. The file selection window appears. Select the ODU firmware file and then click
Open (or OK) button.
• Local PC
• USB Memory
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-41
10. The Warning message dialog dialog box appears. Click OK button.
12. After the download is completed, the Update Complete! window appears.
Check the Program ROM Switching check dialog box and then click OK
button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-42 Control Items
13. The Warning message dialog dialog box appears. Click OK button.
iPASOLINK will be restarted automatically.
14. The Information dialog dialog box appears. Click OK button. The WebLCT
will shut down automatically.
16. Select the Inventory (Equipment Inventory Information) from the LCT
menu.
18. When completed, click Maintenance button on the top of the LCT window to
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-43
19. Confirm that the MAINT color turns from amber to white.
Important:
1. Confirm that data file of FPGA has been already acquired from NEC.
2. Confirm the F/W versions on the IDU tab of the Equipment Inventory
Information window.
3. When executing the FPGA data download, set Maintenance Mode to ON
and do not release Maintenance Mode while controlling download.
Procedure 7-12
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Update (Storage -> NE) Utility from the Equipment Utility sub
menu.
4. The Update (Storage -> NE) Utility window appears. Select the FPGA Data
radio button and then click Execute button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-44 Control Items
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-45
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-46 Control Items
• Local PC
• USB Memory
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-47
11. After the download is completed, the Update Complete! window appears.
Then auto-revert should be executed by clicking the OK button.
12. The Information dialog dialog box appears. Click OK button. The WebLCT
will shut down automatically.
14. Select the Inventory (Equipment Inventory Information) from the LCT
menu.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-48 Control Items
15. The Equipment Inventory (IDU) windows appears. Confirm the new program
running on the Equipment Inventory Information (IDU) window.
16. When completed, click Maintenance button on the top of the LCT window to
exit maintenance mode.
17. Confirm that the MAINT colors turns from amber to white.
Note:
1. Do not share the folder with the existing Configuration Data File and the
Data to download, which allows comparison of each Data.
2. When executing the Configuration Data download, set the Maintenance
Mode to ON. Do not release the Maintenance Mode while downloading data.
Procedure 7-13
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Update (Storage -> NE) Utility from the Equipment Utility sub
menu.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-49
4. The Update (Storage -> NE) Utility window appears. Select the Config
Data radio button then click Execute button.
5. The source selection window appears. Select the specified Config Data Type
(Network Config, Equipment Config, User Config).
6. Select destination storage (Local PC/USB Memory) from the Import File
field and then click File icon button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-50 Control Items
7. The file selection window appears. Select the Config Data file and then click
Open (or OK) button.
• Local PC
• USB Memory
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-51
11. When completed, the Update Complete! window appears. Then auto-revert
should be executed by clicking OK button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-52 Control Items
12. The Information dialog dialog box appears. Click OK button. The WebLCT
will shut down automatically.
14. Upload the Configuration Data File again and then acquire the Configuration
Data.
15. Confirm the Configuration Data by comparing the latest Configuration Data to
the previous data..
17. Confirm that the MAINT color turns from amber to white.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-53
Important:
1. Confirm that the specified Parameter File for MODEM has already arrived
from NEC.
2. Confirm specified Parameter File for MODEM.
Procedure 7-14
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Update (Storage -> NE) Utility from the Equipment Utility sub
menu.
4. The Update (Storage -> NE) Utility window appears. Select the MODEM
Parameter radio buttonthen click Execute button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-54 Control Items
5. The Update (Storage -> NE) Utility option window appears. Select a desired
MODEM and then click OK button.
6. The source selection window appears. Select the destination storage (Local
PC/USB Memory) from the Import File field and then click File icon button.
7. The file selection window appears. Select the MODEM Parameter file and then
click Open (or OK) button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-55
• Local PC
• USB Memory
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-56 Control Items
11. After the download is completed, the Update Complete! window appears.
Then auto-revert should be executed by clicking the OK button.
12. After restarting, open the window of specified MODEM and then confirm the
latest MODEM Parameter Data running by comparing the confirmed parameter
of specified MODEM.
13. When completed, click Maintenance button on the top of the LCT window to
exit maintenance mode.
14. Confirm that the MAINT color turns from amber to white.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-57
Important:
1. When executing the Program ROM Switching, set Maintenance Mode to ON
and do not release Maintenance Mode while controlling switching.
Procedure 7-15
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Program ROM Switching Utility from the Equipment Utility
sub menu.
4. The Program ROM Switching window appears. Click the Main Card in the
Item field.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-58 Control Items
6. The Warning message dialog dialog box appears. Click OK button. Then
auto-revert should be executed by clicking the OK button.
7. The Information dialog dialog box appears. Click OK button. The WebLCT
window will shut down automatically.
9. Select the Equipment Utility (Program ROM Switching) from the LCT
menu.
10. Confirm the Current version of the Main Card in the Program ROM
Switching window.
11. When completed, click Maintenance button on the top of the LCT window to
exit maintenance mode.
12. Confirm that the MAINT colors turns from amber to white.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-59
Important:
When executing the Program ROM Switching, set Maintenance Mode to ON and
do not release Maintenance Mode while controlling switching.
Procedure 7-16
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Program ROM Switching Utility from the Equipment Utility
sub menu.
4. The Program ROM Switching window appears. Click the ODU No. in the
Item field.
5. The Program ROM Switching (ODU) option window appears. Confirm the
information then click OK button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-60 Control Items
10. When completed, click Maintenance button on the top of the LCT window to
exit maintenance mode.
11. Confirm that the MAINT color turns from amber to white.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-61
Procedure 7-17
2. Select the USB Memory Utility from the Equipment Utility sub menu.
3. The USB Memory Utility window appears. Click the Refresh button.
4. After refreshing, the USB Memory Utility window appears again. Confirm that
USB Memory Utility window is updated.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-62 Control Items
Procedure 7-18
4. The Shipment dialog box appears. Select the Provisioning Clear from the
drop-down list and then click OK button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-63
7. The Information dialog box appears. Click OK button The WebLCT will shut
down automatically.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-64 Control Items
Procedure 7-19
1. Expand the Equipment Utility from the LCT menu.
2. Select the Date/Time setting from the Equipment Utility sub menu.
3. The Date/Time Setting window appears. Click Modify button.
4. The Date/Time Setting dialog box appears. Assign a proper value for each
parameter according to the table below.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-65
7. The Date/Time Setting window appears again. Confirm the modified date and
time of the information displayed.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-66 Control Items
Reset control is available only when Maintenance Mode is set to ON. If Maintenance
Mode is set to OFF, Executing the reset control will result in the error response.
• Card Reset
Available to control each option card individually. Main ETH signal will be
downed during the resetting. After Card Reset finished, option card need to be
reset the configuration information that retains by IDU. Card Reset replies NG
response and is not executed if option card has been not registered, not mounted,
or mounted different place.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-67
Procedure 7-20
2. Select the H/W_F/W Reset Control from the Maintenance Control sub
menu.
3. Select the H/W Reset Control from the H/W_F/W Reset Control sub menu.
4. The H/W Reset Control window appears. Click Option in the Item field.
5. The H/W Reset Control dialog box appears. Confirm the information then
click OK button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-68 Control Items
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-69
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-70 Control Items
10. When completed, click Maintenance button on the top of the LCT window to
exit maintenance mode.
11. Confirm that the MAINT color turns from amber to white.
Procedure 7-21
2. Expand the H/W_F/W Reset Control from the Maintenance Control sub
menu.
3. Select the F/W Reset Control from the H/W_F/W Reset Control sub menu.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-71
4. The F/W Reset Control window appears. Click Main Card in the Item field.
5. The F/W Reset Control dialog box appears. Confirm the information then
click OK button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-72 Control Items
7. The Information dialog box appears. Click OK button. The WebLCT window
will shut down automatically.
10. When completed, click Maintenance button on the top of the LCT window to
exit maintenance mode.
11. Confirm that the MAINT color turns from amber to white.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-73
Procedure 7-22
2. Select the H/W_F/W Reset Control from the Maintenance Control sub
menu.
3. Select the F/W Reset Control from the H/W_F/W Reset Control sub menu.
4. The F/W Reset Control window appears. Click specified ODU No. in the
Item field.
5. The F/W Reset Control dialog box appears. Confirm the information then
click OK button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-74 Control Items
8. The CPU Reset (ODU) starts automatically. After restarting, Confirm the
information displayed in the F/W Reset Control window.
9. When completed, click Maintenance button on the top of the LCT window to
exit maintenance mode.
10. Confirm that the MAINT color turns from amber to white.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-75
The function of each control is as follows (These windows are not available when
MAINT is in OFF. Switch to Maintenance mode first is displayed):
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-76 Control Items
z TX Mute Control
Despite the equipment configuration setting, forcing the “TX Mute Control” to
ON will stop the transmit power of the ODU.
Notes
*1 If Mute Control is set to OFF and Mute OFF does not work due to uncontrollable factors,
Mute status will remain ON.
In case of 1+1 HS configuration, the Mute OFF control does not mute both lines.
Moreover, when force Mute is controlled in No.1/No.2, Maintenance Mode
cannot set to OFF.
When TX Mute is controlled by a remote control, the setting of the automatic
restoration time is possible. Therefore, TX Mute Release Time should be set.
TX Mute Release Time is set together with TX Mute Control by the item that
becomes effective only when TX Mute Control is done from a higher-level
device.
z CW Control
The flat rate of the transmission modulation method of the control station in the
AMR mode is temporarily managed.
The modulation method can be set according to the target device regardless of
the AMR Range setting.
Under the 1+0 configuration, each Slot#/Slot# is individually controlled.
This control is done by exchanging request/answer of the control between
local/remote stations as well as LB2.
When the TX Modulation Manual Control setting is returned from Manual to
Auto, the fixed modulation method is returned to QPSK.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-77
Performing this function (Manual Control) sets the Maintenance Mode to ON.
However, in case of Auto setting and if Maintenance Mode is set to OFF, it will
cancel the “auto setting”.
Procedure 7-23
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-78 Control Items
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-79
10. When completed, click Maintenance button on the top of the LCT window to
exit maintenance mode.
11. Confirm that the MAINT color turns from amber to white.
Procedure 7-24
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-80 Control Items
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-81
10. When completed, click Maintenance button on the top of the LCT window to
exit maintenance mode.
11. Confirm that the MAINT color turns from amber to white.
Procedure 7-25
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-82 Control Items
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-83
10. When completed, click Maintenance button on the top of the LCT window to
exit maintenance mode.
11. Confirm that the MAINT color turns from amber to white.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-84 Control Items
7.2.3.3 CW Control
Procedure 7-26
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-85
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-86 Control Items
10. When completed, click Maintenance button on the top of the LCT window to
exit maintenance mode.
11. Confirm that the MAINT color turns from amber to white.
Procedure 7-27
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-87
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-88 Control Items
10. When completed, click Maintenance button on the top of the LCT window to
exit maintenance mode.
11. Confirm that the MAINT color turns from amber to white.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-89
The following Laser management items are available when executing from the LCT.
For SDH optical interface, the ALS (Automatic Laser Shutdown) control
performs the resumption of optical power for a definite period of time.
In addition, this function operates under ALS control execution (optical power
shutdown). If ALS is not activated, the control is not carried out.
Procedure 7-28
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Laser Shutdown Control from the Maintenance Control sub
menu.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-90 Control Items
4. The Laser Shutdown Control window appears. Select Off the Forced
Laser Shutdown Control field.
5. The Laser Shutdown Control dialog box appears. Select a proper value for
the Forced Laser Shutdown Control parameter.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-91
9. The Laser Shutdown Control window appears again. Confirm the parameters
displayed.
10. When completed, click Maintenance button on the top of the LCT window to
exit maintenance mode.
11. Confirm that the MAINT color turns from amber to white.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-92 Control Items
Procedure 7-29
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Laser Shutdown Control from the Maintenance Control sub
menu.
4. The Laser Shutdown Control window appears. Select Control in the ALS
Restart field.
5. The Laser Shutdown Control dialog box appears. Select a propaer value for
the ALS Restart parameter.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-93
9. The Laser Shutdown Control window appears again. Confirm the parameters
displayed.
10. When completed, click Maintenance button on the top of the LCT window to
exit maintenance mode.
11. Confirm that the MAINT color turns from amber to white.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-94 Control Items
When House Keeping input at own station is detected, Cluster Alarm will transmit to
the opposite station by setting up the bit of Cluster ALM input (output toward to
wireless)
When any changes for Cluster ALM output (input toward to wireless) is detected
after Cluster Alarm signal was received by equipment in the opposite station, the
equipment in the opposite station will be set-up bit for House Keeping output control
then Relay output (RL) will be executing.
After receiving a Cluster Alarm signal from the opposite station and another Cluster
Alarm is input (output to the direction of the radio), a setup is performed, Cluster
Alarm signal is sent out to an opposite office. It is possible to transmit the Cluster
Alarm signal.
House Keeping external input port provides six port, four of six ports are
used by both Cluster Alarm and House Keeping and each port is required to
select Alarm function.
When 1 to 4 external input ports are selected as a Cluster Alarm input, F/W
executes to change the signal of HKIN1-4 into Cluster Alarm signal in
wireless frame then output the signal toward to opposite side of wireless. In
addition, any Modems are available to output the Cluster Alarm input signal.
House Keeping output port provides six port, four of six port are used by
both Cluster Alarm and House Keeping and each port (HK1-4) required to
set up individually from F/W to FPGA.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-95
Set up to OK or not OK for each item (parallel alarm required to set up for
each alarm items), execute port output if over one alarm at specified item is
detected.
H/W control output port for other 2 port. (RL1, RL2 port will be fixed for
parallel alarm output by H/W.)
Cluster Alarm output 1 to 4 signals are selected after the incoming signals of
a MODEM under redundant system, and the arbitrary Cluster Alarm is
output to the radio port of CH unit.
Cluster Alarm input and output, and a Through function can be separately
controlled between different ports.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-96 Control Items
Procedure 7-30
3. Select Cluster Alarm Setting from the Relay-Alarm Mapping Setting sub
menu.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-97
5. The Cluster Alarm Setting dialog box appears. Assign necessary parameters.
8. The Cluster Alarm Setting window appears again. Confirm the parameters
displayed.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-98 Control Items
7.2.6 Inventory
Inventory will display information of H/W, in mounted MODEM, Network
information, and Software License Key information for the iPASOLINK.
Procedure 7-31
3. The Equipment Inventory Information window appears. Select the IDU tab.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-99
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-100 Control Items
7. The Save As window appears. Select the proper folder of local PC and then
click Save button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-101
9. Confirm that the Inventory Information file is saved in the selected folder.
Procedure 7-32
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-102 Control Items
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-103
7. The Save As window appears. Select the proper folder of local PC and then
click Save button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-104 Control Items
9. Confirm that the Inventory Information file is saved in the selected folder.
Procedure 7-33
2. Select the S/W License Information from the Inventory sub menu.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-105
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-106 Control Items
6. The Save As window appears. Select the proper folder of local PC and then
click Save button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-107
8. Confirm that the License Information file is saved in the selected folder.
Procedure 7-34
2. Select the Radio Capacity Setting from the S/W License Setup sub menu.
3. The Radio Capacity Setting window appears. Click the Setup button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-108 Control Items
4. The Radio Capacity Setting dialog box appears. Specify the Radio Capacity
License and then selected the desired MODEM (Slot**) from the New State
drop-down list.
5. Click OK button.
7. The Radio Capacity Setting window appears again. Confirm the parameters
displayed.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-109
Procedure 7-35
2. Select the SFP Port License Setting from the S/W License Setup sub
menu.
3. The SFP Port License Setting window appears. Click the Setup button.
4. The SFP Port License Setting dialog box appears. Specify the SFP Port
Usage License and then select the desired GbE (Slot**) from the New State
drop-down list.
5. Click OK button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-110 Control Items
7. The SFP Port License Setting window appears again. Confirm the
parameters displayed.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-111
The PM Register retains all monitoring data of 7-days and current monitoring data
will be transferred to the PM Register according to the timing of 0:00 minute.
- E1 PMON Report
- PMON/RMON/FDB Clear
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-112 Control Items
Procedure 7-36
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-113
5. The MODEM PMON Report (1-day) window appears. Confirm the detail of
MODEM PMON Report.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-114 Control Items
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-115
10. The Save As window appears. Select the proper folder of local PC and then
click Save button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-116 Control Items
11. When completed, the Download Complete window appears. Click Close
button.
12. Confirm that the MODEM PMON Report file is saved in the selected folder.
Procedure 7-37
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-117
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-118 Control Items
10. The Save As window appears. Select the proper folder of local PC and then
click Save button.
E1 1-day: 1day-E1-s1p1-20100924.pmon
E1 15-min: 15min-E1-s1p1-20100922.pmon
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-119
11. When completed, the Download Complete window appears. Click Close
button.
12. Confirm that the E1 PMON Report file is saved in the selected folder.
Procedure 7-38
3. The STM-1 PMON Report window appears. Click DMR RS tab and confirm
the Performance Monitor values that monitored for 15-minute and 1-day will be
displayed.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-120 Control Items
5. The STM-1 PMON Report (1-day) window appears. Confirm the detail of
STM-1 PMON Report.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-121
10. The Save As window appears. Select the proper folder of local PC and then
click Save button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-122 Control Items
11. When completed, the Download Complete window appears. Click Close
button.
12. Confirm that the STM-1 PMON Report file is saved in the selected folder.
(2) RS Tab
Procedure 7-39
3. The STM-1 PMON Report window appears. Click RS tab and confirm the
Performance Monitor values that monitored for 15-minute and 1-day will be
displayed.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-123
4. Click STM-1.
5. The STM-1 PMON Report (1-day) window appears. Confirm the detail of
STM-1 PMON Report.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-124 Control Items
10. The Save As window appears. Select the proper folder of local PC and then
click Save button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-125
11. When completed, the Download Complete window appears. Click Close
button.
12. Confirm that the STM-1 PMON Report file is saved in the selected folder.
Procedure 7-40
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-126 Control Items
3. The ETH RMON Report window appears. Confirm the Remote Network
Monitoring values that monitored for 15-minute and 1-day will be displayed.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-127
5. The ETH RMON Report (1-day) window appears. Confirm the detail of
RMON Report.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-128 Control Items
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-129
10. The Save As window appears. Select the proper folder of local PC and then
click Save button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-130 Control Items
11. When completed, the Download Complete window appears. Click Close
button.
12. Confirm that the ETH RMON Report file is saved in the selected folder.
Procedure 7-41
3. The VLAN Counter Report window appears. Confirm the VLAN Counter
Report values that monitored for 15-minute and 1-day will be displayed.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-131
Procedure 7-42
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-132 Control Items
7. Select the PMON or RMON Report sub menu from the Current/ History
PMON/RMON Report of the LCT menu.
Procedure 7-43
3. The PMON/RMON/FDB Clear window appears. Select the FDB Table Clear
All radio button and then click Execute button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-133
Procedure 7-44
3. The PMON/RMON/FDB Clear window appears. Select the FDB Table Clear
(VLAN ID) radio button and then click Execute button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-134 Control Items
4. The FDB Table Clear (VLAN ID) dialog box appears. Select the VLAN ID
radio button and enter the VLAN ID No., and then click OK button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-135
Procedure 7-45
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Offline Maintenance from the Maintenance Control sub menu.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-136 Control Items
5. The Offline Maintenance Control dialog box appears. Select the specified
status from the DADE Adjust drop-down list, and then click OK button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-137
10. When completed, click Maintenance button on the top of the LCT window to
exit maintenance mode.
11. Confirm that the MAINT color turns from amber to white.
This selection can set up each ODU individually, the avalble suffix Sub Band which
can be set up are the alphabet "A through H, J through N, P, R, and X".
Notes
1. Before changing the Sub Band setting, it is required to set TX Mute to ON,
and also prevent any rewriting data in the ODU Flash ROM.
2. When any ODU which does not support a Sub Band change and change
from a higher-order Sub Band, if a change setup is carried out, an ODU
classification is judged and a Sub Band change setup is not performed.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-138 Control Items
Procedure 7-46
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Offline Maintenance from the Maintenance Control sub menu.
5. The Offline Maintenance Control dialog box appears. Select the specified
value from the RF Sub Band Select drop-down list, and then click OK button.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-139
8. The Offline Maintenance Control window appears again. Confirm that the
status is modified as same as the selection in the DADE Adjust field.
9. When completed, click Maintenance button on the top of the LCT window to
exit maintenance mode.
10. Confirm that the MAINT color turns from amber to white.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-140 Control Items
Procedure 7-47
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the ETH OAM LB/LT Control from the Maintenance Test sub menu.
4. The ETH OAM LB/LT/DM/LM Control window appears. Click the Modify
Test Type button or select the desired Test No.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-141
5. The ETH OAM LB/LT/DM/LM Control dialog box appears. Assign a proper
value for each parameter.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-142 Control Items
(a) LB Result
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-143
(b) LT Result
(c) DM Result
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-144 Control Items
(d) LM Result
Click Export CSV File button on the top of the ETH OAM
LB/LT/DM/LM Control window.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Control Items 7-145
Click Export CSV File button in the LB (LT, DM, or LM) Result
window.
12. The Save As window appears. Select the proper folder of local PC and then
click Save button.
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
7-146 Control Items
13. When completed, the Download Complete window appears. Click Close
button.
14. Confirm that the CSV file is saved in the selected folder.
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Abbreviations 8-1
8. ABBREVIATIONS
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
8-2 Abbreviations
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Abbreviations 8-3
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
8-4 Abbreviations
NWD-118791-01E Maintenance
Submission Prohibited
NEC Internal Use Only
Abbreviations 8-5
WR Warning
WRR Weighted Round Robin
WS Wayside
XCTRL XPIC Control
X-DEM XPIC Demodulator
XFP 10(X) Gigabit Small Form Factor
Pluggable
XIF XPIC IF
XPD Cross Polarization Discrimination Ratio
XPIC Cross Polarization Interference
Canceller
XREF XPIC Reference
Maintenance NWD-118791-01E
Submission Prohibited
NEC Internal Use Only
8-6 Abbreviations
NWD-115477-01E Maintenance