INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745

FireLock® Fire-Pac for FireLock NXT™ Valves


SERIES 745

Cabinet for 1 1/2 – 2-inch/


48.3 – 60.3-mm Valve Sizes
Shown Above

WARNING
WARNING

• Read and understand all instructions before attempting to install Victaulic piping products.
• Depressurize and drain the piping system before attempting to install, remove, or adjust
Victaulic piping products.
• Wear safety glasses, hardhat, and foot protection during installation.
Failure to follow these instructions could result in serious personal injury and/or property
damage.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_G I-745
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

TABLE OF CONTENTS HAZARD IDENTIFICATION


Hazard Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Definitions for identifying the various hazard levels are
­provided below. When you see this symbol, be alert to the
SECTION I - FIRELOCK FIRE-PAC GENERAL INFORMATION possibility of personal injury. Carefully read and fully
u­nderstand the message that follows.
Dimensions for FireLock Fire-Pac Cabinets . . . . . . . . . . . . . . . . . . . . . . 3
FireLock Fire-Pac Figure Number System . . . . . . . . . . . . . . . . . . . . . . . 4 DANGER
FireLock Fire-Pac Fire Alarm Control Panel Options . . . . . . . . . . . . . . . 5 • The use of the word “DANGER” ­identifies an immediate
Internal Cabinet Views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9 hazard with a likelihood of death or serious personal injury
Mechanical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 if instructions, including recommended precautions, are not
followed.
System Gauges and Manual Pull Station . . . . . . . . . . . . . . . . . . . . . . . 10
Opening the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Inspection and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 WARNING
Removing the Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
• T
 he use of the word “WARNING” identifies the presence
SECTION II - FIRELOCK FIRE-PAC ELECTRICAL WIRING of hazards or unsafe practices that could result in death or
­serious personal injury if instructions, including recommended
Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 precautions, are not followed.
Important Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
FireLock Fire-Pac Electrical Schematic Reference . . . . . . . . . . . . . . . . 14
Electrical Enclosure Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Supply Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Initiating Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Notification Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Auxiliary 24 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Programmable Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4XTM Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
ANN-RLY Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Field Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

SECTION III - FIRELOCK FIRE-PAC PROGRAMMING

Programming Matrix for Drawing SCHEM-745-000


(Trim Selection 04) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Programming Matrix for Drawing SCHEM-745-020
(Trim Selections 05, 06, and 07) . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Programming Matrix for Drawings SCHEM-745-030 and
SCHEM-745-050 (Trim Selections 08, 01, and 02) . . . . . . . . . . . . . 24

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_G I-745_1
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

SECTION I - FIRELOCK FIRE-PAC GENERAL


INFORMATION
• Dimensions for Fire-Pac Cabinets
• FireLock Fire-Pac Figure Number System
• FireLock Fire-Pac Fire Alarm Control Panel Options
• Internal Cabinet Views
• Mechanical Connections
• System Gauges and Manual Pull Station
• Opening the Cabinet
• Inspection and Maintenance
• Removing the Compressor

Cabinet for 1 1/2 – 2-inch/


48.3 – 60.3-mm Valve Sizes
Shown Above

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

I-745_2 REV_G
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

DIMENSIONS FOR FIRELOCK FIRE-PAC CABINETS


B C

D M

Front of
Cabinet E

J G

H
L K
I Top View
The drawings shown above are for Fire-Pac cabinets containing 1 1/2 – 2-inch/48.3 – 60.3-mm valve sizes.

Valve Size Dimensions – inches/mm


Actual
Nominal Outside
Size Diameter Approximate
inches inches Height Width Depth Weight Each
mm mm A B C D E F G* H* I* J* K L M lbs/kg
1 ½ 1.900 69.11 23.62 19.89 12.00 9.63 9.69 10.05 9.92 14.42 10.43 2.52 7.06 15.00 350.0
40 48.3 1755.4 599.9 505.2 304.8 244.6 246.1 255.3 252.0 366.3 264.9 64.0 179.3 381.0 158.8
2 2.375 69.11 23.62 19.89 12.00 9.63 9.69 10.05 9.92 14.42 10.43 2.20 7.56 15.00 360.0
50 60.3 1755.4 599.9 505.2 304.8 244.6 246.1 255.3 252.0 366.3 264.9 55.9 192.0 381.0 163.3
2 ½ 2.875 69.11 31.50 23.81 12.00 15.75 8.84 12.15 8.84 16.67 11.62 4.47 4.47 3.00 516.0
65 73.0 1755.4 800.1 604.8 304.8 400.1 224.5 308.6 224.5 423.4 295.1 113.5 113.5 76.2 234.1
3.000 69.11 31.50 23.81 12.00 15.75 8.84 12.15 8.84 16.67 11.62 4.47 4.47 3.00 516.0
76.1 mm
76.1 1755.4 800.1 604.8 304.8 400.1 224.5 308.6 224.5 423.4 295.1 113.5 113.5 76.2 234.1
3 3.500 69.11 31.50 23.81 12.00 15.75 8.84 12.15 8.84 16.67 11.62 5.57 5.57 3.00 522.0
80 88.9 1755.4 800.1 604.8 304.8 400.1 224.5 308.6 224.5 423.4 295.1 141.5 141.5 76.2 236.8
4 4.500 69.11 31.50 23.81 12.00 15.75 8.84 12.15 8.84 16.67 11.62 5.73 5.40 3.00 720.0
100 114.3 1755.4 800.1 604.8 304.8 400.1 224.5 308.6 224.5 423.4 295.1 145.5 137.2 76.2 326.6
6.500 69.11 31.50 23.81 12.00 15.75 8.84 12.15 8.84 16.67 11.62 3.85 3.85 3.00 840.0
165.1 mm
165.1 1755.4 800.1 604.8 304.8 400.1 224.5 308.6 224.5 423.4 295.1 97.8 97.8 76.2 381.0
6 6.625 69.11 31.50 23.81 12.00 15.75 8.84 12.15 8.84 16.67 11.62 3.85 3.85 3.00 840.0
150 168.3 1755.4 800.1 604.8 304.8 400.1 224.5 308.6 224.5 423.4 295.1 97.8 97.8 76.2 381.0

* Dimensions G, H, I, and J apply to both side views of the cabinet

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_G I-745_3
FireLock Series 745 Fire-Pac Figure Number System

I-745_4
S P 040 745 05 B 1 B 1 1 SERIES 745

www.victaulic.com
Style Applicable Compressor Air Maintenance Color
Class Type Size Number Trim Selection Panel Design Wiring Code Selection Selection Selector
S A - Dry 014 1 ½” 745 01 - Dry Actuated A - No Panel 1 - Std. (US) UL Class B B - 1/6 hp †† 1 - Compressor (No Air Maintenance Trim) ** 1 - Red
D - Deluge 020 2” 1A - Dry Actuated with Added Control Valve B - PDRP-2001 Panel (Includes Two - 12V, 12AH Batteries) 2 - Canada ULC Class B C - ¼ hp †† 2 - Air Maintenance Trim Assembly (AMTA) ***@ 9 - Special #
P - Preaction 761 76.1 mm # 02 - Dry Actuated/Accelerated † C - PDRP-2001 Panel/4XTM 3 - US 220V Class B D - 1/3 hp †† 3 - Air Maintenance Trim Assembly with Tank @
165 165.1 mm # 2A - Dry Actuated/Accelerated with Added Control Valve † D - PDRP-2001 Panel/4XTM/ANN-80 4 - Standard Class A E - ½ hp †† 4 - No Compressor
03 - Deluge Pneumatic E - PDRP-2001 Panel/4XTM/ANN-I/O F - ¾ hp ††
024 2 ½” 5 - Canadian Class A 9 - Special #
3A - Deluge Pneumatic with Added Control Valve F - PDRP-2001 Panel/4XTM/ANN-RLY G - 1 hp ††
030 3” 04 - Deluge Electric G - PDRP-2001 Panel/4XTM/ANN-80/ANN-I/O 6 - 220V Class A H - None †††
040 4” 4A - Deluge Electric with Added Control Valve H - PDRP-2001 Panel/4XTM/ANN-80/ANN-RLY 9 - Special #
060 6” 05 - Preaction Single-Interlocked, Electric I - PDRP-2001 Panel/4XTM/ANN-I/O/ANN-RLY
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL

5A - Preaction Single-Interlocked, Electric with Added Control Valve J - PDRP-2001 Panel/ANN-80


5B - Preaction AutoConvert Single-Interlocked, Electric K - PDRP-2001 Panel/ANN-80/ANN-I/O
5C - Preaction AutoConvert Single-Interlocked, Electric with Added Control Valve L - PDRP-2001 Panel/ANN-80/ANN-RLY
06 - Preaction Double-Interlocked, Electric ˆ M - PDRP-2001 Panel/ANN-80/ANN-I/O/ANN-RLY
6A - Preaction Double-Interlocked, Electric with Added Control Valve ˆ N - PDRP-2001 Panel/ANN-I/O
6B - Preaction AutoConvert Double-Interlocked, Electric ˆ P - PDRP-2001 Panel/ANN-RLY
6C - Preaction AutoConvert Double-Interlocked, Electric with Added Control Valve ˆ Q - PDRP-2001 Panel/ANN-I/O/ANN-RLY
07 - Preaction Double-Interlocked, Pneumatic/Electric 9 - Special #
7A - Preaction Double-Interlocked, Pneumatic/Electric with Added Control Valve
7B - Preaction Double-Interlocked, Electric-Pneumatic/Electric
7C - Preaction Double-Interlocked, Electric-Pneumatic/Electric with Added Control Valve
7D - Preaction Single-Interlocked, Pneumatic
7E - Preaction Single-Interlocked, Pneumatic with Added Control Valve
7F - Preaction AutoConvert Double-Interlocked, Pneumatic/Electric
7G - Preaction AutoConvert Double-Interlocked, Pneumatic/Electric with Added Control
FireLock® Fire-Pac for FireLock NXT™ Valves

Valve
7H - Preaction AutoConvert Double-Interlocked, Electric-Pneumatic/Electric
7J - Preaction AutoConvert Double-Interlocked, Electric-Pneumatic/Electric with Added
Control Valve
08 - Preaction, Double-Interlocked Pneumatic/Pneumatic
8A - Preaction, Double-Interlocked Pneumatic/Pneumatic with Added Control Valve
09 - Special #

VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
# Contact Victaulic for pricing and availability @ When ordering the Air Maintenance Trim Assembly along with a compressor, the system must contain a tank (Option 3)
** Valve equipped with an accelerator requires an Air Maintenance Trim Assembly † Requires a Regulated Air Maintenance Trim Assembly (Option 3) with a tank
*** Air Maintenance Trim Assembly without compressor is for use with external, tank-mounted air compressor or shop air †† Applies to 2 ½ - 6-inch/73.0 - 168.3-mm Fire-Pac cabinets only
ˆ Electric Release with panel cross-zoned ††† When the 220-Volt wiring code is specified, the compressor must be ordered as ¾-hp or “None”
I-745

REV_G
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

FIRELOCK FIRE-PAC FIRE ALARM CONTROL PANEL OPTIONS


Option Panel Design Description
A No Panel This option includes a terminal block for wiring connections only.

This option includes the base panel with two 12AH batteries.
The base panel provides the alarm and trouble relays. The
B PDRP-2001 Panel with Two 12-Volt, 12AH Batteries alarm indicates when the valve trips, and the trouble indicates
a technical difficulty (i.e. loss of power, loose wire, etc.). Three
programmable relay contacts are provided for remote signaling.

This option includes option “B,” plus a supervised output for local
C PDRP-2001 Panel with 4XTM energy municipal box transmitter and alarm and trouble reverse
polarity.

D PDRP-2001 Panel with 4XTM/ANN-80 This option includes option “C,” plus a remote LCD annunciator
that mimics the information displayed on the FACP LCD display.

This option includes option “C,” plus an LED driver that can be
E PDRP-2001 Panel with 4XTM/ANN-I/O used as an interface with the FACP to drive most customized
graphic annunciators.

F PDRP-2001 Panel with 4XTM/ANN-RLY-10 This option includes option “C,” plus 10 additional, programmable
Form-C relays.

G PDRP-2001 Panel with 4XTM/ANN-80/ANN-I/O This option combines the features of option “D” and option “E”.

H PDRP-2001 Panel with 4XTM/ANN-80/ANN-RLY-10 This option combines the features of option “D” and option “F”.

I PDRP-2001 Panel with 4XTM/ANN-I/O/ANN-RLY-10 This option combines the features of option “E” and option “F”.

J PDRP-2001 Panel with ANN-80 This option includes option “B,” plus a remote LCD annunciator
that mimics the information displayed on the FACP LCD display.

This option includes option “B,” plus a remote LCD annunciator


K PDRP-2001 Panel with ANN-80/ANN-I/O that mimics the information displayed on the FACP LCD display
and an LED driver that can be used as an interface with the FACP
to drive most customized graphic annunciators.

This option includes option “B,” plus a remote LCD annunciator


L PDRP-2001 Panel with ANN-80/ANN-RLY-10 that mimics the information displayed on the FACP LCD display
and 10 additional, programmable Form-C relays.

M PDRP-2001 Panel with ANN-80/ANN-I/O/ANN-RLY-10 This option includes option “K,” plus 10 additional, programmable
Form-C relays

This option includes option “B,” plus an LED driver that can be
N PDRP-2001 Panel with ANN-I/O used as an interface with the FACP to drive most customized
graphic annunciators.

O PDRP-2001 Panel with ANN-RLY-10 This option includes option “B,” plus 10 additional, programmable
Form-C relays.

P PDRP-2001 Panel with ANN-I/O/ANN-RLY-10 This option combines the features of option “N” and option “O”.

9 Special –

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_G I-745_5
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

INTERNAL VIEW – FIRE-PAC CABINET CONTAINING 1 1/2 – 2-INCH/48.3 – 60.3-MM VALVE SIZES
The front view shown below is of a typical 1 1/2-inch/48.3-mm Series 768 FireLock NXT™ Dry Valve. The brackets for the manual pull station and
pressure gauges, along with brackets for other components, have been removed for clarity.

Electrical
Riser Out Enclosure
to System

Air Compressor*
Air Tank*
Fast-Fill Ball Valve of the Air Slow-Fill Ball Valve of the Air
Maintenance Trim Assembly# Maintenance Trim Assembly#

Air Regulator of the Air


Maintenance Trim Assembly#
Air Tank Bleed Valve
Diaphragm
Pressure Gauge Additional Water Supply
Main Control Valve*
System Air
Pressure Gauge
Air Supervisory
Water Supply Pressure Switch
Pressure Gauge

Water Supply Main


Control Valve

Manual Pull
Station

Connection for
Multi-Unit From Water
Installations Supply ‡

* Optional
# Air Maintenance Trim Assembly is optional To Drain
‡ Can be connected from the left or right side of the cabinet Connection

INTERNAL VIEW – FIRE-PAC CABINET CONTAINING 1 1/2 – 2-INCH/48.3 – 60.3-MM VALVE SIZES
The back view shown below is of a typical 1 1/2-inch/48.3-mm Series 768 FireLock NXT™ Dry Valve. Brackets have been removed for clarity.

Electrical
Enclosure Riser Out to
System

Air Compressor*

Fast-Fill Ball Valve of the Air


Maintenance Trim Assembly#
Air Tank*
Slow-Fill Ball Valve of the Air
Maintenance Trim Assembly#

Air Regulator of the Air


Maintenance Trim Assembly#

Air Tank Bleed Valve


Auto Drain

* Optional
# Air Maintenance Trim
Assembly is Optional

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

I-745_6 REV_G
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

INTERNAL VIEW – FIRE-PAC CABINET CONTAINING 1 1/2 – 2-INCH/48.3 – 60.3-MM VALVE SIZES
The left-side view shown below is of a typical 1 1/2-inch/48.3-mm Series 768 FireLock NXT™ Dry Valve. Brackets have been removed for clarity.

Riser Out to System


Electrical
Enclosure

Air Compressor*

Air Tank* Fire Alarm


Control Panel

Door Handle

System Main Drain Valve


Water Supply Main
Drain Valve

Manual Pull Station

* Optional

INTERNAL VIEW – FIRE-PAC CABINET CONTAINING 1 1/2 – 2-INCH/48.3 – 60.3-MM VALVE SIZES
The right-side view shown below is of a typical 1 1/2-inch/48.3-mm Series 768 FireLock NXT™ Dry Valve. Brackets have been removed for clarity.

Electrical Riser Out to System


Enclosure

Fire Alarm Control Air Tank*


Panel

Air Supervisory Air Tank Bleed Valve


Pressure Switch
Air Manifold

Door Handle

Alarm Pressure Switch

Drip Cup with Cap

Diaphragm-Charge-
Line Ball Valve
Manual Pull Station

* Optional

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_G I-745_7
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

INTERNAL VIEW – FIRE-PAC CABINET CONTAINING 2 1/2 – 6-INCH/73.0 – 168.3-MM VALVE SIZES
The front view shown below is of a typical 6-inch/168.3-mm Series 769 FireLock NXT™ Preaction Valve with Double-Interlocked, Electric/Pneumatic
Release trim. The brackets for the manual pull station and pressure gauges, along with brackets for other components, have been removed for clarity.

Riser Out Electrical


to System Enclosure

Air
Compressor*

Diaphragm
Pressure Gauge Additional Water Supply
Main Control Valve*
System Air
Pressure Gauge Air Tank*

Water Supply
Pressure Gauge Air Supervisory
Pressure Switch
Upper Chamber
Pressure Gauge for System Main
the Series 767 Drain Valve
Electric/Pneumatic Water Supply
Actuator Main Drain Valve

Diaphragm-
Charge-Line
Ball Valve Water Supply Main
Control Valve

Manual Pull
Station

Connection for From Water


Multi-Unit Supply ‡
Installations

* Optional To Drain
‡ Can be connected from the left or right side of the cabinet Connection

INTERNAL VIEW – FIRE-PAC CABINET CONTAINING 2 1/2 – 6-INCH/73.0 – 168.3-MM VALVE SIZES
The back view shown below is of a typical 6-inch/168.3-mm Series 769 FireLock NXT™ Preaction Valve with Double-Interlocked, Electric/Pneumatic
Release trim. Brackets have been removed for clarity.
Electrical
Enclosure
Riser Out to
System

Air Compressor*
Fast-Fill Ball Valve of the Air
Maintenance Trim Assembly#
Air Tank* Slow-Fill Ball Valve of the Air
Maintenance Trim Assembly#
Air Regulator of the Air
Maintenance Trim Assembly#
Air Manifold
Air Tank Bleed
Valve

Alarm Pressure
Switch

Alarm Test Ball Valve


Diaphragm Charge
Line Ball Valve
Drip Cup with Cap

* Optional
# Air Maintenance Trim
Assembly is Optional

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

I-745_8 REV_G
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

INTERNAL VIEW – FIRE-PAC CABINET CONTAINING 2 1/2 – 6-INCH/73.0 – 168.3-MM VALVE SIZES
The left-side view shown below is of a typical 6-inch/168.3-mm Series 769 FireLock NXT™ Preaction Valve with Double-Interlocked, Electric/
Pneumatic Release trim. Brackets have been removed for clarity.
Electrical
Enclosure
Riser Out to System

Air Compressor*

Fire Alarm Control


Panel
Upper Chamber Pressure
Gauge for the Series 767
Electric/Pneumatic Actuator
Door Handle

System Main
Alarm Pressure Switch Drain Valve

Diaphragm-Charge- Water Supply


Line Ball Valve Main Drain Valve

Drip Cup with Cap Alarm Test Ball


Valve

Manual Pull Station

* Optional

INTERNAL VIEW – FIRE-PAC CABINET CONTAINING 2 1/2 – 6-INCH/73.0 – 168.3-MM VALVE SIZES
The right-side view shown below is of a typical 6-inch/168.3-mm Series 769 FireLock NXT™ Preaction Valve with Double-Interlocked, Electric/
Pneumatic Release trim. Brackets have been removed for clarity.
Electrical
Enclosure
Riser Out to
System

Fire Alarm Control


Panel Air Tank*
Air Maintenance
Trim Assembly*
Air Supervisory Air Tank Bleed
Pressure Switch Valve

Door Handle

System Main
Drain Valve Alarm Pressure
Water Supply Switch
Main Drain Valve

Drip Cup
with Cap

Manual Pull Station

* Optional

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_G I-745_9
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

MECHANICAL CONNECTIONS OPENING THE CABINET


Mechanical connections that must be made are the water supply’s inlet,
the system’s outlet, and the drain connection. Refer to the Victaulic
I-100 Field Installation Handbook for proper coupling installation. The
I-100 can be downloaded on the Victaulic website www.victaulic.com.
Internal connections to the valve are made with FireLock grooved pipe
couplings and fittings.
a.) Standard grooved connections for the water supply can be made
from either side of the cabinet.
b.) For Fire-Pac cabinets containing 1 1/2 – 2-inch/48.3 – 60.3-mm
valve sizes, the drain connections are 3/4-inch threaded. Drain
connections can be made from either side of the cabinet.
c.) For Fire-Pac cabinets containing 2 1/2 – 6-inch/73.0 – 168.3-mm
valve sizes, the drain connections are standard grooved. Drain
1. Push the key hole/button to release the handle. Pull up and out
connections can be made from either side of the cabinet.
on the handle to open the cabinet door. Keys are provided on a
d.) A 3-inch/76-mm length of grooved-end pipe is accessible from the keychain to lock the handle, the electrical enclosure, and the Fire
top of the cabinet for connection from the riser out to the system. Alarm Control Panel (FACP) door.

SYSTEM GAUGES AND MANUAL PULL STATION INSPECTION AND MAINTENANCE


1. The panels on the sides and back of the cabinet can be removed
for easy access to all trim components.
2. For required inspection procedures, refer to the installation,
maintenance, and testing manual for the applicable trim
configuration.

Diaphragm Pressure Gauge

System Air Pressure Gauge

Water Supply Pressure Gauge

Manual Pull Station


(Behind This Door)

a.) The diaphragm pressure gauge, system air pressure gauge, water
supply pressure gauge, and manual pull station are located on
front of the cabinet for system operation monitoring.

3. Bleed the valve, located at the bottom of the air tank, once every
three months to remove any moisture from the line.
4. To perform maintenance on any internal valve components (i.e.
replacing the clapper assembly, cover plate gasket, etc.), refer to
the installation, maintenance, and testing manual for the applicable
trim configuration.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

I-745_10 REV_G
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

REMOVING THE COMPRESSOR


WARNING
• Always turn off and lock out the circuit breaker before
attempting to remove the compressor for maintenance.
• Depressurize and drain the piping system before attempting to
perform any maintenance on the system.
• Any activities that require taking the valve out of service may
eliminate the fire protection provided.
• Before servicing the system, notify the authority having
jurisdiction.
• Consideration of a fire patrol should be given in the affected
areas.
Failure to follow these instructions could result in serious personal
injury and/or property damage.

Bracket (Mounted
to Cabinet Frame)

Compressor

4
Bill of Materials
5
Item Qty. Description
1 4 Bolt
2 8 Flat Washer
3 8 Vibration Isolation Mount
4 4 Lock Washer
5 4 Nut

If the compressor needs to be removed from the cabinet, perform the


following steps:
1. Turn off and lock out the circuit breaker.
2. Unplug the compressor’s electrical cord (located on the plate
above the compressor).
3. Disconnect the flexible hose at the compressor.
4. Loosen and remove the four nuts from the compressor.
5. Remove the four bolts/washers, the eight vibration isolation
mounts, and the compressor from the mounting plate.
6. Replace the compressor by re-installing the hardware, as shown in
the drawing above.
7. Plug the compressor’s electrical cord back into the plate above the
compressor.
8. Unlock and turn on the circuit breaker.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_G I-745_11
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

SECTION II - FIRELOCK FIRE-PAC ELECTRICAL


WIRING
• Terminology
• Important Information
• FireLock Fire-Pac Electrical Schematic Reference
• Electrical Enclosure Types
• Supply Power
• Electrical Connections
• Initiating Circuits
• Notification Circuits
• Auxiliary 24 VDC
• Programmable Relays
• 4XTM Option
• ANN-RLY Option
• Field Wiring Diagram

Cabinet for 1 1/2 – 2-inch/


48.3 – 60.3-mm Valve Sizes
Shown Above

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

I-745_12 REV_G
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

TERMINOLOGY b.) For enclosures that contain circuit breakers, the breaker shall be
used as supplemental branch protection. Primary protection shall
The following table contains terminology that will be used throughout
be used when installing the Fire-Pac. Circuit breakers can be used
this section and descriptions for each item.
as a disconnect switch to perform maintenance or replacement
of a device. The operation of each circuit breaker is designed
Item Description to report a breaker that has either tripped or has been operated
manually (except for the enclosure light). For localities that will not
PDRP-2001 (120 Volt) allow supplemental overload protection on the primary fire alarm
Six zone, 24-volt deluge/preaction control
PDRP-2001E (220 Volt) panel for single and dual hazard applications riser, the breakers can be bypassed (please contact Victaulic for
instructions). When any maintenance or work is being performed,
proper lockout/tagout procedures must be followed.
c.) For Fire-Pac cabinets that contain a fire alarm control panel, two
CAC-5X Optional - Used to convert Class “B” style
wiring connections to Class “A” style 12-amp/hour batteries are provided; these batteries are intended
for general use and shall be connected and disconnected only with
primary power supplied to the fire alarm control panel. All battery
Optional - Used to provide a supervised calculations shall be generated in accordance with installation
4XTM output for local energy municipal box requirements. Supplied batteries shall not be used if the battery
transmitter and alarm and trouble reverse
polarity requirement calculations are greater than the capacity of the
supplied batteries (contact Victaulic for additional battery sizes).
Batteries that are greater than 18-amp/hour shall be installed in a
Optional - Remote LCD annunciator that separate, approved enclosure.
ANN-80 mimics the information displayed on the
FACP LCD display d.) Optional modules (4XTM, CAC-5X, etc.) can be configured into
the Fire-Pac when a fire alarm control panel is installed. The
terminal blocks and wiring are the same; therefore, connections
Optional - LED driver module provides for optional modules may be available. DO NOT perform any
ANN-I/O a connection to a user-supplied graphic
annunciator function unless the specific module has been specified during the
ordering process. EXAMPLE: Terminal block TBD has connections
for alarm, trouble, and municipal box. If this option has not been
Optional - Provides 10 programmable Form-C
relays that can be programmed for various ordered, the terminal will not have any function. If an optional
ANN-RLY-10 functions: alarm, trouble, supervisory, AC loss, device is needed at a later time, it can be retrofitted easily into the
waterflow delay, input zones, and silenceable
alarm Fire-Pac using the pre-wired connections. Contact Victaulic for the
required parts and installation instructions.
• FACP - Fire Alarm Control Panel e.) Fire-Pac cabinets that are not provided with a fire alarm control
• LCD - Liquid Crystal Display panel, two terminal blocks are provided for supply power, device
• LED - Light-Emitting Diode supervision, and valve release. All supervisory connections are
• Class “B” - Two-Wire Configuration considered to be “dry” contacts. To use supervisory contacts for
• Class “A” - Four-Wire Configuration functions that require current to flow through the installed devices,
refer to the corresponding device listing, along with the factory wire
IMPORTANT INFORMATION size. Terminal block functions and connections may vary between
Fire-Pac styles and options.
DANGER
f.) For systems without a fire alarm control panel and where a
• Only qualified electricians should connect solenoid coil (Series 753-E Solenoid or Series 767 Electric/
incoming power to the Fire-Pac. Pneumatic Actuator) is used to release or trip a valve, fire alarm
panel compatibility shall be considered to prevent improper valve
Failure to follow this instruction could result in
operation or damage to the fire alarm control panel. Coordination
death or serious personal injury.
shall be made between the authority having jurisdiction (AHJ), fire
alarm panel installer, and the building owner to ensure all system
a.) A separate, keyed electrical enclosure is provided for the installer
devices meet the intent of the work to be performed. Contact
to wire the supply power, initiating devices (such as pull stations
Victaulic for an updated compatibility document.
and detectors), notification devices (such as horns and strobes),
and other auxiliary connections. Two knock-out holes are provided g.) Refer to the following page for a breakdown of electrical
on top of the enclosure to allow for the separation of power- schematics according to trim selection. NOTE: The applicable
limited and non-power-limited wiring. All installation wiring shall schematic is provided in the cabinet.
be performed only in the electrical enclosure by utilizing the top
unwired screw terminals. Fire alarm wiring shall be performed in
accordance with NFPA 72, NFPA 70, and other local regulations.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_G I-745_13
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

FIRELOCK FIRE-PAC ELECTRICAL SCHEMATIC REFERENCE


Electrical Schematic
Trim Selection* Reference Drawing
01 Dry Actuated W-SCHEM-745-050

1A Dry Actuated with Additional Water Supply Main Control Valve W-SCHEM-745-050

02 Dry Actuated with Accelerator W-SCHEM-745-050

2A Dry Actuated with Accelerator and Additional Water Supply Main Control Valve W-SCHEM-745-050

03 Deluge Pneumatic (Dry Pilot) W-SCHEM-745-050

3A Deluge Pneumatic (Dry Pilot) with Additional Water Supply Main Control Valve W-SCHEM-745-050

04 Deluge Electric W-SCHEM-745-000

4A Deluge Electric with Additional Water Supply Main Control Valve W-SCHEM-745-000

05 Preaction Single-Interlocked, Electric W-SCHEM-745-020

5A Preaction Single-Interlocked, Electric with Additional Water Supply Main Control Valve W-SCHEM-745-020

5B Preaction AutoConvert Single-Interlocked, Electric W-SCHEM-745-060

5C Preaction AutoConvert Single-Interlocked, Electric with Additional Water Supply Main Control Valve W-SCHEM-745-060

06 Preaction Double-Interlocked, Electric W-SCHEM-745-020

6A Preaction Double-Interlocked, Electric with Additional Water Supply Main Control Valve W-SCHEM-745-020

6B Preaction AutoConvert Double-Interlocked, Electric W-SCHEM-745-060

6C Preaction AutoConvert Double-Interlocked, Electric with Additional Water Supply Main Control Valve W-SCHEM-745-060

07 Preaction Double-Interlocked, Pneumatic/Electric W-SCHEM-745-020

7A Preaction Double-Interlocked, Pneumatic/Electric with Additional Water Supply Main Control Valve W-SCHEM-745-020

7B Preaction Double-Interlocked, Pneumatic/Electric/Electric W-SCHEM-745-040

7C Preaction Double-Interlocked, Pneumatic/Electric/Electric with Additional Water Supply Main Control Valve W-SCHEM-745-040

7D Preaction Single-Interlocked, Pneumatic W-SCHEM-745-050

7E Preaction Single-Interlocked, Pneumatic with Additional Water Supply Main Control Valve W-SCHEM-745-050

7F Preaction AutoConvert Double-Interlocked, Pneumatic/Electric W-SCHEM-745-060

7G Preaction AutoConvert Double-Interlocked, Pneumatic/Electric with Additional Water Supply Main Control W-SCHEM-745-060
Valve
7H Preaction AutoConvert Double-Interlocked, Electric-Pneumatic/Electric W-SCHEM-745-060

7J Preaction AutoConvert Double-Interlocked, Electric-Pneumatic/Electric with Additional Water Supply Main W-SCHEM-745-060
Control Valve
08 Preaction, Double-Interlocked Pneumatic/Pneumatic W-SCHEM-745-030

8A Preaction, Double-Interlocked Pneumatic/Pneumatic with Additional Water Supply Main Control Valve W-SCHEM-745-030

09 Special –

* This designation corresponds with the “Trim Selection” section of the FireLock Fire-Pac Figure Number System chart on page 4.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

I-745_14 REV_G
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

ELECTRICAL ENCLOSURE TYPES ELECTRICAL CONNECTIONS


With Fire Alarm Control Panel (Optional ANN-RLY Module Shown)
DANGER
• Always de-energize the primary electrical supply
before attempting to make any connections.
Failure to follow this instruction could result in
death or serious personal injury.

Before any connections are made in the Fire-Pac, the primary electrical
supply shall be de-energized, and the proper lockout/tagout procedure
shall be followed. All primary wiring and circuit breakers shall be
sized properly for the application. Refer to Figure 1 and the following
instructions.
Figure 1 - Supply Power Terminal Block
TB1 Input
120 VAC, 60 Hz
L1 N G
Without Fire Alarm Control Panel

1 2 3

SUPPLY POWER Internal


Distribution
Fire-Pac cabinets, that are equipped with a factory-installed compressor
or fire alarm control panel, will have a designated terminal block (TB1)
for the installer to connect 120 VAC. Refer to the current ratings in NOTES:
the tables below to ensure proper circuit protection is provided. The 1. Minimum Wire: 14 AWG, 600 V
2. Max Load = 15.6 A with 1 Hp Compressor
installer is responsible for supplying a dedicated fire alarm circuit with
primary protection to the Fire-Pac that meets NFPA 72, NFPA 70, and 1. Connect the HOT or L1 input voltage wire to Terminal 1 of TB1.
other local regulations. Installed circuit breakers are for supplemental
protection only. 2. Connect the NEUTRAL or N wire to Terminal 2 of TB1.

Table 1 - Compressor Power 3. Connect the GROUND or G wire to Terminal 3 of TB1.


4. Ensure proper torque is applied to terminal screws to secure the
Compressor Size Kw Rating Supply Power
Hp (115 VAC) VAC
wire.
1/6 0.12 110/120-60-1 5. Ensure all non-power-limited wire is at least 1/4 inch/6 mm from
power limited wire.
1/4 0.19 110/120-60-1

1/3 0.25 110/120-60-1

1/2 0.37 110/120-60-1

3/4 0.56 115-60-1

1 0.74 115-60-1

Table 2 - FACP and Enclosure Light


Component Current Draw Rated Power

PDRP-2001 3.66 Amps 120-60-1

Enclosure Light .5 Amp 120-60-1

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_G I-745_15
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

INITIATING CIRCUITS Figure 3 - CAC-5X Class A Wiring


The Fire-Pac is equipped with two alarm initiating circuits that are
supervised for an open, short, or grounded circuit. A 4.7 K ohm end-of-
line resistor performs this function when installed on the last device of +
+ - -
the circuit. Only devices that are listed within the supplied PDRP-2001 + S- + M-
manual shall be connected to these inputs. Maximum loop resistance is
100 ohms with a maximum of 25 detectors per initiating circuit.
a.) Two Class B (2-wire) connections are standard with the Fire-Pac. + - + -
“Zone 1B” and “Zone 2B” are designated as alarm initiating inputs + S- + M-
on the Fire-Pac. Zone connections on terminal block TBA are
broken down to two connections (positive and negative). These
TBA
connection points are configured to initiate an alarm condition on + - + - + - + -
the fire alarm control panel when shorted or closed. “Zone 2B”
on TBA performs the same function as “Zone 1A”, although it is
pre-programmed as a manual pull station input. Devices, including
smoke and heat detectors, pull stations, or any other approved Zone 1B Zone 2B Zone 1A Zone 2A
initiating device, would be connected to these inputs. Refer to
Figure 2 and the following instructions. 1. Connect the positive terminal of Zone XB to the positive terminal
of the device, then connect the positive terminal of Zone XA to the
Figure 2 - Class B Wire Example
positive terminal of the device.
4.7K 4.7K
2. Connect the negative terminal of Zone XB to the negative terminal
S M of the device, then connect the negative terminal of Zone XA to the
negative terminal of the device.
3. Before landing wires on the terminal block, check the circuit for
integrity (open, short, loop resistance, etc.).
S M
4. No 4.7 K ohm resistor is needed for Class A wiring.

NOTIFICATION CIRCUITS
Three supervised Class B notification devices can be connected to
TBA the Fire-Pac. Alarm, trouble, and supervisory conditions will report as
separate signal on terminal block TBA. Each output can have a 3-amp
maximum current draw, and at no time can the DC output exceed 7
amps. Refer to the PDRP-2001 Device Compatibility Appendix for listed
devices that can be connected to these outputs. Refer to Figure 4 and
Zone 1B Zone 2B the following instructions.
1. Install and wire all field devices with a 4.7 K ohm resistor on the Figure 4 - Notification Circuit
end device.
2. Before landing wires on the terminal block, check the circuit for
integrity (open, short, loop resistance, etc.). H H H
3. Land wires to the appropriate connection point on TBA (+/-).
4. Unused inputs shall be terminated with 4.7 K ohm resistors across
terminals. Strobe Strobe Strobe

b.) If the optional CAC-5X module is installed, Class A wiring is


supported. To connect a Class A wired device, connections
on “Zone 1B” and “Zone 1A” on terminal block TBA would be
made. Refer to Figure 3 and the following instructions. The same TBA
connections would apply to the second initiating input circuit;
however, the connection would be made on “Zone 2B” and “Zone
2A”. No end-of-line resistor is used on this class of wiring.

Alarm Supervise Trouble

1. Install and wire the notification devices with properly-sized


conductors.
2. Place a 4.7 K ohm end-of-line resistor on the last device.
3. Before landing wires on the terminal block, check the circuit for
integrity (open, short, loop resistance, etc.).
4. Unused outputs shall be terminated with 4.7 K ohm resistors.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

I-745_16 REV_G
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

AUXILIARY 24 VDC ANN-RLY OPTION


Terminal block TBB contains two separate 24-volt connections for four- The ANN-RLY option provides 10 programmable Form C relay contacts
wire smoke detectors or any other special application. The “RST24V” rated at 2.0 amps @ 30 VDC (resistive) and .5 amp @ 30 VAC
connection on TBB provides 500mA of resettable power to field devices (resistive). This module is factory installed in the top electrical enclosure
(24-volt loss when rest is depressed on the fire alarm control panel). and is wired to the fire alarm control panel. Connection to this module
The “RST24V” point provides a constant 500mA that can be configured is performed directly on the circuit board in accordance with the PDRP-
as a resettable point by moving JP31 on the PDRP-2001. Refer to the 2001 manual. Refer to Figure 6.
PDRP-2001 manual for details. Figure 6 - ANN-RLY Connections
PROGRAMMABLE RELAYS ON
SW1
OFF
Terminal block TBC contains contacts for three Form-C relays that are
factory programmed for alarm, supervisory, and trouble conditions.
Refer to Figure 5 for details. Each relay is rated for 2 amps @ 30 VDC C
(resistive) and .5 amp @ 30 VAC (resistive). Relay function can be
R1 NC ALARM
modified through the programming function of the fire alarm control
panel. NO

TB2
Figure 5 - Standard Relay Contacts C

R2 NC TROUBLE
TBC NO

Trouble C
Alarm (Fail Safe) Super
R3 NC SUPERVISORY
NO
TB4
C

R4 NC IN ZONE 1
NO

R5 NC IN ZONE 2
NO
TB5

R6 NC IN ZONE 3
4XTM OPTION NO

The 4XTM option provides a supervised output for a local municipal box C

transmitter in addition to alarm and trouble reverse polarity. The module R7 NC IN ZONE 4
is wired to terminal block TBD, which contains connections for remote NO
alarm, remote trouble, and municipal box. All outputs are non-power-
TB3

C
limited and can be disabled with a disconnect switch located on the
4XTM module. R8 NC IN ZONE 5
NO

R9 NC IN ZONE 6
NO
TB6

R10 NC DISCHARGE
NO

TB1 - RELAY MODULE


ANN-BUS
- + A B

OPTIONAL ANN-RLY
RELAY MODULE
TB3 - FACP PANEL
389
B
390
A
ANN-BUS
391
+
392
-

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_G I-745_17
Field Wiring Diagram

I-745_18
S = Smoke Detector Strobe = Visual Notification
M = Manual Pull Station = Normally-Open Switch Contact
H = Audible Notification

NOTES:
1. This diagram is a general overview of a typical
Fire-Pac. Refer to the Installation, Maintenance,
and Testing manual for the specific system.
2. Refer to the Fire-Pac Installation, Maintenance,
Testing, and Wiring Manual and the manual for
the Fire Alarm Control Panel for specific
installation instructions.
* Equipment cannot be installed. These devices
are specific to the type of Fire-Pac ordered and is
considered optional hardware.
** Tamper switch is located under each pressure
switch for the ULC version ONLY.
*** No end-of-line resistor (EOLR) is needed
when using the Class A module.

REV_G
NOTES

REV_G I-745_19
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

SECTION III - FIRELOCK FIRE-PAC


PROGRAMMING
• Programming Matrix for Drawing SCHEM-745-000
(Trim Selection 04)
• Programming Matrix for Drawing SCHEM-745-020
(Trim Selections 05, 06, and 07)
• Programming Matrix for Drawings SCHEM-745-030 and
SCHEM-745-050 (Trim Selections 08, 01, and 02)

Cabinet for 1 1/2 – 2-inch/


48.3 – 60.3-mm Valve Sizes
Shown Above

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

I-745_20 REV_G
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

PROGRAMMING MATRIX FOR DRAWING INPUT ZONES


SCHEM-745-000 (TRIM SELECTION 04) 1) Select 2= INPUT ZONES
2) Select 1=ZONE 1
SYSTEM SET UP 3) Go to EDIT mode and set the following
1) Enter programming mode 1=ENABLED
2) Down arrow to 3= SYSTEM SETUP 2=TYPE 2-WIRE SMOKE
3) Select 3=BANNER 3=OUTPUT CIRCUIT MAP
4) Select 2=USER 1=ALARM NAC YES
5) Type “(5 Spaces)FIRE-PAC” 2=RELEASE 1 YES
6) Return to SYSTEM SETUP 4) Return to INPUT ZONES
7) Select 2=TIMERS 5) Select 2=ZONE 2
8) Select 1=SOAK 1 6) Go to EDIT mode and set the following
9) Select 1=ALWAYS ON 1=ENABLED
10) Return to main menu PROGRAMMING 2=TYPE PULL STATION
3=OUTPUT CIRCUIT MAP
OUTPUT CIRCUITS 1=ALARM NAC YES

1) Select 3=OUTPUT CIRCUITS 2=RELEASE 1 YES

2) Select 1=OUTPUT 1 7) Return to INPUT ZONES

3) Set to the following 8) Select 3=ZONE 3

1=ENABLED YES 9) Go to EDIT mode and set the following

2=TYPE ALARM NAC 1=ENABLED

4) Return to OUTPUT CIRCUITS 2=TYPE WATERFLOW

5) Select 2=OUTPUT 2 3=OUTPUT CIRCUIT MAP

6) Set to the following 1=ALARM NAC YES

1=ENABLED YES 2=RELEASE 1 NO

2=TYPE RELEASE CIR 1 UPSUPV SHORTS 10) Return to INPUT ZONES, Press 

7) Return to OUTPUT CIRCUITS 11) Select 1=ZONE 4 (ZONE Not Wired)

8) Select 3=OUTPUT 3 12) Go to EDIT mode and set the following

9) Set to the following 1=ENABLED

1=ENABLED YES 2= TYPE SUPERVSRY AR

2=TYPE SUPV BELL NAC 3=OUTPUT CIRCUIT MAP

10) Return to OUTPUT CIRCUITS, Press  13) Return to INPUT ZONES, Press 

11) Select 1=OUTPUT 4 14) * Select 2=ZONE 5 (ZONE Not Wired)

12) Set to the following 15) Go to EDIT mode and set the following

1=ENABLED YES 1=ENABLED

2=TYPE TROUBLE BELL NAC 2=TYPE SUPERVSRY AR

13) Return to main menu PROGRAMMING 3=OUTPUT CIRCUIT MAP


16) Press  , 2=DESCRIPTION
17) Type “PS COVER”
18) Return to INPUT ZONES, Press 
19) Select 3=ZONE 6
20) Go to EDIT mode and set the following
1=ENABLED
2=TYPE SUPERVSRY AR
3=OUTPUT CIRCUIT MAP
21) Press  , 2=DESCRIPTION
*Note: ULC option only 22) Type “WATER VALVE OFF”

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_G I-745_21
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

PROGRAMMING MATRIX FOR DRAWING 4) Return to INPUT ZONES


SCHEM-745-020 (TRIM SELECTIONS 5) Select 2=ZONE 2
05, 06, AND 07) 6) Go to EDIT mode and Set the following
1=ENABLED
SYSTEM SET UP
2=TYPE PULL STATION
1) Enter programming mode
3=OUTPUT CIRCUIT MAP
2) Down arrow to 3= SYSTEM SETUP
1=ALARM NAC YES
3) Select 3=BANNER
2=RELEASE 1 YES
4) Select 2=USER
7) Return to INPUT ZONES
5) Type “(5 Spaces)FIRE-PAC”
8) Select 3=ZONE 3
6) Return to SYSTEM SETUP
9) Go to EDIT mode and set the following
7) Select 2=TIMERS
1=ENABLED
8) Select 1=SOAK 1
2=TYPE WATERFLOW
9) Select 1=ALWAYS ON
3=OUTPUT CIRCUIT MAP
10) Return to main menu PROGRAMMING
1=ALARM NAC YES
OUTPUT CIRCUITS 2=RELEASE 1 NO

1) Select 3=OUTPUT CIRCUITS 10) Return to INPUT ZONES, Press 

2) Select 1=OUTPUT 1 11) Select 1=ZONE 4 (For Trim Selections 7B and 7C, go to step “A”
on the following page)
3) Set to the following
12) Go to EDIT mode and set the following
1=ENABLED YES
1=ENABLED
2=TYPE ALARM NAC
2=SUPERVISORY AR
4) Return to OUTPUT CIRCUITS
3=OUTPUT CIRCUIT MAP
5) Select 2=OUTPUT 2
13) Go to 2=DESCRIPTION
6) Set to the following
14) Type “LOW/HIGH AIR”
1=ENABLED YES
15) Return to INPUT ZONES, Press 
2=TYPE RELEASE CIR 1 UPSUPV SHORTS
16) * Select 2=ZONE 5
7) Return to OUTPUT CIRCUITS
17) Go to EDIT mode and set the following
8) Select 3=OUTPUT 3
1=ENABLED
9) Set to the following
2=TYPE SUPERVSRY AR
1=ENABLED YES
3=OUTPUT CIRCUIT MAP
2=TYPE SUPV BELL NAC
18) Press  , 2=DESCRIPTION
10) Return to OUTPUT CIRCUITS, Press 
19) Type “PS COVER”
11) Select 1=OUTPUT 4
20) Return to INPUT ZONES, Press 
12) Set to the following
21) Select 3=ZONE 6
1=ENABLED YES
22) Go to EDIT mode and Set the following
2=TYPE TROUBLE BELL NAC
1=ENABLED
13) Return to main menu PROGRAMMING
2=TYPE SUPERVSRY AR
INPUT ZONES 3=OUTPUT CIRCUIT MAP
1) Select 2= INPUT ZONES 23) Press  , 2=DESCRIPTION
2) Select 1=ZONE 1 24) Type “WATER/AIR COMP OFF”
3) Go to EDIT mode and set the following 25) Return to PROGRAMMING
1=ENABLED 26) For Trim Selection 6B (Double-Interlocked, Electric), go to step “B”
on the following page.
2=TYPE 2-WIRE SMOKE
3=OUTPUT CIRCUIT MAP
1=ALARM NAC YES
2=RELEASE 1 YES *Note: ULC option only

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

I-745_22 REV_G
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

A. DOUBLE-INTERLOCKED, ELECTRIC-PNEUMATIC/ELECTRIC
(TRIM SELECTIONS 7B AND 7C)
1) Follow to step 11 on the previous page
2) Go to EDIT mode and set the following
1=ENABLED
2=TYPE COMBO SUP AR
3=OUTPUT CIRCUIT MAP
1=ALARM NAC YES
2=RELEASE 1 YES
3) Go to 2=DESCRIPTION
4) Type “LOW/HIGH AIR”

CROSS-ZONED
1) Select 1=CROSS INPUT ZONES
2) Select 1=RELEASE 1 GROUPS
3) Select 1=NONE
4) 1=ZONE 1 YES
5) Press 
6) 1=ZONE 4 YES
7) ESC to REL 1 CROSS GROUPS
1= X 1 4
2= NONE
8) Select 2=NONE
9) Select ZONE 2 and 4
10) ESC to REL 1 CROSS GROUPS (Confirm Setting)
1= X 1 4
2= X 2 4
11) Return to step 15 on the previous page

B. DOUBLE-INTERLOCKED, ELECTRIC (TRIM SELECTION 6B)


1) Select 1=CROSS INPUT ZONES
2) Select 1=RELEASE 1 GROUPS
3) Select 1=NONE
4) 1=ZONE 1 YES
5) 2=ZONE 2 YES
6) ESC to REL 1 CROSS GROUPS
1= X 1 2
2= NONE

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_G I-745_23
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

PROGRAMMING MATRIX FOR DRAWINGS 6) Go to EDIT mode and set the following
SCHEM-745-030 AND SCHEM-745-050 1=ENABLED
(TRIM SELECTIONS 08, 01, AND 02) 2=TYPE PULL STATION
3=OUTPUT CIRCUIT MAP
SYSTEM SET UP 1=ALARM NAC YES

1) Enter programming mode 2=WATERFLOW NAC NO

2) Down arrow to 3=SYSTEM SETUP 7) Return to INPUT ZONES

3) Select 3=BANNER 8) Select 3=ZONE 3

4) Select 2=USER 9) Go to EDIT mode and set the following

5) Type “(5 Spaces)FIRE-PAC” 1=ENABLED

6) Return to main menu PROGRAMMING 2=TYPE WATERFLOW


3=OUTPUT CIRCUIT MAP

OUTPUT CIRCUITS 1=ALARM NAC YES


2=WATERFLOW NAC NO
1) Select 3=OUTPUT CIRCUITS
10) Return to INPUT ZONES, Press 
2) Select 1=OUTPUT 1
11) Select 1=ZONE 4
3) Set to the following
12) Go to EDIT mode and set the following
1=ENABLED YES
1=ENABLED
2=TYPE ALARM NAC
2=TYPE SUPERVSRY AR
4) Return to OUTPUT CIRCUITS
3=OUTPUT CIRCUIT MAP
5) Select 2=OUTPUT 2 (Not Wired)
13) Go to 2=DESCRIPTION
6) Set to the following
14) Type “LOW/HIGH AIR”
1=ENABLED YES
15) Return to INPUT ZONES, Press 
2=TYPE WATERFLOW NAC
16) * Select 2=ZONE 5
7) Return to OUTPUT CIRCUITS
17) Go to EDIT mode and set the following
8) Select 3=OUTPUT 3
1=ENABLED
9) Set to the following
2=TYPE SUPERVSRY AR
1=ENABLED YES
3=OUTPUT CIRCUIT MAP
2=TYPE SUPV BELL NAC
18) Press  , 2=DESCRIPTION
10) Return to OUTPUT CIRCUITS, Press 
19) Type “PS COVER”
11) Select 1=OUTPUT 4
20) Return to INPUT ZONES, Press 
12) Set to the following
21) Select 3=ZONE 6
1=ENABLED YES
22) Go to EDIT mode and set the following
2=TYPE TROUBLE BELL NAC
1=ENABLED
13) Return to main menu PROGRAMMING
2=TYPE SUPERVSRY AR
3=OUTPUT CIRCUIT MAP
INPUT ZONES
23) Press  , 2=DESCRIPTION
1) Select 2= INPUT ZONES
24) Type “WATER/AIR COMP OFF”
2) Select 1=ZONE 1
25) PRESS “ESC”, save settings
3) Go to EDIT mode and set the following
1=ENABLED
2=TYPE 2-WIRE SMOKE
3=OUTPUT CIRCUIT MAP
1=ALARM NAC YES
2=WATERFLOW NAC NO
4) Return to INPUT ZONES
5) Select 2=ZONE 2
*Note: ULC option only

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

I-745_24 REV_G
NOTES

REV_G I-745_25
INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL I-745
FireLock® Fire-Pac for FireLock NXT™ Valves
SERIES 745

For complete contact information, visit www.victaulic.com


I-745 3227 REV G UPDATED 06/2010 Z000745002