Professional Documents
Culture Documents
IBU-SMO-DC D002 Barrier Guidelines - Revision 3.1 (2020)
IBU-SMO-DC D002 Barrier Guidelines - Revision 3.1 (2020)
This document contains proprietary information of Chevron Corporation. Any use of this
document without express, prior, written permission from Chevron Corporation and/or its
affiliates is prohibited.
1
Contents
1.0 Purpose, Objective, and Scope.........................................................................................4
1.1. Purpose and Objective......................................................................................................4
1.2. Scope................................................................................................................................ 4
2.0 Well Control Procedure for Single Barrier Operation......................................................4
2.1. General.............................................................................................................................. 4
2.1.1. Non-Shearables and/or Non-Sealables across the BOP................................................4
2.1.1.1. Shut in Procedure for Well Control Event during Drilling Operation............................5
2.1.1.2. Shut in Procedure for Well Control Event during Tripping Operation..........................5
2.1.1.3. Shut in Procedure for Well Control Event when ESP Motor is at the
Rotary Table/Working Platform.................................................................................6
2.1.1.4. Shut in Procedure for Well Control Event During Run Screen or
Perforated Liner........................................................................................................6
2.1.2. Wells Unable to Hold Full Column of Fluid......................................................................7
2.2. Drilling................................................................................................................................ 7
2.2.1. Installation of Casing Hanger or Casing Pack Off...........................................................7
2.3. Workover and Routine Service...........................................................................................9
2.3.1. BOP, Tree, and Wellhead Accessories Removal/Installation for Non-Flange
Type Tubing Hanger....................................................................................................9
2.3.1.1. Oil Producer with ESP (GOR < 1 MSCF/STB)............................................................9
2.3.1.2. Oil Producer with ESP (GOR > 1 MSCF/STB)...........................................................13
2.3.1.3. Water and Steam Injector Well..................................................................................17
2.3.1.4. Gas Producer Well....................................................................................................20
2.3.1.5. Rigless Operation.....................................................................................................23
2.3.2. Removing Tubing Hanger Following Failure(s) on BOP test..........................................24
2.3.3. Running/Pulling ESP (Non-Sealable due to ESP Cable)...............................................25
2.3.4. BOP, Tree, and Wellhead Accessories Installation/Removal for Sucker Rod
Pumps Including Running/Pulling Sucker Rods..........................................................26
2.3.5. Wireline and Perforations Operations............................................................................31
2.3.6. Underbalance Perforation.............................................................................................31
2.3.7. Non-Mandrel ESP Cable Penetrator Tubing Hanger.....................................................32
2.3.8. N/D X-Mas Tree with Flange Type Tubing Hanger........................................................33
2.3.8.1. For Wells without Production/Injection Packer...........................................................33
2.3.8.2. For Wells with Production/Injection Packer................................................................38
2.3.9. Wellhead Change......................................................................................................... 41
2.3.10. LPT Seal as Temporary Barrier....................................................................................43
2.3.11. Tree Installation for Non-Gas Wells...............................................................................44
3.0 Other Consideration..........................................................................................................46
3.1. Well Suspension.............................................................................................................. 46
4.0 Resources, Roles, and Responsibilities..........................................................................47
Ensure connection crossover is ready per connection type and size being used
(This will be called as kick control joint). Kick control joint is a preinstalled FOSV
to 1 joint DP/pup on top and a crossover to a non-shearable/non-sealable
connection (size and type).
For DSF (Steam Injected Area), in case of steam flow from inside string, asses
the possibility to make up the kick control joint connection safely on top of non-
shearable/non-sealable tubular while diverting the steam through choke lines.
The assessment shall cover gas detection surrounding the well (LEL <10%, H2S
<1 ppm).
If uncontrollable flow occurred, drop the string and shut in the well with Blind Ram.
If LEL and H2S detected, evacuate people to safe area and asses the possibility
to keep pumping the wellbore.
2.1.1.1. Shut in Procedure for Well Control Event during Drilling Operation
Follow 3S’s procedure for drilling:
Prior to perform 3S’s procedure, need to make sure the well is in full condition and
perform static test as per Table 1 of DCM-BST-102006-C-IBU-SMO.
1. Space out
If practical, space out in order to locate the sealable area of tubular across
Annular, so that it will seal in properly.
If not practical to locate the sealable area of tubular across Annular, assess the
possibility to install kick control joint safely and locate the kick control joint across
BOP stack. Otherwise, drop the string.
2. Shut down pump
3. Shut in well with Annular BOP or Blind/Shear Ram should we drop the string.
For any pipe light indication (string moving upward), open HCR valve to divert the
flow, drop the string and shut in with Blind Ram.
2.1.1.2. Shut in Procedure for Well Control Event during Tripping Operation
Follow 3S’s procedure for tripping:
Prior to perform 3S’s procedure, need to make sure the well is in full condition and
perform static test as per Table 1 of DCM-BST-102006-C-IBU-SMO.
1. Stab-in Full Opening Safety Valves
2. Space Out
If practical, space out in order to locate the sealable area of tubular across
Annular, so that it will seal in properly.
If not practical to locate the sealable area of tubular across Annular, assess the
possibility to install kick control joint safely and locate the kick control joint across
BOP stack. Otherwise, drop the string.
3. Shut in well with Annular BOP or Blind/Shear Ram should we drop the string.
For any pipe light indication (string moving upward), open HCR valve to divert the
flow, drop the string and shut in with Blind Ram.
2.1.1.3. Shut in Procedure for Well Control Event when ESP Motor is at the Rotary
Table/Working Platform
Stab in FOSV is not applicable:
1. If practical, assess the possibility to install kick control joint safely and
locate the kick control joint across BOP stack. Otherwise, drop the string.
2. Shut in well with Annular BOP or Blind/Shear Ram should we drop the
string.
For any pipe light indication (string moving upward), open HCR valve to divert the
flow, drop the string and shut in with Blind Ram.
2.1.1.4. Shut in Procedure for Well Control Event During Run Screen or Perforated
Liner
Prior to perform 3S’s procedure, need to make sure the well is in full condition
and perform static test as per Table 1 of DCM-BST-102006-C-IBU-SMO.
1. If practical, assess the possibility to install kick control joint safely and locate
the kick control joint across BOP stack. Otherwise, drop the string.
2. Shut in well with Annular or Blind/Shear Ram should we drop the string.
For any pipe light indication (string moving upward), open HCR valve to divert the
flow, drop the string and shut in with Blind Ram.
2.2. Drilling
2.2.1. Installation of Casing Hanger or Casing Pack Off
This procedure is applicable for following well designs:
Casing Hanger Installations
Casing Pack Off Installations
Refer to Sonolog data of the individual well to verify SFL and to confirm the well
is subnormal. If losses observed, determine fill up rate and calculate required
volume of water or kill weight fluid on hands to support:
Minimum 3 hours continuous pumping with 1 bpm pumping rate for the wells
with SFL data taken from Sonolog; OR
Minimum 3 hours continuous pumping with 2 bpm for the wells without
Sonolog data
In case only one casing valve is functioning, line it up to choke manifold, thus
the choke manifold is functioning as bleed-off dan pump-in line.
Refer to Sonolog data of the individual well to verify SFL and to confirm the well
is subnormal. If losses observed, determine fill up rate and calculate required
volume of water or kill weight fluid on hands to support:
Minimum 3 hours continuous pumping with 1 bpm pumping rate for the wells
with SFL data taken from Sonolog; OR
Minimum 3 hours continuous pumping with 2 bpm for the wells without
Sonolog data
Picture: Common Configuration IBU-SMO Wellhead for Steam and Water Injector Tree
All gas wells shall have BPV installed inside Tubing Hanger prior to removing Tree.
In case the BPV cannot be installed, nipple down gas Tree operation shall follow
single barrier operation SOP as detailed below.
Picture: Common Configuration IBU-SMO Wellhead for Gas Producer Well Tree
Swab Tank and MGS must be located at the farthest area from public facilities and any potenti
3. Hook up annulus side outlet #1 to bleed line (manifold) and annulus side outlet #2
to mud pump.
In case only one valve is functioning, then lineup to the choke manifold, thus the
choke manifold is functioning as bleed-off dan pump-in line.
Choke line arrangement:
Swab Tank and MGS must be located at the farthest area from public facilities and any potenti
Whenever BOP connection test failed against existing Tubing Hanger, please check:
1. If the well completed with packer or not?
2. If the well completed with packer, is the packer still intact or not?
Perform BOP Shell Test for wells with intact packer.
3. If the packer still intact and no leak, call TL and follow possible solution to close
side outlet annulus valve and test BOPE against packer. For high pressure test,
consider existing casing condition.
Pre-requirements:
Keep the hole full to maintain hydrostatic barrier, continuous pumping
from the annulus if the well unable to hold a full column of fluid.
Prepare blank Tubing Hanger or packer or cup-type BOP tester to test the
BOP, ensure rating and sizes are match with Wellhead / casing sizes.
Procedure:
1. Pick up landing joint and connect to FOSV installed on top of Tubing Hanger
2. Pull out of hole existing Tubing Hanger.
If flow occurred during pulling out Tubing Hanger, space out and shut in the well.
Prepare for bullhead operation to kill the well and proceed to next step.
3. Remove existing Tubing Hanger and replace with test plug component to test the BOP
(Test plug alternatives: blank Tubing Hanger, Cup type tester or Packer).
For wells with ESP, cut cable at one join below Tubing Hanger, and secure/clamped
cable to the tubing (using a cable clamp).
If flow occurred after removing existing Tubing Hanger, assess the possibility to
reinstall FOSV safely, space out and shut in the well. Prepare for bullhead
operation to kill the well and proceed to next step.
If uncontrollable flow occurred, drop the string and shut in the well with Blind
Ram.
4. Run test plug in hole and set as follow:
a. Tubing Hanger: land and set inside the Wellhead
Ensure annulus valve in open position prior to and during BOPE test.
b. Packer: follow the specific installation procedure
c. Cup type tester: follow the specific installation procedure
5. Perform BOP Connection Pressure Test
Ensure FOSV is ready at the rig floor, has same connection type and size with the
production string.
Ensure hacksaw to cut the cable is available in the rig floor during running/pulling
ESP.
Procedure:
1. Prepare all tools and equipment required for tripping ESP with cable
2. Trip ESP assembly as per approved program
3. Maintain hydrostatic barrier at all time:
If the well can hold full column of fluid, fill up well until well full and maintain
hydrostatic barrier
If well cannot hold full column of fluid, continuous pumping with Slow Pump
Rate (SPR) throughout the job.
4. If well is flowing during running/pulling, Driller shall sound alarm, and assess
possibility to shut in the well by following 3S’s procedure. The assessment shall
cover gas detection surrounding the well (LEL <10%, H2S <1 ppm, non-steam kick,
and non-gas well). The shut-in procedure (3S’s) as follow:
a) Stab FOSV and close the valve.
b) Rise up the last joint around 20 ft(*), open HCR to divert flow, close Annular
BOP to reduce flow rate coming out allowing rig crew to clamp and cut the
cable.
NOTE:
(*) Each of rig may have different requirement based on their RSP.
The intention is to reduce strong flow up to rig floor by diverting the flow to
blueline while the crew are cutting the cable.
If uncontrollable flow occurred, drop the string and shut in the well with Blind Ram.
c) Open Annular BOP
d) Strip In – Lower the string to locate the sealable tubing area crossing BOP Stack.
e) Shut in well with Annular BOP.
For any pipe light indication (string moving upward) or uncontrolled flow, drop the
string and shut in with Blind Ram.
2.3.4. BOP, Tree, and Wellhead Accessories Installation/Removal for Sucker Rod Pumps
Including Running/Pulling Sucker Rods
In case only one valve is functioning, then lineup to the manifold, thus the
manifold is functioning as bleed-off dan pump-in line.
Example of lineup arrangement (from available annulus valve, lineup might be
connected to the Pump Manifold):
1. Ensure the well is in static Condition. If the well in loss condition, follow the
procedure of non-routine SOP “Well Unable to Hold Full Column of Fluid”.
2. R/U wireline Unit.
3. Continue job with wireline Operation.
Note: Wireline operators to prepare wireline cutter as contingency plan
4. If well flowing during wireline job:
a. If practical to POOH wireline tools immediately to surface clear from BOP stack
and shut the well in with Blind Ram. It is only applicable if the logging tool length
can be cleared off from BOP stack.
NOTE
Never shut in the well on logging tools or when Logging tool crossing the BOP
stack
b. If not practical to pull all wireline tools to surface, shut the well in with Annular
BOP on wireline cable. Kill the well with bullheading method. In case of Annular
BOP could not seal on wireline cable, cut wireline using wireline cutter. Drop
logging tools and shut in using Blind Ram.
NOTE
Driller, or designated person as identified in PJSM, shall report to DWSM and
Tool Pusher for well shut in verification and pressure monitoring
Refer to MOCP 18-001D, a non-mandrel ESP cable penetrator Tubing Hanger is still
acceptable for the following application:
MASP = 0 psi
Non-Gas producer wells or Oil Producer Wells with GOR < 400 SCF/BBL
No LOC/HES issues with individual well and surrounding adjacent wells
Pre-requisites:
Must change out Tubing Hanger seals
Must use ESP Flat Power Cable #1
Installation Procedure:
1. RIH ESP and cable to desired depth based on well program
NOTE
Maintain hydrostatic pressure at all time:
If well can hold full column of fluid, fill up the well until full and maintain the
hydrostatic barrier
If well cannot hold full column of fluid, continuous pumping with Slow Pump
Rate (SPR) throughout the job.
2. Install Tubing Hanger complete FOSV on top of tubing string.
3. Check ESP Cable Reading. Ensure Cable Reading is still MET with requirement
from ESP provider
4. Ensure to have ESP cable AWG-1 across Tubing Hanger. Cable hole sizes on
Tubing Hanger seal must be the same with the cable size.
5. Cut ESP Cable and Do Splicing (if needed).
6. Insert ESP Cable pass through the Tubing Hanger.
In case only one valve is functioning, then lineup to the choke manifold, thus the
choke manifold is functioning as bleed-off dan pump-in line.
One line to mud tank
One line to pump discharge line
One line to the Mud Gas Separator (MGS)
Stop operation, re-group, and discuss with TL Operation if no valves are
functioning.
4. Test hook up line to expected maximum pumping pressure +500 psi.
5. Open tubing and annulus valve to read the pressure
Report to TL Operation and Engineering for further analysis and advice.
Follow Bleed-Off 101 Rule.
If the pressure reading is zero psi in the tubing side and in the annulus side, open
annulus valve to check for flow for 30 minutes, confirm no flow, fill up the well with
water and go to step to nipple down Tree. Otherwise, prepare for bullhead.
6. If found pressure in annulus side:
Bullhead from the annulus side, at least 2x hole volume for well that unable to
hold column of fluid.
Bullhead from the annulus side, with 1.1x hole volume in case the well can
maintain full column of fluid.
WSR to report estimate fill up rate based on bullhead result to TL Operation. This
is critical information to determine required water volume on hand prior to
pulling/running sucker rods.
7. Bleed off trapped pressure on both tubing (#4) and annulus side (#8).
8. Observe annulus pressure for at least 30 minutes:
If found pressure still exist or flow indication, continue bullhead and consider
using kill weight fluid or LCM / polymer mud.
If no pressure, continue to next step while keep the hole full to maintain
hydrostatic barrier, or continuous pumping from the annulus if the well unable to
hold full column of fluid.
9. Proceed to pulling/running out sucker rod string. Keep the hole full to maintain
hydrostatic barrier throughout the job or continuous pumping from the annulus if the
well unable to hold a full column of fluid.
NOTE:
If flow occurred, assess the possibility to stab in FOSV onto Tubing Hanger/Rod
BOP safely, otherwise, evacuate people to safe area. The assessment shall cover
gas detection surrounding the well (LEL <10%, H2S <1 ppm, non-steam kick, and
non-gas well).
Mitigation plan if well flowing after risk assessment process involving Operations
Leaders:
a. Stop pumping fluids from annulus side, divert the flow to mud tank from annulus
by opening side outlet casing valves to reduce flow rate coming out from tubing
side allowing rig crew to work around Wellhead.
b. Prepare for FOSV installation.
i. Lower elevator close to Rod BOP, open elevator and drop sucker rod string.
Note: if elevator cannot be opened, cut-off sucker rod and drop
ii. Stab in the FOSV in open position onto Rod BOP.
iii. Close FOSV and shut-in well.
iv. Commence bullhead to kill the well through annulus. Observe annulus pressure
for at least 30 minutes after bullhead process
WSR call TL Operation to report fill up rate observed and total water on hand
before proceed nipple down Tree.
1. If initial kill less than or equal to 100 bbls, required water on hand shall be
260 bbls.
2. If initial kill more than 100 bbls, required water on hand shall be 360 bbls.
10. Open side outlet casing valve (Bleed line).
Ensure bleed line are open to swab tank (if available), otherwise to mud tank to
monitor well condition and/or divert the flow when needed.
11. N/D Tree (Remove Rod BOP, pumping tee and production nipple).
Note:
If flow occurred, assess the possibility to stab in FOSV onto Tubing Hanger
safely, otherwise, evacuate people to safe area. The assessment shall cover gas
detection surrounding the well (LEL <10%, H2S <1 ppm, non-steam kick, and
non- gas well).
12. Stab in FOSV and close it.
13. Observe annulus pressure for at least 30 minutes:
If found pressure still exist or flow indication, continue bullhead and consider
using kill weight fluid or LCM-polymer mud.
If no pressure, continue to next step while keep the hole full to maintain
hydrostatic barrier, or continuous pumping from the annulus if the well unable to
hold a full column of fluid.
14. Pull out flange type Tubing Hanger. Slip the tubing on Wellhead
15. Disconnect and remove flange type Tubing Hanger from tubing
16. Install temporary blank Tubing Hanger with FOSV installed on it and land the
Tubing Hanger on Wellhead
Note:
If flow occurred, assess the possibility to re-install flange Tubing Hanger with
FOSV safely or install BOP safely, otherwise, evacuate people to safe area. The
assessment shall cover gas detection surrounding the well (LEL <10%, H 2S <1
ppm, not steam kick, and not gas well). Communicate with operation leader for
the resolution.
17. N/U BOP and Test.
2.3.8.2. For Wells with Production/Injection Packer
For gas well, it is mandatory to perform Wellhead Maintenance and Inspection prior
to rig move into the well location and use of Mud-Gas Separator.
All gas wells shall have BPV installed inside Tubing Hanger prior to removing Tree.
In case the BPV cannot be installed, nipple down gas Tree operation shall follow
single barrier operation SOP as detailed below.
Picture: Configuration Wellhead and Tree with flange type hanger at gas well
In case only one valve is functioning, then lineup to the choke manifold, thus
the choke manifold is functioning as bleed-off dan pump-in line.
In IBU-SMO, there are some cases related to missing Wellhead and require replacement
with incapability to maintain two barriers during operation.
Procedure to Install / Change Wellhead for wells with missing Wellhead and /or
accessories:
Scope for this procedure:
1) Install missing Wellhead
2) Install missing Wellhead accessories i.e. valve, etc.
3) Casing leak near surface or Wellhead leak
Rigless Operation
1. Observe well for any pressure or flow indication minimum for 2 hours
2. Observe and check gas content surrounding the well:
a. If found LEL and H2S, mobilize Injection Water Unit to fill up well.
b. If LEL and H2S continuously detected exceeding MSW requirement, suspend job.
3. Continue to the main job e.g., install casing sleeve, install valve, replace/install
Wellhead. Any test requirement will be detailed in the well program.
4. R/D Rigless unit.
Mitigation Plan:
NOTE
If flow occurred, assess the possibility to stab in FOSV onto Tubing Hanger safely,
otherwise, evacuate people to safe area. The assessment shall cover gas detection
surrounding the well (LEL <10%, H2S <1 ppm, non-steam kick, and non-gas well).
If flow occur during the operation, attempt to shut in the well if practical, otherwise
abandon the well.
Procedure to Change Taper Wellhead (Wellhead size smaller than the Production
casing)
Wells with ESP or OE Tubing Wells with Injection or Production Packer
1. N/U BOPE & test Option #1:
2. POOH ESP 1. N/U BOPE & test
3. Set cement barrier with 2. Unset Packer and raise up to ~300 ft above
minimum 100 ft cement column top perforation zone
length above uppermost 3. Dump sand to ~100 ft above top perforation
perforation zone for temporarily plug the open zones
4. Verify cement barrier with tag 4. Raise up packer to ~50 – 100 ft below
and pressure test Wellhead
5. Change Wellhead to the 5. Land Tubing Hanger
standard size 6. R/U CTU and test
7. Set cement barrier at with minimum 100 ft
cement column length at ~100 ft above
uppermost perforation
8. Verify cement barrier with tag and pressure
test
9. R/D CTU
10. Change with the standard Wellhead
Option #2:
1. N/U BOPE & test
2. Cut tubing above packer, estimated 30 ft
above packer
3. Dump sand to 30 ft above top fish (sand must
cover tubing cut).
4. Tag TOS
5. Set Cement Barrier with minimum 100 ft
cement column length above TOS
6. Verify cement barrier with tag and pressure
test
7. Change Wellhead to the standard size
2.3.10. LPT Seal as Temporary Barrier
This is applicable for following well designs, but not limited to:
Prior completing well intervention (WS/WO) before well POP
The well already on production mode but have a leak on the seal Tubing Hanger.
Pre-requisite:
Ensure Safe condition around Wellhead
NOTE:
If flow occurred, assess the possibility to install LPT seal safely. Otherwise,
evacuate people to safe area. The assessment shall cover gas detection
surrounding the well (LEL <10%, H2S <1 ppm, not steam kock and not gas well).
Installation Procedure:
1. Install Pressure gauge at casing side to check pressure.
NOTE:
Prepare WCT or Injection Water Unit to support killing / pumping activity
2. R/U WCT or Injection Water Unit
3. Kill well / Cool down well using WCT or Injection Water Unit.
4. Monitor shut in pressure.
5. Observed annulus for any flow / pressure build up for 30 minutes,
If flow occur or pressure build up, continue killing operation with bullhead from
annulus side and consider using kill weight fluid.
If no flow, continue to next step while keep the hole full to maintain hydrostatic
barrier, continuous pumping from the annulus if the well unable to hold full
column of fluid.
6. Install LPT seal:
Unscrewed 4 bolts on the Wellhead an in alignment with LPT position,
Install LPT rubber to wrap around the neck of the Tubing Hanger (above
Wellhead cover plate),
Install LPT plate c/w seal and screwed tightly to the Wellhead.
Picture: LPT Seal Component and Installation
7. Observe the condition of Tubing Hanger (after LPT installation), do flow check for 30
minutes to confirm no leaks from Tubing Hanger, the flow check also as barrier
verification of the hydrostatic Pressure.
NOTE
Longer flow check is recommended for repetitive leakage wells (1-2 hours)
Pre-requisite:
1. Perform offline pressure test of Production Tree, Valves and its accessories on the
first change after it is nipple down from the well.
NOTE
Immediately replace parts of production Tree which found leak/fail to hold
pressure during pressure test production Tree.
2. Ensure all connections are in good condition
3. Ensure whether downhole check valve is available in the well.
Installation Procedure:
1. Land Tubing Hanger with FOSV in close position on Wellhead
2. Test Tubing Hanger
For Non-Mandrel Tubing Hanger, Tubing Hanger test will follow MOCP-18 001D
3. Check for flow for 30 minutes
If flow occur or pressure build up, kill the well with bullhead from annulus side
and consider using kill weight fluid.
If no flow, continue to next step while keep the hole full to maintain hydrostatic
barrier, continuous pumping from the annulus if the well unable to hold full
column of fluid.
4. N/D BOPE as per procedure
5. Installed production Tree above Tubing Hanger
6. Pressure test production Tree and all connection as per below procedure:
A. For ESP with downhole check valve
a. Fill up tubing and check for any leaks by visual observation on all production
Tree component and its connections.
b. Pressure test Tree and all connections against check valve. Ensure Master Valve
in open position during pressure test.
Engineering shall define the type of barrier used, in consideration of barrier lifetime and
future intervention. Considering the lifetime of mechanical type barrier, its usage for
well suspension without predetermined future shall be avoided. Planned schedule (i.e.
Rig Schedule) may serve as strong foundation for engineers to use mechanical barrier
in well suspension. For undetermined future action after well suspension, cement cap
or full cement column shall be used as the barrier.
Barrier for well suspension still follow the barrier requirement, qualification, verification,
and type as guided on Global Technical Standard.
4.0 Resources, Roles, and Responsibilities
The following table outlines the roles and responsibilities associated with this procedure.
Table 1: Roles and Responsibilities
Role Responsibilities
Drilling and • Responsible for ensuring that IBU D&C Design and planning
Completion Engineer activities adhere to the requirements in this SOP and all
other applicable standard
• Understand what is considered as single barrier operation
per Barrier Guideline SOP and its application in well program
• Ensure all mitigation based on this SOP and additional (as
required) are well informed in well program
• Understand when operation is not listed in this SOP, any
single barrier operations required MOC in place prior
execution
IBU-SMO X Susilo Hw
Manager, D&C Engineering
Manager, D&C Engineering
Signed by: Susilo Hadi Widodo
IBU-SMO X
Manager, SMO D&C Rig Hub
Manager, SMO D&C Rig Hub
Signed by: Candy Wijaya
IBU X J. Lelono
General Manager, Drilling &
General Manager, Drilling & Completion
Completion Signed by: Joko Lelono
Table 3: Document Control Information
Description
3.1 14 June 2020 Revised version from New Barrier GTS (3.0)