Manual
1 General
FCS/W portable test kit is used to test main characteristic of BT2 & BT3 series air circuit breaker. It
tests tripping characteristic of breaker by simulating signal to intelligent controller of breaker. It has
many testing functions, for example three class protection.
2 Attentions
Read this manual carefully before using and maintenance, in order to use this test kit safely.
Warning
——This kit must operated and maintained by specialized staff.
——Cut off the power before moving or breaking the wire.
——Do not use the power that exceed the rated value (this test kit's rated voltage is AC230V),
otherwise it will burnt down.
——Connect the test wire correctly before testing, do not hot swapping.
——Move this test kit carefully.
1
3 Group Part
Upper cover
(Internally putting testing accessories)
Supply switch
Testing interface1
Testing interface2
USB interface
Connecting line
Supply line Testing line B
2
4 Technical Parameter
≤0.5s ±5ms
Accuracy
>0.5s ±1%
Tripping time measuring
Resolution Ratio 1ms
Range 0 ~ 3000s
Dimension 327mm(L)×282mm(W)×218mm(H)
3
5 Testing Function
EA35 EA36
EP35 EP36
M26
Controller Type L25 M25 P25 P26 EQ35 EQ36
H26
EG35 EG36
EN35 EN36
Long Time
√ √ √ √ √ √ √
Delay
Automatic Short Time
√ √ √ √ √ √ √
Testing Delay
Instantaneous √ √ √ √ √ √ √
Long Time
√ √ √ √ √ √ √
Delay
Short Time
√ √ √ √ √ √ √
Senior Delay
Testing
Instantaneous √ √ √ √ √ √ √
Manual Grounding
× × × √ √ × √
Testing Fault
Current
× × ○ × ○ ○ ○
-Unbalance
MCR √ √ √ √ √ √ √
ZSI × ○ ○ ○ ○ ○ ○
Long Time
√ √ √ √ √ √ √
Delay
Short Time
√ √ √ √ √ √ √
Delay
Simple Testing
Instantaneous √ √ √ √ √ √ √
Grounding
× × × √ √ × √
Fault
Supply Testing √ √ √ √ √ √ √
Note:
"√": Controller has this function; test kit can test this item.
"○": Only the controller having this function is tested by test kit.
"×": Controller haven't this function, don't be tested by test kit.
4
6 Connecting
Testing line and connecting type are determined by controller type. Testing interface and position are
different from controller type. Please connect by the following.
Fig 6.1
5
6.2 BT2-2000~6300 Series Connecting Way
Fig 6.2.1
6
Fig 6.2.2
ZSI testing terminal connecting way (please void without ZSI function)
7
6.3 BT3 Series Connecting Way
6.3.1 Senior Connecting Way
8
6.3.2 Simple Test Connecting Way
9
7 Operation & Use
10
7.3.1 Simple Test
After the test is complete, click "NEXT" to save this test Fig 7.8 Simple Test Result
result, click "SAVE" to complete this test to save the txt
file. Test file name with the date of the test, the test
results on the same day will be saved in the same file,
and different tests to distinguish specific test time (Fig
7.9).
Note: After exiting the test or the end of the test, press
the clear light button on the controller of the circuit
breaker. Fig 7.9 Test File Save
11
7.3.2 Senior Test
7.3.2.1 Automatic Test
Select the "SENIOR TEST" to enter automatic test and
manual test selection interface (Fig 7.5), select the
"AUTOMATIC TEST" to enter "CONFIGURE
PROTECTION PARAMETERS" interface (Fig 7.10)
Attention: automatic test is available for the controller
with test interface, and the protection parameters are
special designed. It may different from the tested Fig 7.10 Configure Protection
controller; the parameter will be return to original after the Parameters
test.
Click the "NEXT" button at "CONFIGURE PROTECTION
PARAMETERS" interface (Fig 7.11), click the needed
protection type, Fig 7.12 is the situation that three section
protection test function put in.
After configured the protection type, click "NEXT" button
to enter the test alert interface (Fig 7.13), test interface
shows and test begins after confirming (Fig 7.14). Fig 7.11 Configure Protection Type
Click the "NEXT" button to show file name of the test (Fig
7.15), click "SAVE" button to save the file.
Attention: the test date is the test file name, the same
test result saved in the same txt file, differentiated by Fig 7.13 Alert Screen
specific test time.
12
7.3.2.2 Manual Test
13
Click the "NEXT" button to enter alert interface (Fig 7.20)
after inputting the parameters, and test begins after
confirming (Fig 7.21).
Click the "NEXT" button to show file name of the test (Fig
7.15), click "SAVE" button to save the file.
Fig 7.21 Long-time Manual Test
Attention: the test date is the test file name, the same
test result saved in the same txt file, differentiated by
specific test time.
14
7.4 Power Test
Click the "POWER TEST" button to enter power test alert
interface (Fig 7.22), and power test interface (Fig 7.23)
shows after confirming, if the status bar shows the
following status in the test:
—— TESTING: Power input the controller, start power test.
—— PASSED: Controller's self-power supply functions well.
—— FAILED: Controller's self-power supply test failed.
Click the "NEXT" button to show file name of the test (Fig 7.15), Fig 7.22 Alert Screen
click "SAVE" button to save the file.
Attention: the test date is the test file name, the same
test result saved in the same txt file, differentiated by
specific test time.
8 Maintenance
8.1 Replace the Fuse
1. Turn off the power switch, pluck the plug.
2. Pry upward of the fuse stand in power switch module with screwdriver (Fig 8.1), take out
the fuse stand.
3. Replace the fuse in fuse stand with suitable fuse (3A).
4. Push the fuse stand into the groove of the power switch slightly.
5. Confirm the installation is reliable, connect the power, turn on the power switch, and touch
screen light on normally.
Fig 8.1
16
8.3 Change the test wire
The test wire is for the test kit's exclusive use, prohibit user privately restructure and
manufacture, contact with us if necessary.
8.4 Maintain
Do not dismount this product optionally, contact with us if any fault occurs.
17