00813-0300-4485 Rosemount DP Flow Meters June 13
00813-0300-4485 Rosemount DP Flow Meters June 13
June 2013
00813-0300-4485, Rev EC
5-year stability
(1) The enhanced 4-20 mA HART device can be ordered with Transmitter Output option code A plus any of
the following new option codes: DA0, M4, QT, DZ, CR, CS, CT, HR5, HR7.
Additional Information
Specifications: page 22
Certifications: page 30
Dimensional Drawings: page 42
Contents
Rosemount 3051CF Flowmeter Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2
Rosemount 3051CFA Annubar Flowmeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3
Rosemount 3051CFC Compact Flowmeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 11
Rosemount 3051CFP Integral Orifice Flowmeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 16
3051CF specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 22
3051CF product certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 30
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 42
Installation and Flowmeter Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Click Here
2 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 3
Rosemount DP Flow June 2013
4 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 5
Rosemount DP Flow June 2013
6 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 7
Rosemount DP Flow June 2013
8 www.rosemount.com
June 2013 Rosemount DP Flow
(3) HART Revision 5 is the default HART output. The Enhanced 3051 can be factory or field configured to HART Revision 7. To order HART Revision 7 factory configured, add
option code HR7.
(4) Option code M4 - LCD Display with Local Operator Interface required for local addressing and configuration.
(6) Instrument Connections for Remote Mount Options and Isolation Valves for Flo-tap Models are not included in the Material Traceability Certification.
www.rosemount.com 9
Rosemount DP Flow June 2013
(8) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits apply to
certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
(10) Select Configuration Buttons (option code D4 or DZ) or Local Operator Interface (option code M4) if local configuration buttons are required.
(11) Only available with 4-20 mA HART output (output Code A).
(14) The T1 option is not needed with FISCO Product Certifications, transient protection is included with the FISCO Product Certification code IA.
(15) Not available with FOUNDATION fieldbus (Output Code F) or Profibus (Output Code W).
(16) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field.
(17) The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.
(18) Configures the HART output to HART Revision 5. The device can be field configured to HART Revision 7 if needed.
(19) Configures the HART output to HART Revision 7. The device can be field configured to HART Revision 5 if needed.
10 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 11
Rosemount DP Flow June 2013
12 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 13
Rosemount DP Flow June 2013
14 www.rosemount.com
June 2013 Rosemount DP Flow
(2) For the 10-in. (250 mm) and 12-in. (300 mm) line size, the alignment ring must be ordered (Installation Accessories).
(3) 10-in. (250 mm) and 12-in. (300 mm) line sizes not available with Primary Element Technology A.
(4) For 2-in. (50 mm) line sizes the Primary Element Type is 0.6 for Primary Element Technology Code C.
(6) HART Revision 5 is the default HART output. The Enhanced 3051 can be factory or field configured to HART Revision 7. To order HART Revision 7 factory configured,
add option code HR7.
(7) Option code M4 - LCD Display with Local Operator Interface required for local addressing and configuration.
(10) For Annubar Option A, consult factory for pipe schedules other than Sch. 40.
(12) Not available with FOUNDATION fieldbus (Output Code F) or Profibus (Output Code W).
(13) Select Configuration Buttons (option code D4 or DZ) or Local Operator Interface (option code M4) if local configuration buttons are required.
(14) Only available with 4-20 mA HART output (output Code A).
(15) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits apply
to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
(18) The T1 option is not needed with FISCO Product Certifications, transient protection is included with the FISCO Product Certification code IA.
(20) Not available with FOUNDATION fieldbus (Output Code F) or Profibus (Output Code W).
(21) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field.
(22) The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.
(23) Configures the HART output to HART Revision 5. The device can be field configured to HART Revision 7 if needed.
(24) Configures the HART output to HART Revision 7. The device can be field configured to HART Revision 5 if needed.
www.rosemount.com 15
Rosemount DP Flow June 2013
Self-centering plate design prevents alignment errors that magnify measurement inaccuracies in small
line sizes
16 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 17
Rosemount DP Flow June 2013
18 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 19
Rosemount DP Flow June 2013
(1) To improve pipe perpendicularity for gasket sealing, socket diameter is smaller than standard pipe O.D.
20 www.rosemount.com
June 2013 Rosemount DP Flow
(2) HART Revision 5 is the default HART output. The Enhanced 3051 can be factory or field configured to HART Revision 7. To order HART Revision 7 factory configured, add
option code HR7.
(3) Option code M4 - LCD Display with Local Operator Interface required for local addressing and configuration.
(8) Not available for bore sizes 0010, 0014, 0020, 0034, 0066, or 0109.
(9) Not available with DIN Process Connection codes D1, D2, or D3.
(10) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits apply to
certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
(11) Not available with FOUNDATION fieldbus (Output Code F) or Profibus (Output Code W).
(12) Select Configuration Buttons (option code D4 or DZ) or Local Operator Interface (option code M4) if local configuration buttons are required.
(13) Only available with 4-20 mA HART output (output Code A).
(16) The T1 option is not needed with FISCO Product Certifications, transient protection is included with the FISCO Product Certification code IA.
(18) Not available with FOUNDATION fieldbus (Output Code F) or Profibus (Output Code W).
(19) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field.
(20) The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.
(21) Configures the HART output to HART Revision 5. The device can be field configured to HART Revision 7 if needed.
(22) Configures the HART output to HART Revision 7. The device can be field configured to HART Revision 5 if needed.
www.rosemount.com 21
Rosemount DP Flow June 2013
3051CF specifications
3051CF performance specifications
This product data sheet covers both HART, FOUNDATION fieldbus and Profibus PA protocols unless specified.
For zero-based spans, reference conditions, silicone oil fill, glass-filled PTFE o-rings, SST materials, Coplanar flange (3051C) or
1
/2 in.- 14 NPT (3051T) process connections, digital trim values set to equal range points.
(1) Range 1 flowmeters may experience an additional uncertainty up to 0.9%. Consult your Emerson Process Management Representative for exact
specifications.
Total performance
Total Performance is based on combined errors of reference accuracy, ambient temperature effect, and static pressure effect.
For ±50 °F (28 °C) temperature changes, up to 1000 psi (6,9 MPa) line pressure (CD only), from 1:1 to 5:1 rangedown.
Models Total Performance
3051CF
Ranges 2-5 ±0.15% of span
3051CF
±0.125% of URL for 5 years
Ranges 2-5
±50 °F (28 °C) temperature changes, and up to 1000 psi (6,9 MPa) line pressure.
3051CF Low/Draft Range
Ranges 0-1 ±0.2% of URL for 1 year
22 www.rosemount.com
June 2013 Rosemount DP Flow
Dynamic performance
4 - 20 mA HART(1) FOUNDATION fieldbus
1-5 Vdc HART Low and Profibus PA Typical HART Transmitter Response Time
Power protocols(3)
Total Response Time (Td + Tc) ( 2):
152 ms
3051CF, Ranges 2-5: 100 ms
307 ms
Range 1: 255 ms Transmitter Output vs. Time
N/A
Range 0: 700 ms
152 ms Pressure Released
3051T: 100 ms Td = Dead Time
See Instrument
3051L: See Instrument Toolkit® Td Tc
Tc = Time Constant
Toolkit 100%
Response Time = Td +Tc
Dead Time (Td) 45 ms (nominal) 97 ms
Update Rate 22 times per second 22 times per second 36.8%
63.2% of Total
Step Change
(1) Dead time and update rate apply to all models and ranges; analog output only 0%
Time
(2) Nominal total response time at 75 °F (24 °C) reference conditions.
(3) Transducer block response time, Analog Input block execution time not included.
RFI effects
±0.1% of span from 20 to 1000 MHz and for field strength up to
30 V/m.
Note
Calibrations at 68 °F (20 °C) per ASME Z210.1 (ANSI)
www.rosemount.com 23
Rosemount DP Flow June 2013
Max. Loop Resistance = 43.5 (Power Supply Voltage – 10.5) Current draw
17.5 mA for all configurations (including LCD display option)
Indication
Load (Ohms)
24 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 25
Rosemount DP Flow June 2013
1-5 Vdc HART low power For 3051L or Level Flange Option Codes FA, FB, FC, FD, FP, and
FQ, limit is 0 psia to the flange rating or sensor rating, whichever
(output code M)
is lower.
Output Table 5. 3051L and Level Flange Rating Limits
Three wire 1-5 Vdc or 0.8-3.2 Vdc (Option Code C2) Standard Type CS Rating SST Rating
user-selectable output. Also user selectable for linear or square
ANSI/ASME Class 150 285 psig 275 psig
root output configuration. Digital process variable
ANSI/ASME Class 300 740 psig 720 psig
superimposed on voltage signal, available to any host
ANSI/ASME Class 600 1480 psig 1440 psig
conforming to the HART protocol. Low-power transmitter
At 100 °F (38 °C), the rating decreases
operates on 6-12 Vdc with no load. with increasing temperature, per ANSI/ASME B16.5.
Power consumption DIN PN 10-40 40 bar 40 bar
DIN PN 10/16 16 bar 16 bar
3.0 mA, 18-36 mW
DIN PN 25/40 40 bar 40 bar
Minimum load impedance At 248 °F (120 °C), the rating decreases
with increasing temperature, per DIN 2401.
100 k (Vout wiring)
Indication
Static pressure limit
Optional 5-digit LCD display Rosemount 3051CD only
26 www.rosemount.com
June 2013 Rosemount DP Flow
Up to 600# ANSI (1440 psig at 100 °F (99 bar at 38 °C)) Volumetric displacement
Less than 0.005 in3 (0,08 cm3)
Integral temperature measurement is not available with
Flanged mounting type greater than class 600 Damping
Remote Mount Transmitter 4-20 mA HART
Up to 2500# ANSI (6000 psig at 100 °F (416 bar at 38 °C)). Analog output response to a step input change is user-selectable
from 0 to 36 seconds for one time constant. This software
damping is in addition to sensor module response time.
(1) Static pressure selection may effect pressure limitations.
FOUNDATION fieldbus
For 3051CFC temperature limits Transducer block: 0.4 seconds fixed
AI Block: User configurable
Process temperature limits
Direct Mount Transmitter Profibus PA
AI Block only: User configurable
-40 to 450 °F (-40 to 232 °C)
Note
When the temperature is 400-850 °F (204-454 °C), the DP Limit should
be 400 inH2O (1 bar).
www.rosemount.com 27
Rosemount DP Flow June 2013
Flange face finish per ANSI B16.5, 125 to 250 RMS Isolating Diaphragm Material
Body bolts/studs
316L SST •
ASTM A193 Gr B8M studs Alloy C-276 •
Alloy 400 •
ASTM A193 Gr B8M Class 2 body studs provided for high
Tantalum •
temperature option code G
Gold-plated Alloy 400 •
Gold-plated SST •
28 www.rosemount.com
June 2013 Rosemount DP Flow
Non-wetted parts
Electronics housing
Low-copper aluminum or CF-8M (Cast version of 316 SST).
Enclosure Type 4X, IP 65, IP 66, IP 68
Coplanar sensor module housing
CF-3M (Cast version of 316L SST, material per ASTM-A743)
Bolts
ASTM A449, Type 1 (zinc-cobalt plated carbon steel)
ASTM F593G, Condition CW1 (Austenitic 316 SST)
ASTM A193, Grade B7M (zinc plated alloy steel)
Alloy K-500
Sensor module fill fluid
Silicone oil (D.C. 200) or Fluorocarbon oil (Halocarbon or
Fluorinert® FC-43 for 3051T)
Process fill fluid (3051L only)
Syltherm XLT, D.C. Silicone 704,
D.C. Silicone 200, inert, glycerin and water, Neobee M-20 or
propylene glycol and water
Paint
Polyurethane
Cover O-rings
Nitirile Butadiene (NBR)
www.rosemount.com 29
Rosemount DP Flow June 2013
Ordinary Location Certification for Factory Mutual Canadian Standards Association (CSA)
As standard, the transmitter has been examined and tested to All CSA hazardous approved transmitters are certified per
determine that the design meets basic electrical, mechanical, ANSI/ISA 12.27.01-2003.
and fire protection requirements by FM, a nationally recognized
testing laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).
30 www.rosemount.com
June 2013 Rosemount DP Flow
E6 Explosion-Proof, Dust Ignition Proof and Class I Division 2 N1 ATEX Non-incendive/Type n and Dust
Certificate No.: 1053834 Certification No.: BAS 00ATEX3105X
Applicable Standards: CSA Std. C22.2 No. 142 – M1987, Applicable Standards: EN60079-0:2012,
CSA Std. C22.2 No. 30 – M1986, CSA Std. C22.2 No. 213 – EN60079-15:2010, EN60079-31:2009
M1987, ANSI/ISA 12.27.01-2003. Markings: II 3 GD, Ex nA IIC Gc T5 (–40 Ta 70 °C),
Markings: Explosion-Proof for Class I, Division 1, Groups B, Ex ta IIIC T50 °C T500 60°C Da, IP66
C, and D. 1180
Dust-Ignition-Proof for Class II and Class III, Division 1,
Groups E, F, and G. Specific Conditions for Safe Use (X):
Suitable for Class I, Division 2 Groups A, B, C, and D.
1.) The apparatus is not capable of withstanding the 500 V
Enclosure type 4X, factory sealed. Single Seal (See
insulation test required by EN60079-15. This must be
Drawing 03031-1053).
taken into account when installing the apparatus.
C6 Intrinsically Safe
2.) This device contains a thin wall diaphragm. Installation,
Certificate No.: 1053834
maintenance, and use shall take into account the
Applicable Standards: CSA Std. C22.2 No. 142 – M1987,
environmental conditions to which the diaphragm will be
CSA Std. C22.2 No. 157 – 92, ANSI/ISA 12.27.01-2003.
subjected. The manufacturer’s instructions for installation
Markings: Intrinsically safe for Class I, Division 1, Groups A,
and maintenance shall be followed in detail to assure
B, C, and D when connected in accordance with
safety during its expected lifetime. In case of repair,
Rosemount drawings 03031-1024. Temperature Code
contact the manufacturer for more information on the
T3C. Enclosure Type 4X, Single Seal. Single Seal (See
dimensions of the flameproof joints.
Drawing 03031-1053).
E8 ATEX Flameproof and Dust
European Certifications
Certification No.: KEMA00ATEX2013X,
I1 ATEX Intrinsic Safety and Dust Baseefa11ATEX0275
Certificate No.: BAS 97ATEX1089X, Baseefa11ATEX0275 Applicable Standards: EN60079-0:2012, EN60079-1:2007,
Applicable Standards: EN60079-0:2012, EN60079-1:2007, EN60079-26:2007, EN60079-31: 2009
EN60079-26:2007, EN60079-31: 2009 Markings: II 1/2 G, Ex d IIC T6 (–50 Ta 65 °C) Ga/Gb,
Markings: II 1 GD, Ex ia IIC T4 Ga (–60 Ta +70 °C), Ex d IIC T5 (–50 Ta 80 °C) Ga/Gb,
Ex ia IIC T5 Ga (–60 Ta +40 °C) II 1D Ex ta IIIC T50 °C T500 60 °C Da
Ex ta IIIC T50 °C T500 60°C Da, IP66, 1180
1180
Process
Ambient Temp Temp Class
Temp
Table 8. Input Parameters -50 to 65 -50 to 65 T6
Ui = 30V
-50 to 80 -50 to 80 T5
Ii = 200 mA
Pi = 0.9W Special Conditions for Safe Use:
Ci = 0.012 μF
1.) In case of repair, contact the manufacturer for
information on the dimensions of the flameproof joints.
Table 9. RTD Assembly (3051CFx Option T or R)
Ui = 5 Vdc 2.) This device contains a thin wall diaphragm. Installation,
Ii = 500 mA maintenance and use shall take into account the
Pi = 0.63W environmental conditions to which the diaphragm will be
subjected. The manufacturer's instructions for installation
Special Conditions for Safe Use (X): and maintenance shall be followed in detail to assure
safety during its expected lifetime.
1.) The apparatus is not capable of withstanding the 500 V
insulation test required by EN60079-11. This must be 3.) The capacitance of the wrap around label to the
taken into account when installing the apparatus. enclosure, 1.6E-9 F, exceeds the limit in Table 9 of IEC
60079-0. The user shall determine suitability for the
2.) The enclosure may be made of aluminum alloy and specific application.
given a protective polyurethane paint finish; however care
should be taken to protect it from impact or abrasion if
located in Zone 0.
www.rosemount.com 31
Rosemount DP Flow June 2013
China certifications
Process
Ambient Temp Temp Class
Temp E3 Flameproof
NEPSI Certificate No.: GYJ101313X
-50 to 65 -50 to 65 T6
Applicable Standards: GB3836.1-2000, GB3836.2-2000
-50 to 80 -50 to 80 T5 Markings: Ex d II C T5/T6,
T5: -50 °C Ta +80 °C
Conditions of Certification (X): T6: -50 °C Ta +65 °C
1.) This device contains a thin wall diaphragm. Installation, Specific Conditions for Safe Use (X):
maintenance, and use shall take into account the
environmental conditions to which the diaphragm will be 1. Symbol “X” is used to denote specific conditions of use:
subjected. The manufacturer's instructions for installation
a. This device contains a thin wall diaphragm. Installation,
and maintenance shall be followed in detail to assure
maintenance and use shall take into account the
safety during its expected lifetime.
environmental conditions to which the diaphragm will be
subjected.
32 www.rosemount.com
June 2013 Rosemount DP Flow
2. The relation between T code and ambient temperature a. If the apparatus is fitted with an optional 90V transient
range is: suppressor, it is not capable of withstanding the 500V
Transmitter Model T Code Temperature Range insulation test for 1 minute. This must be taken into
account when installing the apparatus.
Using 644 temperature
T4 -40 °C Ta +65 °C
transmitter b. The enclosure may be made of aluminum alloy and
No 644 temperature T5 -50 °C Ta +80 °C given a protective polyurethane paint finish; however, care
transmitter T6 -50 °C Ta +65 °C should be taken to protect it from impact or abrasion if
located in Zone 0.
3. The earth connection facility in the enclosure should be
connected reliably. 2. The relation between T code and ambient temperature
range is:
4. During installation, use and maintenance of the
Temperature
product, observe the warning “Don’t open the cover when Transmitter Model T Code
Range
the circuit is alive”.
Using 644 temperature
5. During installation, there should be no present mixture T4 -40 °C Ta +60 °C
transmitter
harmful to the flameproof housing. Revision1 T5 -60 °C Ta +40 °C
3051C T4 -60 °C Ta +70 °C
6. Cable entry and conduit, certified by NEPSI with type of No 644
protection Ex d IIC and appropriate thread form, should be Revision5
temperature T4 -60 °C Ta +70 °C
applied when installed in hazardous locations. Blanking 3051C
transmitter
elements should be used on the redundant cable entries. Fieldbus/FISCO
T4 -60 °C Ta +60 °C
Version
7. End users are not permitted to change any internal
components, but to settle the problem in conjunction with 3. Intrinsically safe parameters:
the manufacturer to avoid damage to the product. Transmitter Maximum Maximum Maximum Maximum
Model input input input internal
8. Maintenance should be done in non-hazardous voltage: Ui current: Ii power: Pi parameters:
locations. (V) (mA) (W) Ci (nF) Li (μH)
Revision1/
9. During installation, use and maintenance of this 30 200 0.9 12 0
5 3051C
product, observe the following standards:
3051
30 300 1.3 0 0
GB3836.13-1997 “Electrical apparatus for explosive gas Fieldbus
atmospheres Part 13: Repair and overhaul for apparatus 3051
used in explosive gas atmospheres” Fieldbus 17.5 380 5.32 5 10
FISCO
GB3836.15-2000 “Electrical apparatus for explosive gas
atmospheres Part 15: Electrical installations in hazardous
area (other than mines)” Note
FISCO parameters apply to both Group IIC and IIB.
GB3836.16-2006 “Electrical apparatus for explosive gas
atmospheres Part 16: Inspection and maintenance of When 644 temperature transmitter is used, the 644
electrical installation (other than mines)” temperature transmitter should be used with Ex-certified
GB50257-1996 “Code for construction and acceptance of associated apparatus to establish an explosion protection
electric device for explosion atmospheres and fire hazard system that can be used in explosive gas atmospheres.
electrical equipment installation engineering”. Wiring and terminals should comply with the instruction
manual of both 644 temperature transmitter and
I3 Intrinsic Safety associated apparatus. The cables between 644
NEPSI Certificate No.: GYJ101312X temperature transmitter and associated apparatus should
Applicable Standards: GB3836.1-2000, GB3836.4-2000
be shielded cables (the cables must have an insulated
Markings: Ex ia IIC T4/T5
shield). The shield has to be grounded reliably in a
T4: -60°C Ta +70°C
non-hazardous area.
T5: -60°C Ta +40°C
Specific Conditions for Safe Use (X): 4. 3051CF series Flowmeter comply with the requirements
for FISCO field devices specified in IEC60079-27:2008. For
1. Symbol “X” is used to denote specific conditions of use:
the connection on an intrinsically safe circuit in accordance
to the FISCO model, FISCO parameters of 3051CF series
Flowmeter are listed in the table above.
www.rosemount.com 33
Rosemount DP Flow June 2013
Combinations of Certifications
Stainless steel certification tag is provided when optional
approval is specified. Once a device labeled with multiple
approval types is installed, it should not be reinstalled using any
other approval types. Permanently mark the approval label to
distinguish it from unused approval types.
KB K5 and C6 combination
K5 E5 and I5 combination
34 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 35
Rosemount DP Flow June 2013
36 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 37
Rosemount DP Flow June 2013
7. End users are not permitted to change any internal 3. Intrinsically safe parameters:
components, but to settle the problem in conjunction with Maximum
Maximu Maximu Maximum
the manufacturer to avoid damage to the product. Transmitter m input m input input internal
Model voltage: current: power: parameters:
8. Maintenance should be done in non-hazardous
locations. Ui (V) Ii (mA) Pi (W) Ci (nF) Li (μH)
Revision1/5
9. During installation, use and maintenance of this 30 200 0.9 12 0
3051C
product, observe the following standards:
3051
30 300 1.3 0 0
GB3836.13-1997 “Electrical apparatus for explosive gas Fieldbus
atmospheres Part 13: Repair and overhaul for apparatus 3051
used in explosive gas atmospheres” Fieldbus 17.5 380 5.32 5 10
FISCO
GB3836.15-2000 “Electrical apparatus for explosive gas
atmospheres Part 15: Electrical installations in hazardous
area (other than mines)” Note
FISCO parameters apply to both Group IIC and IIB.
GB3836.16-2006 “Electrical apparatus for explosive gas
atmospheres Part 16: Inspection and maintenance of When 644 temperature transmitter is used, the 644
electrical installation (other than mines)” temperature transmitter should be used with Ex-certified
GB50257-1996 “Code for construction and acceptance of associated apparatus to establish an explosion protection
electric device for explosion atmospheres and fire hazard system that can be used in explosive gas atmospheres.
electrical equipment installation engineering”. Wiring and terminals should comply with the instruction
manual of both 644 temperature transmitter and
I3 Intrinsic Safety associated apparatus. The cables between 644
NEPSI Certificate No.: GYJ101312X
temperature transmitter and associated apparatus should
Applicable Standards: GB3836.1-2000, GB3836.4-2000
be shielded cables (the cables must have an insulated
Markings: Ex ia IIC T4 (-60°C Ta +60°C)
shield). The shield has to be grounded reliably in a
non-hazardous area.
Specific Conditions for Safe Use (X):
4. 3051CF series Flowmeter comply with the requirements
1. Symbol “X” is used to denote specific conditions of use: for FISCO field devices specified in IEC60079-27:2008. For
the connection on an intrinsically safe circuit in accordance
a. If the apparatus is fitted with an optional 90V transient
to the FISCO model, FISCO parameters of 3051CF series
suppressor, it is not capable of withstanding the 500V
Flowmeter are listed in the table above.
insulation test for 1 minute. This must be taken into
account when installing the apparatus. 5. The product should be used with Ex-certified associated
apparatus to establish an explosion protection system that
b. The enclosure may be made of aluminum alloy and
can be used in explosive gas atmospheres. Wiring and
given a protective polyurethane paint finish; however, care
terminals should comply with the instruction manual of
should be taken to protect it from impact or abrasion if
the product and associated apparatus.
located in Zone 0.
6. The cables between this product and associated
2. The relation between T code and ambient temperature
apparatus should be shielded cables (the cables must have
range is:
insulated shields). The shield has to be grounded reliably in
Temperature a non-hazardous area.
Transmitter Model T Code
Range
Using 644 temperature 7. End users are not permitted to change any internal
T4 -40 °C Ta +60 °C components, but to settle the problem in conjunction with
transmitter
Revision1 T5 -60 °C Ta +40 °C the manufacturer to avoid damage to the product.
3051C T4 -60 °C Ta +70 °C 8. During installation, use and maintenance of this
No 644
Revision5 product, observe the following standards:
temperature T4 -60 °C Ta +70 °C
3051C
transmitter
Fieldbus/FISCO GB3836.13-1997 “Electrical apparatus for explosive gas
T4 -60 °C Ta +60 °C atmospheres Part 13: Repair and overhaul for apparatus
Version
used in explosive gas atmospheres”
38 www.rosemount.com
June 2013 Rosemount DP Flow
GB3836.15-2000 “Electrical apparatus for explosive gas
atmospheres Part 15: Electrical installations in hazardous
area (other than mines)”
Combinations of Certifications
Stainless steel certification tag is provided when optional
approval is specified. Once a device labeled with multiple
approval types is installed, it should not be reinstalled using any
other approval types. Permanently mark the approval label to
distinguish it from unused approval types.
K5 – E5, I5
K7 – E7, I7, N7
K8 – E8, I1
www.rosemount.com 39
Rosemount DP Flow June 2013
40 www.rosemount.com
June 2013 Rosemount DP Flow
5.250 to 5.472-in. (133.35 to 138.99 0.134 to 0.3919-in. (3.4 to
A
mm) 9.9 mm)
5.473 to 5.760-in. (139.01 to 146.30 0.134 to 0.327-in. (3.4 to 8.3
6-in. 6.93-in. 0.134 to B
Sensor
Size 1
mm) mm)
(150 (176.02 060 0.614-in.
5.761 to 6.065-in. (146.33 to 154.05 0.134 to 0.31-in. (3.4 to 7.9
mm) mm) (3.4 to 15.6 mm) C
mm) mm)
6.066 to 6.383-in. (154.08 to 162.13 0.134 to 0.297-in. (3.4 to 7.5
D
mm) mm)
5.250 to 5.472-in. (133.35 to 139.99 0.134 to 1.132-in. (3.4 to
A
mm) 28.7 mm)
5.473 to 5.760-in. (139.01 to 146.30 0.134 to 1.067-in. (3.4 to
6-in. 6.93-in. 0.134 to B
Sensor
Size 2
www.rosemount.com 41
Rosemount DP Flow June 2013
Dimensional drawings
Rosemount 3051CFA Pak-Lok Annubar Flowmeter(1)
Front View Side View Top View
B C
(1) The Pak-Lok Annubar model is available up to 600# ANSI (1440 psig at 100 °F (99 bar at 38 °C)).
42 www.rosemount.com
June 2013 Rosemount DP Flow
D
C
B
(1) The Flange-Lok Annubar model can be direct mounted up to 600# ANSI (1440 psig at 100 °F (99 bar at 38 °C)).
www.rosemount.com 43
Rosemount DP Flow June 2013
D
B
44 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 45
Rosemount DP Flow June 2013
D
C
B
A
(1) The Flanged Flo-Tap Annubar Flowmeter is available with both the manual and gear drive options.
46 www.rosemount.com
June 2013 Rosemount DP Flow
(1) The Threaded Flo-Tap Annubar Flowmeter is available with both the manual and gear drive options.
www.rosemount.com 47
Rosemount DP Flow June 2013
D
(Primary Element Type code C and P)
Conditioning Flowmeter
B C
48 www.rosemount.com
June 2013 Rosemount DP Flow
(1) Downstream length shown here includes plate thickness of 0.162-in. (4.11 mm).
www.rosemount.com 49
Rosemount DP Flow Product Data Sheet
00813-0300-4485 Rev EC June 2013