The Refrigerant R1234yf in Air Condition

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

Energy 36 (2011) 6110e6120

Contents lists available at ScienceDirect

Energy
journal homepage: www.elsevier.com/locate/energy

The refrigerant R1234yf in air conditioning systems


Claudio Zilio a, *, J. Steven Brown b, Giovanni Schiochet a, Alberto Cavallini a
a
Dipartimento di Fisica Tecnica, Università di Padova, Via Venezia, 1, I-35131 Padova, Italy
b
Department of Mechanical Engineering, Catholic University of America, Washington, DC 20064, USA

a r t i c l e i n f o a b s t r a c t

Article history: Experiments were conducted for a typical R134a compact European automotive air conditioning system
Received 1 March 2011 equipped with an internally controlled variable displacement compressor, minichannel condenser, TXV,
Received in revised form and minichannel evaporator. A “drop-in” R1234yf system was tested together with two modified R1234yf
2 August 2011
systems with the primary goal to document some laboratory results and their analyses which could
Accepted 4 August 2011
Available online 27 August 2011
prove useful in aiding manufacturers and researchers by indicating “minor” system modifications which
could be implemented in existing air conditioning systems, with the aim to achieve with R1234yf similar
capacity and efficiency as modern R134a systems. Since the experimental results indicate that, for a given
Keywords:
Air conditioning
cooling capacity, R1234yf systems present lower performance than the baseline R134a, numerical
Automobile simulations were used to investigate the effects of “major” system modifications, such as, the use of an
R1234yf enhanced condenser and/or an enhanced evaporator.
R134a Ó 2011 Elsevier Ltd. All rights reserved.

1. Introduction temperature data published in the public domain, several have low
GWP and normal boiling temperatures relatively close to R134a
Over the last several years, much research and development (from about 3.7  C lower to about 8  C higher); however, among
effort has been focused on potential refrigerants possessing low them, R1234yf is the one closest to commercialization (its normal
Global Warming Potentials (GWPs). As discussed in [1], the catalyst boiling temperature is approximately 3.7  C lower than that of
for much of this effort can be attributed to European regulations R134a). It has a GWP of 4 [7] and is being widely considered as
regarding the use of R134a (GWP relative to CO2 based on a 100- a possible replacement for R134a in automotive applications or as
year time horizon, which is the reference that will be used a component in non-azeotropic mixtures for heat pump applica-
throughout this paper, is 1430 [2]) in automotive applications. In tions [8].
particular, the European Union’s F-gas regulations [3,4] specify that To-date, researchers and manufacturers have focused their
beginning on January 1, 2011 new models and on January 1, 2017 R1234yf research and development efforts primarily on charac-
new vehicles fitted with air conditioning cannot be manufactured terizing its flammability, toxicity, environmental impact, materials
with fluorinated greenhouse gases having global warming poten- compatibility, oil compatibility, air conditioning system perfor-
tials (GWP) greater than 150. Possible candidate refrigerants that mance, thermophysical property data, and in the developing of
possess GWP < 150, and that are being considered, include R-152a, simple equations of state (EoS). Excluding thermophysical property
R-744 (CO2), and R1234yf. R-152a has been investigated in the data and EoS modeling, much of the remaining published work has
recent years in several applications [5], anyway, if used in air been presented by chemical manufacturers and vehicle manufac-
conditioning applications, would likely be implemented in turers through organizations such as VDA (German Association of
a secondary loop system because of its flammability. R-744, if used, the Automotive Industry), SAE (Society of Automotive Engineers),
would likely be implemented in a transcritical cycle requiring and JAMA (Japan Automobile Manufacturers Association). For
significant modifications to the currently used automotive air example, VDA organizes an annual alternative refrigerant winter
conditioning systems [6] because of its considerably different meeting where chemical manufacturers and vehicle manufacturers
thermophysical properties when compared to R134a. Among the have presented some of their R1234yf work beginning with its
fluorinated propene isomers which have normal boiling point February 2008 meeting. SAE [9] through its Cooperative Research
Program CRP 1234-1, CRP 1234-2 and CRP 1234-3 has focused its
efforts on safety and risk assessment, air conditioning system
* Corresponding author. Tel.: þ39 049 827 6893; fax: þ39 049 827 6896. performance, and materials compatibility, with much of this work
E-mail address: claudio.zilio@unipd.it (C. Zilio). having been presented at an annual automotive alternate

0360-5442/$ e see front matter Ó 2011 Elsevier Ltd. All rights reserved.
doi:10.1016/j.energy.2011.08.002
C. Zilio et al. / Energy 36 (2011) 6110e6120 6111

Nomenclature y Variable that represents either COP, Cooling Capacity,


_
or m
COP Coefficient of Performance
CRP Cooperative Research Program Greek Symbols
 
DISP geometric displacement volume per revolution (cm3) yR1234yf  yR134a
3
DISP* displacement volume per revolution (cm3) yR134a
EoS Equation of State hV volumetric efficiency (%)
GWP Global Warming Potential r density (kg m3)
m_ mass flow rate (kg s1)
N rotational speed (RPM) Subscripts
OCR Oil Circulation Ratio (%) air air
P pressure (kPa, MPa) disch discharge
PAG Polyalkylene Glycol evap evaporator
POE Polyol Ester in inlet
Q cooling capacity (kW) max maximum
R (hv DISP/DISPmax)  100 out outlet
RH Relative Humidity (%) suc suction
TXV Thermal Expansion Valve sup superheat
T temperature ( C)

refrigerant systems symposium beginning with its June 2008 Standard 34-2007 [17] specifies R1234yf with a Safety Classification
meeting. In the previously mentioned work, the researchers, for the of A2, it is a likely candidate to receive a 2L Flammability Subclass
most part, have concluded that R1234yf appears to be a promising defined in Addendum ak to ANSI/ASHRAE Standard 34-2007 [17].
candidate to replace R134a in automotive applications, with SAE Note: the 2L Flammability Subclass includes Class 2 refrigerants
[10] concluding R1234yf “can be used as the global replacement with burning velocities 0.10 m s1.
refrigerant in future mobile air conditioning systems and it can be A third issue is the environmental performance of R1234yf.
safely accommodated through established industry standards and Koban [18] performed Life Cycle Climate Performance (LCCP)
practices for vehicle design, engineering, manufacturing, and simulations and has shown under her assumptions that R1234yf
service.” Notwithstanding the preceding statement, several issues results in reductions of 17e20% when compared to R134a.
are still being investigated through ongoing research and devel- Finally, the compatibility of R1234yf with common materials
opment work. R1234yf, for example, has somewhat lower ther- and oils appears promising [16].
modynamic performance (e.g., Bang [11]) showed that the cooling Recently, several research groups have begun publishing
capacity of R1234yf is 3e7% lower and its COP is 1e3% lower than R1234yf thermophysical property data. For example, Tanaka and
R134a when used as a “drop-in” replacement for R134a. However, Higashi [19] measured its critical properties, saturation pressure
Meyer [12] showed that with relatively simple system modifica- from 310 to 360 K, and surface tension from 273 to 340 K. Tanaka
tions the cooling capacity and COP of R1234yf could be made et al. [20] measured its liquid isobaric heat capacity and its liquid
approximately equal to the baseline R134a values. Along these density from 310 to 360 K at pressures up to 5 MPa. Then, Akasaka
same lines, more recently, Petitjean and Benouali [13] experimen- et al. [21] developed both a Patel-Teja EoS and an Extended Cor-
tally studied the effects of using an improved condenser, an responding State EoS based on their research group’s data. Di Nicola
improved evaporator, an adjusted (“tuned”) Thermal Expansion et al. [22] measured saturation pressures from 224 to 366 K. Fedele
Valve (TXV), a modified compressor, and a liquid-line/suction-line et al. [23] measured saturation pressures for reduced temperatures
heat exchanger (llsl-hx) in an automotive air conditioning system. ranging from 0.67 to 0.93. Brown et al. [24,25] developed a simple
Regarding the conventional heat exchangers, they concluded that Peng-Robinson (P-R) EoS model coupled with group contribution
the condenser plays a much more important role than the evapo- estimation techniques to easily and relatively accurately predict
rator in the optimization of the R1234yf performance. This also can thermophysical property data, which were then used to make
be seen from Cavallini et al. [14] who showed analytically and Del performance predictions in a typical automotive air conditioning
Col et al. [15] who showed experimentally that the condensation system [26]. Leck [27] used his employer’s data to develop
heat transfer coefficients for R1234yf can be up to 30% or so lower a Martin-Hou EoS and then used it to predict the performances for
than R134a at high vapor qualities at the same mass flux and several refrigeration examples. Hulse et al. [28] measured its critical
saturation temperature; however, Del Col et al. [15] showed temperature, saturation pressure, liquid density, ideal gas heat
experimentally that the condensation heat transfer coefficients for capacity, liquid viscosity, and surface tension, and then developed
R1234yf are nearly the same as those of R134a for lower vapor an Extended Corresponding States EoS using their data.
qualities or for single phase liquid heat transfer. Finally, Petitjean
and Benouali [13] also show that to optimize the R1234yf perfor- 2. Motivation for this study
mance, the TXV needs to be properly tuned, that the use of a llsl-hx
has a bigger impact for R1234yf than for R134a, and that the Given the above, particularly the facts that (1) Zilio et al. [26],
compressor capacity needs to be properly adjusted. In conclusion, through a numerical approach, and Petitjean and Benouali [13],
they show that with properly designed and tuned components, the through an experimental approach, demonstrated that it is theo-
R1234yf performance can match or even better that of R134a. retically possible to achieve nearly the same cooling capacity and
A second issue is the flammability of R1234yf, where testing has COP for R1234yf and R134a with some system modifications, (2)
shown that, while flammable, a significantly larger amount of the deadlines established by European regulations are fast
energy is required to ignite the refrigerant than for other common approaching, and (3) the sponsors of SAE CRP 1234 have concluded
Class 2 refrigerants [16]. While Addendum w to ANSI/ASHRAE that R1234yf appears to be a promising global replacement
6112 C. Zilio et al. / Energy 36 (2011) 6110e6120

refrigerant for future automotive systems, one of the principal


questions that should interest automotive and component manu-
facturers, and which this paper will attempt to address, is if and
what “minor” system modifications would allow R1234yf to have
equal cooling capacity to R134a, while maintaining similar COP
values between the two systems, particularly for vehicles smaller
than ones considered in SAE CRP 1234.
It is worth mentioning that the transition from R134a to R1234yf
and the accompanying system modifications most likely will not
occur “instantaneously”, but will occur over several years similar to
the way the transition from R12 to R134a happened. It is also worth
remembering (see, e.g. [29]), that automotive manufacturers had to
make several system changes to accommodate R134a, including:
(1) introducing condensers with approximately 20% higher
condensing capacity in order to maintain similar operating pres-
sures, and thus allowing for the same compressors to be used and
(2) for TXV systems the valve settings had to be adjusted. Moreover,
as is well known, the mineral lubricants used with R12 systems had
to be replaced by synthetic POE or PAG oils (Note: it appears that
R1234yf will not require such a “revolutionary” change in the
lubricant). Other R134a system improvements have been intro-
duced over time, including the now widespread use of minichannel
heat exchangers and variable displacement compressors.
To-date, SAE CRP 1234-1,2,3 are the only publically available
studies from a large consortium of worldwide companies that had Fig. 1. Schematic of experimental apparatus.
the purpose to assess the performance potential of R1234yf in
existing automotive systems which have undergone only “minor”
changes. In particular, the baseline system used in SAE CRP 1234
was the same one considered in SAE CRP 150, namely, a Cadillac CTS humidification equipment, and associated controls, (2) a closed-
with a fixed displacement compressor and a cross-charged TXV. loop air circuit for the condenser, including centrifugal fan,
However for SAE CRP 1234, two “minor” changes were made to the chiller, electric resistance heater and associated controls, (3) the
baseline system in order to obtain the same cooling capacity as refrigerant circuit, including a minichannel evaporator, a mini-
R134a, namely, (1) the TXV spring preload was adjusted to increase channel condenser, a variable volume swash-plate compressor, and
the bulb pressure to a corresponding temperature of 0  C and (2) a TXV, all components from the air conditioning system of a typical
the compressor suction line diameter was increased. The SAE European compact automobile, and (4) the instrumentation
studies do not report results for a purely “drop-in” system. In system.
a different study (SAE ARCRP [9]), the not so minor change of The inlet air temperatures for both the evaporator and the
including a liquid-line/suction-line exchanger was considered for condenser are controlled using two closed-loop air circuits, whose
the R1234yf system. ductwork configurations provide uniform temperature and velocity
While the systems used in the previously mentioned SAE profiles at the inlet faces of the heat exchangers. The volumetric air
studies contained fixed displacement compressors, nowadays, flow rates are measured using ISA 1932 nozzles per ISO 5167-
many vehicles are equipped with variable displacement compres- 4:2003 [30] to accuracies of 0.8% of the measured values. A chiller
sors, where the stroke is modulated by the crankcase pressure. supplies conditioned water to a cross-flow heat exchanger to
With this discussion in mind, in this paper, the performance maintain the condenser inlet air temperature to near the desired
potentials of R134a and R1234yf are compared in a typical Euro- value. Then, a PID-controlled electric resistance heater located
pean compact automobile equipped with an internally controlled upstream from the condenser controls the inlet air temperature to
variable displacement compressor and minichannel condenser and the desired value. A separate, but similar, system controls the
evaporator. In particular, experimental data from the baseline evaporator inlet dry-bulb air temperature to the desired value. An
R134a system are compared to data from three systems: (i) the industrial vapor generator located sufficiently far upstream of the
baseline system operating with an optimal charge of R1234yf with evaporator to ensure uniform conditions at the evaporator inlet
the baseline TXV setting, (ii) the system of i with an optimal charge face controls the relative humidity. A grid of nine evenly spaced
of R1234yf with a TXV setting optimized for R1234yf, (iii) the type T thermocouples for the condenser and six for the evaporator
system of ii with the variable displacement compressor control are used to measure the mean inlet air temperature for the
valve deactivated. The experimental part of the analysis outlines respective heat exchanger. The air downstream from each heat
the limitations of systems i, ii, iii and indicates strategies for system exchanger is well-mixed prior to its temperature being measured
performance enhancement through “minor” system modifications. by separate grids of nine evenly spaced type T thermocouples. For
Then, one possible enhanced system is further investigated using both air circuits and for the refrigerant system, a Pt-100 platinum
a simulation model which was validated using the experimental resistance thermometer with an accuracy of 0.02  C was used to
results. calibrate the temperature measuring system (consisting of ther-
mocouple, electronic ice point and multimeter) to an accuracy of
3. Experimental apparatus 0.05  C. The relative humidity (RH) of the evaporator air circuit is
measured in two ways: (1) using a capacity transducer with an
Fig. 1 shows a schematic of the experimental apparatus, which accuracy of 3% RH and (2) using a load cell that measures the
consists of four basic systems: (1) a closed-loop air circuit for the amount of water condensed in a specified time with an accuracy of
evaporator, including centrifugal fan, electric resistance heater, 0.5 g.
C. Zilio et al. / Energy 36 (2011) 6110e6120 6113

Calibrated type T thermocouples measure the refrigerant Table 1


temperature immediately before and after each major component. Operating conditions.

Diaphragm-type differential pressure transducers measure the Evaporator air inlet 35  C & 40% RH 25  C & 80% RH 15  C & 80% RH
pressure drop across both the evaporator and the condenser to Evaporator air volumetric 400  3% 400  3% 400  3%
accuracies of 0.1 kPa. Strain gauge pressure transducers measure flow rate (m3 h1)
Condenser air inlet 35  C 25  C 15  C
the absolute pressures in the evaporator to 0.8 kPa and in the Condenser air volumetric 1580  3% 1580  3% 1580  3%
condenser to 1.6 kPa. flow rate (m3 h1)
The refrigerant enthalpies are determined from measured Compressor speed (rpm) 900 2500 4000 900 2500 4000 900 2500 4000
temperature and pressure values, where the refrigerant quantities
are calculated using a version of the P-R EoS of Brown et al. [24,25].
The predictions used in this paper are from 1% lower to þ1% 5. Results and discussion
greater when compared to the saturation data of Di Nicola et al. [22]
over the temperature range from 220 to 360 K. The version used in More than 140 steady-state tests were conducted. The energy
this paper is based on using the normal boiling point temperature balances on the airside and refrigerant-side for both the evaporator
of Di Nicola et al. [22] and the critical state property data of Tanaka and the condenser differed by a maximum of 4%.
and Higashi [19]. The R134a oil circulation ratio (OCR) was measured per ASHRAE
A Coriolis flow meter located in the liquid line measures the 41.4e1986 (R2006) [32]. Similar measurements were not per-
refrigerant mass flow rate to an accuracy of 0.1% of the measured formed for R1234yf since the experimental procedure consumes
value. considerable fluid, which was not available at the time of the tests.
An asynchronous electric motor drives the compressor. An Therefore, the R1234yf OCR values were assumed to be those of
optical system measures the compressor speed to an accuracy of R134a at the same compressor displacement, which are reported in
0.01% of the measured value and a torsiometer located on the Table 2. The refrigerant/Polyalkylene Glycol (PAG) oil enthalpies for
shaft that couples the electric motor with the compressor measures both refrigerants were calculated per [31].
the torque to an accuracy of 0.2 N m. The expanded uncertainty The optimal refrigerant charge was determined per [31] for each
on the mechanical power delivered to the refrigerant is less than 2% of the four system configurations, where in each case the airside
for compressor speeds of 900 and 2500 RPM and less than 3% for conditions were fixed at 35  C and 40% relative humidity for both
compressor speeds of 4000 RPM. the condenser and the evaporator. The air volumetric flow rates for
A desiccant-based drier and a sight glass are located between the condenser and the evaporator were 1600 m3 h1 and
the condenser and the mass flow meter. 400 m3 h1, respectively.
The total expanded uncertainties for the airside heat transfer In what follows in the next several paragraphs, particular
rate measurements are 1%. The total expanded uncertainties for attention will be paid to the variable displacement compressor
the refrigerant-side heat transfer rate measurements are 4% for since its internal control valve with factory settings regulates the
the evaporator and 3% for the condenser, with the largest compressor capacity based on R134a. In particular, the compres-
contributor being the uncertainties in the thermodynamic property sor’s internal valve control action controls the displacement as
estimates calculated using the P-R EoS of Brown et al. [21]. a function of the difference between the suction and discharge
It is worth noting that while the tests were not conducted per pressures, while the compressor attempts to maintain the evapo-
SAE J 2765-2008 [31], they were carried out per ASHRAE and ISO ration pressure at a constant value. The suction pressure is simply
standards that ensure accuracies as high as the ones required the evaporator outlet pressure reduced by the suction line pressure
by [31]. drop. For fixed air inlet conditions and for a fixed TXV setting, the
evaporator pressure is a function of the refrigerant’s thermophys-
4. Test conditions ical properties and the refrigerant mass flux, which affect both the
in-tube heat transfer coefficient and the refrigerant-side pressure
The system tested is a typical R134a based compact European drop (and thus also the local saturation temperature).
automobile, which had a nominal cooling capacity of 5.8 kW at For the internally controlled variable displacement compressor
a compressor volumetric flow rate of 7.8 m3 h1. Four systems were used in this study, the possible working conditions are the ones
tested: (i) the baseline R134a system, (ii) the same system as i located in the upper part of Fig. 2, that is, operating conditions
operating with an optimal charge of R1234yf with the baseline TXV located above line BC.
setting, (iii) the system of ii operating with a TXV setting optimized The position of line BC is fixed by the control valve setting:
for R1234yf, and (iv) the system of iii operating with the variable adjustment of the spring moves the line BC either up or down
displacement compressor control valve deactivated. While the relative to its baseline position. Regardless, operating conditions
operating conditions were not meant to exactly duplicate actual in- below line BC are not possible. Note that without changing the
vehicle conditions, they were chosen to cover typical European valve setting, given that the R1234yf saturation temperature is
conditions. In particular, they covered three compressor speeds, slightly different from that of R134a, lines AB and CD will result in
three ambient temperatures (the inlet air temperature of both the different refrigerant temperatures (since the pressure is fixed).
evaporator and the condenser), and two relative humidity values Therefore, the first thing to be verified is that line CD will not result
for the evaporator inlet air stream. The evaporator and condenser in a saturation temperature at the evaporator outlet below 0  C for
fan speeds (air mass flow rates) were held constant throughout the the given refrigerant.
tests (while this is not the case in a real vehicle, it reduced the
complexity of the test matrix while still allowing for a comparison
Table 2
of the performance potential of R1234yf relative to R134a). Table 1 Oil Circulation Ratio (OCR).
provides the operating conditions. Note: in the figures that follow,
Compressor speed (RPM) OCR (%)
the naming convention of Ambient Temperature/Relative
Humidity/Compressor Speed is used. For example, 15/80/900 900 3.0
2500 4.2
represents the condition with an ambient temperature of 15  C, 80% 4000 4.5
relative humidity, and a compressor speed of 900 RPM.
6114 C. Zilio et al. / Energy 36 (2011) 6110e6120

Fig. 2. Relationship between the suction and discharge pressures for the internally
controlled variable displacement compressor.
Fig. 4. Evaporator refrigerant superheat values. Note: for a given label along the
abscissa, the first number is the ambient temperature in  C, the second number is the
relative humidity in percent, and the third number is the compressor speed in RPM.
Now, turning our attention to the compressor discharge, we
note that the discharge pressure is simply the condenser inlet
pressure increased by the discharge line pressure drop. The The experimental compressor suction pressures for systems i, ii,
condenser includes an integrated liquid receiver in the manifold, and iii described in Section 4 are shown in Fig. 3. Then, Fig. 4 shows
separating the two-phase region from the subcooling region, such the evaporator superheat values for the same systems. As can be
that if the refrigerant charge is determined per [31], the tubes after seen, the “drop-in” system has significantly higher superheat
the separator will be fed with saturated liquid. Cavallini et al. [14] values than the R134a system. Thus, in order to obtain more
showed theoretically, through an exergetic analysis, that for reasonable superheat values for the R1234yf systems, the TXV was
a given condenser design (with desuperheating and two-phase modified (system iii, referred to as “TXV tuned” in the figure) from
regions) with fixed saturation temperature that the heat flux its original setting of 0.20 MPa gauge at 0  C to 0.29 MPa gauge at
which can be rejected with R1234yf is lower than that of R134a. 0  C. Similar to the evaporator, the experimental compressor
Also, Zilio et al. [26] showed for an ideal vapor compression cycle discharge pressures are shown for the same systems in Fig. 5.
that the COP of R1234yf is lower than R134a, where the gap Fig. 6 shows that the experimental suction line pressure drop as
worsens if the actual compressor isentropic efficiencies are taken a function of refrigerant mass flow rate is very similar for both
into account. Therefore, for constant cooling capacity for the R1234yf and R134a; whereas, Fig. 7 shows that the suction line
R1234yf and R134a systems, the condensation heat rejection will be pressure drop for R1234yf is greater than that of R134a for equal
higher for the R1234yf system. Consequently, the R1234yf system cooling capacity, which is due to the somewhat lower specific
will result in a greater saturation temperature at the condenser latent heat of vaporization for R1234yf.
inlet. Therefore, based on the preceding discussion, the discharge Because of the previously discussed issues, SAE ARCRP recom-
pressures for R1234yf and R134a will be different, resulting in the mended increasing the suction line diameter; however, for the
compressor control valve reacting differently for the two fluids. The compact automobile system considered herein the suction line
effect of the compressor’s internal control valve deactivation pressure drop is smaller than the pressure drop of the compressor
(dashed line in Fig. 2) will be discussed later in the paper.

Fig. 3. Compressor refrigerant suction pressures. Note: for a given label along the Fig. 5. Compressor refrigerant discharge pressures. Note: for a given label along the
abscissa, the first number is the ambient temperature in  C, the second number is the abscissa, the first number is the ambient temperature in  C, the second number is the
relative humidity in percent, and the third number is the compressor speed in RPM. relative humidity in percent, and the third number is the compressor speed in RPM.
C. Zilio et al. / Energy 36 (2011) 6110e6120 6115

Fig. 6. Suction line refrigerant pressure drops vs. refrigerant mass flow rates.
Fig. 8. Relative cooling capacities. Note: for a given label along the abscissa, the first
number is the ambient temperature in  C, the second number is the relative humidity
in percent, and the third number is the compressor speed in RPM.
manifold. Therefore, modification of the suction line would only
marginally reduce the overall pressure drop for this system. Also,
note that modification of the suction manifold would not be
considered a “minor” modification and thus is not considered in effects of this second approach can clearly be seen: the X marks are
this paper. located in an area that is non reachable using the baseline setting.
Now turning our attention to cooling capacity and COP, Fig. 8 Now, turning our attention more in detail to the compressor: for
reports the cooling capacity deviations for systems (i) and (ii) a reciprocating positive displacement compressor, the displace-
relative to the R134a baseline system, and Fig. 9 reports the COP ment volume is given by:
deviations for the same systems. In the figures, the deviation is
defined as 3 ¼ ðyR1234yf  yR134a =yR134a Þ, where y is the cooling _
60m
DISP* ¼ hv DISP ¼ (1)
capacity, the COP, or the refrigerant mass flow rate. rsuc N
As Fig. 8 shows, the R1234yf systemeeven with a tuned where DISP is the geometric displacement, N is the rotation speed
TXVeseverely lacks cooling capacity. In order to overcome this in RPM, hv is the volumetric efficiency, rsuc is the suction density,
deficit, the compressor displacement internal control valve setting and m_ is the refrigerant mass flow rate.
was modified using the model of Dou et al. [33]. In particular, their Fig. 10 plots the term R ¼ (hv DISP/DISPmax)  100 as a function
model consists of a mechanical-fluid dynamic representation of the of the difference between the discharge and suction pressures,
internally driven control valve, where the crankcase pressure and where the lines are simply interpolations of the experimental data.
the spring force represent the actuation signal for displacement Note: the compressor used in this study has a DISPmax ¼ 126 cm3.
control. The signal is a function of Pdisch, Psuc, and of the flow and Note that at 900 RPM the new valve setting results in the
design characteristics of the suction and discharge ports. Thus, one maximum displacement possible (it achieves a value of nearly
possible approach to adjusting the valve control for R1234yf is to 100%; recall that DISP* is reduced by the volumetric efficiency).
modify the port characteristics (i.e. flow coefficients and port
sections). A second possibility is to simply change the valve spring
preload, which is what the dashed line in Fig. 2 represents. The

Fig. 9. Relative COPs. Note: for a given label along the abscissa, the first number is the
ambient temperature in  C, the second number is the relative humidity in percent, and
Fig. 7. Suction line refrigerant pressure drops vs. cooling capacities. the third number is the compressor speed in RPM.
6116 C. Zilio et al. / Energy 36 (2011) 6110e6120

Fig. 10. Relative compressor displacement as a function of the difference between the
suction and discharge pressures.
Fig. 12. Relative refrigerant mass flow rates. Note: for a given label along the abscissa,
the first number is the ambient temperature in  C, the second number is the relative
humidity in percent, and the third number is the compressor speed in RPM.
Fig. 11 shows the cooling capacity data, including results for the
modified compressor valve setting. Despite this modification, the
system is still not able to provide the same cooling capacity as temperatures were always higher than 3  C (see [31]), an example
R134a at an ambient temperature of 35  C. For an ambient is shown in Fig. 16.
temperature of 25  C the same cooling capacity as the R134a system Figs. 17 and 18 show the compressor discharge pressures and
is achievable for the 2500 RPM condition but not for the other temperatures, respectively. Even though the R1234yf discharge
compressor speeds. Finally, for an ambient temperature of 15  C the pressures are always greater than those of R134a (with the only
system achieves greater cooling capacity than the R134a baseline exception being the condition 35/40/2500), the discharge temper-
system for all compressor speeds. atures of R1234yf are always lower than those of R134a, as would
Fig. 12 shows a large mass flow rate increase for all conditions be expected because of the thermodynamic properties of R1234yf
for the modified R1234yf systems due to the combined effects of (see [26]).
increased DISP* and the greater R1234yf suction density [26]. Fig. 19 shows COP results, including ones for the modified
The greater cooling capacity for R1234yf at an ambient compressor internal control valve. The figure shows that in regions
temperature of 15  C results in much lower evaporator inlet (e.g., Northern Europe) possessing low year-round ambient
temperatures for R1234yf (see Fig. 13), where the mismatch temperatures, R1234yf could lead to significantly lower seasonal
decreases with increasing ambient temperature. Thus, for an energy efficiency values as compared to R134a for the investigated
ambient temperature of 15  C, the R1234yf evaporator outlet systems (i, ii, iii). While this conclusion seems to contradict previ-
pressures (see Fig. 14) and temperatures (see Fig. 15) are lower than ously cited studies (e.g. [9e11,18]), the present study clearly shows
R134a. that efficiency is strongly related to system design and that one
It is worth noting that because of the regulating action of the should, where possible, use a system that has been optimized for
compressor internal control valve, even at ambient temperatures of a given refrigerant, which is consistent with the experimental
15  C, the compressor did not cycle since the air outlet results and conclusions of Petitjean and Benouali [13].

Fig. 11. Relative cooling capacities. Note: for a given label along the abscissa, the first Fig. 13. Evaporator refrigerant inlet temperatures. Note: for a given label along the
number is the ambient temperature in  C, the second number is the relative humidity abscissa, the first number is the ambient temperature in  C, the second number is the
in percent, and the third number is the compressor speed in RPM. relative humidity in percent, and the third number is the compressor speed in RPM.
C. Zilio et al. / Energy 36 (2011) 6110e6120 6117

Fig. 16. Evaporator air outlet temperature distribution for the case 15/80/2500.
Fig. 14. Evaporator refrigerant outlet pressures. Note: for a given label along the
abscissa, the first number is the ambient temperature in  C, the second number is the
relative humidity in percent, and the third number is the compressor speed in RPM.

To illustrate this assertion, it is worth considering in more detail


the operating condition (25/80/2500) where the cooling capacities
are the same for the two systems (see Fig. 11). This analysis is
shown in Table 3.
For this condition, the heat rejection rate for the R1234yf
condenser is approximately 5% greater, with a 2 K higher liquid
subcooling value and a greater inlet pressure (corresponding to
a 2.6 K increase in the saturation temperature). Furthermore,
because of the greater R1234yf pressure drop, the saturation
temperature drop through the condenser is 70% higher for R1234yf.
These results clearly demonstrate that R1234yf could benefit from
a redesigned condenser. As mentioned earlier, Shah [29] indicated
that R134a benefited from a similar exercise during the transition
from R12 to R134a. Furthermore, these experimental results are
consistent with the theoretical approach of Cavallini et al. [14].
A similar conclusion can be made for the evaporator: because of
Fig. 17. Compressor refrigerant discharge pressures. Note: for a given label along the
the larger R1234yf saturation temperature drop (1.5 K greater) at
abscissa, the first number is the ambient temperature in  C, the second number is the
nearly the same vapor superheat (0.9 K higher), the R1234yf relative humidity in percent, and the third number is the compressor speed in RPM.
evaporator could benefit from an improved design. Moreover, the
higher R1234yf pressure drop (for a given cooling capacity) along

Fig. 18. Compressor refrigerant discharge temperatures. Note: for a given label along
Fig. 15. Evaporator refrigerant outlet temperatures. Note: for a given label along the the abscissa, the first number is the ambient temperature in  C, the second number is
abscissa, the first number is the ambient temperature in  C, the second number is the the relative humidity in percent, and the third number is the compressor speed in
relative humidity in percent, and the third number is the compressor speed in RPM. RPM.
6118 C. Zilio et al. / Energy 36 (2011) 6110e6120

On the basis of the present experimental observations, the


present authors simulated the performance of an “enhanced”
system, i.e., one containing an “enhanced” condenser and an
“enhanced” evaporator, together with the same overridden
compressor.
The simulation model used is described in detail in Casson et al.
[34], and thus will only be discussed briefly here. It consists of
a compressor model, a minichannel evaporator model, and a mini-
channel condenser model. For calculation purposes, the heat
exchangers are divided into a series of small three-dimensional
cells. This simple approach allows a finned coil to be solved
regardless of how complicated is the lay-out of the tube circuits.
Regarding the condenser, the refrigerant-side heat transfer
coefficient is evaluated with the Cavallini et al. [35] correlation, the
pressure drops are estimated through the Mishima and Hibicki
correlation [36]. Considering the evaporator, reference to [36] is
made for the refrigerant heat transfer coefficient and pressure drop
calculation.
Fig. 19. Relative COPs. Note: for a given label along the abscissa, the first number is the The airside heat transfer coefficients, including surface effi-
ambient temperature in  C, the second number is the relative humidity in percent, and ciency, are assumed to be uniform and are evaluated through
the third number is the compressor speed in RPM.
experimental correlations obtained with a modified Wilson plot
procedure, implemented by feeding with hot water both the
Table 3 condenser and evaporator.
Data for the 25/80/2500 condition. The compressor isoentropic efficiency was fitted on the exper-
imental values obtained from the tests herein reported. The
Measured value R134a R1234yf for TXV
tuned and compressor map for displacement and related volumetric efficiency
compressor was implemented basing on data in Fig. 10.
valve overridden Air temperature, relative humidity and flow rate at the inlet of
Refrigerant mass flow rate (kg s1) 0.0258 0.0323 the condenser and the evaporator are input data, as well as the
Condenser heat rejection rate (kW) 5.07 5.34 refrigerant superheating at the compressor suction. The actual
Compressor refrigerant discharge 75.6 68.4
geometry of the heat exchanger (including among others the
temperature ( C)
Compressor refrigerant discharge 1.15 1.22 minichannel diameter, flattened tube length, height and width,
pressure (MPa) actual circuitry refrigerant side, fin spacing, thickness, length and
Condenser refrigerant saturation 44.5 47.1 height) is an input as well.
temperature @ Pdisch ( C) A simulation proceeds by iterating on the evaporation and
Condenser refrigerant 10.2 12.0
subcooling ( C)
condensation pressures, ceasing when the model successfully
Compressor refrigerant suction 0.29 0.27 matches the refrigerant mass flow rate of the compressor to those
pressure (MPa) in the evaporator and condenser.
Compressor pressure ratio 3.98 4.46 The model was validated using some of the experimental data
Condenser refrigerant 55.3 79.4
reported earlier in the paper. The calculated cooling capacity was
pressure drop (kPa)
Condenser refrigerant saturation 2.0 3.4 found to be consistent with the experimental values, both for R134a
temperature drop ( C) and R1234yf.
Evaporator refrigerant 76.8 102.1 The validated model was then used to simulate an “enhanced”
pressure drop (kPa) system. Previous discussions indicate that, for a completely opti-
Evaporator refrigerant 10.4 11.3
mized design, a thorough optimization of the refrigerant-side
superheat ( C)
circuitry would need to be conducted for both the condenser and
the evaporator. This exercise, however, is far outside the scope of
the suction line decreases the R1234yf suction pressure. This, this paper. However, aiming to provide “numerical” evidence to our
coupled with the larger R1234yf discharge pressure, results in experimental analyses, we provide simulation results for a system
a pressure ratio for R1234yf that is approximately 12% higher than with a condenser with 20% larger face area and an evaporator with
for R134a. 10% larger face area. The original refrigerant circuitry was

Table 4
Deviations for cooling capacity (Q) and COP between the simulation results for an R1234yf system with “enhanced” condenser and evaporator and the
experimental values for the baseline R134a system.
   
Test condition QenhancedR1234yf  QbaselineR134a COPenhancedR1234yf  COPbaselineR134a
3Q ¼ 3 COP ¼
QbaselineR134a COPbaselineR134a
15/80/900 30.7 8.3
15/80/2500 36.5 5.7
15/80/4000 38.7 7.4
25/80/900 1.0 0.6
25/80/2500 1.0 6.9
25/80/4000 1.0 2.8
35/40/900 1.0 0.1
35/40/2500 1.0 4.4
35/40/4000 1.0 7.6
C. Zilio et al. / Energy 36 (2011) 6110e6120 6119

maintained. Moreover, the fin spacing, length, thickness and height [2] Solomon S, Qin D, Manning M, Chen Z, Marquis M, Averyt KB, et al., editors.
Climate change 2007: The physical science basis e contribution of working
were left unchanged. Conservatively, the same volumetric air flow
group I to the fourth assessment report of the intergovernmental panel
rates measured during the experiments were used for the climate change. Intergovernmental panel on climate change of the World
“enhanced” condenser and the “enhanced” evaporator. Meteorological Organization and the United Nations environment programme
The simulations were carried out for equal cooling capacities for (UNEP). Cambridge UK: Cambridge University Press; 2007.
[3] Regulation (EC) No 842/2006 of the European Parliament and of the Council of
the “enhanced system” running with the “overridden” compressor 17 May 2006 on certain fluorinated greenhouse gases. Official Journal of the
and the baseline system operating with R134a, under exactly the European Union. Retrieved online at, http://eur-lex.europa.eu/LexUriServ/
same operating conditions of the experiments. The COP deviations LexUriServ.do?uri¼OJ:L:2006:161:0001:0011:EN:PDF 2006. July 7, 2010.
[4] Directive 2006/40/EC of The European Parliament and of the Council of 17
are reported in Table 4. May 2006 relating to emissions from air-conditioning systems in motor
Unfortunately, with the present compressor, even at the lowest vehicles and amending Council Directive 70/156/EC. Official Journal of the
displacement and considering saturated R1234yf liquid at the European Union. Retrieved online at, http://eur-lex.europa.eu/LexUriServ/
LexUriServ.do?uri¼OJ:L:2006:161:0012:0018:EN:PDF 2006. July 7, 2010.
condenser outlet, the cooling capacity is higher than the baseline [5] Bolaji BO. Experimental study of R152a and R32 to replace R134a in
with R134a at 15  C air temperature. The cooling capacity devia- a domestic refrigerator. Energy 2010;35:3793e8.
tions are reported as well in Table 4. [6] Kim M-H, Bullard CW. Development of a microchannel evaporator model for
a CO2 air-conditioning system. Energy 2001;26:931e48.
The simulation results indicate that, with the “enhanced” [7] Nielsen OJ, Javadi M, Sulback Andersen MP, Hurley MD, Wallington TJ, Singh R.
condenser and “enhanced” evaporator, the R1234yf system effi- Atmospheric chemistry of CF3CF¼CH2: Kinetics and mechanisms of gas-phase
ciency is higher than the baseline R134a system, at ambient reactions with Cl atoms, OH radicals, and O3. Chemical Physical Letters 2007;
439:18e22.
temperatures of 25  C and 35  C. The efficiency penalization at
[8] Zhang SJ, Wang HX, Guo T. Evaluation of non-azeotropic mixtures containing
15  C is a consequence of the much larger cooling capacity of the HFOs as potential refrigerants in refrigeration and high-temperature heat
R1234yf system. This latter penalization (recall: much lower than in pump systems. Science China Technological Sciences 2010;53:1855e61.
Fig. 19) could be eliminated considering a modified compressor [9] SAE International. Cooperative research program. Retrieved online at: http://
www.sae.org/standardsdev/tsb/cooperative/altrefrig.htm, July 7, 2010.
with a lower value for the minimum displacement. Finally, it should [10] SAE International. SAE International releases test results of the low GWP
be mentioned that the present results are not “optimal” ones, since refrigerant for mobile air-conditioning. Retrieved online at: http://www.sae.
the exercise does not include optimization of the refrigerant org/servlets/pressRoom?OBJECT_TYPE¼PressReleases&PAGE¼showRelease&
RELEASE_ID¼1109, July 7, 2010.
circuitries for the heat exchangers. [11] Bang S. Evaluation result of HFO-1234yf as an alternative refrigerant for
automotive air conditioning. In: Proceedings of the VDA alternative refrig-
erant winter meeting 2008, Saalfelden, Austria.
6. Conclusions
[12] Meyer J. R1234yf system enhancements and comparison to R134a. In:
Proceedings of the SAE alternative refrigerant systems symposium; 2008,
Experiments were conducted for a typical R134a compact Phoenix, AZ, USA.
European automotive air conditioning system having a nominal [13] Petijean S, Benouali J. R-1234yf validation & A/C system energy efficiency
improvements. In: SAE Alternate Refrigerant Symposium. Scottsdale, (AZ):
cooling capacity of 5.8 kW at a compressor volumetric flow rate of AARS; 2010. July 13e15.
7.8 m3 h1. Three R1234yf systems were tested using the baseline [14] Cavallini A, Brown JS, Del Col D, Zilio C. In-tube condensation performance of
hardware with some modifications: (i) the baseline system oper- refrigerants considering penalization terms (exergy losses) for heat transfer
and pressure drop. International Journal of Heat and Mass Transfer 2010;53:
ating with an optimal charge of R1234yf with the baseline TXV 2885e96.
setting, (ii) the system of i operating with a TXV setting optimized [15] Del Col D, Torresin D, Cavallini A. Heat transfer and pressure drop during
for R1234yf, and (iii) the system of ii operating with the variable condensation of the low GWP refrigerant R1234yf. International Journal of
Refrigeration 2010;33:1307e18.
displacement compressor control valve deactivated. [16] Spatz M, Minor B. HFO-1234yf low GWP refrigerant update. In: Groll EA,
The cooling capacity and COP of the “drop-in” R1234yf system Braun EA, editors. Proceedings of the International Refrigeration and Air
are considerably lower than the baseline R134a system. However, Conditioning Conference at Purdue; 2008. West Lafayette, Indiana, USA.
[17] ANSI/ASHRAE 34. Designation and safety classification of refrigerants; 2007.
their values can be improved significantly, even approaching or for [18] Koban M. HFO-1234yf low GWP refrigerant LCCP analysis. In: Proceedings of
some operating conditions exceeding, the baseline R134a values SAE world congress; 2009, Detroit, MI, USA.
with some simple hardware modifications: (1) tuning the TXV [19] Tanaka K, Higashi Y. Thermodynamic properties of HFO-1234yf (2,3,3,3-
Tetrafluoropropene). In: Proceedings of the 3rd IIR conference on thermo-
setting for R1234yf and (2) optimizing the variable displacement
physical properties and transport processes of refrigerants; 2009, Boulder, CO,
compressor control valve. The experimental analyses presented in USA.
this paper show that for a given cooling capacity and set of oper- [20] Tanaka K, Higashi Y, Akasaka R. Measurements of the isobaric specific heat
ating conditions, the R1234yf systems could be further improved capacity and density for HFO-1234yf in the liquid phase. Journal Chemical
Engineering Data 2010;55(2):901e3.
beyond among other things, optimizing the condenser and evap- [21] Akasaka R, Tanaka K, Higashi Y. Thermodynamic property modeling for
orator refrigerant circuitries [14,26]. The numerical simulations 2,3,3,3-tetrafluoropropene (HFO-1234yf). International Journal of Refrigera-
show that enhancing the face area of the condenser by 20%, the one tion 2010;33:52e60.
[22] Di Nicola GD, Polonara F, Santori G. Saturated pressure measurements of
of the evaporator by 10%, and using the overridden compressor, the 2,3,3,3 Tetrafluoroprop-1-ene (HFO-1234yf). Journal Chemical Engineering
R1234yf system showed higher COP values than the baseline R134a Data 2010;55:201e4.
for equal cooling capacities. [23] Fedele L, Bobbo S, Groppo F, Brown JS, Zilio C. Saturated pressure measure-
ments of 2,3,3,3 Tetrafluoroprop-1-ene (R1234yf) for reduced temperatures
The results and analyses presented in this paper demonstrate ranging from 0.67 to 0.93. Journal Chemical Engineering Data 2011;56:
the attractiveness of pursuing R1234yf as a potential replacement 2608e12.
for R134a in automotive applications. [24] Brown JS, Zilio C, Cavallini A. Thermodynamic properties of eight fluorinated
olefins. International Journal of Refrigeration 2010;33:235e41.
[25] Brown JS, Zilio C, Cavallini A. Critical review of the latest thermodynamic and
Acknowledgments transport property data and models, and equations of state for R-1234yf. In:
Groll EA, Braun EA, editors. Proc 13th Int Refrig Air Cond Conf; 2010. W
Lafayette, IN, USA.
The authors thank Dr. R. Monforte of the FIAT Automotive Group [26] Zilio C, Brown JS, Cavallini A. Simulation of R1234yf performance in a typical
for his financial support. automotive system. In: Proceedings of the 3rd IIR conference on thermo-
physical properties and transport processes of refrigerants; 2009, Boulder, CO,
USA.
References [27] Leck TJ. Evaluation of HFO-1234yf as a replacement for R134a in refrigeration
and air conditioning applications. In: Proceedings of the 3rd IIR conference on
[1] Brown JS. HFO’s: new low global warming potential refrigerants. ASHRAE thermophysical properties and transport processes of refrigerants; 2009,
Journal 2009;51:22e9. Boulder, CO, USA.
6120 C. Zilio et al. / Energy 36 (2011) 6110e6120

[28] Hulse R, Singh R, Pham H. Physical properties of HFO-1234yf. In: Proceedings [33] Dou C, Yang X, Tian C, Li X. Numerical analysis on the performance of control
of the 3rd IIR conference on thermophysical properties and transport valve in variable displacement wobble plate compressor. Journal of
processes of refrigerants; 2009 Boulder, CO, USA. Mechanical Design e Transactions of the ASME 2005;127:326e33.
[29] Shah RK. Automotive air conditioning systems e Historical developments, the state [34] Casson V, Del Belin Peruffo G, Fornasieri E, Zilio C. Energy efficiency of
of technology, and future trends. Heat Transfer Engineering 2009;30(9):720e35. a household air conditioner using new HFC refrigerants. In: Proceedings of the
[30] International Standards OrganizationISO 5167e4:2003. Measurement of fluid 21st international congress of refrigeration; 2003, Washington, DC, USA.
flow by means of pressure differential devices inserted in circular cross- [35] Cavallini A, Doretti L, Matkovic M, Rossetto L. Update on condensation heat
section conduits running fulldPart 4: venturi tubes; 2004. transfer and pressure drop inside minichannels. Heat Transfer Engineering
[31] SAE J 2765. Procedure for measuring system COP (Coefficient of Performance) 2006;27(4):74e87.
of a mobile air conditioning system on a test bench; 2008. [36] Sun L, Mishima K. An evaluation of prediction methods for saturated flow
[32] ASHRAE 41.4-1986. Standard method for measurement of proportion of boiling heat transfer in mini-channels. International Journal Heat Mass
lubricant in liquid refrigerant; 2006. Transfer 2009;52:5323e9.

You might also like