Shenzhen Plot Electronic Co., Ltd
3/33
⑴
MAM-860
MAM-860VF
MAM-870
MAM-880
MAM-880VF 点击产品型号可出现相应产品图片
MAM-890
MAM-890E
MAM-660
MAM-660VF
MAM-680
MAM-680VF
KY02S/MAM-100
KY02S VF3/MAM-100C
KY02S/MAM-200
KY02S VF3/MAM-200C
KY12S/MAM-260
点击产品型号可出现相应产品图片
KY12S/MAM-280
KY16S/MAM-100
KY16S/MAM-200
KY08S/MT6070IH
KY08S/MT6070IP
KY18S/MT6070IH
KY18S/MT6070IP
⑴ Voltage:220V Range:110~240V
KY02S
KY02S series、KY08S
series、KY08S series
series
Voltage:220V KY16S
KY16S series、KY18S
series、KY18S series
series
KY12S
KY12S series
series
Voltage:24V MAM-860/870/880/890
MAM-860/870/880/890
MAM-660/680
MAM-660/680
Note:All in one controller use switching power supply and mostly 24VAC
If voltage too low,switching power supply is not available;
If voltage too high,filter capacitor will be damaged and switching power supply
will not be available for voltage protection.Please pay special attention to the
switching power supply which is capacitive load and place a transformer in front
of power input for isolation.In the absence of good filtering,switching power
supply can‘t connect with the output of the inverter because high frequency
inverter has very high voltage pulse which can damage the internal varister and
filtering capacitance.Controller need connect with AC independently if use
variable-frequency power supply.
Shenzhen Plot Electronic Co., Ltd
7/33
1 Digital Input
3 Analog Input:Temperature
controller
5 Analog Input:Transformer Current
6 Analog Output:4~20 mA
1 Digital Input
2 Relay Output
3 Analog Input:Temperature
Resistance temperature sensor:PT100 or PT1000,shown
as below:
4 Analog Input:Pressure
4~20mA pressure sensor,shown as below:
Sample resistance R is 10Ω at 40A and 100A; 5.1Ω at 200A and 400A; 51Ω at
600/5A
For fan ,100Ω at 100A,51Ω at 200A,24Ω at 400A.
User can measure the resistance in current input terminal by multimeter to make
sure of current level.
• Notes:
• VSD freq sourse selectable: current or voltage.Some inverter need choose
current signal or pressure signal.Pay attention to inverter wiring diagram
• When set as current ,inverter parameter needs to be adjusted,4~20mA
current signal is chosen.
7 Relay output:
7.1 MAM-860/870/880/660/680、KY12S has 5 relay output:
MAM-860
MAM-860
MAM-870
MAM-870 MAM-KY12S
MAM-KY12S
MAM-880
MAM-880
Voltage Testing
Controller with voltage detecting function:
Controller have high voltage and low voltage protection by testing two phase
voltage.For mactab controller,monitor should match with controller,otherwise,monitor
will not display voltage error detected
•Setting Method:
slave set:In stop mode,press“↓”enter interface and select "user parameter".Press“→”enter "operation
mode" ,and set "communication mode":block. "Communication code" start from 0002 to 0016,
(Notes:same No. is not allowed in the net).Return to "user parameter",and select "block parameter
set",press“→”enter block parameter setting,choose "block state" :slave
" block control","alternative time","block quantity","block pressure min","block pressure max","block
delay time" is suggested to be set the same with master for the convinience of maintainance and
replacement.
RUN PARAMETER
CALENDAR
CUSTOMER PARAMETER
FACTORY PARAMETER
SET P、TEMP. BLOCK STATE:SLAVE
SET DELAY TIME BLOCK ON/OFF:ALONE
OPERATION MODE TURN TIME:99H
BLOCKING MODE BLOCK NUMBER:16
•Net connection :
Good shielded cable to connect controller communication terminal of A and B in parallel is
required in block mode control. Avoid high voltage interference in wiring, also,seperate signal
cable and power cable should be placed in different conduit
Compressor net connection structure is shown as below
………
1 2 3 4 ……… N
master slave slave slave slave
………
1 2 3 4 ……… N
………
1 2 3 4 ……… 8
•DEFINITIONS :
Block quantity:Set in the block parameter of master marked as 001 and16 pcs at most is allowed in the net
including master.
Block delay:In block mode,master has to delay for a while before it sends command to the slaver
twice(example:When master send command of turning on or loading,air tank will not get pressure
immediately,master needs a delay time(block delay time set here) and compare air supply pressure and block
pressure min,master will analysis if the pressure supply is less than block pressure min for a while,and sent
command to next compressor for turning on or loading to avoid frequently on-off operation)。
Master:"Communication code" is set as 001, "block parameter" is set as master.Only one controller can set as
master and master needs to set "block quantity","block pressure max","block pressure min" and" block delay" .
Slave:"Communication code" is set as “002-016”."Block parameter " is set as “slave”.Slave communication code is
different from each other.
Block pressure min:Set in the block parameter.In block mode .When compressor is at standby or stop
status,master will choose one controller to load or turn on when pressure supply is under block pressure min .
Block pressure max:Set in the block parameter.In block mode ,when some compressor is loading ,master will
choose one controller to unload when pressure supply is beyond block pressure max.
Notes:Controller need to power off and reset after reset the communication parameter. In block control,you need
only start the master to start network.The slave is under the control of master.Master will not start block mode
automatically after power off and restart,you need press the button to start block control.If only slave is power off
and restart ,slave will join the block mode automatically by the control of master.You need to stop the network by
pressing the stop button in master,after that,master will not control slave any more.When a running compressor is
encounter failure stop and there is a compressor at stop mode in the net, compressor at stop mode will not run by
the command of master until master pressure supply is under the block pressure min .In this way,pressure is
always under the limit set by user.
Shenzhen Plot Electronic Co., Ltd
27/33
Note;
1、First transformer has to connect
correctly:
2、Second transformer's reel has to be
consistant,otherwise ,current is unbalance.
Phase sequence a、Phase sequence wrong Check if the phase sequence is correct,if wrong sequence
wrong not,check if the input voltage is normal or b、Replace or reconnect for open
4 b、Open phase
adujst any two of the cable or adjust the phase
c、Controller failure phase sequence protection parameter. c、Reset threshold value,replace
controller
a、No rated voltage input Check 43,44 voltage,if no a、Connect with rated voltage
b、Check if 21,22,9,10 terminal problem,disconnect 21,22,9,10 terminal,if
5 No power supply b、Repair short circuit
suffer short circuit or not still powered on,check where suffer short
circuit,if not,the controller is defective c、Replace controller
c、controller failure
a、Switch of corresponding digital
input failure Use shorting stub to simulate a、Replace external defective
corresponding on-off status,if work accessory
Digital input b、Connection cable defective or
6 failure disconnected
normal,problem should be external (such
b、Reconnect or replace cable
as cable connection and
c、Digital input inside controller switches),otherwise,controller is defective c、Replace controller
30/33
Check the three phase current with LEM,if work normally,tighten the
Motor current failure(open a、 Wrong data setting terminal connecting transformer and controller to avoid poor contac
7 phase ,overload, b、Transformer failure problem persist,use multimeter to check if the resistance of the three
unbalance) c、Controller failure connecting 9th terminal is the same and meet the correponding gear
so,transfomer is defective ,otherwise,controller is defective
Moter overload during start- Set motor delay time less than star-
8 Check data set
up delta delay time
a、Cable disconnect Test if the temperature sensor functions well(PT100 :100 Omh at 0
Temperature
b、Sensor failure Omh at 1000℃),if no prblem,reconnect to controller and make sure
9 incorrect,temperature sensor
c、Controller temperature circuit connection well and see if temperature is correctly measured,if
failure
failure not,controller is defective
a、Sensor failure Power on and connect multimeter in series to test current,if current
Pressure incorrect,pressure voltage matches and controller display wrong voltage which means
10 b、Cable broken or connect reversely
failure controller is defective,otherwise ,pressure sensor is defective.In
c、Controller failure addition,when power off,resistance between pressure input(12) and
temperature terminal (9)could be 220 Omh
深圳市普乐特电子有限公司
31/33
Category
Failure Analysis
Current signal c、Connection cable between transformer and controller is damaged or poorly
contacted
d、Component for controller moter and fan current testing is damaged by lightning
stroke
a、Temperature sensor misuse(PT100/PT1000)
b、Temperature sensor failure
Controller Tempreture signal c、Temperature sensor failed to connect with the corresponding terminal according to
the electrical diagram.
d、Component for controller temperature testing is defective or damaged by lightning
signal stroke
wrong a、Pressure sensor failure or is damaged by lightning stroke
b、Pressure sensor fail to connect with the corresponding terminal according to the
Pressure signal electrical diagram.
c、Controller pressure measurement and sensor is not match
d、Controller pressure testing component is defective or damaged by lightning stroke
a、Monitor and controller not match
b、Communication cable and communication socket is damaged
Other signal c、Communication cable suffer poor contact
incorrect(including
above three d、Communication circuit for controller or monitor and other relative circuit
problem) component is damaged
e、Main board is broken or damaged by water and pollution
32/33