Download as pdf or txt
Download as pdf or txt
You are on page 1of 36

Instruction book for stationary compressors

ZT18-ZT22-ZT30-ZT37-ZT45-ZT55-
ZT75-ZT90
ZR45-ZR55-ZR75-ZR90
with Elektronikon® regulator

Important

1. This book applies exclusively to the above-mentioned compressors equipped with an


electronic regulator as shown below.

2. This book must be used together with the "User manual for Elektronikon® regulator",
printed matter No. 2920 1291 0x.

F2536

Registration code This instruction book meets the requirements for instructions specified by the
Collection: APC Z ≤ 90 machinery directive 89/392/EEC and is valid for CE as well as non-CE labelled
Tab: 38
Sequence: 992
machines

Oil-free Air Division - B-2610 Wilrijk - Belgium

No. 2920 1326 00

1996-01 *2920132600*
Oil-free Air Division Instruction book

This instruction book describes how to handle and operate the subject machine(s) to ensure safe operation, optimum working economy and
long service life.

Read this book before putting the machine into operation to ensure correct handling, operation and proper maintenance from the
beginning. The maintenance schedule comprises measures for keeping the compressor in good repair.

Keep the book available for the operator(s) and make sure that the compressor is operated and that maintenance is carried out according to
the instructions. Record all operating data, maintenance work effected, etc. in an operator's logbook available from Atlas Copco. Follow all
applicable safety precautions, amongst others those mentioned in this book.

Repairs must be carried out by trained personnel from Atlas Copco who can also be contacted for any further information.

In all correspondence mention the type and the serial number, shown on the data plate.

The company reserves the right to make changes without prior notice.

CONTENTS
Page Page
1 Leading particulars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 4.4 Storage after installation . . . . . . . . . . . . . . . . . . . . . . . 29
1.1 General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 4.5 Service kit numbers for filters . . . . . . . . . . . . . . . . . . . . 29
1.2 Electrical system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2.1 Electronic regulator . . . . . . . . . . . . . . . . . . . . . . 7 5 Servicing procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
1.2.2 Control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 5.1 Air filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.2 Oil and oil filter change . . . . . . . . . . . . . . . . . . . . . . . . . 29
2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 5.3 Safety valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.1 Dimension drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 5.4 Coolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.2 Installation proposals . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.3 Electric cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 6 Problem solving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.3.1 Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.3.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 7 Principal data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2.4 Cooling water requirements . . . . . . . . . . . . . . . . . . . . . 21 7.1 Readings on display . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2.5 Pictographs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 7.2 Programmable settings . . . . . . . . . . . . . . . . . . . . . . . . 31
7.3 Settings of safety valves . . . . . . . . . . . . . . . . . . . . . . . 31
3 Operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 7.4 Motor type - settings of overload relay and circuit
3.1 Preparation for initial start-up . . . . . . . . . . . . . . . . . . . . 21 breaker - main fuses . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.2 Compressor control modes . . . . . . . . . . . . . . . . . . . . . 24 7.4.1 Motor type - settings of motor overload relay -
3.3 Before starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 main fuses for 50 Hz compressors . . . . . . . . . 32
3.4 Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 7.4.2 Motor type - settings of motor overload relay -
3.4.1 Routine starting . . . . . . . . . . . . . . . . . . . . . . . . 24 main fuses for 60 Hz compressors
3.4.2 Starting after emergency stopping or (Y/D starter) . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
shut-down . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 7.4.3 Setting of fan motor circuit breaker for 50 Hz
3.4.3 Manual restarting . . . . . . . . . . . . . . . . . . . . . . . 25 compressors . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.5 During operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 7.4.4 Setting of fan motor circuit breaker for 60 Hz
3.5.1 Checking the display . . . . . . . . . . . . . . . . . . . . 25 compressors . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.6 Manual control of compressor operation . . . . . . . . . . . 26 7.5 Compressor specifications . . . . . . . . . . . . . . . . . . . . . . 34
3.6.1 Manual unloading . . . . . . . . . . . . . . . . . . . . . . . 26 7.5.1 Reference conditions . . . . . . . . . . . . . . . . . . . . 34
3.6.2 Manual loading . . . . . . . . . . . . . . . . . . . . . . . . . 26 7.5.2 Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.7 Stopping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 7.5.3 Specific data of ZT/ZR18/55 7.5 bar - 50 Hz . . 34
3.8 Taking out of operation . . . . . . . . . . . . . . . . . . . . . . . . . 26 7.5.4 Specific data of ZT/ZR18/55 8.6 bar - 50 Hz . . 34
7.5.5 Specific data of ZT/ZR18/55 7.5 bar - 60 Hz . . 35
4 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 7.5.6 Specific data of ZT/ZR18/55 8.6 bar - 60 Hz . . 35
4.1 Preventive maintenance schedule for the 7.5.7 Specific data of ZT/ZR75/90 8 bar - 50 Hz . . . 35
compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 7.5.8 Specific data of ZR75/90 10 bar - 50/60 Hz . . 36
4.2 Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 7.5.9 Specific data of ZT/ZR75/90 7.5 bar - 60 Hz . . 36
4.2.1 Fan motor bearings . . . . . . . . . . . . . . . . . . . . . 29 7.5.10 Specific data of ZT/ZR75/90 8.6 bar - 60 Hz . . 36
4.2.2 Compressor motor greasing . . . . . . . . . . . . . . 29 7.6 Conversion list of SI units into British/American units . 36
4.3 Oil specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

2 2920 1326 00
Instruction book Oil-free Air Division

1 LEADING PAR
PAR TICULARS
ARTICULARS The compressors are available in following pressure variants:

1.1 General description Type Frequency Maximum working pressure


Hz bar(e)
ZT18 up to ZT55, ZR45 and ZR55 are two-stage tooth compressors.
ZT75, ZT90, ZR75 and ZR90 are two-stage screw compressors. The
compressors are electric motor driven and deliver oil-free, pulsation- ZT18 50 or 60 7.5 or 8.6
free air. ZT are air-cooled, whereas ZR are water-cooled. ZT22 50 or 60 7.5 or 8.6
ZT30 50 or 60 7.5 or 8.6
ZT37 50 or 60 7.5 or 8.6
ZT/ZR45 50 or 60 7.5 or 8.6
ZT/ZR55 50 or 60 7.5 or 8.6

ZT75/90 50 8
ZT75/90 60 7.5 or 8.6
ZR75/90 50 8 or 10
ZR75/90 60 7.5, 8.6 or 10

AF. Air filter


AS. Air silencer
AV. Air outlet valve
BR. Breather
Ca. Aftercooler
Ci. Intercooler
Co. Oil cooler
CV. Check valve
Dmo. Oil drain valve
Eh. High-pressure compressor
element
El. Low-pressure compressor
element
FC. Oil filler plug
FN. Cooling fan
M1. Compressor motor
M2. Fan motor
MTa. Moisture trap, aftercooler
OF. Oil filter
SG. Oil level sight-glass
SVh. High-pressure safety valve
TV. Full-load/no-load valve
VI. Air filter service indicator
Y1. Loading solenoid valve
1. Elektronikon® regulator
2. Door, access to coolers
3. Transport bolt
4. Vibration damper, compressor
5. Electric cabinet
6. Vibration damper, motor

Fig. 1. ZT37

2920 1326 00 3
Oil-free Air Division Instruction book

Fig. 2. ZT45

AF. Air filter Eh. High-pressure compressor element SVh. High-pressure safety valve
AS. Air silencer El. Low-pressure compressor element SVl. Low-pressure safety valve
BR. Breather FC. Oil filler plug TV. Full-load/no-load valve
Ca. Aftercooler M1. Compressor motor Y1. Loading solenoid valve
Ci. Intercooler MTa. Moisture trap, aftercooler 1. Elektronikon® regulator
Co. Oil cooler MTi. Moisture trap, intercooler 2. Electric cabinet
CV. Check valve PD. Pulsation damper 3. Transport bolt
Dmo. Oil drain valve SG. Oil level sight-glass 4. Flange, pulsation damper

Figs. 2 and 3. ZT45 and ZR55

4 2920 1326 00
Instruction book Oil-free Air Division

Fig. 3. ZR55

The compressors are enclosed in a sound-insulated bodywork and 1.2 Electrical system
include mainly:
- Air filter The system includes mainly:
- Low-pressure compressor element 1. Compressor motor (M1-Fig. 1)
- Intercooler 2. Elektronikon® control system including an electronic regulator and
- High-pressure compressor element a control panel (Fig. 7)
- Aftercooler 3. Pressure and temperature sensors
- Electric motor 4. Electric cabinet (Fig. 10) including the starting equipment of the
- Drive coupling motor
- Gear casing
- Elektronikon® control system
- Safety valves

2920 1326 00 5
Oil-free Air Division Instruction book

Fig. 4. ZT75

AF. Air filter FN. Cooling fan Vfi. Regulating valve, intercooler cooling
AV. Air outlet valve M1. Compressor motor water flow
Ca. Aftercooler M2. Fan motor Y1. Loading solenoid valve
Ci. Intercooler MTa. Moisture trap, aftercooler 1. Elektronikon® regulator
Co. Oil cooler MTi. Moisture trap, intercooler 2. Electric cabinet
Dmo. Oil drain valve OF. Oil filter 3. Transport bolt
DPo. Oil drain plug SG. Oil level sight-glass 4. Vibration damper, compressor
Eh. High-pressure compressor element SVh. High-pressure safety valve 5. Door, access to coolers
El. Low-pressure compressor element TV. Full-load/no-load valve 6. Flange, intercooler moisture trap
FC. Oil filler plug Vfa. Regulating valve, aftercooler cooling
water flow

Figs. 4 and 5. ZT75 and ZR90

6 2920 1326 00
Instruction book Oil-free Air Division

Fig. 5. ZR90

1.2.1 Electronic regulator (Fig. 7) arning


War ning
A number of time-based automatic start/stop commands may be
The regulator has following functions: programmed 1) 1). Take into account that a start command will be
executed (if programmed and activated), even after manually
stopping the compressor.
1.2.1.1 Automatic control of compressor operation
1.2.1.2 Protecting the compressor
The regulator maintains the net pressure between programmable limits
by automatically loading and unloading the compressor. A number of Shut-down
programmable settings, e.g. the unloading and loading pressures, The compressor will be shut down if:
the minimum stop time and the maximum number of motor starts are - the motor current exceeds the permissible maximum
taken into account. - the air outlet temperature of the low- or high-pressure compressor
element exceeds the pre-set value
The regulator stops the compressor whenever possible to reduce the - the air inlet temperature of the high-pressure compressor element
power consumption and restarts it automatically when the net pressure exceeds the pre-set value
decreases. In case the expected unloading period is too short, the - the oil pressure drops below the pre-set value
compressor is kept running to prevent too-short standstill periods.
1) This function is called the Timer function. See "User manual for
Elektronikon® regulator", section "Timer submenu".

2920 1326 00 7
Oil-free Air Division Instruction book

M1. Compressor motor


M2. Fan motor (ZT18/37 and ZT75/90 only)

Fig. 6. Electrical connections (typical example)

8 2920 1326 00
Instruction book Oil-free Air Division

Remedy the trouble and reset the message on display (4-Fig. 7) 1.2.1.5 External compressor status indication
before restarting. See "User manual for Elektronikon® regulator",
section "Status data submenu". The regulator is provided with auxiliary contacts (K05, K06, K07 and
K08) at the back of the module for external indication of:
Shut-down warning - low or high air pressure (K05)
Before any shut-down level is reached, except for the motor overload, - manual load/unload or automatic operation (K06)
a message will appear on display (4-Fig. 7) and general alarm LED - warning condition (K07)
(3) will light up, to warn the operator that the shut-down warning level - shut-down condition (K08)
is exceeded. The shut-down warning level is a programmable setting
below the shut-down level. Maximum load for these contacts: 1 A / 250 V AC. Stop the compressor
and switch off the voltage before connecting external equipment.
The message disappears as soon as the cause of the trouble is Consult Atlas Copco.
remedied.

1.2.2 Control panel (Fig. 7)


1.2.1.3 Monitoring components subject to service

The regulator continuously monitors the oil, motor grease, oil filter Indicators, keys and buttons
and air filter. Each input is compared to programmed time intervals
or pressure drops. If these limits are exceeded, a message will appear
1 Automatic operation LED
on display (4) to warn the operator to replace the indicated component,
Indicates that the electronic regulator is automatically
to change the oil or to grease the motor as the case may be.
controlling the compressor: the compressor is loaded,
unloaded, stopped and restarted depending on the air
consumption and the limitations programmed in the regulator.
1.2.1.4 Automatic restart after voltage failure
2 Voltage on LED
For compressors leaving the factory, this function is made inactive. If Indicates that the voltage is switched on.
desired, the function can be activated. Consult Atlas Copco.
3 General alarm LED
arning
War ning Is alight if a shut-down warning condition exists. See section
If activated and provided the regulator was in the automatic 1.2.1.
operation mode and the compressor control mode (local, remote
1 or remote 2 - see section 3.2) was not changed during the voltage Blinks if a shut-down condition exists, if a sensor used to
failure, the compressor will automatically restart if the supply protect the compressor is out of order or after an emergency
voltage to the module is restored within a programmed time period stop. See section 1.2.1.
(this time period is called the power recovery time
time).

Fig. 7. Control panel

2920 1326 00 9
Oil-free Air Division Instruction book

Fig. 7. Control panel

Selecting a menu
Indicators, keys and buttons
To facilitate controlling the compressor, menu-driven programs are
implemented in the electronic regulator. Use the function keys (5) to
4 Display select the menus in order to program and monitor the compressor.
Indicates messages concerning the compressor operating The "User manual for Elektronikon® regulator" deals elaborately with
condition, a service need or a fault. See "User manual for all regulator functions.
Elektronikon® regulator", sections "Status data submenu" and
"Service submenu". Function keys
The functions of the keys vary depending on the displayed menu.
5 Function keys The actual function is indicated just above the relevant key. The
Keys to control and program the compressor. See below. most common functions are listed below:

6 Scroll keys
Keys to scroll through the display. Designation Function

7 Tabulator key
Key to go to the next field of the display. Add To add compressor start/stop commands (day/hour)
Cancel To cancel a programmed setting when programming
8 Start button parameters
Push button to start the compressor. LED (1) lights up Delete To delete compressor start/stop commands
indicating that the electronic regulator is operative (in Limits To show limits for a programmable setting
automatic operation). The LED goes out after unloading the List To list programmed start/stop commands (day/hour)
compressor manually. Load To load the compressor manually
9 Stop button Main Screen To return from a menu to the main display (Fig. 8)
Push button to stop the compressor. LED (1) goes out. The Menu Starting from the main display (Fig. 8), to initiate the
compressor will run unloaded for 3 seconds before stopping. main menu (Fig. 9) which gives access to submenus
Starting from a submenu, to return to the main menu
S2 Emergency stop button (Fig. 9)
Push button to stop the compressor immediately in case of Modify To modify programmable settings
emergency. After remedying the trouble, unlock the button Show More To have a quick look at the compressor status
by turning it anti-clockwise. Program To program modified settings
Reset To reset a timer or message
S5 Control mode switch Return To return to a previously shown option or menu
Key switch to select the compressor control modes. See Select To select a submenu or to read more details of a
section 3.2. selection shown on the display
Unload To unload the compressor manually

10 2920 1326 00
Instruction book Oil-free Air Division

Compressor outlet 7.5 bar


Oil 2.1 bar Status data
Automatically Loaded ↓
Menu Show More Unload Main Screen Select
F1 F2 F3 F1 F2 F3

Fig. 8. Example of the main display Fig. 9. Example of a main menu

F1/2. Fuses K23. Delta contactor T1/T2. Transformers


F3/5. Circuit breakers L1/3. Terminal, mains connection 1X1/3. Terminal strips
F21. Compressor motor overload relay PE. Earth terminal 1. Label, torques
K21. Line contactor Q25. Fan motor circuit breaker (ZT18/37
K22. Star contactor and ZT75/90 only)

Fig. 10. Electric cabinet (typical example)

2920 1326 00 11
Oil-free Air Division Instruction book

2 INSTALLA
INSTALLATION
ALLATION
2.1 Dimension dr
draa wings (Figs
(Figs.. 11)

Fig. 11a. Dimension


drawing, ZT18/37

Fig. 11b. Dimension


drawing, ZT45/55

12 2920 1326 00
Instruction book Oil-free Air Division

Fig. 11c. Dimension


drawing, ZR45/55

Fig. 11d. Dimension


drawing, ZT75/90

2920 1326 00 13
Oil-free Air Division Instruction book

Fig. 11e. Dimension


drawing, ZR75/90

2.2 Installation proposals (Figs. 12)

Ref. Description

1. Install the compressor on a level floor suitable for taking the P = the absolute pressure at the compressor outlet
weight of the compressor. Recommended minimum in bar(a)
distance between the top of the bodywork and the ceiling: Qc = free air delivery of the compressor in l/s
1200 mm (except for ventilation proposals 2 and 3).
As a rule of thumb, following formula can be used to
2. Fit the air outlet valve (AV-Figs. 1 up to 5). Close the valve calculate the recommended volume of the air net:
and connect it to the air net.
30 x C x p x Q
3. The maximum total length of the delivery pipe can be V = ________________________

calculated as follows: ∆P

∆P x d5 x P
_________________________
L = V = recommended air net volume in l
450 x Qc1.85 ∆P = pressure difference between unloading and
loading pressures in bar (recommended
L = length of delivery pipe in m minimum = 0.5)
∆P = the maximum allowable pressure drop p = compressor inlet pressure in bar absolute
(recommended 0.1 bar) Q = free air delivery of compressor in l/s
d = inner diameter of the delivery pipe in mm C = correction factor, see below

14 2920 1326 00
Instruction book Oil-free Air Division

Fig. 12a. Installation proposal, ZT18/37

Correction factor C

Air consumption divided by C Example: air consumption = 130 l/s


compressor air delivery compressor air delivery = 180 l/s
inlet pressure = 1 bar absolute
0.9 0.10 unloading pressure = 7.5 bar(e)
0.8 0.15 loading pressure = 6.8 bar(e)
0.7 0.20
0.5 0.25 Recommended air net volume (sum of receiver volume and
0.3 0.20 volume of pipe net) = 1540 l. Consult Atlas Copco if in any
0.2 0.15 doubt.
0.1 0.10

2920 1326 00 15
Oil-free Air Division Instruction book

Fig. 12b. Installation proposal, ZT45/55

4. The inlet grids and ventilation fan should be installed in For alternatives 1 and 3:
such a way that any recirculation of cooling air to the For ZT compressors: Qv = 1.05 N/∆T
compressor or dryer (optional) is avoided. The air velocity For ZR compressors: Qv = 0.1 N/∆T
to the grids is limited to 5 m/s.
Qv = required ventilation capacity in m3/s
The required ventilation to limit the compressor room N = shaft input of the compressor in kW
temperature can be calculated as follows: ∆T = temperature rise over ambient in C

16 2920 1326 00
Instruction book Oil-free Air Division

Fig. 12c. Installation proposal, ZR45/55

If an air duct system is going to be installed on ZT collector. See Fig. 15. The drain pipes must not dip into
compressors (ventilation proposal 2), consult Atlas Copco the water of the collector.
for the maximum allowable pressure drop over the duct.
6. Elektronikon control system with control panel.
5. Fit the manual condensate drain valves (Dma/Dmi). Lay
out the drain piping from valves (Dma/Dmi) and automatic 7. See section 2.3 for the recommended cable size of the
condensate outlets (Daa/Dai) towards the condensate supply cables. Check that the electrical connections

2920 1326 00 17
Oil-free Air Division Instruction book

Fig. 12d. Installation proposal, ZT75/90

correspond to the local codes. The installation must be 9. For ZR, remove the plastic plugs (if provided) from the
earthed and protected against short circuits by fuses in all compressor water pipes (1 and 2-Fig. 15) and connect the
phases. An isolating switch must be installed near the pipes to the cooling water circuit. Provide a valve in the
compressor. compressor water inlet pipe and outlet pipe. See section
8. Provide a drain valve in the pipe between the compressor 2.4 for the water requirements.
outlet valve and the air net to enable this pipe to be
depressurized if necessary.

18 2920 1326 00
Instruction book Oil-free Air Division

Fig. 12e. Installation proposal, ZR75/90

2920 1326 00 19
Oil-free Air Division Instruction book

2.3 Electric cables

2.3.1 Size

Remar k: Local regulations remain applicable if they are stricter than the values proposed below.
Remark:
50 Hz compressors
For cable PVC 70 C, at ambient temperature 40 C according to EN60204.

Mains + earth cable


230 V 400 V 500 V

ZT18 3x25 mm + 16 mm 3x10 mm + 10 mm 3x6 mm + 6 mm


ZT22 3x35 mm + 16 mm 3x10 mm + 10 mm 3x10 mm + 10 mm
ZT30 3x50 mm + 25 mm 3x16 mm + 16 mm 3x10 mm + 10 mm
ZT37 3x70 mm + 35 mm 3x25 mm + 16 mm 3x16 mm + 16 mm
ZT/ZR45 3x70 mm + 35 mm 3x35 mm + 16 mm 3x25 mm + 16 mm
ZT/ZR55 3x95 mm + 50 mm 3x50 mm + 25 mm 3x25 mm + 16 mm
ZT75 3x150 mm + 95 mm2 3x95 mm + 35 mm 3x50 mm + 25 mm
ZR75 3x150 mm + 95 mm 3x70 mm + 35 mm 3x50 mm + 25 mm
ZT90 3x240 mm + 120 mm 3x95 mm + 50 mm 3x70 mm + 35 mm
ZR90 3x185 mm + 95 mm 3x95 mm + 50 mm 3x70 mm + 35 mm

60 Hz compressors (except for Canada and USA)


For cable PVC 70 C, at ambient temperature 40 C according to EN60204.

Mains + earth cable


220/230 V 380 V 440/460 V

ZT18 3x25 mm + 16 mm 3x10 mm + 10 mm 3x10 mm + 10 mm


ZT22 3x35 mm + 16 mm 3x10 mm + 10 mm 3x10 mm + 10 mm
ZT30 3x70 mm + 35 mm 3x25 mm + 16 mm 3x16 mm + 16 mm
ZT37 3x70 mm + 35 mm 3x25 mm + 16 mm 3x25 mm + 16 mm
ZT/ZR45 3x95 mm + 50 mm 3x35 mm + 16 mm 3x35 mm + 16 mm
ZT/ZR55 3x120 mm + 70 mm 3x50 mm + 25 mm 3x35 mm + 16 mm
ZT/ZR75 3x185 mm + 95 mm2 3x95 mm + 50 mm 3x70 mm + 35 mm
ZT/ZR90 3x240 mm + 120 mm2 3x120 mm + 70 mm 3x95 mm + 50 mm

60 Hz compressors (for Canada and USA)


For cable PVC 90 C, at ambient temperature 40 C according to CE code Part I Tables 2, 5A, 17 and rules 28-106, 28-108, 28-110).

Mains + earth cable


440/460 V 575 V

ZT18 3xAWG6 + AWG6 3xAWG8 + AWG8


ZT22 3xAWG6 + AWG6 3xAWG8 + AWG8
ZT30 3xAWG4 + AWG4 3xAWG6 + AWG6
ZT37 -- 3xAWG6 + AWG6
ZT/ZR45 3xAWG3 + AWG3 3xAWG4 + AWG4
ZT/ZR55 3xAWG2 + AWG4 3xAWG3 + AWG3
ZT/ZR75 3xAWG00 + AWG4 3xAWG1 + AWG4
ZT90 3xAWG3/0 + AWG1 3xAWG00 + AWG4
ZR90 3xAWG3/0 + AWG1 3xAWG0 + AWG3

20 2920 1326 00
Instruction book Oil-free Air Division

2.3.2 Connection 3 OPERATING INSTR


OPERATING UCTIONS
INSTRUCTIONS
The connections are shown on Fig. 6. The cable size is mentioned in Safety precautions
section 2.3.1. The operator must apply all related safety precautions including those
mentioned in this book.

2.4 Cooling water requirements Outdoor/altitude operation


If the compressor is installed outdoors or if the air inlet temperature
Following requirements are given as a general rule to prevent cooling can be below 0 C (32 F), precautions must be taken. In this case,
water problems. If in any doubt, consult Atlas Copco. and also for altitude operation, consult Atlas Copco.

Moving/lifting
Recommended maxima - mg/l Recirculating Open
The compressor can be moved by a lift truck using the slots in the
system system
frame. Make sure that the forks protrude from the other side of the
frame. The compressor can also be lifted after inserting beams in
Chloride (Cl-) . . . . . . . . . . . . . . . . . . . < 600 < 150 the slots. Make sure that the beams cannot slide and that they
Sulphate (SO4--) . . . . . . . . . . . . . . . . . < 400 < 250 protrude from the frame equally. The chains must be held parallel to
Total solids . . . . . . . . . . . . . . . . . . . . < 3000 < 750 the bodywork by chain spreaders in order not to damage the
Suspended solids (as SiO2) . . . . . . . < 10 < 10 compressor. The lifting equipment must be placed in such a way that
Free chlorine (Cl2) . . . . . . . . . . . . . . . <4 <2 the compressor will be lifted perpendicularly. Lift smoothly and avoid
Ammonia (NH4+) . . . . . . . . . . . . . . . . < 0.5 < 0.5 twisting.
Copper . . . . . . . . . . . . . . . . . . . . . . . < 0.5 < 0.5
Iron . . . . . . . . . . . . . . . . . . . . . . . . . . < 0.2 < 0.2
Manganese . . . . . . . . . . . . . . . . . . . . < 0.1 < 0.1 3.1 Preparation for initial start-up
Oxygen . . . . . . . . . . . . . . . . . . . . . . . <3 <3
Carbonate hardness (as CaCO3) . . . 50-1000 50-500 1. Consult section 2 for the electric cable sizes, installation proposals
Organics (KMnO4 Consumption) . . . . < 25 < 10 and dimension drawings.
2. Read the "User manual for Elektronikon® regulator" to familiarize
yourself with all regulator functions.
Remarks 3. A sticker dealing in short with the operating instructions is delivered
- No algae nor oil. with the literature set. Affix the sticker next to the control panel.
- Chloride and sulphate are interactive. In open systems the sum 4. The compressor and motor are secured to the frame immobilizing
of the squares of these values must not exceed 85,000. For the vibration dampers during transport:
recirculating systems with proper controls and treatment, the sum At the compressor side, unscrew the long transport bolt (3-Figs.
of the squares may be up to 520,000. Note that the sulphate 14) at both supports and fit new shorter bolts 1) 1). Tighten the
value must include any sulphite present. bolts to fix the supports securely to the vibration dampers.
At the motor side:
- for ZT18/37
ZT18/37, unscrew the long transport bolt (3-Fig. 14a) and
2.5 Pictographs (Fig. 13) (See next page) fit a new shorter bolt 1)
1). Tighten the bolt to fix the support
securely to the vibration damper.
- for ZT/ZR45/55
ZT/ZR45/55, unscrew the two long transport bolts (3-Fig.
14b) and fit new shorter bolts 1)1). Tighten the bolts to fix the
support securely to the vibration dampers.
- for ZT/ZR75/90
ZT/ZR75/90, unscrew the two transport bolts (1-Fig. 14c)
and remove spacers (2).
5. Silicagel bags are installed at different locations:
On ZT/ZR45/55:
- Remove the cover of the housing of air filter (AF-Figs. 2 and
3) and the air filter. Take out the silicagel bag. Remove the
tape closing off the air inlet opening on the inside of the air
filter housing. Reinstall the air filter and cover.
- Remove flange (4-Figs. 2 and 3) and take out the silicagel
bags from pulsation damper (PD). Reinstall the flange. 2)

1) The bolts and washers are delivered loose with the compressor.
2) The missing bolts are delivered loose with the compressor.

2920 1326 00 21
Oil-free Air Division Instruction book

26 27 13 15 14 16

1. Automatic operation 11. Key to go to next field on 19. Switch off the voltage and 23. Switch off the voltage
2. Voltage on display depressurize the compres- before removing the
3. Start 12. Alarm sor before maintenance or protecting cover inside the
4. Stop 13. Automatic condensate repair electric cabinet
5. Compressor locked (in off outlet, intercooler 20. Before connecting the 24. Oil the gasket, screw on
position) 14. Automatic condensate compressor electrically, the filter and tighten by
6. Local control outlet, aftercooler consult the Instruction hand (approx. one half
7. Remote control (by 15. Condensate valve, book for the motor rotation turn)
external switches) intercooler direction 25. Consult the Instruction
8. Remote control (by 16. Condensate valve, 21. Torques for steel (Fe) or book before maintenance
computer) aftercooler brass (CuZn) bolts or repair
9. Emergency stop 17. Warning: under tension 22. Consult the instruction 26. Cooling water inlet
10. Keys to scroll through 18. Read Instruction book book before greasing 27. Cooling water outlet
display before starting the 28. Stop the compressor
compressor before servicing the fan

Fig. 13. Pictographs

22 2920 1326 00
Instruction book Oil-free Air Division

Fig. 14a. ZT18/37

Fig. 14c. ZT/ZR75/90

1. Transport bolt
2. Spacer
3. Transport bolt
4. Vibration damper,
compressor
5. Vibration damper, motor
6. Support, compressor
7. Support, motor

Figs. 14. Transport fixations

Fig. 14b. ZT/ZR45/55

On ZT/ZR75/90
ZT/ZR75/90, remove flange (6-Figs. 4 and 5) and take out Check the setting of overload relay (F21) and that the relay is set
the silicagel bags from the intercooler moisture trap (MTi). Refit for automatic resetting. See section 7.4.
the flange. 9. Switch on the voltage. Start the motor and stop it immediately.
6. Check that the cooling water drain valves (customer's installation) Check for correct direction of rotation of the compressor motor
in the inlet and outlet lines are closed. Open the water inlet valve (M1-Figs. 1 up to 5) as indicated by the arrow on the coupling
and outlet valve (customer's installation) and check for water flow. housing. A grating is provided through which the coupling can be
7. Fill the compressor sump to the middle of oil level sight-glass observed. For ZT18/37 and ZT75/90
ZT75/90, also check the fan motor
(SG-Figs. 1 up to 5) with oil as specified in section 4.3. (M2-Figs. 1 and 4) for correct direction of rotation. When facing
8. Check the voltage selecting wires at transformer (T1-Fig. 10) for the drive end of the motors, the correct direction of rotation is
correct connection. counter-clockwise.

2920 1326 00 23
Oil-free Air Division Instruction book

First check the compressor motor. If the rotation direction is 4. On ZRZR, check that the water drain valves are closed and open
wrong, switch off the voltage and reverse two incoming lines. the water inlet valve and outlet valve (customer's installation).
Then check the fan motor. If the cooling air from the fan is not 5. On ZR, open water flow regulating valves (Vfi and Vfa-Figs. 5
blown through the grating above the fan, switch off the voltage and 16). Opening of these valves can be overlooked if, after
and reverse two connections at the terminals of circuit breaker previous operation, the setting has not been disturbed.
(Q25-Fig. 10). 6. Switch on the voltage and check that voltage on LED (2-Fig. 7)
10. Run the compressor for a few minutes; check the oil level. Top lights up.
up, if necessary, to the middle of sight-glass (SG-Figs. 1 up to 5).

3.4 Starting (Fig. 7)


3.2 Compressor control modes
3.4.1 Routine starting
Key switch (S5-Fig. 7) allows the operator to select four control modes:
1. Press start button (8). The compressor starts running in unloaded
Key Compressor control mode condition and automatic operation LED (1) lights up.
position 2. 25 seconds later (programmable), the compressor starts running
loaded. The message on display (4) changes from
<<Automatically unloaded>> to <<Automatically loaded>>.
1 Compressor off. 3. Regulate the water flow with the compressor running loadedloaded.
Consult section 7.1 for the cooling water temperature and sections
2 Local control mode (remote control mode is made 7.5.3 up to 7.5.10 for the cooling water consumption and air outlet
inactive). The compressor can only be controlled by temperature.
the buttons on the control panel.
The compressor can be started and stopped via On ZR45/55 (Fig. 16), the water flow through the oil cooler/
function Timer (see section 1.2.1), if programmed and intercooler circuit and through the aftercooler is regulated by valve
activated. (Vfi) and (Vfa) respectively.
On ZR75/90 (Fig. 5), the water flow through the oil cooler/
3 Remote control mode 1 (local control is made intercooler/LP element circuit is regulated by valve (Vfi), the water
inactive). The compressor can only be started and flow through the aftercooler/HP element by valve (Vfa).
stopped by external switches.
Compressor start/stop commands via function Timer Important
(see section 1.2.1) are still possible, if programmed - If the motor is stopped and automatic operation LED (1-Fig.
and activated. 7) is alight, the motor may start automatically.
Emergency stop button (S2-Fig. 7) remains active. - If the start/stop timer is active (see section 1.2.1), the
compressor can start automatically, even if it was stopped
4 Remote control mode 2. The compressor can be manually.
controlled by computer. Consult Atlas Copco.

3.4.2 Starting after emergency stopping or shut-


Important down
- The control module will only react to a new control mode if the
new position of the control mode switch is maintained for 3 Press the emergency stop button (S2-Fig. 7) (if not yet done so),
seconds. switch off the voltage and then depressurize the compressor. After
- To avoid unauthorized switching over to another control mode, remedying the fault, unlock the emergency button by turning it anti-
take out the key after selecting the required mode. clockwise and restart the compressor as described above.

If the automatic restart function after voltage failure is activated (see


3.3 Before starting section 1.2.1) and the duration of repair is shorter than the
programmed power recovery time, reset the display after remedying
Attention the fault: press the key <<Reset>>, the message <<All protection
The operator must apply all relevant safety precautions, including functions are OK>> will appear, whereafter the compressor can be
those mentioned in this instruction book. restarted. Press the keys <<Menu>> and <<Main Screen>> to return
to the main display (Fig. 8).
1. Check the oil level, which must be in the middle of sight-glass
(SG-Figs. 1 up to 5). Top up, if necessary, with the correct type of
oil.
2. Close condensate drain valves (Dma and Dmi-Fig. 15). 1)
3. Open the air outlet valve (AV-Figs. 1 and 4).
1) Dmi on ZR and ZT75/90 only.

24 2920 1326 00
Instruction book Oil-free Air Division

AV. Air outlet valve


Daa. Automatic condensate drain outlet, aftercooler moisture trap
Dai. 1) Automatic condensate drain outlet, intercooler moisture trap
Dma. Manual condensate drain valve, aftercooler moisture trap
Dmi. 1) Manual condensate drain valve, intercooler moisture trap
1. 2) Cooling water inlet pipe
2. 2) Cooling water outlet pipe

1) ZR and ZT75/90 only.


2) ZR only.

Fig. 15. Air, water and condensate connections

Minimum stop time maximum permissible number of motor starts and on the air
The compressor will not be allowed to restart within a programmed consumption.
time (20 s) after a stop for whatever reason. A start command given 4. To unload the compressor manually, press the key <<Unload>>
during the minimum stop time will be memorized; automatic operation (5) 1)
1). To put the compressor back into automatic operation, press
LED (1-Fig. 7) lights up. The compressor will start when the minimum the key <<Load>> (5) 1)1).
stop time has run out.
Important
- If the compressor is stopped, it may start automatically. See also
section 1.2.1.
3.4.3 Manual restarting - The control module will only react to a new control mode if the
new position of the control mode switch is maintained for 3
In automatic operation, the regulator limits the number of motor starts. seconds.
For low-voltage motors, observe an interval of minimum 20 minutes - To avoid unauthorized switching over to another control mode,
between each manual start. take out the key (S5-Fig. 7) after selecting the required mode.
See also section 3.2.

3.5 During operation (Fig. 7) 3.5.1 Checking the display (4-Fig. 7)

1. When automatic operation LED (1) is alight, starting and stopping 1. Regularly check the display for readings and messages. Normally,
of the motor are automatically controlled: when the motor is the main display (Fig. 8) is shown, indicating the compressor outlet
stopped, it may restart automatically. pressure, the status of the compressor and the functions of the
2. Check the readings on display (4). See below. keys below the display.
3. On reaching the pre-set unloading pressure, shown on display
(4), the compressor will run unloaded. From now on, the electronic
control module will calculate the optimum moment to stop and 1) If the <<Load>> or <<Unload>> function is not indicated on the bottom
restart the compressor motor automatically, depending on the line of display (4), press key <<Menu>> (5) until the function <<Main
Screen>> appears above key (F1), then press the key <<Main Screen>>.

2920 1326 00 25
Oil-free Air Division Instruction book

2. Always check the display and remedy the trouble if alarm LED (3- 3.6.2 Manual loading 1)
Fig. 7) is alight or blinks. Consult section 1.2 and the "User manual
for Elektronikon® regulator", section "Status data submenu". Press the key <<Load>> (5). LED (1) lights up. The command
3. The display will show a service message if one of the monitored <<Load>> does not force the compressor in loaded condition, but it
components is to be serviced; replace the component, change will switch the compressor to automatic operation again, i.e. the
the oil or grease the compressor motor as the case may be. Reset compressor will be loaded if the air net pressure drops below the
the relevant timer. Consult the "User manual for Elektronikon® programmed level.
regulator", section "Service submenu".

arning
War ning 3.7 Stopping (Fig. 7)
Before carrying out any maintenance, repair or adjustment,
stop the compressor, press emergency stop button 1. Close the air outlet valve (AV-Figs. 1 and 4).
(S2-Fig. 7), switch off the voltage and depressurize the 2. Press stop button (9). The compressor will run unloaded for 3
compressor. seconds, after which it will stop.
3. To stop the compressor immediately
immediately, press emergency stop
Notes button (S2). Alarm LED (3) starts blinking. After remedying the
- Whenever a warning, service request, sensor error or motor trouble, unlock the emergency stop button by turning it anti-
overload message is displayed, the free spaces on the display clockwise.
between the function keys (5-Fig. 7) are filled with blinking 4. Open the drain valves (Dmi and Dma-Fig. 15). 4)
indicators (**). 5. On ZR
ZR, close the cooling water inlet valve.
- When more than one message needs to be displayed (e.g. 6. If the compressor is installed in a room where freezing
both warning and service), the messages are continuously temperatures are expected:
displayed for 3 seconds each. - on ZR, drain the cooling system completely by opening the
main drain valves in the water inlet and outlet pipes
4. Regularly press the key <<Show more>> (5-Fig. 7) 2) to call up (customer's installation); on ZR75/90, also remove water drain
the actual compressor condition: plugs (DP1/2-Fig. 17). 5)
- the status of controlling the compressor (automatic or manual, - on ZT45/55
ZT45/55, remove the condensate drain plug from the
local or remote) intercooler and aftercooler. Reinstall them before restarting.
- the status of the compressor start/stop timer (active or not)
3)
- the maximum working pressure
- the outlet pressure
3.8 Taking out of oper ation
operation
- the pressure drop over the air filter (not on ZT18/37)
- the oil pressure At the end of the service life of the compressor, proceed as follows:
- the intercooler pressure
- the outlet temperature (not on ZT18/37) 1. Close the air outlet valve and stop the compressor.
- the temperatures of the compressor elements 2. Switch off the voltage and disconnect the compressor from the
- the cooling water temperatures (not on ZT) mains.
- the status of the overload protection of the compressor motor 3. Shut off and depressurize the part of the air net which is connected
(normal or not) to the outlet valve. Disconnect the compressor air outlet pipe
- the total running and loading hours from the air net.
4. On ZR
ZR, drain the water circuit and disconnect the cooling water
pipes from the compressor.
5. Drain the oil and condensate circuits.
3.6 Manual control of compressor operation (Fig. 7) 6. Disconnect the compressor condensate piping from the
condensate drain net.
Normally, the compressor runs in automatic operation, i.e. the
electronic regulator loads, unloads, stops and restarts the compressor
automatically. LED (1) is then alight.
1) If the <<Load>> or <<Unload>> function is not indicated on the bottom
If required, the compressor can be unloaded manually. In this case, line of display (4), press key <<Menu>> (5) until the function <<Main
the compressor is switched out of automatic operation, i.e. the Screen>> appears above key (F1), then press the key <<Main Screen>>.
compressor remains running unloaded unless it is loaded again 2) If the function <<Show More>> is not indicated on the bottom line of
manually. display (4-Fig. 7), press key <<Menu>> (5) until function <<Main
Screen>> appears above key (F1), then press the key <<Main Screen>>.
3) The compressor is automatically started and stopped if these start/stop
commands are programmed and activated; consult section 1.2.1.
3.6.1 Manual unloading 1) 4) Dmi on ZR and ZT75/90 only.
5) If the compressor element is provided with a small, external pipe at the
Press the key <<Unload>> (5). LED (1) goes out. The message bottom connecting the cooling jacket compartments, remove this pipe
<<Manually Unloaded>> appears on the display. for draining of the water. No plugs are to be removed in this case.

26 2920 1326 00
Instruction book Oil-free Air Division

El. Low-pressure compressor element


MTa. Moisture trap, aftercooler
Vfa. Regulating valve, aftercooler cooling water flow
Vfi. Regulating valve, intercooler cooling water flow

Fig. 16. Water regulating valves on ZR45/55

DP1/2. Water drain plugs


Eh. High-pressure compressor element
El. Low-pressure compressor element
1. Air pipe to intercooler

Fig. 17. Water drain plugs on ZR75/90

2920 1326 00 27
Oil-free Air Division Instruction book

4 MAINTENANCE
Attention
Before carrying out any maintenance or repair, stop the compressor, press the emergency stop button and switch off the voltage. Safeguard
against unintentional "switch-on". Apply all relevant safety precautions, including those mentioned in this book.

4.1 Preventive maintenance schedule for the compressor 1)

The schedule contains a summary of the maintenance instructions. Read the related section before taking maintenance measures.

In servicing, replace all removed gaskets, O-rings and washers.

The "longer interval" checks must also include the "shorter interval" checks.

Period 2) Running Consult See Operation


hours 2) section note

Daily -- -- 1 Check oil level


" 8 3.5/7.1 -- Check readings on display; on ZT18/37, also check air filter service indicator
" 8 -- -- Check that condensate is discharged from the moisture traps during loading
" -- 3.7 -- Drain the aftercooler and intercooler moisture traps after stopping

Weekly -- 7.2 -- Check programmed settings


" -- -- -- Drain condensate from air receiver, if installed
" -- -- 4 Check for possible leaks

3-monthly 1000 4.5/5.1 5 Remove air filter and inspect


" -- 5.4 -- Clean compressor; inspect coolers

Year ly
early 8000 -- -- Replace filter of gear casing breather
" 8000 -- 2 Carry out a LED/display test
" 8000 4.5/5.2 -- Replace oil filter and change oil
" -- 4.5/5.1 -- Replace air filter
" -- 5.3 3 Have safety valves tested
" -- -- -- Have efficiency of coolers tested
" -- -- -- Have the compressor inspected by an Atlas Copco Service representative
" -- -- -- Have operation of sensors, electrical interlockings and components tested
by an electrician

1) Use only author


authoriz iz ed par
ized ts
ts.. An
parts Anyy damage or malfunction caused bbyy the use of unauthor iz
unauthoriz ed par
ized ts is not co
parts covv ered bbyy Warr anty or
arranty
Product Liability
Liability..
2) Whiche
Whichevv er inter
intervv al comes first. The local Atlas Copco Sales Company may overrule the maintenance schedule, especially the service
intervals, depending on the environmental and working conditions of the compressor.

Notes
1. Maintain the level in the middle of the oil level sight-glass.
2. See "User manual for Elektronikon® regulator".
3. Preferably to be carried out by an Atlas Copco Service representative.
4. Any leak should be attended to immediately.
5. More frequently in very dusty surroundings.

28 2920 1326 00
Instruction book Oil-free Air Division

4.2 Motors 4.5 Service kit numbers for filters

Use Atlas Copco spare parts only. The part numbers to order service
4.2.1 Fan motor bearings kits for both the air and oil filters are:

ZT18/37 and ZT75/90 are provided with a fan driven by an electric Compressor type Service kit ordering number
motor. The bearings of this motor must be replaced after 25000
operating hours.
ZT18/22 2906 0071 00
ZT30/37 2906 0070 00
ZT/ZR45/55 2906 0194 00
4.2.2 Compressor motor greasing ZT/ZR75/90 2906 0182 00

Use a lithium-soap-based grease according to DIN 51 825 K3N. Stop


the compressor before greasing. Reset the regreasing service
warning 1) after regreasing. The data below are valid for an air intake
temperature of maximum 40 C.
5 SERVICING PR
SERVICING OCEDURES
PROCEDURES
Compressor Interval Quantity
type (hours) (g) 5.1 Air filter (AF-Fig. 1)

1. For ZT18/37, the filter must be replaced yearly or when the red
ZT18 3000 15 piston of the service indicator (VI-Fig. 1) shows completely. The
ZT22 3000 15 indicator can be reset by pushing the knob in the extremity of the
ZT30 3000 15 body.
ZT37 3000 15 2. For ZT/ZR45/90, the filter must be serviced as soon as the service
ZT/ZR45 2000 20 warning appears on the display or yearly.
ZT/ZR55 2000 20 3. Stop the compressor, press the emergency stop button and switch
ZT/ZR75 2000 20 off the voltage.
ZT/ZR90 2000 20 4. Remove the filter housing cover and clean the filter chamber.
Clean the cover.
5. Remove the filter. Take care that no dirt drops into the inlet pipe.
6. Install the new filter and fit the cover. Never install damaged or
clogged filters.
4.3 Oil specifications 7. Switch on the voltage, unlock the emergency stop button and
reset the air filter service warning. 1)
A high-quality mineral oil for bearings and gears, with oxidation
inhibitors and good water separation properties is recommended. The
viscosity grade for operation in ambient temperatures above 0 C 5.2 Oil and oil filter change (Figs. 1 up to 5)
(32 F) should be ISO VG 68, in conformity with ISO 3448.
1. Run the compressor until warm. Stop the compressor, press the
Mineral motor oils meeting the API requirements CC or CD and with emergency stop button and switch off the voltage.
a viscosity grade of SAE 20W20 (for ambient temperatures above 2. Remove filler plug (FC). Drain the compressor sump by opening
0 C/32 F) may also be used. drain valve (Dmo). On ZR75/90, remove the oil cooler drain plug
(DPo). Close the valve and reinstall the plug after draining.
Consult Atlas Copco ffor
or the recommended oils
oils.. Once a br and
brand 3. Remove the oil filter (OF). Clean the filter seat, oil the gasket of
has been adopted, keep to it. Never mix different oils. the new filter and screw it into place until the gasket contacts the
seat. Then tighten by hand.
4. Fill the compressor sump to the middle of the oil level sight-glass
(SG) with oil as specified in section 4.3. Reinstall the filler plug.
4.4 Storage after installation 5. Switch on the voltage, unlock the emergency stop button and
reset the oil and oil filter service warnings. 1)
Run the compressor, e.g. twice a week, until warm. Load and unload 6. Run the compressor for a few minutes; check the oil level and top
the compressor a few times. up if necessary to the middle of sight-glass (SG).

If the compressor is going to be stored without running from time to


time, protective measures must be taken. Consult Atlas Copco. 1) See "User manual for Elektronikon ® regulator", section "Service
submenu".

2920 1326 00 29
Oil-free Air Division Instruction book

5.3 Safety valves a. Check pneumatic plant


b. Safety valve(s) leaking
Testing b. Remove leaking valve and have it inspected
The valves can be tested on a separate compressed air line. If a c. Unloading pressure incorrectly set
valve does not open at the pressure specified in section 7.3, consult c. See "User manual for Elektronikon® regulator", section "Modify
Atlas Copco. settings submenu"

arning
War ning 5. Oil pressure too low
- Never run the compressor without safety valves. a. Oil level too low
- No adjustments are allowed. a. Top up level to the middle of the oil level sight-glass
b. Oil filter clogged
b. Replace filter
5.4 Coolers
6. Air temperature above normal
On ZT
ZT,, keep the fins of the coolers clean. Remove any dust from a. Inlet temperature too high due to bad room ventilation or
both sides of the coolers with a fibre brush. Never use a wire brush recirculation of cooling air
or metal objects. Clean by air jet. Consult Atlas Copco if it should be a. Improve ventilation of compressor room
necessary to wash the coolers. b. For ZR, insufficient cooling water flow or water inlet
temperature too high
On ZR, consult Atlas Copco for cleaning. b. Check and increase cooling water flow or decrease water inlet
temperature, if possible
c. For ZR, restriction in cooling water system due to formation
of scale or settling down of dirt
c. Consult Atlas Copco
6 PR OBLEM SOL
PROBLEM VING
SOLVING 7. Push button I is pressed, compressor starts running, but
does not load after delay time
arning
War ning a. Pressure in air net is above pre-set loading pressure
Before starting repairs, press stop button (9-Fig. 7), wait until the a. Compressor will load when pressure in air net drops to pre-
compressor has stopped, press emergency stop button (S2-Fig. set loading pressure
7) and switch off the voltage.

Remove the main fuses to avoid an accidental restart. Apply all


relevant safety precautions, including those mentioned in this
book.

Faults and suggested remedies

1. A service message appears on the display


Replace the indicated component, change the oil or grease the
compressor motor as the case may be. Consult the "User manual
for Elektronikon® regulator" to reset the message (section "Service
submenu")

2. A shut-down warning message appears on the display


LED (3-Fig. 7) will light up indicating that a shut-down level is
almost reached. Consult the "User manual for Elektronikon®
regulator" to look for the cause (section "Status data submenu").
Remedy the trouble. The warning message disappears as soon
as the cause of the trouble is remedied

3. Compressor is shut down


LED (3-Fig. 7) will blink indicating that the compressor is stopped
due to a shut-down function. A message appears on the display.
Remedy the trouble. Consult the "User manual for Elektronikon®
regulator" to reset the message (section "Status data submenu")

4. Compressor capacity or working pressure lower than normal


a. Air consumption exceeds capacity of compressor

30 2920 1326 00
Instruction book Oil-free Air Division

7 PRINCIPAL D
PRINCIPAL ATA
DA 7.2 Programmable settings

A number of regulation settings (e.g. loading and unloading pressures),


7.1 Readings on display 1) (Fig. 7) protection settings (e.g. shut-down level for the temperatures of the
compressor elements) and service settings (e.g. oil service life) are
- Maximum working pressure . . See sections 7.5.3 up to 7.5.10 programmable. The "User manual for Elektronikon® regulator" deals
- Outlet pressure . . . . . . . . . . . . Depends on compressor type elaborately with this matter (section "Modify settings submenu").
- ∆p air filter . . . . . . . . . . . . . . . Below 0.050 bar 3)
- Intercooler pressure . . . . . . . . During unloading 2)
ZT18/37 -0.6 bar
ZT/ZR45/55 -0.4 bar 7.3 Settings of safety valves
ZT/ZR75/90 -0.6/0.65 bar
During loading 2) Safety valves Opening pressure
Approx. 2.4 bar(e) bar(e)
- Oil pressure . . . . . . . . . . . . . . Approx. 1.8 bar(e) 2)
- Air temperature element 1 out Approx. 165 C 2)
- Air temperature element 2 out Approx. 170 C 2) Low-pressure safety valve(s) . . . . . . . . . . . . 3.7
- Air temperature element 2 in . ZT: Approx. 45 C 2)
ZR: Approx. 35 C 2) High-pressure safety valve:
- Air outlet temperature . . . . . . . Approx. 30 C 2) 3) - Compressors with max. working
- Cooling water inlet pressure(e) up to 8.6 bar . . . . . . . . . . . . 9.3
temperature . . . . . . . . . . . . . . Below 35 C 4) - Compressors with max. working
- Cooling water outlet pressure(e) above 8.6 bar . . . . . . . . . . . 11
temperature . . . . . . . . . . . . . . Below 50 C 4)

1) At reference conditions. See section 7.5.1.


2) The readings are typical values which may differ depending on
compressor type.
3) Not shown on ZT18/37.
4) Not on ZT.

2920 1326 00 31
Oil-free Air Division Instruction book

7.4 Motor type - settings of overload relay and circuit breaker - main fuses

7.4.1 Motor type - settings of motor overload relay - main fuses for 50 Hz compressors

Compressor Motor type Supply voltage Maximum setting of Maximum fuse


type (V) overload relay F21 (A) ratings (A)

ZT18 1LA5 166-2 230 38 100


ZT18 1LA5 166-2 400 22.5 50
ZT18 1LA5 166-2 500 18 50

ZT22 1LA5 183-2 230 43 100


ZT22 1LA5 183-2 400 25 63
ZT22 1LA5 183-2 500 20 50

ZT30 1LA5 206-2 230 58 125


ZT30 1LA5 206-2 400 33 100
ZT30 1LA5 206-2 500 27 63

ZT37 1LA5 207-2 230 72 125


ZT37 1LA5 207-2 400 42 100
ZT37 1LA5 207-2 500 33 63

ZT/ZR45 1LA6 223-2 230 88 160


ZT/ZR45 1LA6 223-2 400 49 100
ZT/ZR45 1LA6 223-2 500 39 100

ZT/ZR55 1LA6 228-2 230 105 200


ZT/ZR55 1LA6 228-2 400 61 125
ZT/ZR55 1LA6 228-2 500 47 100

ZT/ZR75 1LA6 258-2 230 143 250


ZT/ZR75 1LA6 258-2 400 83 200
ZT/ZR75 1LA6 258-2 500 67 160

ZT/ZR90 1LA6 250-2 230 169 315


ZT/ZR90 1LA6 250-2 400 95 200
ZT/ZR90 1LA6 250-2 500 77 160

7.4.2 Motor type - settings of motor overload relay - main fuses for 60 Hz compressors (Y/D starter)

Compres- Motor type Supply Maximum setting Maximum fuse Maximum setting Maximum fuse Maximum fuse
sor type voltage (V) of overload relay ratings (A) of overload relay ratings ratings
F21 (A) F21 (A) CSA HRC (A) UL Class K5 (A)
CSA/UL

ZT18 1LA5 166-2 220-230 -- -- 47 80 70


ZT18 1LA5 166-2 440-460 -- -- 23 60 60
ZT18 1LA5 166-2 575 -- -- 18 60 60

ZT22 1LA5 183-2 220-230 -- -- 54 80 70


ZT22 1LA5 183-2 440-460 -- -- 27 60 60
ZT22 1LA5 183-2 575 -- -- 20 60 60

32 2920 1326 00
Instruction book Oil-free Air Division

Compres- Motor type Supply Maximum setting Maximum fuse Maximum setting Maximum fuse Maximum fuse
sor type voltage (V) of overload relay ratings (A) of overload relay ratings ratings
F21 (A) F21 (A) CSA HRC (A) UL Class K5 (A)
CSA/UL

ZT30 1LA5 206-2 220-230 -- -- 70 125 150


ZT30 1LA5 206-2 440-460 -- -- 35 80 70
ZT30 1LA5 206-2 575 -- -- 27 80 70

ZT37 1LA5 207-2 220-230 -- -- 87 200 175


ZT37 1LA5 207-2 440-460 -- -- 43 80 70
ZT37 1LA5 207-2 575 -- -- 33 80 70

ZT/ZR45 1LA6 223-2 220-230 97 224 -- -- --


ZT/ZR45 1LA6 223-2 380 57 125 -- -- --
ZT/ZR45 1LA6 223-2 440-460 48 100 48 80 70
ZT/ZR45 1LA6 223-2 575 -- -- 38 80 70
ZT/ZR55 1LA6 228-2 220-230 121 224 -- -- --
ZT/ZR55 1LA6 228-2 380 70 125 -- -- --
ZT/ZR55 1LA6 228-2 440-460 60 125 60 125 125
ZT/ZR55 1LA6 228-2 575 -- -- 47 80 70

ZT/ZR75 1LA6 258-2 220-230 165 355 -- -- --


ZT/ZR75 1LA6 258-2 380 93 224 -- -- --
ZT/ZR75 1LA6 258-2 440-460 83 200 83 150 150
ZT/ZR75 1LA6 258-2 575 -- -- 64 125 125

ZT/ZR90 1LA6 250-2 220-230 201 355 -- -- --


ZT/ZR90 1LA6 250-2 380 115 224 -- -- --
ZT/ZR90 1LA6 250-2 440-460 100 200 100 200 175
ZT/ZR90 1LA6 250-2 575 -- -- 77 175 175

7.4.3 Setting of fan motor circuit breaker for 50 Hz compressors

Compressor type Supply voltage (V) Maximum setting of circuit breaker Q25 (A)

ZT18/37 200-240 4.5


ZT18/37 380-415 2.6
ZT18/37 500 1.75
ZT75/90 200-240 12.1
ZT75/90 380-415 7.0
ZT75/90 500 4.7

7.4.4 Setting of fan motor circuit breaker for 60 Hz compressors

Compressor type Supply voltage (V) Maximum setting of circuit breaker Q25 (A)

ZT18/37 220-230 4.8


ZT18/37 380-460 2.8
ZT18/37 575 2.15

ZT75/90 220-230 10.5


ZT75/90 380-460 5.9
ZT75/90 575 4.4

2920 1326 00 33
Oil-free Air Division Instruction book

7.5 Compressor specifications

7.5.1 Reference conditions

Absolute inlet pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(a) 1


Relative air humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . % 0
Air inlet temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C 20
Nominal effective working pressure . . . . . . . . . . . . . . . . . . . . bar(e) see sections 7.5.3 up to 7.5.10
Cooling water inlet temperature (ZR only) . . . . . . . . . . . . . . . C 20

7.5.2 Limitations

Maximum air inlet temperature . . . . . . . . . . . . . . . . . . . . . . . . C 40


Minimum ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . C 0
Maximum effective working pressure . . . . . . . . . . . . . . . . . . . bar(e) see sections 7.5.3 up to 7.5.10
Maximum cooling water temperature:
- At inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C 35
- At outlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C 50
Maximum cooling water inlet pressure . . . . . . . . . . . . . . . . . . bar(e) 7

7.5.3 Specific data of ZT/ZR18/55 7.5 bar - 50 Hz 1)

ZT18 ZT22 ZT30 ZT37 ZT45 ZT55 ZR45 ZR55

Maximum working pressure . . . . . . . . . . bar(e) 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
Nominal working pressure . . . . . . . . . . . bar(e) 7 7 7 7 7 7 7 7
Air temperature at outlet valve . . . . . . . . C 28 29 30 33 30 30 30 32
Motor shaft speed . . . . . . . . . . . . . . . . . . r/min 2930 2940 2945 2945 2960 2965 2960 2965
Power input 3) . . . . . . . . . . . . . . . . . . . . . kW 21.0 24.5 33.2 41.1 48.2 59.8 48.6 57.5
Oil capacity . . . . . . . . . . . . . . . . . . . . . . . l 21 21 21 21 34 34 34 34
Sound pressure level 2) . . . . . . . . . . . . . dB(A) 70 72 75 76 75 76 75 76
Cooling water consumption at
temperature rise of 15 C . . . . . . . . . . . . l/s -- -- -- -- -- -- 0.68 0.8

7.5.4 Specific data of ZT/ZR18/55 8.6 bar - 50 Hz 1)

ZT18 ZT22 ZT30 ZT37 ZT45 ZT55 ZR45 ZR55

Maximum working pressure . . . . . . . . . . bar(e) 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6
Nominal working pressure . . . . . . . . . . . bar(e) 8 8 8 8 8 8 8 8
Air temperature at outlet valve . . . . . . . . C 28 29 30 33 30 30 30 32
Motor shaft speed . . . . . . . . . . . . . . . . . . r/min 2930 2940 2945 2945 2960 2965 2960 2965
Power input 3) . . . . . . . . . . . . . . . . . . . . . kW 20.5 24.1 33.0 40.0 47.0 58.8 47.2 58.8
Oil capacity . . . . . . . . . . . . . . . . . . . . . . . l 21 21 21 21 34 34 34 34
Sound pressure level 2) . . . . . . . . . . . . . dB(A) 70 72 75 76 75 76 75 76
Cooling water consumption at
temperature rise of 15 C . . . . . . . . . . . . l/s -- -- -- -- -- -- 0.66 0.82

1) At reference conditions (see section 7.5.1).


2) According to PNEUROP / CAGI test code under free field conditions at 1 m distance with a tolerance of µ 3dB.
3) Values may differ up to 0.5% depending on the supply voltage.

34 2920 1326 00
Instruction book Oil-free Air Division

7.5.5 Specific data of ZT/ZR18/55 7.5 bar - 60 Hz 1)

ZT18 ZT22 ZT30 ZT37 ZT45 ZT55 ZR45 ZR55

Maximum working pressure . . . . . . . . . . bar(e) 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
Nominal working pressure . . . . . . . . . . . bar(e) 7 7 7 7 7 7 7 7
Air temperature at outlet valve . . . . . . . . C 28 29 30 33 30 30 30 32
Motor shaft speed . . . . . . . . . . . . . . . . . . r/min 3530 3540 3545 3545 3545 3555 3545 3555
Power input 3) . . . . . . . . . . . . . . . . . . . . . kW 23.5 27.1 36.7 42.8 50.2 63.3 50.7 63.4
Oil capacity . . . . . . . . . . . . . . . . . . . . . . . l 21 21 21 21 34 34 34 34
Sound pressure level 2) . . . . . . . . . . . . . dB(A) 70 72 75 76 75 76 75 76
Cooling water consumption at
temperature rise of 15 C . . . . . . . . . . . . l/s -- -- -- -- -- -- 0.71 0.89

7.5.6 Specific data of ZT/ZR18/55 8.6 bar - 60 Hz 1)

ZT18 ZT22 ZT30 ZT37 ZT45 ZT55 ZR45 ZR55

Maximum working pressure . . . . . . . . . . bar(e) 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6
Nominal working pressure . . . . . . . . . . . bar(e) 8 8 8 8 8 8 8 8
Air temperature at outlet valve . . . . . . . . C 28 29 30 33 30 30 30 32
Motor shaft speed . . . . . . . . . . . . . . . . . . r/min 3530 3540 3545 3545 3545 3555 3545 3555
Power input 3) . . . . . . . . . . . . . . . . . . . . . kW 23.7 27.4 36.4 43.4 50.1 62.0 50.5 63.1
Oil capacity . . . . . . . . . . . . . . . . . . . . . . . l 21 21 21 21 34 34 34 34
Sound pressure level 2) . . . . . . . . . . . . . dB(A) 70 72 75 76 75 76 75 76
Cooling water consumption at
temperature rise of 15 C . . . . . . . . . . . . l/s -- -- -- -- -- -- 0.71 0.89

7.5.7 Specific data of ZT/ZR75/90 8 bar - 50 Hz 1)

ZT75 ZT90 ZR75 ZR90

Maximum working pressure . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 8 8 8 8


Nominal working pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 7.5 7.5 7.5 7.5
Air temperature at outlet valve . . . . . . . . . . . . . . . . . . . . . . . . C 28 30 29 32
Motor shaft speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . r/min 2970 2970 2970 2970
Power input 3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 81.7 97.6 80.2 94.8
Oil capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l 34.5 34.5 29.5 29.5
Sound pressure level 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . dB(A) 75 76 75 76
Cooling water consumption at temperature rise of 15 C . . . . l/s -- -- 1.1 1.4

1) At reference conditions (see section 7.5.1).


2) According to PNEUROP / CAGI test code under free field conditions at 1 m distance with a tolerance of µ 3dB.
3) Values may differ up to 0.5% depending on the supply voltage.

2920 1326 00 35
Oil-free Air Division Instruction book

7.5.8 Specific data of ZR75/90 10 bar - 50/60 Hz 1)

ZR75 ZR90 ZR75 ZR90

Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hz 50 50 60 60
Maximum working pressure . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 10 10 10 10
Nominal working pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 9.5 9.5 9.5 9.5
Air temperature at outlet valve . . . . . . . . . . . . . . . . . . . . . . . . C 30 32 30 32
Motor shaft speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . r/min 2970 2970 3565 3565
Power input 3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 80.6 95.6 87.7 106
Oil capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l 29.5 29.5 29.5 29.5
Sound pressure level 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . dB(A) 75 76 75 76
Cooling water consumption at temperature rise of 15 C . . . . l/s 1.1 1.4 1.2 1.5

7.5.9 Specific data of ZT/ZR75/90 7.5 bar - 60 Hz 1)

ZR75 ZR90 ZT75 ZT90

Maximum working pressure . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 7.5 7.5 7.5 7.5


Nominal working pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 7 7 7 7
Air temperature at outlet valve . . . . . . . . . . . . . . . . . . . . . . . . C 30 32 28 34
Motor shaft speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . r/min 3565 3565 3565 3565
Power input 3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 87.9 103 89.9 102
Oil capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l 29.5 29.5 34.5 34.5
Sound pressure level 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . dB(A) 75 76 75 76
Cooling water consumption at temperature rise of 15 C . . . . l/s 1.2 1.5 -- --

7.5.10 Specific data of ZT/ZR75/90 8.6 bar - 60 Hz 1)

ZT75 ZT90 ZR75 ZR90

Maximum working pressure . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 8.6 8.6 8.6 8.6


Nominal working pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 8 8 8 8
Air temperature at outlet valve . . . . . . . . . . . . . . . . . . . . . . . . C 28 34 30 32
Motor shaft speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . r/min 3565 3565 3565 3565
Power input 3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 87.8 103 86.0 103
Oil capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l 34.5 34.5 29.5 29.5
Sound pressure level 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . dB(A) 75 76 75 76
Cooling water consumption at temperature rise of 15 C . . . . l/s -- -- 1.2 1.5

7.6 Conversion list of SI units into British/American units


1 bar = 14.504 psi 1 kW = 1.341 hp (UK and US) 1 m = 3.281 ft 1 N = 0.225 lbf
1 g = 0.035 oz 1 l = 0.264 US gal 1 mm = 0.039 in 1 Nm = 0.738 lbf.ft
1 kg = 2.205 lb 1 l = 0.220 Imp gal (UK) 1 m3/min = 35.315 cfm x C = (32 + 1.8 x) F 4)
1 km/h = 0.621 mile/h 1 l = 0.035 cu.ft 1 mbar = 0.401 in wc

1) At reference conditions (see section 7.5.1).


2) According to PNEUROP / CAGI test code under free field conditions at 1 m distance with a tolerance of µ 3dB.
3) Values may differ up to 0.5% depending on the supply voltage.
4) A temperature difference of 1 C = a temperature difference of 1.8 F.

36 2920 1326 00

You might also like