Item 347

Engineering Sheet
Customer: York Fire Fighting Danfoss A/S
Valve type: Modular Valve Manifold Industrial
Controls Division
Danfoss code number: 032U5460
Customer code number: 918945-0 Albuen 29
D K-6000 Kolding,
Denmark
CVR nr.: 20 16 57 15

Phone: +45 7635 6565


Fax: +45 7635 6598

Dimensions in mm

Technical data
Valve: Valve type Manifold solution w. solenoid valve unit and
integrated ball valve for drain/test
Dimensions 680 x 110 x 100 mm
Inlet connections G1” tube
Drain/Test connection G1/2” tube
Outlet connection G1”
Medium Water
Max. test pressure 25 bar
Max. opening differential pressure 16 bar
Min. opening differential pressure 0.3 bar
Kv-value 8.5 m 3/h
Max. medium temperature + 120°C
Min. medium temperature - 30°C
Material: Body Anodized aluminium
Internal parts Brass/Stainless steel
Diaphragm NBR
O-rings NBR/Viton

Kolding, 15/09/2005 Page 1 /2

Morten Jensen, Design Engineer Filename: 032U5460.doc


Engineering Sheet
Danfoss A/S
Industrial
Controls Division
Albuen 29
D K-6000 Kolding,
Denmark
CVR nr.: 20 16 57 15

Phone: +45 7635 6565


Fax: +45 7635 6598

Coil: Coil type BB230CS


Voltage 220-230 V, 50/60 Hz.
Voltage tolerance + 10% / - 15%
Power consumption: Holding 10 W
Max. ambient temperature + 50°C
Duty rating Continuous (100%)

Instructions for manuel opening unit to servo


controlled solenoid valve.

Function: Turning the operating screw


counter-
clockwise opens the pilot of the unit and
thereby
opens the solenoid valve main orifice for full
flow.
The valve remains open until the operating
screw
is turned clockwise. This closes the pilot
orifice and,
subsequently, the main orifice.
One full turn of the operating screw is
sufficient
to open and close the valve.

Kolding, 15/09/2005 Page 2 /2