Professional Documents
Culture Documents
Line Trap
Line Trap
Line Trap
a) Genera
l
b) Method of Coupling
Coupling of the power line carrier signals to the power circuit shall be by
means of coupling filters (line matching units), coupling capacitors and line
traps. The methods of coupling used shall be:
c) Line Traps
Line traps shall be rated 1mH, 3150A at 500kV and shall be according to K-
Electric specifications for substation project.
The line traps shall be designed for outdoor service and shall be capable of
withstanding the severe atmospheric conditions experienced in tropical
climates.
The equipment shall be designed, manufactured and tested in accordance with
the latest issue of IEC 60353.
The line traps shall be of the wide-band tuned type covering at least 300kHz at
a blocking resistance of 600 ohm (band to be selected later).500kV line traps
shall in installed on separate steel support structures
Jumper clamps shall be included for connection of the overhead line with the line
traps through down droppers. The clamps shall be suitable for fixing on line traps,
the diameter of the conductor grooves on the clamp must match that of the
down droppers used in each relevant substation.
The line trap shall comprise a main coil with a protective unit and a tuning
device. The tuning unit shall be mounted inside the main coil such that it is
easily accessible and can be changed without removing the line traps Tuning
devices component shall be designed to withstand all relevant electrical and
mechanical stresses
The protective device shall use non-linear type arresters, in accordance with
IEC Recommendations. The nominal discharge current shall preferably be the
same as that of the grid station arresters, installed behind the line trap, but in no
case less than 5kA.
The CCs shall be single phase units, oil-filled type. Each device shall be
connected between the line and ground and shall be equipped with two
secondary windings. Under no condition of operation shall a complex wave
be generated which will interfere with proper operation of the relays. Each unit
shall be furnished with ferro-resonance suppression devices.
The CCs shall be used for PLC signal coupling on transmission lines and shall
be equipped with bushings for connection of PLC coupling equipment and, as
required, with necessary carrier accessories. The carrier coupling accessories
shall
include the drain coil, the arresters or spark gap across the drain coil for
over- voltage protection, external accessible grounding switch across the drain-
coil and a fitting for carrier frequency cable. The carrier accessories shall be
installed in a secondary terminal box fitted at the base of the unit.
The units shall consist of a capacitor divider unit and an electromagnetic unit
properly designed and interconnected. A protective device shall be
incorporated in the coupling capacitor for the purpose of limiting over-
voltage which may appear across one or more of its components, and to
prevent sustained ferro-resonance (harmonic or sub-harmonic oscillation of the
device or its associated burden).
The CC shall be constructed to provide adequate insulation for the insulation class
specified and to withstand the mechanical and thermal stresses produced
under short-circuit conditions.
A dust- and weather-proof base housing shall be provided at the base of the high
voltage capacitor stack, containing the intermediate potential transformer,
compensation devices, ferro-resonance suppression devices and protective
devices.
The tank shall be constructed of welded steel plate and shall be suitably
reinforced to withstand handling and excessive pressures, under fault
conditions, without distortion. Where welding is done, a sealed weld shall be
used in every case so that no crack or pinhole is left where rusting could take
place, or through which pickling solutions might attack the weld.
The CC shall be delivered complete with steel supporting structure. The minimum
creepage distance shall be 4600mm. The Contractor shall provide complete
details of the steel structures with the tender.
The coupling device (CD) shall couple and decouple the high-frequency
signals of the power line carrier unit from and to the transmission system.
The CD shall work like a high-pass filter for coupling to the overhead
transmission lines. For coupling to the underground cable feeders, the CD shall be
designed as band-pass filter.
Broad-band coupling devices shall be provided for each phase. The tuning
range of the unit shall be field programmable and the composite loss over the
range shall not be greater than 2dB. The line side and equipment sides return
losses shall be greater than 12dB over the available bandwidth of the filter. The
line side
impedance shall be in the range 300-600 ohms for coupling to overhead
transmission line and in the range 20-30 ohms for coupling to the underground
cable feeder. The equipment side impedance shall be in the range of 75 ohms
(unbalanced) to 150 ohms (balanced). The coupling unit shall be
programmable for various coupling capacitances, line and equipment side
impedances.
The coupling units shall provide for impedance matching, filtering and
operation safety and shall comply with IEC Recommendation 60481
The units shall be adaptable for either, centre phase to outer phase or inter-
circuit coupling. For phase to phase coupling, it shall be possible to earth
either of the coupling filters and continue with carrier transmission on phase to
ground basis using the other filter.
All components shall be suitable for outdoor operation in the prevailing climatic
conditions. Cubicles shall have weather proof door and cable inputs seals,
adequately protected against condensation and shall be designed to a
protection class of IP54 or better. They shall be suitable for mounting on CC
rectangular lattice type steel support structures.
The unit shall be designed to ensure the safety of operators and the protection
of the carrier equipment against the effects of the network high voltage, and
of transient over-voltage conditions. Full compliance with IEC
recommendations shall be provided.
The unit shall have surge arresters and an earth switch. The terminal of the
device connected directly to the substation earth shall be clearly marked.
All elements such as coupling filters, drain coils or protective devices shall
be suitable for the coupling capacitor to be applied. A drain coil shall earth the
50Hz current so that the applied voltage meets the prevailing safety requirements
i.e.:
The unit shall withstand without damage a shock-wave 1.2/50μs of 6kV peak
value applied on the power line side.
Insulation level shall be of 5kV rms applied for one minute between each
coil and earth and between each coil and screen.
The connecting cable between the coupling unit and the coupling capacitor shall
be included. It shall have a diameter of at least 8mm and shall be isolated
and fixed sufficiently to withstand the mechanical and electrical stresses in case
of HV faults.
Name Plate
The coupling box, the earth switch, the main surge arrester and the drain coil
shall be equipped with name plates of weather-resistant material, placed so
that it is easily visible, with irremovable inscriptions.
f) Coaxial Cable
The cable shall be PVC insulated; galvanized steel tape armored with a further
outer sheath of PVC and shall be suitable for direct laying in the earth/ trenches
and for use in tropical climates (temperature 0-70°C and humidity
approaching 100%). The inner conductor shall be copper with a diameter of 1-
2mm whereas the outer conductor shall be bare copper braid.
The MDF shall be housed in a self-standing cabinet lockable from the outside.
The cabinet shall be dust and vermin proof, designed to a protection class of
IP43 (IEC 60529). Provision shall be made for earthing the cabinet to the earthing
system at each location.
The entry of cables shall be from the bottom through suitable glands provided in
the plates and care shall be exercised that the glands are tightly closed after the
installation of cable.
One Quick connect tool shall be provided with each cabinet, installed in such
a manner that it cannot be removed from the cabinet.
h) TELEPHONE SET
Various Telephone set shall be offered for consideration .These units shall include:
i. General purpose instrument using push-button facility with analog or digital voice
transmission.
Push button telephone with on-hook dialing and last number repeat.
LCD display to check number or facility stored under a button, preparation of
numbers off-line, checking of last number dialed.
Status indication of dialed terminals.
Autos dial number storage.
iii. Sound device shall be provided according to the location of telephone sets and
shall be of the following types:
Normal ring
Strong ring
Very strong ring
Horns
General
Tests for the Telecom Equipment shall be mainly on functional basis and shall
include Factory and Site tests.
Testing of the telecom equipment stated herein shall be performed in line with
this specification and in accordance with the relevant International Standards.
Where no appropriate Standard is available, tests shall be carried out in
accordance with the Manufacturer's standard practice, subject to the approval of the
Engineer/Employer.
Factory Tests
a) Type Tests
The telecom equipment (Power line carrier equipment, outdoor coupling equipment,
Protection signaling equipment and telecom cabinets) should have successfully
undergone, as a minimum, the following type tests:
Dry heat
test.
Damp heat
test.
Humidity cycling
test.
Soak
test.
Vibration test on
rack/cubicle.
Insulation test of wires (2kV
AC).
EMC tests.
Transient interference
tests
Radiation interference
tests.
Long time temperature
tests.
The bidder shall submit certified copies of type test certificates covering the above
Telecom equipment.
Failure to provide the certificates or if the presented type test reports are not in
accordance with the above requirements, then the type tests shall be carried out in
the Manufacturer’s premises or other places in the presence of Engineer/Employer
at no additional cost. These tests shall be performed in the presence of an
internationally recognized laboratory, which should issue the relevant type test
certificates upon successful tests
b) Routine
Tests
General
Visual checks.
Checks of wiring and labeling.
Verification of material and quantities for each equipment.
Test of cubicles internal illumination.
Check of Spare Parts and quantities.
Coupling Device.
Drain Coil:
HF Coaxial Cable
Routine tests on line traps shall be performed in accordance with IEC 60353 and shall
include, as a minimum:
Measurement of rated inductance of the main coil.
Measurement of power frequency inductance of the main coil.
Measurement of blocking resistance and blocking impedance.
Measurement of tapping loss and tapping loss based on the blocking
resistance.
Measurement of frequency range of the tuning units.