Protection Application Example

380 kV OHL

3168 Compensation angle PHI comp. for Sr: This setting is only relevant for
direction decision based on zero sequence power. In this application it is of
no consequence and left on default value of 255ْ.

3169 Forward direction power threshold: This setting is only relevant for direction
decision based on zero sequence power. In this application it is of no
consequence and left on default value of 0.3 VA.

18. Teleprotection for Earth fault overcurrent – Setting


Group A

Figure 55: Teleprotection for earth fault overcurrent settings


3201 Teleprotection for Earth Fault O/C: In this application the teleprotection is
required and applied as “Directional Comparison Pickup”, refer to parameter
132 in Chapter 4. This function is therefore activated by setting it ON.

3202 Type of Line: the line is a Two Terminal line.

3203A Time for send signal prolongation: As the same type of communication with
the same channel delay time is used for distance teleprotection and earth
fault teleprotection the same setting consideration as for parameter 2103A in
Chapter 13 applies here. Therefore in this example a setting of 0.05 sec is
applied.

3209A Transient Block.:duration external flt: As the same type of communication


with the same channel delay time is used for distance teleprotection and
earth fault teleprotection the same setting consideration as for parameter
2109A in Chapter 13 applies here. Therefore in this example a setting of
0.04 sec is applied.

3210A Transient Block.:Blk. T after ext. flt: As the same type of communication with
the same channel delay time is used for distance teleprotection and earth
fault teleprotection the same setting consideration as for parameter 2110A in
Chapter 13 applies here. Therefore in this example a setting of 0.05 sec is
applied.

7SA522/7SA6 Application Example Page 68 of 82