380 kV OHL
3134 Instantaneous trip after SwitchOnToFault: As stated above, only the distance
protection operates with SOTF so set NO here.
3135 Inrush Blocking: As stated above, inrush blocking is not applied so set NO
here.
Figure 53: 3I0 Inverse Time stage settings, earth fault overcurrent
3140 Operating mode: This stage is not required so it is set to Inactive.
Because this stage is inactive, the settings 3141 to 3151 are of no consequence and
left on their default values.
17.6. Direction