Plano Mikrolift Ml50s
Plano Mikrolift Ml50s
A A
B
ML50S CONTROL PANEL CONNECTION, B
C C
D D
Version : 2.11
Standard : EN81-20
Date of Update : 28.5.2019
E E
Important Note : These schemes are advisory. Mikrolift reserves the right to change schemes. Our company cannot be held
responsible for any changes made by persons other than those within our company.
F F
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
R
S
A T A
N
PE
UPS_P_UNFUSE
UPS_P
UPS_N
FKR1 4A
ED_220AC_N
B 6A B
ED_220AC_P
F2 IN OUT F1
..P P.. EARTH
..N UPS N..
100
30mA 1000
2A
GROUND FAULT
PROTECTED F4
AUTOMAT FUSE 220V AC 24V DC BRIDGE
4A
220V AC +
AC
20V AC F5
-
C DC C
35A / 1000V
Main Transformator
RC Filter
CRL-P:2-CR:10B
NC1
4A RUPS-P:2-CR:10B
KP RKP-P:2-CR:10B
Kups
D D
F17
GROUP WOTOMAT
RC Filter
NC1
Kups xxxx-P:xx-CR:xxx
GW1
KP
Sayfa Numarası
Page Number
K-NOTR
PE
NOTR
K220
Title : Main
Power and UPS Connection
L1 L2 L3 N PE
For Electrical Lifts
F TO CAR WIRING F
Project: ML50S Revision: 1
R
S
A T A
N
PE
UPS_P_UNFUSE
UPS_P
UPS_N
4A
FKR2
ED_220AC_N
B F10 B
6A ED_220AC_P
IN OUT F9
..P P.. EARTH
..N UPS N..
100
30mA 1000
2A
GROUND FAULT
PROTECTED F12
AUTOMAT FUSE 220V AC 24V DC BRIDGE
4A
220V AC +
AC
20V AC F13
-
C DC C
35A / 1000V
Main Transformator
4A
D D
F15
GROUP WOTOMAT
xxxx-P:xx-CR:xxx
GW2
Sayfa Numarası
Page Number
K-NOTR
1
PE
K220
NOTR
Title : Main
Power and UPS Connection
L1 L2 L3 N PE
For Hydraulic Lifts
F F
TO CAR WIRING Project: ML50S Revision: 1
R
S
A T A
N
PE
OUTx-P:2-CR:10A
UPS_AKU(-)
UPS_AKU(+)
UPS_P
UPS_N
FKR7
ED_220AC_N
B B
4A ED_220AC_P
F47 EARTH
I1
I2
(-)
(+)
1000
100
AKÜ 30mA 1000
BATTERY 2A
GROUND FAULT
MLPOWER PROTECTED
AUTOMAT FUSE F61
220V AC 24V DC BRIDGE
4A
ÇIKIŞ GİRİŞ 220V AC +
OUTPUT INPUT AC
N
F62
L
20V AC
-
C DC C
35A / 1000V
Main Transformator
RC Filter
F63 6A
CRL-P:2-CR:10B
NC1
RUPS-P:2-CR:10B
KP RKP-P:2-CR:10B
Kups
D D
RC Filter
GROUP WOTOMAT
5 x 12V / 7Ah
4A
-+ -+ -+ -+ -+
NC1
F64
Kups xxxx-P:xx-CR:xxx
GW3
KP
Sayfa Numarası
Page Number
K-NOTR
1
PE
K220
NOTR
Title : Main
Power and MLPOWER Connection
L1 L2 L3 N PE
For Electrical Lifts
F F
TO CAR WIRING Project: ML50S Revision: 1
R
S
A T A
N
PE
UPS_AKU(-)
UPS_AKU(+)
UPS_P
UPS_N
FKR8
ED_220AC_N
B B
4A ED_220AC_P
F67 EARTH
(-)
(+)
100
AKÜ 30mA 1000
BATTERY 2A
GROUND FAULT
60VDC-UPS PROTECTED
AUTOMAT FUSE F69
220V AC 24V DC BRIDGE
4A
ÇIKIŞ GİRİŞ 220V AC +
OUTPUT INPUT AC
N
F70
L
20V AC
-
C DC C
35A / 1000V
Main Transformator
4A
RC Filter
6A
F73
F71
CRL-P:2-CR:10B
NC1
RUPS-P:2-CR:10B
KP RKP-P:2-CR:10B
Kups
D D
RC Filter
GROUP WOTOMAT
5 x 12V / 7Ah
-+ -+ -+ -+ -+
NC1
Kups xxxx-P:xx-CR:xxx
KP
GW4
F74 6A
Sayfa Numarası
Page Number
K-NOTR
PE
NOTR
K220
Title : Main
Power and 60VDC-UPS Connection
L1 L2 L3 N PE
For Electrical Lifts
F F
TO CAR WIRING Project: ML50S Revision: 1
R
S
A T A
N
PE
UPS_P_UNFUSE
UPS_P
UPS_N
4A
FKR9 ED_220AC_N
B F75 6A B
ED_220AC_P
IN OUT F76
..P P.. EARTH
UPS
MAIN BRAKER
..N N..
100
30mA 1000
2A
GROUND FAULT
PROTECTED F79
24V DC BRIDGE
AKS1
20V AC F80
-
C DC C
35A / 1000V
Main Transformator
GW5
CURRENT PROTECTION
RC Filter
3 PHASE LEAK
FKR10
RC Filter
FKR11
F85
NC1
6A
Kups xxxx-P:xx-CR:xxx
KP
A1 PULSE
E CURRENT Bağlantı İsmi Sutun Satır Koordinatı E
A2 SWITCH Connection Name Column Row Coordinate
Sayfa Numarası
Page Number
K-NOTR
3
3S
NS
PE
NOTR
K220
Title : Main
Power and UPS Connections For
L1 L2 L3 N PE WELL WELL
LIGHTING LIGHTING Machine Roomless (MRL) Panel ( For Electical Lifts )
F BUTTON LAMPS F
Project: ML50S Revision: 1
TO CAR WIRING
Date: 28.5.2019 Sheet: 1e www.mikrolift.com
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
R
S
A T A
N
PE
OUTx-P:2-CR:10A
UPS_AKU(-)
UPS_AKU(+)
UPS_P
UPS_N
FKR12
ED_220AC_N
B B
4A ED_220AC_P
I1
I2
(-)
(+)
1000
AKÜ F90 EARTH
BATTERY 100
30mA 1000
MLPOWER GROUND FAULT 2A
PROTECTED
ÇIKIŞ GİRİŞ AUTOMAT FUSE F92
OUTPUT INPUT 220V AC 24V DC BRIDGE
4A
N
N
L
220V AC +
AC
20V AC F93
F94 -
C DC C
6A
4A
35A / 1000V
Main Transformator
MAIN BRAKER
RC Filter
F96
5 x 12V / 7Ah
-+ -+ -+ -+ -+
AKS2
CRL-P:2-CR:10B
NC1
RUPS-P:2-CR:10B
PANEL FUSE
FKR13
KP RKP-P:2-CR:10B
F97 6A Kups
D D
GW6
CURRENT PROTECTION
RC Filter
LEAK CURRENT
PROTECTION 6A
NC1
FKR14
Kups xxxx-P:xx-CR:xxx
KP
A1
3S
NS
PE
NOTR
K220
Title : Main
Power And MLPOWER Connections For
L1 L2 L3 N PE WELL WELL
LIGHTING LIGHTING Machine Roomless (MRL) Panel ( For Electical Lifts )
F BUTTON LAMPS F
TO CAR WIRING
Project: ML50S Revision: 1
R
S
A T A
N
PE
UPS_AKU(-)
UPS_AKU(+)
UPS_P
UPS_N
(-)
(+)
AKÜ FKR15 ED_220AC_N
B BATTERY B
4A ED_220AC_P
EARTH
60VDC-UPS F103
100
ÇIKIŞ GİRİŞ 30mA 1000
OUTPUT INPUT 2A
GROUND FAULT
N
N
L
L
PROTECTED
AUTOMAT FUSE F105
220V AC 24V DC BRIDGE
4A
F106 6A 220V AC +
AC
20V AC F107
MAIN BRAKER
-
C DC C
5 x 12V / 7Ah 35A / 1000V
Main Transformator
-+ -+ -+ -+ -+
AKS3
RC Filter
4A
PANEL FUSE
F109
LEAK CURRENT NC1
RUPS-P:2-CR:10B
PROTECTION
CURRENT PROTECTION
KP RKP-P:2-CR:10B
Kups
D D
F111 6A
3 PHASE LEAK
RC Filter
FKR16
FKR17
F89 NC1
6A Kups xxxx-P:xx-CR:xxx
KP
Title : Main
Power And 60VDC-UPS Connections For
K-NOTR
3
3S
NS
PE
NOTR
K220
A A
UPS_P UPS_P
UPS_N UPS_N
3A
F141
LR-P
LR-N
B B
BR-P
BR-N
C C
D D
E E
A A
UPS_P UPS_P
UPS_N UPS_N
3A
F142
LR-P
220V AC
70V AC
LR-N
B B
BR-P
BR-N
Brake Transformator
C C
D D
E E
A A
UPS_P UPS_P
UPS_N UPS_N
3A
F143
LR-P
LR-N
220V AC
70V AC
B B
BR-P
BR-N
Cam & Brake Transformator
C C
D D
E E
A A
UPS_P UPS_P
UPS_N UPS_N
3A
F144
LR-P
LR-N
220V AC
55V AC
B B
BR-P
BR-N
Cam Transformator
220V AC
70V AC
C C
Brake Transformator
D D
E E
A A
UPS_P UPS_P
UPS_N UPS_N
3A
F145
LR-P
220V AC
55V AC
LR-N
B B
BR-P
BR-N
Brake Transformator
C C
D D
E E
A A
UPS_P UPS_P
UPS_N UPS_N
3A
F146
LR-P
LR-N
220V AC
70V AC
B B
BR-P
BR-N
Cam Transformator
220V AC
55V AC
C C
Brake Transformator
D D
E E
A A
UPS_P UPS_P
UPS_N UPS_N
3A
F147
LR-P
LR-N
220V AC
55V AC
B B
BR-P
BR-N
Cam & Brake Transformator
C C
D D
E E
A A
TO CONTROL
PANEL
L1
L3
L2
PE
B B
MAIN BRAKER
FKR26
AKS4
F153 6A
FKR27
CURRENT PROTECTION
C C
PULSE
3 PHASE LEAK
A1 CURRENT
SWITCH
A2
L1
L3
L2
PE
3S
NS
PE
NOTR
D D
MAIN LINE WELL WELL
LIGHTING LIGHTING TO CAR WIRING
BUTTON LAMPS
E E
R-P:1-CR:10A R-P:1-CR:10A
S-P:1-CR:10A S-P:1-CR:10A
T-P:1-CR:10A T-P:1-CR:10A
N-P:1-CR:10A N-P:1-CR:10A
A PE-P:1-CR:10A PE-P:1-CR:10A A
OUT1
OUT2
RCOM
RC1
CRL
RU2 RKP
RU1 RUPS
S4
S3 RX1
S2 RX2
S1 RD1
B B
11 RD2
RB1
RB2
S1
RU1
OUT1
RC1
RX1
RD1
RB1
11
S3
S
MP
RKP
RUPS
T
S2
S4
RU2
OUT2
CRL
RX2
RD2
RB2
RCOM
R 1000-P:1-CR:10B
15V 100-P:1-CR:10B
10B 10B GND
140 140 A
135 135 -A
130 130 B
120 120 -B
10A 10A
C PTC C
LCD 1000
130F 130F 100
OSG1 OSG1
OSG2 OSG2 ML50S ENTER
KXO1 KXO1
KXO2 KXO2
KN1 KN2
DHG
KRC
HRF
PG5
PG6
PG7
PG8
PG9
MLD
ESC
PG5
1000
PG6
100
P1
P2
P3
P4
P5
P6
D PG7 D
PG8
PG9
KRC
HRF
DHG
Machine
Motor PTC Well PTC
Room PTC
Flat Cable 16 Flat Cable 16
xxxx-P:xx-CR:xxx
E E
KN1 Bağlantı İsmi Sutun Satır Koordinatı
KN2 Connection Name Column Row Coordinate
Sayfa Numarası
Page Number
N-P:1x-CR:10A N-P:1x-CR:10A
A PE-P:1x-CR:10A PE-P:1x-CR:10A A
1000-P:1x-CR:10B
TL5 100-P:1x-CR:10B
TL4
TL3 SC
ML2 SD
ML1
1-P:1x-CR:5E
GA4
GA3 K220-P:1x-CR:5E
GA2 K-NOTR-P:1x-CR:5E
GA1
B B
KN2-P:2-CR:1E
KN1-P:2-CR:1E
Flat Cable 16
Flat Cable 16
GA1
ML1
1
GA3
TL3
EH1
GA2
ML2
TL5
EH3
SC
GA4
PE
1000
TL4
SD
1000
100
PE
K220
EH2
EH4
NOTR
K-NOTR
CAN1
KN1 KN2
C MLKLM50S-A C
K-NOTR
NOTR
500K
501K
K220
YAN
ML1
ML2
1000
ALB
ALB
1000
C2H
DEP
EH1
EH2
EH3
EH4
PG1
PG2
PG3
PG4
C2L
TL3
TL4
TL5
+12
+12
870
100
869
100
817
818
PE
PE
1
YAN Flexible Cable 32
DEP
PG1
PG2
D PG3 D
PG4
ALB
+12
870-P:9-CR:1B
501-P:9-CR:1B
500-P:9-CR:1B
100-P:9-CR:1B
xxxx-P:xx-CR:xxx
E E
Bağlantı İsmi Sutun Satır Koordinatı
TO MLKABIN-R50 Connection Name Column Row Coordinate
Sayfa Numarası
(PAGE 8) Page Number
A A
UPS_P-P:1x-CR:10B UPS_P-P:1x-CR:10B
UPS_N-P:1x-CR:10B UPS_N-P:1x-CR:10B
100-P:1x-CR:10B 100-P:1x-CR:10B
1000-P:1x-CR:10B 1000-P:1x-CR:10B
OSG1-P:2-CR:1C
OSG2-P:2-CR:1C
HRF-P:2-CR:1D
B NO2 B
KXO1-P:2-CR:1C
KX1
KXO2-P:2-CR:1C
NO2 NO3
130-P:2-CR:1C
KF KF
130F-P:2-CR:1C
C C
4A
F7
OSG SELENOID BRIDGE
D D
35A / 1000V
AC
DC
xxxx-P:xx-CR:xxx
+
-
HBR2
BK1
BK2
OSG OSG
Selenoid Selenoid
NC Contact
A A
UPS_P-P:1x-CR:10B UPS_P-P:1x-CR:10B
UPS_N-P:1x-CR:10B UPS_N-P:1x-CR:10B
100-P:1x-CR:10B 100-P:1x-CR:10B
1000-P:1x-CR:10B 1000-P:1x-CR:10B
OSG1-P:2-CR:1C
OSG2-P:2-CR:1C
HRF-P:2-CR:1D
B NO2 B
KXO1-P:2-CR:1C
KX1
KXO2-P:2-CR:1C
NO2 NO3
130-P:2-CR:1C
220V AC
KF KF
130F-P:2-CR:1C
C 28V AC C
4A
F33
OSG SELENOID BRIDGE
D D
35A / 1000V
AC
DC
xxxx-P:xx-CR:xxx
+
-
HBR2
BK1
BK2
OSG OSG
Selenoid Selenoid
NC Contact
A A
UPS_N-P:1x-CR:10B UPS_N-P:1x-CR:10B
SG_P-P:6x-CR:1B
B B
SET RESET
C C
SG-R
SG-S
D N D
xxxx-P:xx-CR:xxx
A1 A2 A1 A2
Bağlantı İsmi Sutun Satır Koordinatı
Connection Name Column Row Coordinate
Set Selenoid Reset Selenoid
Sayfa Numarası
Page Number
E E
OVERSPEED GOVERNOR
A A
UPS_N-P:1x-CR:10B UPS_N-P:1x-CR:10B
SG_P-P:6x-CR:1B
-
DC
+
AC
B 35A / 1000V B
SET RESET
C C
SG-R
SG-S
N
D D
xxxx-P:xx-CR:xxx
A1 A2 A1 A2
Bağlantı İsmi Sutun Satır Koordinatı
Connection Name Column Row Coordinate
Set Selenoid Reset Selenoid
Sayfa Numarası
Page Number
E E
OVERSPEED GOVERNOR
Title : Remote
Control For Overspeed Governor
(For 190VDC Coil)
F F
Project: ML50S Revision: 1
UPS_AKU(+)-P:1C-CR:10B
UPS_AKU(-)-P:1C-CR:10B UPS_P-P:1x-CR:10B
UPS_N-P:1x-CR:10B
A 100-P:1x-CR:10B 100-P:1x-CR:10B A
1000-P:1x-CR:10B 1000-P:1x-CR:10B
PE-P:1x-CR:10A
ED_220AC_N-P:1x-CR:10B NC1 NC1 NC1
KRC-P:2-CR:1D
ED_220AC_P-P:1x-CR:10B KF KX1 KX2
DHG-P:2-CR:1D
S2-P:2-CR:1B
R-P:1x-CR:10A
S4-P:2-CR:1B
S-P:1x-CR:10A
S1-P:2-CR:1B
T-P:1x-CR:10A
RU2-P:2-CR:1B
PE-P:1x-CR:10A
RU1-P:2-CR:1B
30mA 11-P:2-CR:1B
FKR18 LR-N-P:1hx-CR:10B
B LR-P-P:1hx-CR:10B B
GROUND FAULT
RD1-P:2-CR:10B
PROTECTED
RD2-P:2-CR:10B
F21 10A AUTOMAT FUSE
PE
L3
L2
L1
BR-N-P:1hx-CR:10B
BR-P-P:1hx-CR:10B
10A-P:2-CR:1C
LINE
FILTER Kups
10B-P:2-CR:1C
NO1
AC1 140-P:2-CR:1C
PE
L3
L2
L1
NO1
RMB1
RMB2
RFO
RFCOM
AC2 RC Filter
KP
KX1
KF
S2 RX1-P:2-CR:10B
C R S6 RX2-P:2-CR:10B C
S1 NO1 RC Filter
S
RSC
T Kups
MLDRIVER
UP
NO1
DOWN KX1 (1*)
PE COM
KX2
ENB RC Filter
W
U
V
B
P
35A / 1000V
35A / 1000V
KX2 (1*)
AC
AC
NO2 NO2
DC
DC
KX1 KX2
110-P:7-CR:1D
KX2
+
+
-
KF (2*)
KF (2*)
E E
W1
B1
B2
2001
2000
840
UPS_AKU(+)-P:1C-CR:10B
UPS_AKU(-)-P:1C-CR:10B UPS_P-P:1x-CR:10B
UPS_N-P:1x-CR:10B
A 100-P:1x-CR:10B 100-P:1x-CR:10B A
1000-P:1x-CR:10B 1000-P:1x-CR:10B
PE-P:1x-CR:10A
ED_220AC_N-P:1x-CR:10B NC1 NC1 NC1
KRC-P:2-CR:1D
ED_220AC_P-P:1x-CR:10B KF KX1 KX2
DHG-P:2-CR:1D
S2-P:2-CR:1B
R-P:1x-CR:10A
S4-P:2-CR:1B
S-P:1x-CR:10A
S1-P:2-CR:1B
T-P:1x-CR:10A
RU2-P:2-CR:1B
PE-P:1x-CR:10A
RU1-P:2-CR:1B
30mA FKR19 11-P:2-CR:1B
B GROUND FAULT B
LR-N-P:1hx-CR:10B
PROTECTED
LR-P-P:1hx-CR:10B
AUTOMAT FUSE
10A F27 RD1-P:2-CR:10B
PE
L3
L2
L1
RD2-P:2-CR:10B
10A-P:2-CR:1C
LINE
FILTER Kups
10B-P:2-CR:1B
NO1
AC1
PE
L3
L2
L1
RMB1
RMB2
RFO
RFCOM
AC2 RC Filter
KP
S2
KF
C R S6 C
S1 RC Filter
S NO1
RSC
T Kups
MLDRIVER
UP
DOWN KX1 (1*)
PE COM
ENB RC Filter
W
U
V
B
P
PI KF (1*)
Control Panel
Emergency
Stop Button RX2-P:2-CR:10B
D D
CAM BRIDGE
35A / 1000V
KX1
KX2 (1*)
AC
NO2 NO2
PI-P:6x-CR:1A
DC
KX1 KX2
110-P:7-CR:1D
+
-
KX2
2001
810
E E
Door Lock
KX1 (2*) KX2 (2*)
Magnet Coil 1* Contactors must be of AC-3 class with 220VAC coils!
RC filters must connected across the coils of contactors!
V1
B1
B2
Bağlantı İsmi Sutun Satır Koordinatı Title : MLDRIVER and Contactors Connection
Synchronous Motor Coil Brake Connection Name Column Row Coordinate
Resistance For Gearless Machine
F Sayfa Numarası F
Page Number Project: ML50S Revision: 1
UPS_AKU(+)-P:1C-CR:10B
BR-N-P:1hx-CR:10B
UPS_AKU(-)-P:1C-CR:10B
BR-P-P:1hx-CR:10B
A 100-P:1x-CR:10B 100-P:1x-CR:10B A
1000-P:1x-CR:10B 1000-P:1x-CR:10B
PE-P:1x-CR:10A
ED_220AC_N-P:1x-CR:10B NC1 NC1 NC1
KRC-P:2-CR:1D
ED_220AC_P-P:1x-CR:10B KF KX1 KX2
DHG-P:2-CR:1D
S1-P:2-CR:1B
R-P:1x-CR:10A
S2-P:2-CR:1B
S-P:1x-CR:10A
S3-P:2-CR:1B
T-P:1x-CR:10A
S4-P:2-CR:1B
PE-P:1x-CR:10A
RU2-P:2-CR:1B
30mA RU1-P:2-CR:1B
FKR3
11-P:2-CR:1B
B GROUND FAULT LR-N-P:1hx-CR:10B B
PROTECTED LR-P-P:1hx-CR:10B
10A F54 AUTOMAT FUSE RD1-P:2-CR:10B
PE
L3
L2
L1
RD2-P:2-CR:10B
10A-P:2-CR:1C
LINE
FILTER
Kups
Kups 1N4007
10B-P:2-CR:1B
1N4007 140-P:2-CR:1B
PE
L3
L2
L1
NO1
RC Filter
1N4007 RX1-P:2-CR:10B
KX1
NO1
RX2-P:2-CR:10B
C1
100
1000
RHO
RFO
RHA
RFA
KP 1N4007
C V0 C
R V1 RC Filter
KF
V2
S
T
ADRIVE V3
UP
NO1
DOWN KX1 (1*)
PE EN
15 NO2 NO2 RC Filter
B1
B2
KX2
W
U
V
35A / 1000V
35A / 1000V
CAM BRIDGE
KX2 (1*)
AC
AC
DC
DC
KX2 110-P:7-CR:1D
+
+
-
- KF (2*)
KF (2*)
E E
W1
U1
V1
B1
B2
2000
High Brake
810
840
UPS_AKU(+)-P:1C-CR:10B
LR-N-P:1hx-CR:10B
UPS_AKU(-)-P:1C-CR:10B
LR-P-P:1hx-CR:10B
A 100-P:1x-CR:10B 100-P:1x-CR:10B A
1000-P:1x-CR:10B 1000-P:1x-CR:10B
PE-P:1x-CR:10A
ED_220AC_N-P:1x-CR:10B NC1 NC1 NC1
KRC-P:2-CR:1D
ED_220AC_P-P:1x-CR:10B KF KX1 KX2
DHG-P:2-CR:1D
S1-P:2-CR:1B
R-P:1x-CR:10A
S2-P:2-CR:1B
S-P:1x-CR:10A
S3-P:2-CR:1B
T-P:1x-CR:10A
S4-P:2-CR:1B
PE-P:1x-CR:10A
RU2-P:2-CR:1B
30mA RU1-P:2-CR:1B
FKR4
11-P:2-CR:1B
B GROUND FAULT B
PROTECTED RD1-P:2-CR:10B
10A F58 AUTOMAT FUSE RD2-P:2-CR:10B
PE
L3
L2
L1
10A-P:2-CR:1C
LINE
FILTER Kups
Kups
1N4007
10B-P:2-CR:1B
1N4007
PE
L3
L2
L1
NO1
RC Filter
1N4007
RX2-P:2-CR:10B
C1
100
1000
RHO
RFO
RHA
RFA
KP 1N4007
KF
C V0 C
R V1 RC Filter
V2
S
T
ADRIVE V3
UP
DOWN KX1 (1*)
PE EN
Control Panel
15 NO2 NO2 RC Filter
Emergency
X-ENC
Stop Button
KX1 KX2 KF (1*)
B1
B2
W
U
V
4 Cable
D D
35A / 1000V
CAM BRIDGE
KX2 (1*)
AC
KX1 X-ENC
PI-P:6-CR:1A
DC
ENCABIT 110-P:7-CR:1D
24V
+
-
PI1
PI2
PI3
X-ENC1
KX2
15 Cable
E E
xxxx-P:xx-CR:xxx
B24V
BRM
T1
T2
810
V1
Title : ADrive
and Contactors Connection
Synchronous Motor Coil For Gearless Machine
1* Contactors must be of AC-3 class with 220VAC coils!
F RC filters must connected across the coils of contactors! F
Project: ML50S Revision: 1
UPS_AKU(+)-P:1C-CR:10B
UPS_AKU(-)-P:1C-CR:10B
A 100-P:1x-CR:10B 100-P:1x-CR:10B A
1000-P:1x-CR:10B 1000-P:1x-CR:10B
PE-P:1x-CR:10A
ED_220AC_N-P:1x-CR:10B NC1 NC1 NC1
KRC-P:2-CR:1D
ED_220AC_P-P:1x-CR:10B KF KX1 KX2
DHG-P:2-CR:1D
R-P:1x-CR:10A
S2-P:2-CR:1B
S-P:1x-CR:10A
S4-P:2-CR:1B
T-P:1x-CR:10A
RU2-P:2-CR:1B
PE-P:1x-CR:10A
RU1-P:2-CR:1B
30mA FKR28 11-P:2-CR:1B
LR-N-P:1hx-CR:10B
B GROUND FAULT LR-P-P:1hx-CR:10B B
PROTECTED RD1-P:2-CR:10B
AUTOMAT FUSE RD2-P:2-CR:10B
F149 10A
PE
L3
L2
L1
BR-N-P:1hx-CR:10B
BR-P-P:1hx-CR:10B
10A-P:2-CR:1C
LINE RB1-P:2-CR:10B
FILTER Kups RB2-P:2-CR:10B
NO1
PE
L3
L2
L1
NO1
10B-P:2-CR:1C
140-P:2-CR:1C
KP
KX1
KF
RC Filter
30B
30C
Y5C
Y5A
CM
C R X4 C
RX1-P:2-CR:10B
X3
S RX2-P:2-CR:10B
X2 RC Filter
T FUJI X1
REV
INVERTER
NO1
FWD
PE PLC
CMY KX1 (1*)
KX2
EN
B1
B2
W
RC Filter
U
V
Control Panel
D KX1 D
CAM BRIDGE
35A / 1000V
35A / 1000V
AC
AC
NO2
DC
DC
KX2 (1*)
KX1
110-P:7-CR:1D
KX2
+
+
-
KF (2*)
NO2 NO2
KX2 KF KF (2*)
E E
B1
B2
2001
2000
Speed".
810
840
PGx-P:2-CR:1D
HRF-P:2-CR:1D
UPS_N-P:1x-CR:10B
A UPS_P-P:1x-CR:10B A
100-P:1x-CR:10B
PI-P:5x-CR:10D
NOTE : If “Brake Tracing-2” assignment is not made
140-P:2-CR:1C
to programmable inputs, brake tracing contacts must
RX1-P:2-CR:10B
be connected in series to “HRF” input.
4A
EMERGENCY
RESCUE SWITCH
A B F36
B B
SG_P-P:4x-CR:1A (2*)
NO3
NO2
WORKING PUSH
WORKING PUSH
1. MECHANICAL BRIDGE
BUTTON 1
KF
KF
BUTTON 2
( Normal Working )
35A / 1000V
DC
AC
DC
+
-
C C
RC Filter RC Filter
KX1
+
-
NO1
KX2
KS1 (1*) KS2 (1*)
NO1
D D
KS1 KS2
2000B
2000A
points with subdividing, a safer test run can be made.
FCA1
FCB1
FCA2
FCB2
840B
840A
FEEDBACK FEEDBACK
COIL COIL
NC CONTACT NC CONTACT
PGx-P:2-CR:1D
HRF-P:2-CR:1D
UPS_N-P:1x-CR:10B
A UPS_P-P:1x-CR:10B A
100-P:1x-CR:10B
220V AC
PI-P:5x-CR:10D
NOTE : If “Brake Tracing-2” assignment is not made
140-P:2-CR:1C
to programmable inputs, brake tracing contacts must
RX1-P:2-CR:10B
be connected in series to “HRF” input.
28V AC
4A
EMERGENCY
RESCUE SWITCH
A B F114
B B
SG_P-P:4x-CR:1A (2*)
NO3
NO2
WORKING PUSH
WORKING PUSH
1. MECHANICAL BRIDGE
BUTTON 1
KF
KF
BUTTON 2
( Normal Working )
35A / 1000V
DC
AC
DC
+
-
C C
RC Filter RC Filter
KX1
+
-
NO1
KX2
KS1 (1*) KS2 (1*)
NO1
D D
KS1 KS2
2000B
2000A
points with subdividing, a safer test run can be made.
FCA1
FCB1
FCA2
FCB2
840B
840A
FEEDBACK FEEDBACK
COIL COIL
NC CONTACT NC CONTACT
PGx-P:2-CR:1D
HRF-P:2-CR:1D
UPS_N-P:1x-CR:10B
A UPS_P-P:1x-CR:10B A
100-P:1x-CR:10B
220V AC
PI-P:5x-CR:10D
NOTE : If “Brake Tracing-2” assignment is not made
140-P:2-CR:1C
to programmable inputs, brake tracing contacts must
RX1-P:2-CR:10B
be connected in series to “HRF” input.
55V AC
4A
EMERGENCY
RESCUE SWITCH
A B F119
B B
SG_P-P:4x-CR:1A (2*)
NO3
NO2
WORKING PUSH
WORKING PUSH
1. MECHANICAL BRIDGE
BUTTON 1
KF
KF
BUTTON 2
( Normal Working )
35A / 1000V
DC
AC
DC
+
-
C C
RC Filter RC Filter
KX1
+
-
NO1
KX2
KS1 (1*) KS2 (1*)
NO1
D D
KS1 KS2
2000B
2000A
points with subdividing, a safer test run can be made.
FCA1
FCB1
FCA2
FCB2
840B
840A
FEEDBACK FEEDBACK
COIL COIL
NC CONTACT NC CONTACT
PGx-P:2-CR:1D
HRF-P:2-CR:1D
UPS_N-P:1x-CR:10B
A UPS_P-P:1x-CR:10B A
100-P:1x-CR:10B
220V AC
PI-P:5x-CR:10D
NOTE : If “Brake Tracing-2” assignment is not made
140-P:2-CR:1C
to programmable inputs, brake tracing contacts must
RX1-P:2-CR:10B
be connected in series to “HRF” input.
70V AC
4A
EMERGENCY
RESCUE SWITCH
A B F123
B B
SG_P-P:4x-CR:1A (2*)
NO3
NO2
WORKING PUSH
WORKING PUSH
1. MECHANICAL BRIDGE
BUTTON 1
KF
KF
BUTTON 2
( Normal Working )
35A / 1000V
DC
AC
DC
+
-
C C
RC Filter RC Filter
KX1
+
-
NO1
KX2
KS1 (1*) KS2 (1*)
NO1
D D
KS1 KS2
2000B
2000A
points with subdividing, a safer test run can be made.
FCA1
FCB1
FCA2
FCB2
840B
840A
FEEDBACK FEEDBACK
COIL COIL
NC CONTACT NC CONTACT
xxxx-P:xx-CR:xxx
140-P:2-CR:1C
GASB
135-P:2-CR:1C
B B
130-P:2-CR:1C
RUN 120-P:2-CR:1C
10A-P:2-CR:1C
PE-P:1x-CR:10A
GACB
BPS1
PGA1
PGA3
BPS2
PGA2
PGA5
135
10
PGA4
140
137
130
120
PE
110
10A
MLKLM50S-B
GA
119A
117A
119A
111A
113B
119B
117B
119B
111B
111C
120
135
137
140
135
130
120
110
116
116
118
118
C C
PE
GA3-P:3-CR:1B
GA2-P:3-CR:1B
GA1-P:3-CR:1B YHB PE-P:10-CR:xB
GA4-P:3-CR:1B 120-P:10-CR:xB
130-P:10-CR:xB
135-P:10-CR:xB
NC1
TO MLKABIN-R50
AHB
(PAGE 8)
MYSB KUYUKK
D MACHINE ROOM D
BPS2-P:11x-CR:1A
BPS1-P:11x-CR:1A
10B-P:2-CR:1C
110-P:5x-CR:10D Flexible Cable 32
111C-P:9-CR:1B
113B-P:9-CR:1B
119B-P:9-CR:1B NC1 NC1 NC1
119A-P:9-CR:1B
116-P:9-CR:1B
DBK YBK HRK
E MACHINE ROOM E
GASB : RECALL EMERGENCY STOP BUTTON
GACB : RECALL RUN BUTTON
GA : RECALL CONTACT NC1
YHB : UP MOVEMENT BUTTON
AHB : DOWNT MOVEMENT BUTTON USKK PIT
USKK : ULTIMATE LIMIT SWITCH CONTACT
DBK : LOW PRESSURE CONTACT (FOR HYDRAULIC SYSTEMS
YBK : HIGH PRESSURE CONTACT (FOR HYDRAULIC SYSTEMS) Title : Safety Circuit Connections -1-
HRK : OVERSPEED GOVERNOR CONTACT
F MYSB : TRACTION GEAR STOP BUTTON F
KUYUKK : WELLACCESS CONTACT Project: ML50S Revision: 1
RKMS
BKK NC1
PGA1 RUN
PGA2
ML1
TL1
EIN1
EO1
EIN3
EIN5
ALB
K5B
K15B
1000
MLO
ML2
100
817
818
TL2
+12
1000
100
EIN2
EIN4
804
100
ER1O
ER2O
HOP+
AKU+
HOP-
AKU-
ERCOM
K3B
AA
PCELL
NC1 PGA3
AKK
PGA4
RKCB
PGA5
PE
BKK2 GA4 FAN
BKK1 GA3 NOTR
B B
STOP AKK2 GA2 2
AKK1 GA1 MLKABIN-R50 NOTR
1 RA
NC1 STOP PGA5 NOTR
KGHK
STOP / KGHK PGA4
GA3
KGHK / KCKK PGA3 K220
MLSERI_SES + GA2
KCKK PGA2 K-NOTR
NC1 MODULE GA1
KCKK KLKK PGA1 EH1 RVY
GA4
KLKK / PK CAN2X EH2
PK KABINX EH3
K-NOTR
CAN2
EH4
NOTR
NC1
K220
119A
119B
ML1
ML2
1000
1000
KLKK
ALB
C2H
EH1
EH2
EH3
EH4
C2L
TL3
TL4
TL5
+12
120
135
137
140
869
100
817
818
118
PE
PE
C RVA C
1
PK NC1
Flexible Cable 32
KABINX-P:13-CR:2D
12 WIRE
D D
A A
111C-P:7-CR:1E
113B-P:7-CR:1E
119B-P:7-CR:1E
119A-P:7-CR:1E
116-P:7-CR:1E
B B
PKR1
KDMS
RUN
KY1
3
12
KY2
3S
NS
100
870
AL
PE
PKR3 119B
PKR4 113B
501K 501K
500K 500K
PKR1 116
PKR2 119A
PKR5 111C
C PKR2 C
MLKDK
870
100
AL
12
3 NS PE KDCB
PKR3 KDRA
112A
112A
113A
112B
111C
KY1
KY2
PKR4
100
114
114
115
115
116
3S
PKR5
3
D KDY D
870
501
500
100
KDA
NC1 NC1 NC1 NC1 NC1
E E
HRKGK : TENSION WEIGHT CONTACT
HPVK : HOSE BLOW VALVE CONTACT (FOR HYDRAULIC SYSTEMS)
KTK : BUFFER CONTACT
KATK : COUNTER WEIGHT BUFFER CONTACT
ASKK : PIT END LIMIT SWITCH CONTACT
KDMS : PIT EMERGENCY STOP BUTTON
KDRA : PIT INSPECTION CONTACT
KDCB : PIT INSPECTION RUN BUTTON
KDY : PIT INSPECTION UP BUTTON Title : Safety
KDA : PIT INSPECTION DOWN BUTTON
Circuit Connections - 3 -
F F
Project: ML50S Revision: 1
135-P:7-CR:10C 135-P:7-CR:10C
130-P:7-CR:10C 130-P:7-CR:10C
120-P:7-CR:10C 120-P:7-CR:10C
PE-P:7-CR:10C PE-P:7-CR:10C
B B
NC1
NC1
FK3
FLOOR 2
FK3
NC1
KK3
GND
DOOR
GND
C DOOR C
NC1
FK2
FLOOR 1
NC1
FK2
NC1
KK2
D GND D
GND
DOOR DOOR
NC1
FLOOR 0
FK1
NC1
FK1
NC1
E E
KK1
GND
GND
DOOR DOOR
A
MULTI STEPS CAM SWITCHES A
140-P:2-CR:1C
135-P:2-CR:1C
130-P:2-CR:1C 0 1
120-P:2-CR:1C
BPS1-P:7x-CR:1D
BPS2-P:7x-CR:1D
2
100-P:1x-CR:10B
PGx-P:2-CR:1C 3
C C
SAFETY CIRCUIT BRIDGING BOX CAUTION !
(BYPASS UNIT) These switches must be suitable to
EN 60947-5-1 standard.
S0_NC2
100 SCBO
E E
Title : Safety
Circuit Bridging Box Scheme
For Only Car Door Automatic
F F
Project: ML50S Revision: 1
A
MULTI STEPS CAM SWITCHES A
140-P:2-CR:1C
130-P:2-CR:1C 0 1
120-P:2-CR:1C
BPS1-P:7x-CR:1D
BPS2-P:7x-CR:1D
2
100-P:1x-CR:10B
PGx-P:2-CR:1C 3
S0_NC1
S0_NC1 S0_NC2
S1_NO S2_NO S1_NO
BPS2
S2_NO
S3_NO
SAFETY CIRCUIT BRIDGING BOX
C (BYPASS UNIT) C
CAUTION !
S0_NC2 These switches must be suitable to
EN 60947-5-1 standard.
100 SCBO
D D
E E
Title : Safety
Circuit Bridging Box Scheme
For Full Automatic
F F
Project: ML50S Revision: 1
100-P:1x-CR:10B
1000-P:1x-CR:10B
A A
FSLA
ASM
YSM
KKEK
TYK
AYK
12V / 2W
SPEAKER
B (Alarm & Gong) B
EMERGENCY LAMP
MINIMUM 5 LUX
KSR2
Dry Battery
KSR1
100
NTC
DOOR BRIDGING
C ALARM UNIT C
ML2
MOTOR NTC
ML1
1 ~
ML1
TL1
EIN1
EO1
EIN3
EIN5
ALB
K5B
K15B
1000
MLO
ML2
100
817
818
TL2
+12
1000
100
EIN2
EIN4
804
100
ER1O
ER2O
HOP+
AKU+
HOP-
AKU-
ERCOM
K3B
AA
CAN2
EH4
NOTR
K220
119A
119B
ML1
ML2
1000
1000
ALB
C2H
EH1
EH2
EH3
EH4
C2L
TL3
TL4
TL5
+12
120
135
137
140
869
100
817
818
118
PE
PE
1
E E
(PAGE 9) CAM
Coil of the Door
Lock Magnet
ASM : DOWN RE-LEVELLING MONO-STABILE SWITCH KSR1 : DOWN LIMIT BI-STABLE SWITCH
YSM : UP RE-LEVELLING MONO-STABILE SWITCH KSR2 : UP LIMIT BI-STABLE SWITCH
TYK : FULL LOAD CONTACT ML1 : DOOR OPEN ZONE MONO STABLE SWITCH Title : Top Of The Car Wiring Connection
AYK : OVERLOAD CONTACT ML2 : DOOR OPEN ZONE MONO STABLE SWITCH
FSLA : PHOTOCELL CONTACT
F F
KKEK : CAR DOOR EXTRA CONTACT Project: ML50S Revision: 1
ALB : ALARM BUTTON
FSLA : PHOTOCELL CONTACT FOR DOOR A Date: 28.5.2019 Sheet: 12 www.mikrolift.com
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
CONTROL PANEL
K-NOTR
NOTR
K220
119A
119B
ML1
ML2
1000
1000
ALB
C2H
EH1
EH2
EH3
EH4
C2L
TL3
TL4
TL5
A A
+12
869
100
817
818
120
135
137
140
118
PE
PE
1
MACHINE ROOM
B B
C C
Flexible Cable 32
D D
TOP OF THE CAR
ML1
EH1
TL3
EH3
869
ML2
TL5
817
818
+12
EH2
135
137
ALB
PE
1000
TL4
C2H
C2L
1000
100
PE
K220
EH4
118
120
140
NOTR
K-NOTR
119B
119A
E E
+12V
119A
A A
119B
113B
111C
ALB
100
501
500
870
116
NS
PE
3S
3
CONTROL PANEL
MACHINE ROOM
B B
KY1
3
12
KY2
3S
NS
100
870
AL
PE
PKR3 119B
PKR4 113B
501K 501K
500K 500K
PKR1 116
PKR2 119A
PKR5 111C
PKR2
WELL
KDMS
MLKDK
PKR3
870
100
AL
12
3 NS PE
KDCB RUN PKR4
112A
112A
113A
112B
111C
KY1
KY2
100
114
114
115
115
116
PKR5
3S
3
SOCKET
KDRA 870
D D
501
KDY
A A
B B
MLKAT-D4M
EIO
UP
CAN1X CAN1X DOWN
CAN2
1
15
13
11
3
AC
16
14
12
10
9
7
6
2
KAPA
FAN
VAT
2.KABIN-K
MLKABIN-K
CAN2X CAN2X
KAPI-A
KAPI-B
C C
4 WIRE
SPEAKER
ON
ACL
ID
ALC- / 1000
ALB
INTERKOM
KABINX
ACL+
EIN1
EIN2
ALB
EO1
EO2
EO3
EO4
EO5
EO6
EO7
EO8
TL1
TL2
TL3
+12
100
-12
KABINX-P:8-CR:2D
12 WIRE
D D
3 WIRE
EMERGENCY
TELEPHONE LAMP
UNIT
ALARM BUTTON
E E
CONTROL PANEL
A A
CAN1
MLKLM50S-A
YAN
B CAN-BUS MAIN LINE CABLE B
( 2 x 2 x 0,75 )
100-P:1x-CR:10B
MLKAT-DS
C C
( 2 x 2 x 0,22 )
BUTTONS CABLE
TOP FLOOR
CAN-BUS FLOOR
YK
D D
MLKAT-DS
( 2 x 2 x 0,75 )
E E
( 2 x 2 x 0,22 )
BUTTONS CABLE
CAN-BUS FLOOR
F YK F
G G
MLKAT-DS
( 2 x 2 x 0,75 )
H H
KATX
( 2 x 2 x 0,22 )
BUTTONS CABLE
CAN-BUS FLOOR
FLOOR 0
YK
END OF LINE
RESISTOR
I I
LANDING OPERATION PANEL
CONTROL PANEL
A A
CAN1 CAN1
MLKLM50S-A MLKLM50S-A
YAN
YAN
CAN-BUS MAIN LINE CABLE
( 2 x 2 x 0,75 )
B B
100-P:1x-CR:10B
( 2 x 2 x 0,75 )
C C
KATX
( 2 x 2 x 0,22 )
BUTTONS CABLE
TOP FLOOR
( 2 x 2 x 0,22 )
CAN-BUS FLOOR
BUTTONS CABLE
CAN-BUS FLOOR
YK YK
MLDUBLEX
D D
( 2 x 2 x 0,75 )
E E
KATX
MIDDLE FLOOR
( 2 x 2 x 0,22 )
BUTTONS CABLE
CAN-BUS FLOOR
( 2 x 2 x 0,22 )
BUTTONS CABLE
CAN-BUS FLOOR
F YK YK F
MLDUBLEX
G G
MLKAT-DS MLKAT-DS
( 2 x 2 x 0,75 )
( 2 x 2 x 0,75 )
H H
KATX
KATX
( 2 x 2 x 0,22 )
BUTTONS CABLE
( 2 x 2 x 0,22 )
CAN-BUS FLOOR
BUTTONS CABLE
CAN-BUS FLOOR
FLOOR 0
YK YK
MLDUBLEX
UPS_P-P:1x-CR:10B UPS_P-P:1x-CR:10B
UPS_N-P:1x-CR:10B UPS_N-P:1x-CR:10B
A 100-P:1x-CR:10B 100-P:1x-CR:10B A
1000-P:1x-CR:10B 1000-P:1x-CR:10B
PE-P:1x-CR:10A
ED_220AC_N-P:1x-CR:10B
ED_220AC_P-P:1x-CR:10B NC1 NC1 NC1
KRC-P:2-CR:1D
KU2 KTR KST
FKR20 RCOM-P:2-CR:10A
R-P:1x-CR:10A RC1-P:2-CR:10A
S-P:1x-CR:10A
T-P:1x-CR:10A 10A-P:2-CR:1C
110-P7-CR:1D
30mA 24VDC Relay
LR-N-P:1hx-CR:10B
B GROUND FAULT B
LR-P-P:1hx-CR:10B
PROTECTED RLIR
AUTOMAT FUSE 11-P:2-CR:1B
10B-P:2-CR:1B
RC Filter
NC2
Control Panel
KTR (1*) KST
Emergency
Stop Button
RC Filter NO2
C CRL-P:1a-CR:10D C
KU2
NO1
KTR KST RKP-P:1a-CR:10D
KU2 NC2
RUPS-P:1a-CR:10D
KST (1*) KTR 140-P:2-CR:1B
NO1
RLIR RC Filter
NO1
35A / 1000V
RC Filter
AC
DC
NO1
KU2
KA3 (1*) RA3a
+
-
RC Filter
NO1
E E
RDHa
KDH(1*) (2*)
1* Contactors must be of AC-3 class with 220VAC coils!
W1
W2
2001
U1
V1
U2
V2
UPS_P-P:1x-CR:10B UPS_P-P:1x-CR:10B
UPS_N-P:1x-CR:10B UPS_N-P:1x-CR:10B
A 100-P:1x-CR:10B 100-P:1x-CR:10B A
1000-P:1x-CR:10B 1000-P:1x-CR:10B
PE-P:1x-CR:10A
ED_220AC_N-P:1x-CR:10B
ED_220AC_P-P:1x-CR:10B NC1 NC1
KRC-P:2-CR:1D
KU2A KU2B
FKR25 RCOM-P:2-CR:10A
R-P:1x-CR:10A RC1-P:2-CR:10A
S-P:1x-CR:10A
T-P:1x-CR:10A 10A-P:2-CR:1C
110-P7-CR:1D
30mA 24VDC Relay
LR-N-P:1hx-CR:10B
B GROUND FAULT B
LR-P-P:1hx-CR:10B
PROTECTED RLIR
AUTOMAT FUSE 11-P:2-CR:1B
10B-P:2-CR:1B
140-P:2-CR:1B
RC Filter
Control Panel
Emergency NO1
Stop Button
KU2A (1*) RU2a
C C
NO1
KU2A
KU2B (1*)
NO1
RLIR
RC Filter
KU2A
NO1
35A / 1000V
RC Filter
AC
DC
KU2B NO1
+
-
RDHa
KDH(1*) (2*)
E E
810
U
V
Hydraulic Unit
xxxx-P:xx-CR:xxx
Title : ContactorsConnection For Hydraulic Lift
Bağlantı İsmi Sutun Satır Koordinatı
Connection Name Column Row Coordinate ( Direct Start )
F Sayfa Numarası F
Page Number Project: ML50S Revision: 1
A A
RX1-P:2-CR:10B
FKR5 RX2-P:2-CR:10B
3A
140-P:2-CR:1B RD1-P:2-CR:10B
F43 RD2-P:2-CR:10B
220V AC
55V AC
+
B AC RB1-P:2-CR:10C B
30mA
RB2-P:2-CR:10C
-
10B-P:2-CR:1B GROUND FAULT DC
PROTECTED 35A / 1000V
PE-P:1x-CR:10A AUTOMAT FUSE 1000-P:1x-CR:10B
1N4007
RU2-P:2-CR:1B
RU2a 24VDC Relay
C 1N4007 C
NO NO
KA3 KDH
S3-P:2-CR:1B
RA3a 24VDC Relay
1N4007
S4-P:2-CR:1B
RDHa 24VDC Relay
D D
Valve Test
Button
VB
VC
L10
V10
VD
VA
E xxxx-P:xx-CR:xxx E
A3 Valve Valve Up Low Up High Down High Down Low Bağlantı İsmi Sutun Satır Koordinatı
Comman Speed Valve Speed Valve Speed Valve Speed Valve Connection Name Column Row Coordinate
Sayfa Numarası
Page Number
A A
RX1-P:2-CR:10B
FKR6 RX2-P:2-CR:10B
3A
140-P:2-CR:1B RD1-P:2-CR:10B
F45 RD2-P:2-CR:10B
220V AC
55V AC +
B AC RB1-P:2-CR:10C B
30mA
RB2-P:2-CR:10C
-
10B-P:2-CR:1B GROUND FAULT DC
PROTECTED 35A / 1000V
AUTOMAT FUSE 1000-P:1x-CR:10B
PE-P:1x-CR:10A 1N4007
RU2-P:2-CR:1B
RU2a 24VDC Relay
C 1N4007 C
NO
KA3
S3-P:2-CR:1B
RA3a 24VDC Relay
D D
Valve Test
Button
L10
V10
Vhs
Vdw
Vup
E xxxx-P:xx-CR:xxx E
A3 Valve Valve Up Direction High Speed Down Direction Bağlantı İsmi Sutun Satır Koordinatı
Common Valve Valve Valve Connection Name Column Row Coordinate
Sayfa Numarası
Page Number
A A
RX1-P:2-CR:10B
FKR21 RX2-P:2-CR:10B
3A
140-P:2-CR:1B RD1-P:2-CR:10B
F126 RD2-P:2-CR:10B
220V AC
28V AC
+
B AC RB1-P:2-CR:10C B
30mA
RB2-P:2-CR:10C
-
10B-P:2-CR:1B GROUND FAULT DC
PROTECTED 35A / 1000V
PE-P:1x-CR:10A AUTOMAT FUSE 1000-P:1x-CR:10B
1N4007
RU2-P:2-CR:1B
RU2a 24VDC Relay
C 1N4007 C
NO NO
KA3 KDH
S3-P:2-CR:1B
RA3a 24VDC Relay
1N4007
S4-P:2-CR:1B
RDHa 24VDC Relay
D D
Valve Test
Button
VB
VC
L10
V10
VD
VA
E xxxx-P:xx-CR:xxx E
A3 Valve Valve Up Low Up High Down High Down Low Bağlantı İsmi Sutun Satır Koordinatı
Comman Speed Valve Speed Valve Speed Valve Speed Valve Connection Name Column Row Coordinate
Sayfa Numarası
Page Number
Title : Valves
Connections For Blain EV100 Hydraulic Unit
( Valve Voltage 24V DC )
F F
Project: ML50S Revision: 1
A A
RX1-P:2-CR:10B
FKR22 RX2-P:2-CR:10B
3A
140-P:2-CR:1B RD1-P:2-CR:10B
F128 RD2-P:2-CR:10B
220V AC
55V AC +
B AC RB1-P:2-CR:10C B
30mA
RB2-P:2-CR:10C
-
10B-P:2-CR:1B GROUND FAULT DC
PROTECTED 35A / 1000V
AUTOMAT FUSE 1000-P:1x-CR:10B
PE-P:1x-CR:10A 1N4007
RU2-P:2-CR:1B
RU2a 24VDC Relay
C 1N4007 C
NO
KA3
S3-P:2-CR:1B
RA3a 24VDC Relay
D D
Valve Test
Button
L10
VMP
V10
VML
VMD
E xxxx-P:xx-CR:xxx E
A3 Valve Bağlantı İsmi Sutun Satır Koordinatı
Valve Up Direction High Speed Down Direction
Common Valve Valve Valve Connection Name Column Row Coordinate
Sayfa Numarası
Page Number
A A
RX1-P:2-CR:10B
FKR23 RX2-P:2-CR:10B
3A
140-P:2-CR:1B RD1-P:2-CR:10B
F130 RD2-P:2-CR:10B
220V AC
55V AC +
B AC RB1-P:2-CR:10C B
30mA
RB2-P:2-CR:10C
-
10B-P:2-CR:1B GROUND FAULT DC
PROTECTED 35A / 1000V
AUTOMAT FUSE 1000-P:1x-CR:10B
PE-P:1x-CR:10A 1N4007
RU2-P:2-CR:1B
RU2a 24VDC Relay
C 1N4007 C
NO
KA3
S3-P:2-CR:1B
RA3a 24VDC Relay
D D
Valve Test
Button
L10
V10
Vhs
Vdw
Vup
E xxxx-P:xx-CR:xxx E
A3 Valve Valve Up Direction High Speed Down Direction Bağlantı İsmi Sutun Satır Koordinatı
Common Valve Valve Valve Connection Name Column Row Coordinate
Sayfa Numarası
Page Number
A A
RX1-P:2-CR:10B
FKR24 RX2-P:2-CR:10B
3A
140-P:2-CR:1B
F136
220V AC
55V AC +
B AC RB1-P:2-CR:10C B
30mA
RB2-P:2-CR:10C
-
10B-P:2-CR:1B GROUND FAULT DC
PROTECTED 35A / 1000V
AUTOMAT FUSE 1000-P:1x-CR:10B
PE-P:1x-CR:10A 1N4007
RU2-P:2-CR:1B
RU2a 24VDC Relay
C 1N4007 C
NO NO
KA3 RL-ML1
S3-P:2-CR:1B
RA3a 24VDC Relay
NO
RL-ML2
NO
ML1-P:3-CR:1B
KTR (1*)
RL-ML1 24VDC Relay
D D
1N4007
ML2-P:3-CR:1B
RL-ML2 24VDC Relay
20
22
34
16
COM
E xxxx-P:xx-CR:xxx E
A3 Valve Bağlantı İsmi Sutun Satır Koordinatı
Valve High Speed Down Direction
Common Valve Valve Connection Name Column Row Coordinate
Sayfa Numarası
Page Number
A A
RX1-P:2-CR:10B
FKR29 RX2-P:2-CR:10B
3A
140-P:2-CR:1B RD1-P:2-CR:10B
F160 RD2-P:2-CR:10B
220V AC
55V AC +
B AC RB1-P:2-CR:10C B
30mA
RB2-P:2-CR:10C
-
10B-P:2-CR:1B GROUND FAULT DC
PROTECTED 35A / 1000V
AUTOMAT FUSE 1000-P:1x-CR:10B
PE-P:1x-CR:10A 1N4007
RU2-P:2-CR:1B
RU2a 24VDC Relay
C 1N4007 C
NO
KA3
S3-P:2-CR:1B
RA3a 24VDC Relay
D D
Valve Test
Button
EB
E /D
EA
HM-SV
V10
E xxxx-P:xx-CR:xxx E
A A
15cm 4.5cm
15cm 4.5cm
B B
TOP FLOOR
C 15cm 4.5cm C
15cm 4.5cm
D D
FLOOR 2
MLB 4.5cm
E E
4.5cm
F F
FLOOR 1
G G
10cm : RIBBON MAGNET FOR ADVANCED DOOR
OPENNING ZONE
P.S.: IT'S NOT NEEDED TO USE ASM AND YSM WHERE THE ROPE
ML1 YSM
KSR2
KSR1
CAUTION !
I I
ML1,ML2,ASM and YSM Mono-Stable switches must be suitable to
5.11.2.5 article at EN81-20 standard.
A A
15cm
15cm
B B
TOP FLOOR
C 15cm C
15cm
D D
FLOOR 2
MLB
E E
F F
FLOOR 1
G G
ML1
KSR2
KSR1
ML2
FLOOR 0
CAUTION !
I I
ML1 and ML2 Mono-Stable switches must be suitable to
5.11.2.5 article at EN81-20 standard.
A A
15cm 4.5cm
15cm 4.5cm
B B
TOP FLOOR
C 15cm 4.5cm C
15cm 4.5cm
D D
FLOOR 2
MLB 4.5cm
E E
DM
4.5cm
YHM2
F F
FLOOR 1
ML2 ASM
KSR1
JF
M0
FLOOR 0
I
CAUTION ! I
ML1,ML2,ASM and YSM Mono-Stable switches must be
suitable to 5.11.2.5 article at EN81-20 standard.
CAR Title : 2
Magnets M0 Pulse System For Electrical Lifts
With Advenced Door Openning And Re-Levelling
J Project: ML50S Revision: 1 J
A A
15cm
15cm
B B
TOP FLOOR
C 15cm C
15cm
D D
FLOOR 2
E
MLB E
DM
YHM2
F F
FLOOR 1
G G
YHM1
ML1
ML2
JFY
JFA
KSR1
M0
FLOOR 0
I
CAUTION ! I
ML1 and ML2 Mono-Stable switches must be suitable to
5.11.2.5 article at EN81-20 standard.
CAR Title : 2
Magnets M0 Pulse System For Hydraulic Lifts
With Advenced Door Openning And Re-Levelling
J Project: ML50S Revision: 1 J
A A
15cm
15cm
B B
TOP FLOOR
C 15cm C
15cm
D D
FLOOR 2
E MLB E
DMY
YHM2
15cm
H H
ML1
ML2
KSR1
KSR2
JFY
JFA
M0
FLOOR 0
I I
CAUTION !
ML1 and ML2 Mono-Stable switches must be suitable to 5.11.2.5
article at EN81-20 standard.
A A
1000-P:1x-CR:10B
ML1-P:3-CR:1B
ML2-P:3-CR:1B
B B
MLKTA
+12V
ML1
ML2
1000
L+
L-
C C
12V 1W (MAX)
AT FLOOR LEVEL LIGHT
+12V
D D
E E
xxxx-P:xx-CR:xxx
100-P:1x-CR:10B
+15V RA +15V
B B
GND GE GND OV
ML50S LS Inverter ML50S ADrive Inverter
A RB A OA
-A GE -A OB
B B JP
-B -B
C C
100-P:1x-CR:10B 100-P:1x-CR:10B
D D
+15V +15V
GND GND
ML50S MEIDEN Inverter ML50S FUJI Inverter
A PAO A PAO
-A PBO -A PBO
E E
B COM B CM
-B -B
xxxx-P:xx-CR:xxx
Title : Encoder Connections With Inverters
Bağlantı İsmi Sutun Satır Koordinatı
Connection Name Column Row Coordinate
F Sayfa Numarası F
Page Number Project: ML50S Revision: 1
NO1
(2*) NO1 (2*)
PGx-P:2-CR:1D PGx-P:2-CR:1D
CONTROL PANEL
100-P:1x-CR:10B 100-P:1x-CR:10B
10B-P:2-CR:1C 10B-P:2-CR:1C
135-P:7-CR:10C 135-P:7-CR:10C
130-P:7-CR:10C 130-P:7-CR:10C
K130A
K130A
120-P:7-CR:10C 120-P:7-CR:10C
PE-P:7-CR:10C R130A (1*) PE-P:7-CR:10C
R130A (1*)
B B
RC Filter
RC Filter
NC1 NC1
NC1 NC1
FK3_A FK3_B
FLOOR 2
FK3_B FK3_A
NC1 NC1
KK3_A KK3_B
C GND GND C
DOOR-B DOOR-A
GND GND
DOOR-A DOOR-B
NC1 NC1
FK2_A FK2_B
FLOOR 1
NC1 NC1
FK2_B FK2_A
NC1 NC1
D KK2_A KK2_B D
GND GND
GND GND
DOOR-B DOOR-A DOOR-A DOOR-B
NC1 NC1
FLOOR 0
FK1_A FK1_B
NC1 NC1
E FK1_B FK1_A E
NC1 NC1
KK1_A KK1_B
GND GND
GND GND
DOOR-B DOOR-A DOOR-A DOOR-B
FKx_A : A SIDE DOOR SOCKET SWICHES Title : Double Landing Doors Contacts Connections
FKx_B : B SIDE DOOR SOCKET SWICHES 1* These relays comply with EN 50205 and they must have 220VAC coils!
RC filters must connected across the coils of relays!
KKx_A : A SIDE DOOR LOCK SWITCHES
F F
KKx_B : B SIDE DOOR LOCK SWITCHES 2* These inputs are programmable input of ML50S . Project: ML50S Revision: 1
A A
NO1
(2*)
PGx-P:2-CR:1D
100-P:1x-CR:10B
10B-P:2-CR:1C
CONTROL PANEL
R135A (1*)
BPS1
PGA1
PGA3
BPS2
PGA2
PGA5
135
10
PGA4
140
137
130
120
PE
110
10A
MLKLM50S-B
B RC Filter B
119A
117A
119A
111A
113B
119B
117B
119B
111B
111C
120
135
137
140
135
130
120
110
116
116
118
118
PE
C C
KKEK_A
KKEK_B
ML1
TL1
EIN1
EO1
EIN3
EIN5
ALB
K5B
K15B
1000
MLO
ML2
100
817
818
TL2
+12
1000
100
EIN2
EIN4
804
100
ER1O
ER2O
HOP+
AKU+
HOP-
AKU-
ERCOM
K3B
AA
PCELL
TOP OF THE CAR
PE
BKK2 GA4 FAN
BKK1 GA3 NOTR
D AKK2 GA2 2 D
AKK1 GA1 MLKABIN-R50 NOTR
1
STOP PGA5 NOTR
STOP / KGHK PGA4
KGHK / KCKK PGA3 K220
MLSERI_SES +
KCKK PGA2 K-NOTR
MODULE
KLKK PGA1 EH1
KLKK / PK CAN2X EH2
PK KABINX EH3
K-NOTR
CAN2
EH4
NOTR
K220
119A
119B
ML1
ML2
1000
1000
ALB
C2H
EH1
EH2
EH3
EH4
C2L
TL3
TL4
TL5
+12
120
135
137
140
869
100
817
818
118
PE
PE
1
E E
KKEK_A : CAR DOOR A EXTRA CONTACT 1* These relays comply with EN 50205 and they must have 220VAC coils!
KKEK_B : CAR DOOR B EXTRA CONTACT RC filters must connected across the coils of relays! Title : Double Car Doors Contacts Connections
2* These inputs are programmable input of ML50S .
F F
Project: ML50S Revision: 1