TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-06, Rev. 0

TABLE OF CONTENTS

1.0 SCOPE

2.0 CROSS-REFERENCES

3.0 APPLICABLE CODES AND STANDARDS

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

5.0 TEMPERATURE SENSING CABLE DESIGN

6.0 DTS SYSTEM SOFTWARE

7.0 DTS SYSTEM HARDWARE

8.0 TESTING AND INSPECTION

9.0 PACKING AND SHIPPING

10.0 DATA SCHEDULE

11TMSS06R0/ WAM Date of Approval: July 18, 2013 PAGE 2 OF 17


License=Mohammed Al-Ojaimi Cont. Est./SA-2078 Not For Resale ,2/26/2020 12:37:45 PM Saudi Time
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-06, Rev. 0

1.0 SCOPE

This Transmission Material Standards Specifications (TMSS) specifies the minimum


technical requirements for design, engineering, manufacture, inspection, testing and
performance of the Distributed Temperature Sensing (DTS) System and temperature sensing
cable, which will be laid along with cables from 110kV up to 380kV in National Grid Saudi
Arabia system to sense the cable temperature and calculate the dynamic current ratings.

2.0 CROSS-REFERENCES

The Transmission Material Standard Specification (TMSS) shall be read in conjunction with
the latest revision of General Specification No. 01-TMSS-01 titled "General Requirements
for all Equipment/Materials" which shall be considered as an integral part of this TMSS.

This TMSS shall also be read in conjunction with Purchase Order or Contract Schedule for
project, as applicable.

3.0 APPLICABLE CODES AND STANDARDS

For applicable technical standards, tests and general requirements, reference shall be made
to the latest version of:

3.1 01-TMSS-01 General requirements

3.2 31-TMSS-01 Relay and control panels

3.3 48-TMSS-02 Non-metallic fiber optic cables

3.4 IEC 60287 Electrical cables – calculation of the current rating

3.5 IEC 60853 Calculation of the cyclic and emergency current rating of cables

3.6 IEC 61236 EMC requirement for electrical equipment for measurement.

3.7 IEC 61000 Electromagnetic Compatibility (EMC).

3.8 IEC 61508 Functional safety of electrical/electronic/programmable electronic


safety-related systems.

3.9 IEC 61010-1 Safety requirements for electrical equipment for measurement.

3.10 IEC 60825-1 Laser Safety

3.11 IEC 60068 Environmental Testing

3.12 EPRI Underground Transmission Systems Reference Book

11TMSS06R0/ WAM Date of Approval: July 18, 2013 PAGE 3 OF 17


License=Mohammed Al-Ojaimi Cont. Est./SA-2078 Not For Resale ,2/26/2020 12:37:45 PM Saudi Time
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-06, Rev. 0

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

4.1 General

The required Distributed Temperature Sensing (DTS) system is meant for monitoring
the temperature of high voltage underground power cable system based on fiber optic
DTS system that provides continuous, repeatable and distributed measurements, in
real-time, of the location and the temperature of defined points along the optical fiber
sensor. The principle of operation shall be based on optical time-domain
reflectometry (OTDR) with double-end or single-end measurement by sensing the
RAMAN back scattered signals.

4.2 Design Criteria

4.2.1 DTS system will be supplied as an integrated cable monitoring system. DTS
equipment will be housed in a rack cabinet and integrate all software
processing into the existing computing infrastructure with all existing safety
and networking tools. In case the computing infrastructure is not available on
the substation the rack cabinet shall include the monitor, DTS computer,
server computer, keyboard, video, visual display unit and mouse (KVM)
Switch, Fiber Distribution Frame (FDF), signal interface and a dry contact
relay output is included for interfacing to an alarm/control system. All
necessary software shall be supplied to enable the network connection over
local area network (LAN) in the substation as well as wide area network
(WAN) in National Grid Saudi Arabia network.

4.2.2 Temperature sensing fibers shall be in multi/single-mode and the number of


fibers shall be four depending on the SOW/TS requirements.

4.2.3 Temperature sensing cable shall have the ability to sense the temperature
either by placing it inside the power cable, externally attached on the jacket of
the power cable or in separate duct or close to the power cable depending on
the site conditions & SOW/TS requirements. Further, each phase of the cable
shall be monitored by using temperature sensing cable.

4.2.4 DTS system shall be designed as Single End (SE) or Double End (DE) to
guarantee fully providing the power cable temperature profile.

5.0 TEMPERATURE SESING CABLE DESIGN

5.1 Properties of temperature sensing cable

5.1.1 The characteristics of single mode temperature sensing fibers shall be as per
table 01.

11TMSS06R0/ WAM Date of Approval: July 18, 2013 PAGE 4 OF 17


License=Mohammed Al-Ojaimi Cont. Est./SA-2078 Not For Resale ,2/26/2020 12:37:45 PM Saudi Time
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-06, Rev. 0

Table 01: Characteristics of the Single Mode Fiber

Items Units Specifications


≤ 0.45 at 1300 nm
Attenuation dB/km
≤ 0.25 at 1550 nm
≤ 3.5 at 1285 nm ~ 1330
Chromatic Dispersion ps/nm.km nm
≤ 20 at 1550 nm
Zero Dispersion Wavelength nm 1300 ~ 1324
Zero Dispersion Slope 2 ps/nm .km ≤ 0.093
Cut-off Wavelength
nm ≤ 1250
(λcc, 22m of a cabled fiber)
9-10 µm ± 5% at 1300 nm
Mode Field Diameter µm
1 µm ± 10% at 1550 nm
Mode Field Concentricity µm ≤1
Cladding Diameter µm 125 ± 2.0
Cladding Non-circularity % ≤ 2.0
Coating Diameter µm 245 ~ 400
Proof Test kpsi ≥ 100

5.1.2 The characteristics of multi-mode temperature sensing fibers shall be as per


table 02.

Table 02: Characteristics of the Multimode Fiber

Items Units Specifications


≤ 2.4 at 850 nm
Attenuation dB/km
≤ 0.7 at 1300 nm
≥ 400 at 850 nm
Bandwidth MHz.km
≥ 600 at 1300 nm
Numerical Aperture - 0.20 ± 0.015
Core Diameter µm 50 ± 3.0

Core Non-circularity % ≤ 6.0

Cladding Diameter µm 125 ± 2.0


Cladding Non-circularity % ≤ 2.0
Core/Cladding Concentricity Error µm ≤ 1.0
Coating Diameter µm 250 ~ 400
Proof Test kpsi ≥ 100

11TMSS06R0/ WAM Date of Approval: July 18, 2013 PAGE 5 OF 17


License=Mohammed Al-Ojaimi Cont. Est./SA-2078 Not For Resale ,2/26/2020 12:37:45 PM Saudi Time
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-06, Rev. 0

5.2 Fiber optic sensor cable shall consist of central gel-filled buffer tube. The tube of the
sensor cable shall be made up of polycarbonate protected by glass yarns to protect
against water crush, rodent resistance as well as high water resistance. Additionally,
the tube shall be reinforced with layers of aramid yarns.

5.3 Outer sheath of the temperature sensing cable shall be made up of Black HDPE or
Black PVC compound ideally suitable for outdoor deployment. The tube shall have
type and meter markings.

5.4 The color code of the individual fibers in temperature sensing cable shall be in
accordance with Table 3.

5.5 Cross section of fiber optic sensing cables shall be as shown in the Figure.1.

Table 03: The Color Code of the Individual Fibers


No. of Fiber Color Fiber mode
1 Blue Multi/Single mode
2 Yellow Multi/Single mode
3 Green Multi/Single mode
4 Red Multi/Single mode

6.0 DTS SYSTEM SOFTWARE

6.1 General

DTS system software shall be designed to provide temperature profiles, hot spots,
changes in both, power cable and fiber optic environment parameters for specified
underground cable circuits. Software shall display the cable asset (circuit) with
geographical orientation to the environment and grid stations. Displayed cable asset
shall show the entire temperature profile in colors. History charts shall be displayed
containing free configurable point-of-interests (hot spots) showing the temperature
development over time (hourly, weekly, monthly, yearly). DTS system software shall
have inherent self-checking to generate automatic alarms in case of DTS system
failure including loss of AC supply, fiber break, and temperature profiles of the
monitored power cables. Alarm data shall be stored in a database and shall be
available for display on the DTS computer.

6.2 DTS system software shall have the advanced features of Real Time Thermal Rating
(RTTR) to provide a predictive model for cable loading using real-time algorithms
based on IEC 60287/60853 models and automatically steady-state, dynamic cable
ratings and emergency overloading. RTTR software shall calculate and submit
results via analogue or digital interfaces (on-line) to the Grid Station Control Room
and Load Dispatch Center (LDC) as following:

a. Single cable connection between Sub/Grid Stations: Steady-dynamic cable


rating and emergency over-load/time.

11TMSS06R0/ WAM Date of Approval: July 18, 2013 PAGE 6 OF 17


License=Mohammed Al-Ojaimi Cont. Est./SA-2078 Not For Resale ,2/26/2020 12:37:45 PM Saudi Time
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-06, Rev. 0

b. Parallel cable connections between Sub/Grid Stations: Steady-dynamic cable


rating for each cable and emergency over-load of the other cable if one cable
breaks down to simulate the worst-case scenario (two cables connected at star
configuration and one cable breaks down).

6.3 Communication

Information to be provided at Grid Station Control Room and Load Dispatch Center
for each Cable Circuit shall be shown on the screen in the following format:

a. Load (A).
b. Conductor Temperature (ºC) (requires RTTR).
c. Calculated Permissible Maximum Load (A) (requires RTTR).
d. Calculated Overload/time of 1st circuit in case second circuit is OFF for
Maintenance.
e. Actual Emergency overload (A)/time of healthy circuit if other circuit is
broken-down (for example joint failure)

6.4 This Software License shall include the use of Windows-based operating software
and proprietary operating system. Storage of temperature profile is achieved by data
storage in an SQL database. Microsoft SQL Server shall be used to manage the
database, which will allow an unlimited number of users to access the database, up to
the full disc capacity. Server Software shall have the ability to Data management,
Alarm detection and Data Analysis module.

6.5 Reporting

6.5.1 DTS software shall have the features that will help the clients to understand
server software with easy interface and functions as follows:

a. Temperatures of cable surface, sheath, insulator and conductor.


b. The capacity of current transmission.
c. Alarm conditions.
d. Stored history data, i.e. temperatures, alarm, capacity of current
transmission and so on.

6.5.2 DTS software including all the above functions could be changed according to
National Grid Saudi Arabia recommendations.

7.0 DTS SYSTEM HARDWARE

7.1 General

Hardware comprises of an Opto-Electronic Measurement Unit (OEMU) connected to


a fiber optic cable acting as an intrinsic sensing element. The fiber optic sensor cable
transmits optical data back to OEMU where it is analyzed to calculate temperature
and positional information. Zone and alarm processing are also carried out within the
OEMU.

11TMSS06R0/ WAM Date of Approval: July 18, 2013 PAGE 7 OF 17


License=Mohammed Al-Ojaimi Cont. Est./SA-2078 Not For Resale ,2/26/2020 12:37:45 PM Saudi Time
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-06, Rev. 0

7.2 The Opto-Electronic Measurement Unit contains the following components:

a. An optical front and containing a laser source and detectors.


b. Processor and memory cards, which execute embedded software to complete
the signal processing and transformation of data into temperature versus
distance traces and alarms.
c. Real-Time operating system (RTOS) designed for the use in embedded
systems in compliance with IEC 61508 and ARIC 653-1.
d. A high-speed communications interface to the DTS computer.

7.3 The overall cabinet dimensions shall be enough to accommodate the required
equipment to operate DTS system. In addition, the cabinet shall include a copper
earth bar; Miniature circuit breaker (MCB) to protect the cabinet wiring, a rear door
operated light and two spare 13 A power sockets (one BS standard and another ANSI
standard). Wiring and equipment shall be labeled in accordance with schematic
drawings.

7.4 The DTS system shall have a computer for operating management software which
communicates with DTS.

7.5 The system shall have a server computer for operating server software, client
software and optional analysis software including database for data management.

7.6 A rack mounted Un-interruptible Power Supply (UPS) unit shall be housed within
the DTS system enclosure. The UPS shall have the battery backup, which will
provide uninterrupted power supply to DTS system and computer operation for a
nominal period of three hours in the event of loss of power. In addition, the DTS
system shall also be fed from the available substation battery bank.

7.7 DTS system shall be equipped with Fiber Distributed Frame which is used as splice
box between Sensor cable and DTS system.

7.8 The DTS system shall have a switch hub which is used to provide the
communication path in the cabinet.

7.9 Monitor & Rack-mount panel shall be attached to the cabinet for display.

7.10 The DTS system shall have keyboard, video, or visual display unit, mouse (KVM)
switch which are used to enable keyboard, mouse and monitor to connect on DTS
computer and Server computer.

7.11 The DTS system shall have a signal interface output for alarm signal.

7.12 The DTS system shall have Ethernet card to enable checking of the data through a
separate computer.

7.13 The DTS system shall have the capability to operate and live access through a local
area network (LAN) and wide area network (WAN).

11TMSS06R0/ WAM Date of Approval: July 18, 2013 PAGE 8 OF 17


License=Mohammed Al-Ojaimi Cont. Est./SA-2078 Not For Resale ,2/26/2020 12:37:45 PM Saudi Time
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-06, Rev. 0

7.14 The system shall have a printer and it shall be installed in appropriate place inside the
cabinet.

7.15 In case of long distances, The DTS Data Warehouse (DDW) & DTS Remote Unit
(DRU) shall be used with design guarantee, stability & reliability of the supplied
power.

8.0 TESTING AND INSPECTION

8.1 General

The type test shall be carried out at an approved independent international test
laboratory and duly witnessed by a representative of National Grid Saudi Arabia or
independent inspection agency (IIA) appointed by National Grid Saudi Arabia.

8.2 Evidence shall be given that the proposed DTS being supplied under this Contract
has been type tested at an internationally independent testing laboratory. If needed,
National Grid Saudi Arabia will decide on whether additional tests are necessary to
be performed by the manufacturer. An internationally recognized laboratory shall
certify the type test reports. The manufacturer shall submit certified copies of type
test certificates covering the proposed DTS equipment. Type tests certificates/reports
shall be considered acceptable if results are in compliance with the relevant National
Grid Saudi Arabia standards & specifications and the following:

a. Type Tests shall be carried out at an internationally recognized laboratory


acceptable to National Grid Saudi Arabia.

b. Type Tests shall be witnessed by National Grid Saudi Arabia or approved


third party inspector appointed by National Grid Saudi Arabia.

8.3 If the presented type test reports are not in accordance with the above requirements,
National Grid Saudi Arabia may decide to ask the manufacturer to repeat the type
tests to be carried out in the factory premises or approved independent testing
laboratory subject to the approval of National Grid Saudi Arabia at no additional cost
to the company, and in the presence of a third party inspector who should issue the
relevant type test certificates upon successful completion of the tests.

8.4 The type test shall cover but not limited to a simulation test to check the integrity of
the DTS at the factory.

8.5 The type test for fiber optical cable which is used in DTS system shall be performed
according to latest revision of 48-TMSS-02 and relevant international standards.

8.6 The sample test shall comprise of visual and functional inspection to all system
components.

8.7 The routine test shall include the following:


a. The visual inspection to system components.
b. The functional tests on simulation basis for the system.

11TMSS06R0/ WAM Date of Approval: July 18, 2013 PAGE 9 OF 17


License=Mohammed Al-Ojaimi Cont. Est./SA-2078 Not For Resale ,2/26/2020 12:37:45 PM Saudi Time
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-06, Rev. 0

8.8 The manufacturer shall carry out electrical and function tests upon installing the
complete DTS system. The site test procedure/protocol of the supplied DTS system
shall be submitted for approval prior to commencing testing. The tests shall generally
cover the functions of the system as illustrated in this specification.

The site test shall comprise of, at least:

a. Test on Fiber optic Cores including the attenuation test and the backscatter
tests.
b. Functional tests before and after energizing and loading of the power cable.

9.0 PACKING AND SHIPPING

In addition to the applicable items of 01-TMSS-01 "General Requirements for all


Equipments/Materials", the following Packing and Shipping instructions are applicable:

9.1 Progressive length on the cable shall be marked at 1m (one meter) intervals.

9.2 The temperature sensing cable ends shall be sealed with a waterproof, heat
shrinkable plastic or elastomeric end cap with adhesive type sealing compound. The
temperature sensing cable ends shall be properly secured to the reel.

9.3 The temperature sensing cable shall be delivered without splices, on standard sized
non-returnable wood drums properly packed and lagged externally to prevent the
cable from possible damage during transportation. Wood lagging shall be used and
have a minimum thickness of 19 mm.

9.4 For all the temperature sensing cable purchases, the standard order length shall be
2000 meters. For The temperature sensing cable intended for Turnkey Projects, the
order length shall be as specified in Data Schedule.

9.5 Reel markings of temperature sensing cable

9.5.1 Fiber optical sensing cable reels/drums shall be marked in legible and
indelible letters giving the following particulars:
a. Name of the company.
b. Number of Optical Fiber.
c. Fiber optical sensing cable Description.
d. Length and Weight of Fiber optical sensing cable on Reel.
e. Gross Weight.
f. Dimensions of Reel.
g. Manufacturer's Name and Country of Origin.
h. Purchase Order Number/Contract Number.
i. Serial Number of Reel.
j. Stock number in 10 cm high bold numerals.
k. Direction of Rolling of Reel.
l. 11-TMSS-06.

9.5.2 All markings shall appear on both sides of the reel. Reel marking locations
shall be shown as in Figure.2.
11TMSS06R0/ WAM Date of Approval: July 18, 2013 PAGE 10 OF 17
License=Mohammed Al-Ojaimi Cont. Est./SA-2078 Not For Resale ,2/26/2020 12:37:45 PM Saudi Time
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-06, Rev. 0

9.5.3 Temperature sensing cable reel identifications shall include any additional
information as required in the shipping instructions by the National Grid
Saudi Arabia.

11TMSS06R0/ WAM Date of Approval: July 18, 2013 PAGE 11 OF 17


License=Mohammed Al-Ojaimi Cont. Est./SA-2078 Not For Resale ,2/26/2020 12:37:45 PM Saudi Time
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-06, Rev. 0

Figure.1: Cross section for temperature sensing cable.

Figure.2: Reel markings locations

11TMSS06R0/ WAM Date of Approval: July 18, 2013 PAGE 12 OF 17


License=Mohammed Al-Ojaimi Cont. Est./SA-2078 Not For Resale ,2/26/2020 12:37:45 PM Saudi Time
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-06, Rev. 0

10.0 DATA SCHEDULE

DISTRUBTED TEMPERATURE SENSING (DTS) SYSTEM FOR U/G POWER CABLE

Enquiry No.: Date:

Purchase Order No. OR


Contract No. Date:

PTS No. / Project Title With J.O. No.:

REFERENCE DESCRIPTION ‘A’ ‘B’ ‘C’


SECTION NO.

3.0 APPLICABLE CODES AND STANDARDS


Standards to which material (*)
shall conform.

4.0 DESIGN & CONSTRUCTION REQUIREMENTS

Design Criteria. (*)

Cable Voltage level


(110kV / 115kV / 132kV /
230kV / 380kV). (*)

4.2.2 Temperature sensing fibers


mode
(Single Mode/Multi Mode) (*)

Numbers of fibers (*)

4.2.3 Place of temperature sensing


cable (*)

4.2.4 Design of Distributed


Temperature Sensing (DTS)
system (Single End/Double
End) (*)

'A'- NATIONAL GRID SAUDI ARABIA SPECIFIED DATA/PARAMETER


'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS
'C'- REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'
(*)- DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/
VENDOR/CONTRACTOR IN COLUMN 'B'

11TMSS06R0/ WAM Date of Approval: July 18, 2013 PAGE 13 OF 17


License=Mohammed Al-Ojaimi Cont. Est./SA-2078 Not For Resale ,2/26/2020 12:37:45 PM Saudi Time
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-06, Rev. 0

10.0 DATA SCHEDULE

DISTRUBTED TEMPERATURE SENSING (DTS) SYSTEM FOR U/G POWER CABLE

5.0 TEMPERATURE SESING CABLE DESIGN

5.1.1 Single Mode (as per Table.01)


Attenuation (*)
Chromatic Dispersion (*)
Zero Dispersion Wavelength (*)
Zero Dispersion Slope (*)
Cut-off Wavelength
(λcc, 22m of a cabled fiber) (*)
Mode Field Diameter (*)
Mode Field Concentricity (*)
Cladding Diameter (*)
Cladding Non-circularity (*)
Coating Diameter (*)
Proof Test (*)

5.1.2 Multi Mode (as per Table.02)


Attenuation (*)
Bandwidth (*)
Numerical Aperture (*)
Core Diameter (*)
Core Non-circularity (*)
Cladding Diameter (*)
Cladding Non-circularity (*)
Core/Cladding Concentricity
Error (*)
Coating Diameter (*)
Proof Test (*)

5.2 Filling Compound (*)

5. 3 Secondary Coating (*)

5.4 Outer Sheath


Black HDPE or Black PVC (HDPE
compound Or PVC)

5.5 Fiber identification for 4 fibers


(colour) Blue
Orange
Green
Brown

11TMSS06R0/ WAM Date of Approval: July 18, 2013 PAGE 14 OF 17


License=Mohammed Al-Ojaimi Cont. Est./SA-2078 Not For Resale ,2/26/2020 12:37:45 PM Saudi Time
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-06, Rev. 0

10.0 DATA SCHEDULE

DISTRUBTED TEMPERATURE SENSING (DTS) SYSTEM FOR U/G POWER CABLE

7.0 DTS HARWARE

7.3 Cabinet size (*)

7.4 DTS computer


CPU (*)
Memory (*)
HDD (*)
Operating system (*)
CD-ROM (*)
FDD (*)
RS232C (*)
Power supply (*)

7.5 Server computer


CPU (*)
Memory (*)
HDD (*)
Operating system (*)
CD-ROM (*)
FDD (*)
RS232C (*)
Power supply (*)

7.6 Uninterrupted Power Supply (UPS)


Dimension (*)
capacity (*)
Input voltage (*)
Output (*)

7.7 Fiber Distribution Frame (FDF)


Mount Type (*)
Core slots (*)

7.8 Switch hub


Mount Type (*)
Ports (*)
Speed (*)

11TMSS06R0/ WAM Date of Approval: July 18, 2013 PAGE 15 OF 17


License=Mohammed Al-Ojaimi Cont. Est./SA-2078 Not For Resale ,2/26/2020 12:37:45 PM Saudi Time
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-06, Rev. 0

10.0 DATA SCHEDULE

DISTRUBTED TEMPERATURE SENSING (DTS) SYSTEM FOR U/G POWER CABLE

7.9 Monitor & Rack-mount panel


Screen Size (*)
Screen (*)

7.10 KVM Switch


Alarm Signal Output (*)
Analog Signal Input (*)

11TMSS06R0/ WAM Date of Approval: July 18, 2013 PAGE 16 OF 17


License=Mohammed Al-Ojaimi Cont. Est./SA-2078 Not For Resale ,2/26/2020 12:37:45 PM Saudi Time
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-06, Rev. 0

10.0 DATA SCHEDULE

DISTRUBTED TEMPERATURE SENSING (DTS) SYSTEM FOR U/G POWER CABLE

A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY


NATIONAL GRID SAUDI ARABIA:

B. ADDITIONAL SUPPLEMENTARY DATA OR FEATURES PROPOSED BY


BIDDER/VENDOR/SUPPLIER/CONTRACTOR:

C. OTHER PARTICULARS TO BE FILLED-UP BY BIDDER/VENDOR/SUPPLIER/


CONTRACTOR:

Actual Manufacturer Vendor/Supplier/


of Equipment/Material Contractor

Name of the Company


Location and Address

Name and Signature of Authorized


Representative and Date

Official Seal/Stamp of the Company


and Date.

11TMSS06R0/ WAM Date of Approval: July 18, 2013 PAGE 17 OF 17